Special Instruccion
Special Instruccion
Page 1 of 49
Shutdown SIS
Previous Screen
Special Instruction
Procedure to Upgrade EMCP 1, EMCP 2, EMCP 2+, EMCP 3.1, EMCP 3.2, and EMCP 3.3 to
EMCP 4.4 {4490}
Media Number -REHS9132-04 Publication Date -06/10/2014 Date Updated -29/05/2020
i08029527
Introduction
Table 1
Revision History
Revision Summary of Change
04 Updated and added the revision history, schematic 9, 10, 11, 12.
This Special Instruction provides information about upgrading electric power generator set control mounted
panels to the EMCP 4.4 control. The following is a list of the controls that can be upgraded to the EMCP
4.4:
• EMCP2
• EMCP2+
• EMCP3.1
• EMCP3.2
• EMCP3.3
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMCP ... Page 2 of 49
The EMCP4.4 control is intended for applications that require generator paralleling for low voltage
applications less than 1000 V. Cat® floor-standing control or switch gear must be utilized for medium and
high-voltage applications.
Proper application of EMCP4.4 paralleling controllers is critical. In various areas of this document, the
document will refer to the unit as the generator set or engine. These terms are to be used interchangeably.
Reference Section
Reference: Systems Operations Troubleshooting/Testing and Adjusting, UENR1210-01, "EMCP4.3/4.4"
Reference: Application and Installation Guide, LEBE0007, "EMCP 4.3/4.4 Generator Set Control"
Work safely. Most accidents that involve product operation, maintenance, and repair are caused by failure
to observe basic safety rules or precautions. An accident can often be avoided by recognizing potentially
hazardous situations before an accident occurs.
A person must be alert to potential hazards. This person must also have the necessary training, skills, and
tools to perform these functions properly.
Safety precautions and warnings are provided in this instruction and on the product. If these hazard
warnings are not heeded, bodily injury or death could occur to you or to other persons. Caterpillar cannot
anticipate every possible circumstance of a potential hazard.
Therefore, the warnings in this publication and the warnings that are on the product are not all inclusive.
Avoid using a tool, a procedure, a work method, or operating technique that is not recommended by
Caterpillar.
Ensure that the product will not be damaged or the product will be made unsafe by the operation,
lubrication, maintenance, or the repair procedures.
Do not operate or work on this product unless you have read and
understood the instruction and warnings in the relevant Operation and
Maintenance Manuals and relevant service literature. Failure to follow
the instructions or heed the warnings could result in injury or death.
Proper care is your responsibility.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMCP ... Page 3 of 49
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMCP ... Page 4 of 49
Illustration 1 g06276183
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMCP ... Page 5 of 49
Make sure you use all the necessary protective equipment required to do
the job.
Make sure that you read and understand all directions and hazards
described on the labels and material safety data sheet of any chemical
that is used.
Observe the safe working load limits of all lifting and blocking devices
and keep a safe distance from suspended/blocked loads. Personnel may
be seriously injured or killed by falling loads.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMCP ... Page 6 of 49
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMCP ... Page 7 of 49
There may be government regulations, local regulations, or site-specific rules that govern the operation,
service, and maintenance of high-voltage components and machines. Comply with applicable rules and
regulations for the work place.
Appropriate high-voltage protective equipment should be worn as defined by local rules and
regulations.
DO NOT remove covers, or open enclosures, that will expose energized high-voltage electrical
components.
Refer to the Maintenance Section in the Operation and Maintenance Manual for additional information.
Residual energy can remain in high-voltage components even after operation has stopped. Always assume
that a hazardous level of voltage could be present.
Before performing any type of service, repair, or maintenance on high-voltage electrical components,
perform the following:
Note: Use electrical measuring tools that have the capacity to measure the high-voltage components being
checked. The level of voltage present must be confirmed to be below 50 Volts before any exposure to the
high-voltage components can take place.
Read and understand the instructions and warnings found in Operation and Maintenance Manual,
"Electrical Shutdown and Voltage Discharge" , to shut down the electrical system and discharge high-
voltage electrical components.
Table 2
Required Parts
Qty Part Number Part Name
Overview
Applicability
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMCP ... Page 8 of 49
Illustration 2 g06552457
Enclosure dimensions
(D1) 323.8 mm (12.7 inch)
(D2) 323.8 mm (12.7 inch)
(D3) 603.2 mm (23.7 inch) to 698.5 mm (27.5 inch)
The kit is intended to replace EMCP control panels that are fitted in a generator-mounted enclosure with
the dimensions shown in Illustration 2. The enclosure included with the kit has three conduit holes in the
bottom while some of the original controls only have two holes. The third hole can be blocked, if
necessary.
