HVAC Balancing Report

This document contains air balancing parameters for 3 packaged air conditioning units (PAC-01, PAC-02, and PAC-03) at a McDonald's restaurant. It shows the design and measured values for factors like supply air flow, temperature, humidity, voltage, and sound levels. Signatures from the client, HVAC contractor, and third party testing, adjusting and balancing company are at the bottom to verify the work.

Uploaded by

Hassan Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
137 views13 pages

HVAC Balancing Report

This document contains air balancing parameters for 3 packaged air conditioning units (PAC-01, PAC-02, and PAC-03) at a McDonald's restaurant. It shows the design and measured values for factors like supply air flow, temperature, humidity, voltage, and sound levels. Signatures from the client, HVAC contractor, and third party testing, adjusting and balancing company are at the bottom to verify the work.

Uploaded by

Hassan Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

CLIENT HVAC CONTRACTOR THIRD PARTY TAB

AIR SIDE BALANCING PARAMETERS


UNIT TAG NUMBER: PAC-01 MODEL: PACS-52045 CM COMPANY: SKM
Sr # Description Unit Design After Balancing Remarks

INDOOR UNIT
1 Supply Air Flow CFM 8500 7616

2 Fresh Air Flow CFM 2600 2306 FA 75 % open

3 Environment Dry Bulb Temp. Deg ºC 9.6


4 Environment Wet Bulb Temp Deg ºC 7.6

5 Space Dry Bulb Temp. Deg ºC 26.76


6 Space Wet Bulb Temp Deg ºC 17.62

7 Space Related Humiduty %RH 37.1


8 Ambient Related Humiduty %RH 71.17
9 Indoor`s Fan Blower Speed RPM 1112

10 Indoor`s Fan Motor Speed RPM 1750 1395


11 Unit Current Amps 71.8,72.1,72.2 Amps taken from main panel

12 Indoor`s Motor Capacity KW 5.5 5.5


13 Unit Voltage V 400 417,413,416 Voltage taken from main panel
14 Unit Sound Level with Heating DB 64 Thermoset at 22 ºC
mode
15 Enviorment Sound Level DB 60.8

16 Indoor`s Fan Pulley Size Dia 170 mm

17 Indoor`s Motor Pulley Size Dia 138 mm

18 Status of Filter Cleaning clean filters should be clean on


monthly basis

Signature: Signature: Signature:

Name of Client: Name of HVAC Contactor: Name of TAB:


CLIENT HVAC CONTRACTOR THIRD PARTY TAB
AIR SIDE BALANCING PARAMETERS
UNIT TAG NUMBER: PAC-02 MODEL: PPHc 160-2 COMPANY: PETRA
Sr # Description Unit Design After Balancing Remarks

INDOOR UNIT
1 Supply Air Flow CFM 3918 2668

2 Fresh Air Flow CFM 435 550 FA 100 % open

3 Environment Dry Bulb Temp. Deg ºC 9.6


4 Environment Wet Bulb Temp Deg ºC 7.6
5 Space Dry Bulb Temp. Deg ºC 23.8

6 Space Wet Bulb Temp Deg ºC 15.9

7 Space Related Humiduty %RH 33.9


8 Ambient Related Humiduty %RH 71.17

9 Indoor`s Fan Blower Speed RPM 1200 862


10 Indoor`s Fan Motor Speed RPM 1464 1485

11 Unit Current Amps 4.2,4.9,4.5 Amps taken from main panel


12 Indoor`s Motor Capacity KW 3 3

13 Unit Voltage V 400 414,413,411 Voltage taken from main panel


14 Unit Sound Level with Heating DB 62 Thermoset at 22 ºC
mode
15 Enviorment Sound Level DB 60
16 Indoor`s Fan Pulley Size Dia 213 mm

17 Indoor`s Motor Pulley Size Dia 137 mm


18 Status of Filter Cleaning clean filters should be clean on
monthly basis

Signature: Signature: Signature:

Name of Client: Name of HVAC Contactor: Name of TAB:


CLIENT HVAC CONTRACTOR THIRD PARTY TAB
AIR SIDE BALANCING PARAMETERS
UNIT TAG NUMBER: PAC-03 MODEL: PPHc 195 COMPANY: PETRA
Sr # Description Unit Design After Balancing Remarks

