0% found this document useful (0 votes)
646 views2 pages

EOCR-3DM2 Motor Protection Relay Guide

This document provides specifications for a 3DM2-WRDUH motor protection relay that can monitor 0.5 to 60 amps at 100 to 240 volts AC/DC. It summarizes the relay's key characteristics including overload, underload, locked rotor, and phase protection functions as well as adjustable time delays, display options, and environmental specifications. The relay has a 18 month warranty period.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
646 views2 pages

EOCR-3DM2 Motor Protection Relay Guide

This document provides specifications for a 3DM2-WRDUH motor protection relay that can monitor 0.5 to 60 amps at 100 to 240 volts AC/DC. It summarizes the relay's key characteristics including overload, underload, locked rotor, and phase protection functions as well as adjustable time delays, display options, and environmental specifications. The relay has a 18 month warranty period.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Product Overview
  • Main Features
  • Offer Sustainability
  • Contractual Warranty
  • Environmental Compliance

Product datasheet 3DM2-WRDUH

Characteristics motor protection relay - 0.5..60 A - 100..240 V AC/


DC

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product EOCR
Device short name EOCR-3DM2
Product or component type Protection relay
Protection type Overload, In > OC setting
Underload, In < UC setting
Locked rotor for starting, In > 2...8 times OC setting
Locked rotor for running, In > 1.5...5 times OC setting
Sensitivity to phase loss
Phase unbalance, 10...50 %
Sensitivity to phase reverse
Product specific application Motor protection
Network type AC
Network frequency 50...60 Hz
Protection ajustment range 0.5...60 A
Tripping threshold 0.5...32 A (inverse and thermal)
0.5...60 A (definite)

Complementary
[Us] rated supply voltage 100...240 V AC/DC
Mounting support Panel
35 mm DIN rail
Contacts type and composition 1 NC + 1 NO (OL)
1 NO (AL/UL/TO)
Short-circuit and overload protection By 4 A gG fuse
[Ue] rated operational voltage Power circuit : 600 V AC 50...60 Hz UL
Power circuit : 690 V AC 50...60 Hz CSA
Power circuit : 690 V AC 50...60 Hz IEC 60947-4-1
[Uimp] rated impulse withstand voltage 6 kV IEC 60947-4-1
Reset Electrical 0...1 s by interruption of power supply
Manual reset
Automatic reset 0.5...1200 s

Jan 7, 2019
1
Time delay type D-Time : 0...200 s
O-Time : 0.2...30 s (definite)
O-Time : 1...30 class (inverse and thermal)
U-Time : 0.5...30 s
Display type 7 segments LED
Bar graph
Power consumption per relay <3W
Connections - terminals Control circuit : 2 cable 1...1.5 mm² - flexible - with cable end - M3
Control circuit : 2 cable 1...1.5 mm² - flexible - without cable end - M3
Control circuit : 1 cable 1...2.5 mm² - flexible - with cable end - M3
Control circuit : 1 cable 1...2.5 mm² - flexible - without cable end - M3
Tightening torque 0.8...1.2 N.m for control circuit - cable - 4.7 mm head
Height 56.3 mm
Width 70 mm
Depth 108.1 mm
Product weight 0.355 kg

Environment
Standards IEC 60947-4-1
Product certifications UL
IP degree of protection IP20 IEC 60529
Ambient air temperature for operation -20...60 °C IEC 60947-4-1
Ambient air temperature for storage -40...85 °C
Operating altitude 2000 m
Fire resistance 650 °C IEC 60695-2-12
960 °C UL 94
Shock resistance 15 gn for 11 ms IEC 60068-2-7
Vibration resistance 4 gn on panel mounting IEC 60068-2-6
2 gn on 35 mm DIN rail IEC 60068-2-6
Dielectric strength 2 kV at 50...60 Hz in between case and circuit IEC 60255-5
1 kV at 50...60 Hz in between contact IEC 60255-5
2 kV at 50...60 Hz in between circuit IEC 60255-5
Surge withstand 6 kV IEC 61000-4-5
Electromagnetic compatibility Resistance to electrostatic discharge 8 kV air, 6 kV contact IEC 61000-4-2
Resistance to radiated electromagnetic fields 10 V/m level 3 IEC 61000-4-3
Resistance to fast transient 2 kV IEC 61000-4-4
Conducted RF disturbances 10 V EN 61000-4-6
Conducted RF disturbances class A EN 55011
[Ith] conventional free air thermal 3 A, control circuit
current
Permissible current 250 V, 3 A AC

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0951 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available

Contractual warranty
Warranty period 18 months