The sensors listed above and the needed electrical connectors are included in the upgrade kit. The EMCP
4.4 control has been pre-configured for the new sensors.
Features
The EMCP 4.4 control offers more features and communication options than what was available with the
older EMCP models. See the Application and Installation Guide, LEBE0007 for a complete description.
The EMCP 4.4 control is able to do dead bus arbitration and load sharing.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMCP ... Page 9 of 49
The purpose of hard wired dead bus arbitration (HDBA) is to determine whether a dead bus condition
exists. Also, the purpose of HDBA is to provide dead bus close arbitration in the absence of a multiple
generator set data link.
The EMCP 4.4 control actively monitors the real (kW) and reactive (kVAr) load requirement of all
paralleled generator sets as shown on the load sharing lines. The EMCP 4.4 control adjusts output of the
generator set to maintain a balanced loading of all generator sets.
The EMCP 4.4 control includes logic to sequence generator sets based on the total load requirement of the
system.
Required Documents
The documents are available on the "Caterpillar Service Information System" website. Review the
documents and if needed for reference, print the required portions prior to beginning the upgrade.
Power Requirements
The control is designed to operate on 24 VDC only. Current draw of the control package is less than 2 A.
External solenoids, loads driven by the control relays, and connection of a Cat ET communications adapter,
will add to the current draw.
Note: All ground wires shall connect to terminal blocks labeled 201 through 209. Every device shall have
its own ground wire that runs from the device to one of the ground terminal blocks, do not “Share” a
common ground wire between multiple devices. The connection to Battery (-) shall be made at terminal
block 201.
New Features
As implemented, the EMCP 4.4 control offers more features and communication options than what was
available with the earlier EMCP models. Refer to Application and Installation Guide, LEBE0007, "EMCP
4.3/4.4 Generator Set Control" for a complete description.
Safety
Electrical Safety
Refer to the "Important Safety Information" and "Introduction" sections of Special Instruction, REHS9132
for safety information.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 10 of 49
Take the following precautions while installing, removing, and handling the control:
• Handle equipment correctly. Use ESD protective packaging and material handling containers that are
anti-static and provide discharge protection and electric field suppression.
• Use protective devices. ESD - protective workstations and/or work surfaces that include a grounding
mat anti-static wrist strap.
• Keep all plastic items away from the devices. Any plastic item is a potential static generator. The
plastic includes candy wrappers, foam cups, synthetic carpet, and foam cushions.
• Do not use an anti-static bag for any other purpose than to enclose a product.
NOTICE
The 120-pin connector and 70-pin connector on the back of the control
is the most vulnerable area to electrostatic discharge (ESD). While
handling the EMCP 4.4, extra attention is required to the back of the
control. The control may become damaged or inoperable if extra care
is not taken.
Note: Consult the Electrostatic Discharge Association for proper procedure during particular situations at
http://www.esda.org.
Turn the battery disconnect switch to the OFF position and lockout the
battery disconnect switch with a safety lock.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 11 of 49
Illustration 3 g03682962
"Do Not Operate" warning tags
(1) Tag Side A
(2) Tag Side B
Note: Illustration 3 is an example of the "Do Not Operate" tags required for lockout and tag out of the unit.
1. Resolve any existing issues with the control, the generator set, or the wiring between the control and
the generator set.
2. Perform voltage and continuity checks to insure that the schematic conforms to the as-built or
corrected schematic of the existing installation.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 12 of 49
Resolve any existing issues with the control, the generator set, or the wiring between the control and the
generator set.
If the existing installation has generator set or control issues, both must be repaired prior to performing a
control upgrade. Troubleshooting a failure will only become more difficult after the new control is
installed. Performing the following tasks may not be possible if the control has failed.
Use the documentation appropriate for the control. The documentation should be available on the Service
Information System (SIS ).
Check the control for stored diagnostic codes and repair the issues that are causing the codes.
As much as practical, insure that the control and generator set are working without issues.
2. Measure the voltage at every point shown on the schematic that is connected to battery (+).
3. Check continuity for every point on the schematic that is connected to ground, terminal block
position 201 through 208.
4. Mark up the latest schematic with any changes that have occurred since the original installation.
Note: The tolerance for the continuity is < 10 ohms. The tolerance for the voltage is the V bat +/- 0.5 V.
The value of the generator set parameters will be needed to verify that there are no problems after the
installation of the new sensors.
Start the generator set and force the generator to remain at idle. The governor must be disconnected or
disabled. When the coolant temperature has stabilized, record the following values listed in Table 3.
Table 3
Value Unit
Engine Idle Speed RPM = ________
Enable the generator set to go to rated speed. When the coolant temperature has stabilized, record the
values listed in Table 4.