INDOOR UNIT
1 Supply Air Flow CFM 3006 3076
2 Fresh Air Flow CFM 611 640 FA 70% open
3 Environment Dry Bulb Temp. Deg ºC 9.6
4 Environment Wet Bulb Temp Deg ºC 7.6
5 Space Dry Bulb Temp. Deg ºC 24.07
6 Space Wet Bulb Temp Deg ºC 16
7 Space Related Humiduty %RH 38.2
8 Ambient Related Humiduty %RH 71.17
9 Indoor`s Fan Blower Speed RPM 2200 1393
10 Indoor`s Fan Motor Speed RPM 1464 1475
11 Unit Current Amps 27.7,25.2,26.1 Amps taken from main panel
12 Indoor`s Motor Capacity KW 3 3
13 Unit Voltage V 400 414,411,413 Voltage taken from main panel
14 Unit Sound Level with Heating DB 63.4 Thermoset at 22 ºC
mode
15 Enviorment Sound Level DB 61.6
16 Indoor`s Fan Pulley Size Dia 136 mm
17 Indoor`s Motor Pulley Size Dia 136 mm
18 Status of Filter Cleaning clean filters should be clean on
monthly basis

Signature: Signature: Signature:

Name of Client: Name of HVAC Contactor: Name of TAB:


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

UNIT TEST REPORT


UNIT TAG PAC-01 SYSTEM SUPPLY AIR

LOCATION ROOF TOP SUPPLY AIR 8500 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 7616 CFM

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN PRELIMINARY FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW (CFM) FLOW (CFM)

Hall 1 Diffuser 18'' X 18'' 597 603 491


Hall 2 Diffuser 18'' X 18'' 597 540 527
Hall 3 Diffuser 18'' X 18'' 597 477 541
Hall 4 Diffuser 18'' X 18'' 597 709 557
Hall 5 Diffuser 18'' X 18'' 597 373 506
Hall 6 Diffuser 18'' X 18'' 597 468 533
Hall 7 Diffuser 18'' X 18'' 597 550 409
Hall 8 Diffuser 18'' X 18'' 597 870 478
Hall 9 Diffuser 18'' X 18'' 597 820 517
Hall 10 Linear Diffuser 36'' X 1'' 447 445 621
Hall 11 Linear Diffuser 36'' X 1'' 447 300 410
Hall 12 Linear Diffuser 36'' X 1'' 447 224 320
Hall 13 Linear Diffuser 36'' X 1'' 447 405 460
Entrance 14 Grille 8'' X 8'' 127 47 116
Play Area 15 Grille 16'' X 16'' 600 658 560
Play Area 16 Grille 16'' X 16'' 600 702 570

TOTAL 8488 8191 7616

REMARKS:
No VCD is given to linear diffusers

Technician Name: Jamal TEST DATE : 21-12-2020


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

UNIT TEST REPORT


UNIT TAG PAC-01 SYSTEM RETURN AIR

LOCATION ROOF TOP RETURN AIR 5900 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 5500 CFM

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN PRELIMINARY FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW (CFM) FLOW(CFM)

Hall 1 Grille 15'' X 15'' 980 420 358


Hall 2 Grille 15'' X 15'' 980 685 592
Hall 3 Grille 15'' X 15'' 980 1174 929
Hall 4 Grille 15'' X 15'' 980 1592 1317
Hall 5 Grille 15'' X 15'' 980 1292 1054
Play Area 6 Grille 12'' X 12'' 500 540 500
Play Area 7 Grille 12'' X 12'' 500 828 750

TOTAL 5900 6531 5500

REMARKS:
No VCD and levers are given in return grills

Technician Name: Jamal TEST DATE : 21-12-2020


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

UNIT TEST REPORT


UNIT TAG PAC-02 SYSTEM SUPPLY AIR

LOCATION ROOF TOP SUPPLY AIR 3918 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 2668 CFM

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN PRELIMINARY FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW (CFM) FLOW (CFM)

Kitchen 1 Two Way Diffuser 24'' X 24'' 690 478 570


Kitchen 2 Two Way Diffuser 24'' X 24'' 690 470 580
Kitchen 3 Two Way Diffuser 24'' X 24'' 690 427 526
Kitchen 4 Two Way Diffuser 24'' X 24'' 690 288 317
Kitchen 5 Diffuser 15'' X 15'' 386 375 237
Kitchen 6 Diffuser 15'' X 15'' 386 319 212
Kitchen 7 Diffuser 15'' X 15'' 386 391 226

TOTAL 3918 2748 2668

REMARKS:
No VCD and lever is given in two way diffuser # 1,2 & 3

Technician Name: Jamal TEST DATE : 21-12-2020


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

UNIT TEST REPORT


UNIT TAG PAC-02 SYSTEM RETURN AIR

LOCATION ROOF TOP RETURN AIR 3485 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 2118 CFM