Table 4
Value Unit
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 13 of 49
Illustration 4 g03557376
Use documentation found in the service information system website to determine how to access the
generator set parameters. The parameters will be needed to program the new control. Record the data for
the list of parameters that are shown in Illustration 4.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 14 of 49
Bodily contact with electrical potential can cause bodily injury or death.
To avoid the possibility of injury or death, ensure that the main power
supply has been disconnected before performing any maintenance or
removing any modules.
1. Insure that the generator has been disconnected and/or isolated from any other power source and the
load. Ensure that the unit has been appropriately locked out and tagged.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 15 of 49
5. Inspect the wiring coming out of the conduit that enters the bottom of the panel. All the wires must
be labeled with the number of the terminal blocks that the wires are connected to. Make sure to
match the wire numbers shown on the schematic for the existing installation. The labeling is shown
on the schematic for the existing installation. The wire numbers are critical in determining where to
connect the wires in the EMCP 4.4 panel. When all the wires have been labeled, disconnect the wires
from the terminal blocks.
6. Leave the wires that are in the conduit or spiral wrap and remove the wires from the bottom of the
panel.
7. If the governor/speed control is going to be reused in the new panel, remove the governor/speed
control from the old panel. After removal, set the governor/speed control aside, for installation in the
new panel.
3. Install the new engine speed sensor, coolant temperature sensor, oil pressure sensor, and the required
new wiring.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 16 of 49
Illustration 5 g03712294
EMCP 4.4 control panel hole location information - top view of enclosure
(5) Existing holes in the generator enclosure
If replacing an EMCP 2 or EMCP 2+, the conduit holes will line up. However, four new mounting holes
may need to be drilled for the vibration isolation mounts. The conduit entry holes on the bottom of the
enclosure are standard in all three enclosure sizes.
Refer to Illustration 5 for dimensions information to mark the location of the mounting holes for the EMCP
4.4 control panel.
Since the EMCP 4.4 can replace many different controls, the existing wire numbers will likely not
correspond with the EMCP 4.4 terminal blocks.
The wire numbers on the existing wiring along with the schematic for the existing control will help to
identify the function for each wire. Use the schematic for the EMCP 4.4 to find the corresponding function
and the terminal block number. Connect each wire to the correct terminal block. In many installations there
will be wiring that is not used. If the wire will not be used, the wire can be pulled out of the conduit and
discarded.
If the fuel control valve was originally wired for "Energize to Run", no changes to the EMCP 4.4 control
are required. If the fuel control valve was originally wired for "Energize to Stop", then the wire from
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 17 of 49
terminal block 7 to terminal 7 of the fuel control relay (FCR), must be moved to terminal 3 of the FCR.
Refer to Table 5.
Table 5
Fuel Control Valve Function Connect To
Energize to Run Terminal Block 7 FCR, terminal 7 As shipped
The EMCP 4.4 control can directly monitor generator voltages up to 600 V. Voltages more than 600 V
must use potential transformers (PT). The purpose of the PT is to scale the generator voltage to less than
600 V. If potential transformers are used, the voltage ratio is set in the EMCP 4.4 parameter settings.
Use Cat® Electronic Technician (Cat ET ) Service Tool to perform the following steps to access the
parameters.
Illustration 6 g03692434
Generator potential transformer primary winding current parameters on Cat ET
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 18 of 49
4. Type the desired value in the "Values" field. Cat ET will automatically update the control.
Use the following steps to access the "Generator Potential Transformer Secondary Winding Rating" using
Cat ET.
Illustration 7 g03692406
Generator potential transformer secondary winding current parameters on Cat ET
4. Type the desired value. Cat ET will automatically update the control.
Note: Fuse protection is needed if the generator is wired directly to the EMCP 4.4 or if potential
transformers are used. Fuses with rating of 5 amps or less, with the appropriate voltage rating, must be
installed immediately after the connection to the generator.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 19 of 49
The EMCP 4.4 control must use current transformers to measure generator output current. The current
transformers must scale the generator output current from 0 A to 5 A for use by the EMCP 4.4. The current
transformer ratio is set in the EMCP 4.4 parameter settings.
Note: Refer to Special Instruction, M0107220, "Procedure to upgrade EMCP 1, EMCP 2, EMCP 2+,
EMCP 3.1, EMCP 3.2, and EMCP 3.3 to EMCP 4.3/4.4"
Use the following steps to access the primary winding rating parameters using Cat ET.
Illustration 8 g03707532
3. Type the desired value. Cat ET will automatically update the control.
Use the following steps to access the secondary winding rating parameters using Cat ET.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 20 of 49
Illustration 9 g03707533
New sensors have been provided in the kit, to insure compatibility with the EMCP 4.4 control.
Install the three new sensors and related wiring. The new sensors are as follows:
The oil pressure and coolant temperature sensors are active pulse width modulated (PWM) sensors. The
sensors require a supply voltage and ground. The sensor output is a pulse width modulated signal that is
read by the EMCP 4.4 control. A three wire 371-6415 Electrical Cable is included with the sensor kit. The
cable has a red (+8 V), a black (negative), and a white (analog input positive) wire.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 21 of 49
The oil pressure sensor is an "absolute" sensor, as opposed to a "gauge" sensor. An absolute pressure sensor
measures pressure using vacuum as a reference. The sensor will read atmospheric pressure of 101.35 kPa
(14.7 psi) when there is no apparent pressure being applied to the gauge. When the generator set is not
running, this gauge will read 101.35 kPa (14.7 psi) even though the generator set has no oil pressure.
The oil pressure settings for idle speed, oil step, and rated speed must each be increased by 101.35 kPa
(14.7 psi) to be valid. Therefore, the calculation for "psi" is 14.7 psi + normal gauge reading (psi) =
absolute pressure gauge in psi.
For metric readings, the calculation would be 101.35 kPa + normal gauge reading (kPa) = absolute pressure
gauge in kPa.
The following is an example. If the idle speed oil pressure was measured at 117 kPa (17 psi), the absolute
pressure gauge reading will be 117 kPa (17 psi) + 101.35 kPa (14.7 psi) = 219.35 kPa (31.82 psi).
When configuring the oil pressure transducer parameters in the EMCP 4.4 control, use the following data:
When configuring the coolant temperature sensor parameters in the EMCP 4.4 control, use the following
data:
On some installations, the Governor shares the engine speed magnetic pickup unit (MPU) with the EMCP
control. A new MPU has been included with the kit to allow the EMCP 4.4 and the Governor to each have
a dedicated MPU.
Refer to Systems Operation, SENR3535, "Service Procedure F - Speed Sensor Adjustment" for installation
and setup of the new MPU.
The MPU engine speed sensor uses only two wires (white and black) of the supplied cable.
Install the sensors at the appropriate points on the generator set. Connect the sensors to the EMCP 4.4
control as per the schematic shown in Illustration 12, Illustration 13, and Illustration 15.
• E-Stop validation
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 22 of 49
Note: The engine speed sensor MPU white wire, terminal 2 to TB 302, in Table 6, is used by the EMCP 4.4
control.
Note: The engine speed sensor MPU white wire, terminal 2 to TB 323, listed in Table 6, is for use by the
electronic governor only.
Note: Prior to checking for continuity of the wiring from the generator output to the EMCP 4.4, ensure that
no voltage is present. Remove the three fuses that isolate the wiring from the generator output to the EMCP
4.4. Fuse removal will allow continuity checks of the wiring. Replace the fuses after the continuity checks
have been completed.
Note: The validation assumes that potential transformers are not being used.
Check for continuity between the following points that are listed in Table 6.
Table 6
FROM PIN TO PIN
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 23 of 49
Power On Tests
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 24 of 49
Connect the battery terminals to the battery. Connect the battery charger to the battery and insure the
battery charger is connected to an AC source.
Refer to Illustration 12 schematic for fuse terminal block identification. Use terminal block 201 as ground.
Check that there is battery (+) voltage on the following points:
• Fuse 9 terminal 2
• Fuse 8 terminal 2
• Fuse 7 terminal 2
• Fuse 6 terminal 2
• Fuse 5 terminal 2
• Fuse 4 terminal 2
• Fuse 2 terminal 2
• Fuse 1 terminal 2
Verify that the EMCP 4.4 control and annunciator panels have powered up.
Refer to Systems Operation Troubleshooting Testing and Adjusting, UENR1210, "Password Entry" for
information about EMCP 4.4 implemented security passwords.
Refer to Systems Operation Troubleshooting Testing and Adjusting, UENR1210, "Real-Time Clock
Programming" for information about how to set the time and date on the EMCP 4.4 control.
The EMCP 4.4 control does not have inputs for battery charger fault detection. Refer to Systems Operation
Troubleshooting Testing and Adjusting, UENR1210, "Digital Input Programming" for instructions on how
to set up digital inputs to monitor the battery charger status.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 25 of 49
1. Remove Fuse 6. Removing the fuse will prevent the fuel control relay (FCR) from:
2. If the observed generator set cranking cycle is not what is desired, review the times that have been set
in the "Cycle Crank Time" configuration.
3. The battery charger is to be disconnected while the generator set is cranking. Observe the battery
charger and note that the battery charging current drops to zero when the generator set is cranking.
4. Acknowledge the cranking cycle faults and reset the EMCP 4.4 control.
The following are steps to conduct the "Cranking Cycle" and "E-Stop" tests.
1. The E-Stop test will verify that the generator set cranking cycle can be stopped with the E-Stop
button. The generator set should not start, since the FCR has been previously disabled.
2. Press the "RUN" button and allow the generator set to go through the first crank/rest cycle. When the
second crank cycle begins, press the E-Stop button to verify that the generator set can be stopped.
3. Acknowledge the cranking cycle faults and reset the EMCP 4.4 control.
4. Replace "Fuse 6" to allow the fuel control relay (FCR) to function.
Disconnect or disable any speed governor, to prevent the generator set from running at rated speed.
The idle speed and E-stop test will verify that the generator set can be stopped at idle speed with the E-Stop
button.
1. Press the "RUN" button and allow the generator set to start and run at idle speed.
2. Press the E-Stop button to verify that the generator set will come to a controlled stop.
1. Press the "RUN" button on the EMCP 4.4 control panel. The generator set will start and run at idle
speed.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 26 of 49
Note: Check the coolant temperature as the generator set starts and verify that temperature is close to
the block temperature of the generator set. The check is to determine if the coolant temperature
sensor and related wiring are functional.
2. Allow the coolant temperature to stabilize and then read the following parameters from the "EMCP"
display.
3. All parameters values must be near the values recorded from "Baseline Generator Set Operating
Parameters". Any parameter value that is not close to the original parameter value data will need to
be investigated and resolved before proceeding.
Note: Regarding this section, the "Idle Speed Parameter Determination" must be investigated and
resolved before proceeding.
4. Press the "Stop" button on the EMCP 4.4. The generator set should come to a controlled stop.
5. Correct any issues that prevented the generator set from starting, idling, or verification of the idle
speed parameters.
The engine speed sensor loss test will verify that the generator set will stop if the engine speed sensor fails.
1. Push the "RUN" button and allow the generator set to start and run at idle speed.
2. Jumper terminal 302 to terminal 303. The generator set should shut down immediately. Loss of
engine speed results in an "Unexpected Engine Shutdown" fault. To recover from the fault, press the
RESET button that is on the front of the EMCP 4.4.
3. Restart the generator set and allow the generator to run at idle speed.
4. Disconnect the engine speed sensor from either terminal 302 or 303. The generator set should shut
down immediately. Reconnect the engine speed sensor and cycle the power on the EMCP 4.4.
5. Reconnect or enable the governor to allow the generator set to run at rated speed.
1. Push the "RUN" button on the EMCP 4.4. The generator set should crank, start, and run at idle speed
while building oil pressure. The EMCP 4.4 and governor will bring the generator set to rated speed
once idle speed and oil pressure conditions have been met.
2. After the generator set comes up to rated speed, monitor the coolant temperature as the temperature
rises. When the coolant temperature has stabilized, check the engine rated speed operating
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 27 of 49
parameters. Compare the engine rated speed operating parameters listed below against the values
recorded in "Determine Idle, and Rated, Speed Parameters".
3. Put the EMCP 4.4 into the "Stop Mode". Observe that the engine speed is reduced to idle while the
generator set cools down for the period recorded as "Cooldown Duration".
4. Reconnect or enable any previously disconnected or disabled speed governor. Correct any issues that
prevented the generator set from starting, idling, running at rated speed, cooling down or recording
the rated speed parameters.
Each of the following tests will require a jumper wire connected to ground. Connect a wire to terminal 201
to use for this purpose.
E-Stop Test
1. Use the EMCP 4.4 run button to start the generator set and allow the generator to come up to speed.
Do not wait for the generator set to warm up.
2. Using the ground wire, touch terminal 22 and verify that the generator set stops running.
3. If a remote "E-Stop" switch is part of the installation, connect the switch to the control using terminal
22 in the EMCP 4.4 control panel. Start the generator set and allow to come up to rated speed. Press
the remote "E-Stop" switch to verify that the switch works as intended.
4. Correct any issues that prevented the generator set from starting, idling, running at rated speed,
cooling down or stopping.
1. With the generator set stopped, and the EMCP 4.4 control in "Auto", touch the ground wire to
terminal 14. The generator set should crank, start, idle, and run at rated speed.
2. If a "Remote Initiate" switch is part of the installation, connect the switch to the control using
terminal 14 in the EMCP 4.4 panel. Press the "Remote Initiate" switch to verify that this switch
works as intended.
3. Stop the generator set using the "Stop" button on the EMCP 4.4 control panel.
4. Correct any issues that prevented the generator set from starting, idling, running at rated speed,
cooling down or stopping.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 28 of 49
The engine set point verification procedure verifies that the EMCP 4.4 operates correctly when a "Low Oil
Pressure" or a "High Coolant Temperature" event occurs. The engine set point verification procedure also
verifies that the EMCP 4.4 operates correctly when an "Engine Overspeed" event occurs.
Low oil pressure and high coolant temperature each have two events, "Warning" and "Shutdown". The
EMCP 4.4 will issue a warning whenever the warning threshold is reached. The EMCP 4.4 will issue a
shutdown whenever the shutdown threshold is reached. The verification procedure will modify
configuration set points used in normal operation. The following information outlines how to perform a
"Low Oil Pressure Shutdown" and a "High Coolant Temperature Shutdown" procedure. A similar process
can be used for a "Low Oil Pressure Warning" or a "High Coolant Temperature Warning", along with Low
Idle, Low Oil Pressure.
During the procedure, each configuration set point must be recorded prior to adjustment. Each
configuration set point must be returned to the original setting after the set point has been verified.
The following conditions are required before the engine set points are verified:
• The set points must be correct for the generator set application.
• No shutdown events should be present. If necessary, troubleshoot, correct, and reset any shutdown
events.
Note: The low oil pressure shutdown is disabled during start-up and while the generator set is not running
by the "Fault Protection Timer" (FPT). The fault protection timer starts timing when crank terminate rpm is
reached during the starting sequence. The fault protection timer will then run for a programmed time. The
time is determined by the "Engine Start Fault Protection Activation Delay Time" set point. Make sure that
the fault protection timer has elapsed before starting the "Low Oil Pressure Verification".
1. Start the generator set and run the generator set at rated speed.
2. Adjust the set point value for "Analog Input #1 Low Shutdown Event Threshold" to a value that is
above the oil pressure at which the generator set is operating. The shutdown event will occur after the
programmable time delay. The time delay is referred to as the "Analog Input #1 Low Shutdown
Event Delay Time" set point.
3. View the event by going to the EMCP 4.4 event log. Reset the event.
4. Return the set point value for "Analog Input #1 Low Shutdown Event Threshold" to the original
value.
Note: "Analog Input #2 High Shutdown" is disabled during start-up and while the generator set is not
running by the "Fault Protection Timer" (FTP). The fault protection timer starts timing when the "Crank
Terminate" rpm is reached during the starting sequence. The fault protection timer will then run for a
programmed time (the "Engine Start Fault Protection Activation Delay Time" set point). Make sure that the
fault protection timer has elapsed before starting the "High Coolant Temperature Verification".
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 29 of 49
1. Start the generator set and run the generator set at rated speed.
2. Adjust the set point value for "Analog Input #2 High Shutdown Event Threshold". Set the parameter
to a value that is below the engine coolant temperature that the generator set is operating at. The
minimum value for the set point is 49° C (120° F). The generator set may have to run for a few
minutes to get the temperature above the minimum value. The shutdown event will occur after the
programmable time delay which is the "Analog Input #2 High Shutdown Event Delay Time" set
point.
3. View the event by going to the EMCP 4.4 control event log. Reset the event.
4. Return the set point value for "Analog Input #2 High Shutdown Event Threshold" to the original
value.
1. Start the generator set and run the generator set at rated speed.
2. Adjust the set point value for "Engine Over Speed Setpoint" to a value that is below the speed that
the generator set is running at. An engine over speed set point event will occur immediately after the
set point is changed. The generator set will shut down.
3. View the event by going to the EMCP 4.4 control event log. Reset the event.
4. Return the set point value for the "Engine Overspeed Set point" to the original value.
Illustration 10 g06519236
Schematic for the EMCP4.4 application (With Terminal Block Relay). Refer to Illustration 15 for the legend.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 30 of 49
Illustration 11 g06552226
Schematic for the EMCP4.4 application (With hermetically sealed relay Relay).
Illustration 12 g06519244
Schematic for the EMCP4.4 application. Refer to Illustration 15 for the legend.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 31 of 49
Illustration 13 g06519397
Wiring diagram for the EMCP4.4application.
Illustration 14 g06552236
Hermetically sealed relay
Illustration 15 g06519264
Wiring diagram for the EMCP4.4 application.
Installation notes for Illustration 15. Illustration 15 is an example of the wiring of the original EMCP 1
drawings. The current transformers are wired so the current is 180 degrees out of phase with the voltage
causing a power factor of -1. The solution is to swap the white 51, 52, and 53 leads with the black leads that
are all labeled as 50.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 32 of 49
Illustration 16 g03557494
The parameters discussed in this section are accessed with Cat ET. The factory default values that are
provided are programmed into the EMCP 4.4.
Illustration 17 g03557496
The parameter indicates the level of security required to modify configuration parameters. The default
value is set to "0 - No Security", which means that everyone has access to the parameters.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 33 of 49
Illustration 18 g03557498
Illustration 19 g03557501
Configuration of the "Engine Service Hours" is done by selecting the "Information" tab. Then, from the
drop-down menu, click "Current".
Display Preferences
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 34 of 49
Illustration 20 g03557502
Illustration 21 g03557504
Analog Inputs
During normal operation, there are two analog inputs from the generator set to the EMCP. The inputs are
listed as "Analog Input #1" for the engine oil pressure, and "Analog Input #2" for the engine coolant
temperature.
Each of the two analog inputs triggers an event code when the set values are exceeded. The nominal default
values for the two analog inputs are set at the factory prior to shipping.
"Analog Input #1" is associated with a "Low Shutdown Threshold" event, and "Analog Input #2" is
associated with a "High Coolant Temperature Shutdown" event.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 35 of 49
A "Low Shutdown Event Threshold" is listed as "Analog Input #1 Low Shutdown Event Threshold". The
range of the parameter is 13.4 kPa (2 psi) to 880 kPa (128 psi). The factory default value is set at 150 kPa
(22 psi).
Illustration 22 g03731251
Note: The Minimum and Maximum Data Range units for pressure are kilo Pascals (kPa). The Minimum
and Maximum Data Range units for temperature are Centigrade Degrees. All configuration parameters
are entered in SI (Metric) units even though the display may show English units.
A "High Coolant Temperature Shutdown" is listed as "Analog Input #2 High Shutdown Event Threshold".
The range of the parameter is 95° C (203° F)to 120° C (248° F). The factory default value is set at 108° C
(226° F).
Automatic Start/Stop
Configuration of the automatic start/stop parameters is done using Cat ET. The parameters are discussed in
the following sections.
The "Cycle Crank Configuration" is listed as "Crank Duration". The range of the parameter is 1 to 60
seconds. The default value is set at 10 seconds.
The range of the parameter is 1 to 60 seconds. The default value is set at 5 seconds.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 36 of 49
The "Cool down Configuration" is listed as "Cool down Duration". The range of the parameter is 0 to 30
minutes. The default value is set at 5 minutes.
The "Crank Termination Speed Configuration" is listed as "Crank Terminate RPM". The range of the
parameter is 100 to 1000 rpm. The default value is set at 300 rpm.
Illustration 23 g03565819
The "Engine Fuel Type Configuration" value will always read "Diesel", cannot be changed, and will not
affect the operation of a gas generator set.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 37 of 49
Illustration 24 g03565797
The "Idle Speed Oil Pressure Shutdown" is listed as "Low Idle Low Engine Oil Pressure Shutdown Event
Threshold". The range of the parameter is 20 kPa (3 psi) to 420 kPa (61 psi).The default value is set at
207 kPa (30 psi).
Low Idle Low Engine Speed Oil Pressure Warning Event Threshold
The range of the parameter is 22 kPa (3.2 psi) to 462 kPa (67 psi). The default value is set at 241.3 kPa
(35 psi). The value of the parameter must be set at least 110% of the value of the "Idle Speed Oil Pressure
Shutdown" parameter.
Illustration 25 g03557512
The "Oil Step Speed" parameter is listed as "Low Engine Oil Pressure Step Speed". The range of the oil
step speed parameter is 400 to 1800 RPM. The default value is set at 400 RPM.
The "Ring Gear Teeth" parameter is listed as "Flywheel Teeth". The range of the ring gear teeth parameter
is 110 to 260. The default value is set at 183.
Over Speed
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 38 of 49
Illustration 26 g03557513
The "Over Speed" parameter is listed as "Engine Overspeed Setpoint". The default value is set at 1540
RPM. The engine over speed set point value is generator set-specific.
Illustration 27 g03557514
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 39 of 49
Illustration 28 g03707582
Cat service tool CAN 2 annunciator default configuration values dialog
The EMCP CAN annunciator serves to display system alarm conditions and status indications. The CAN
annunciator has been designed for use on the EMCP accessory CAN data link. The CAN annunciator may
be used in either local or remote applications. The CAN annunciator provides customers with enhanced site
flexibility.
In local application, the CAN annunciator may be mounted on the package generator set with the EMCP to
provide a complete package-mounted monitoring solution.
The CAN annunciator also may be mounted separately from the generator set. A remotely mounted
annunciator provides remote indication of system operating and alarm conditions.
Refer to Systems Operation Troubleshooting Testing and Adjusting, UENR1210, "Annunciator Module"
for annunciator features, specifications, wiring, and comprehensive discussion of annunciator features.
Illustration 29 g03558919
Illustration 29 provides the location of the status light indicators for the module network system on the
annunciator. Refer to Table 7 for an explanation of the status lights.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 40 of 49
Table 7
Module Network Status
Icon List
Illustration 30 g03558842
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 41 of 49
• A 9-pin Deutsch connector, for the service connection to the "Primary Datalink (CAN 1)"
• A 9-pin Deutsch connector, for the service connection to the "Accessory Datalink (CAN 2)"
• The new application software flash file for the EMCP 4.4
Note: The new software is available in the form of a flash file through the Caterpillar Service Information
System (SIS). A newer part number may be available. SIS web only displays the latest available flash file.
Note: The configuration file is the most recent .xml file and is subject to change.
Note: The new software is available in the form of a flash file through the Caterpillar Service Information
System (SIS). A newer part number may be available. SIS web only displays the latest available flash file.
Note: The configuration file is the most recent .xml file and is subject to change.
Illustration 31 g03560896
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 42 of 49
1. Connect to the EMCP 4.4, using the Cat Service Tool, to the CAN 2 port.
The message, "No data is available. Load from the ECM now?", will appear. Click "No".
Illustration 32 g03560898
2. After the desired changes are completed, click "Load from File" at the "Fleet Configuration" dialog
to save the file.
Illustration 33 g03560916
3. Navigate to the .xml file. Click "Open". Refer to the "General Kit Information" for the most recent
(.xml) configuration file . A dialog will appear to confirm that the file was loaded. Refer to
Illustration 33.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 43 of 49
Illustration 34 g03560917
4. Select which control configuration data is to be programmed into the EMCP 4.4 by clicking the box
to the left of the parameter. A check mark must appear next to the parameter that is to be added. If a
parameter is not desired, do not click that parameter. If the box has a check mark, but that parameter
is not desired, click the box again to remove the check mark for that parameter. Refer to Illustration
33 as an example of having the boxes checked next to the desired parameters. After any selection
changes are completed, click "Program ECM" from the bottom of the ECM Replacement dialog to
load the file into the EMCP 4.4.
Illustration 35 g03560918
The dialog in Illustration 35 will appear to confirm that programming the ECM is completed.
Annunciator Control
The annunciator control is only accessible through the CAN 2 port/Accessory datalink. In the case of the
annunciator, ECM replacement should be used via the CAN 2 port/Accessory datalink only.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 44 of 49
Illustration 36 g03560920
Cat Service Tool EMCP 4.4 summary dialog
1. Connect to the EMCP 4.4, using the Cat Service Tool, to the CAN 2 port. From the "Cat Service
Tool" menu, select the following.
Illustration 37 g03560922
2. The Cat ET dialog shown in Illustration 37 will appear. The dialog will have the message "No data is
available. Load from the ECM now?". Click "Yes" .
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 45 of 49
Illustration 38 g03560923
3. Select "Alarm Module #1" from the ECM list. The alarm module will allow the software to connect
to the annunciator.
Illustration 39 g03560924
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 46 of 49
Illustration 40 g03560928
5. After the data is loaded, the current file parameters will be displayed.
6. Select which control configuration data is to be programmed into the EMCP 4.4 by clicking the box
to the left of the parameter. A check mark must appear next to the parameter that is to be added. If a
parameter is not desired, do not click that parameter. If the box has a check mark, but that parameter
is not desired, click the box again to remove the check mark for that parameter. Refer to Illustration
33 as an example of having the boxes checked next to the desired parameters.
Illustration 41 g03560998
7. After the desired changes are completed, click "Save to File" to save .xml the file. Make sure to note
where the file is stored.
1. Connect to the EMCP 4.4, using the Cat Service Tool, to the CAN 2 port. From the "Service Tool"
menu, select the following.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 47 of 49
Illustration 42 g03561017
2. After the desired changes are completed, click "Load from File" to save the file.
Illustration 43 g03561019
3. Navigate to the desired file and click "Open". Refer to the "General Kit Information" for the most
recent configuration file (.xml). The software will confirm that the file has been opened. Refer to
Illustration 43.
4. Select which control configuration data is to be programmed into the EMCP 4.4 by clicking the box
to the left of the parameter. A check mark must appear next to the parameter that is to be added. If a
parameter is not desired, do not click that parameter. If the box has a check mark, but that parameter
is not desired, click the box again to remove the check mark for that parameter. Refer to Illustration
33 as an example of having the boxes checked next to the desired parameters.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 48 of 49
Illustration 44 g03561020
5. After the desired changes are completed, click "Program ECM" to load the file into the EMCP 4.4.
Illustration 45 g03561022
7. Click "Yes".
Illustration 46 g03561023
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024
Systems & Components - REHS9132 - Procedure to Upgrade EMCP 1, EMCP 2, EMC... Page 49 of 49
Illustration 47 g03561026
Illustration 48 g03561028
Copyright 1993 - 2024 Caterpillar Inc. Thu Jan 25 21:00:28 UTC-0400 2024
All Rights Reserved.
Private Network For SIS Licensees.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 1/25/2024