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN PRELIMINARY FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW (CFM) FLOW (CFM)

Lobby 1 Grille 12'' X 12'' 485 280 286


Kitchen 2 Grille 15'' X 15'' 750 463 508
Kitchen 3 Grille 15'' X 15'' 750 742 793
Kitchen 4 Grille 15'' X 15'' 750 315 330
Kitchen 5 Grille 15'' X 15'' 750 176 201

TOTAL 3485 1976 2118

REMARKS:
No VCD and levers are given in return grills

Technician Name: Jamal TEST DATE : 21-12-2020


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

UNIT TEST REPORT


UNIT TAG PAC-03 SYSTEM SUPPLY AIR

LOCATION ROOF TOP SUPPLY AIR 3006 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 3076 CFM

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN PRELIMINARY FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW (CFM) FLOW (CFM)

Lobby 1 Two Way Diffuser 24'' X 24'' 250 445 420


Lobby 2 Two Way Diffuser 24'' X 24'' 250 359 280
Lobby 3 Two Way Diffuser 24'' X 24'' 250 340 223
Control Room 4 Diffuser 10'' X 10'' 272 557 283
Kitchen 5 Two Way Diffuser 24'' X 24'' 620 562 603
Kitchen 6 Two Way Diffuser 24'' X 24'' 620 28 560
Kitchen 7 Diffuser 18'' X 18'' 300 637 270
Washroom 8 Diffuser 8'' X 8'' 110 267 108
Washroom 9 Diffuser 8'' X 8'' 110 210 90
Staff Washroom 10 Diffuser 12'' X 12'' 224 240 239

TOTAL 3006 3645 3076

REMARKS:
No VCD and lever is given in two way diffuser # 1

Technician Name: Jamal TEST DATE : 21-12-2020


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

UNIT TEST REPORT


UNIT TAG PAC-03 SYSTEM RETURN AIR

LOCATION ROOF TOP RETURN AIR 2395 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 2448 CFM

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN PRELIMINARY FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW (CFM) FLOW (CFM)

Staff Washroom 1 Grille 8'' X 6'' 105 103 90


Kitchen 2 Grille 14'' X 14'' 680 592 560
Kitchen 3 Grille 14'' X 14'' 680 807 755
Kitchen 4 Grille 14'' X 14'' 680 636 620
Control Room 5 Grille 10'' X 10'' 250 482 423

TOTAL 2395 2620 2448

REMARKS:
No VCD and levers are given in return grills

Technician Name: Jamal TEST DATE : 21-12-2020


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

FAN TEST REPORT


UNIT TAG EAF-03 (1-2) SYSTEM EXHAUST AIR

LOCATION KITCHEN EXHAUST AIR 720 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 650 CFM

AMPERE (A) 1.36 VOLTAGE (V) 220 PHASE 1 POWER (kW) 0.3

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW(CFM)

Kitchen 1 Round Duct 10" Dia 720 650

TOTAL 720 650

REMARKS:
No VCD are given in exhaust duct

Technician Name: Jamal TEST DATE : 21-12-2020


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

FAN TEST REPORT


UNIT TAG EAF-03 (2-2) SYSTEM EXHAUST AIR

LOCATION KITCHEN EXHAUST AIR 720 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 660 CFM

AMPERE (A) 1.36 VOLTAGE (V) 220 PHASE 1 POWER (kW) 0.3

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW(CFM)

Kitchen 1 Round Duct 10" Dia 720 660

TOTAL 720 660

REMARKS:
No VCD are given in exhaust duct

Technician Name: Jamal TEST DATE : 21-12-2020


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

FAN TEST REPORT


UNIT TAG EAF-04 (1-1) SYSTEM EXHAUST AIR

LOCATION KITCHEN EXHAUST AIR 1175 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 1050 CFM

AMPERE (A) 2.27 VOLTAGE (V) 220 PHASE 1 POWER (kW) 0.5

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW(CFM)

Kitchen 1 Round Duct 12" Dia 1175 1050

TOTAL 1175 1050

REMARKS:
No VCD are given in exhaust duct

Technician Name: Jamal TEST DATE : 21-12-2020


CLIENT HVAC CONTRACTOR THIRD PARTY TAB

PROJECT: McDonald's Peshawar Road Rawalpindi

FAN TEST REPORT


UNIT TAG EAF-02 (1-1) SYSTEM EXHAUST AIR

LOCATION CUSTOMER WASHROOM EXHAUST AIR 720 CFM

TRAVERSE FLOW N/A DIFFUSER FLOW 413 CFM

AMPERE (A) 1.81 VOLTAGE (V) 220 PHASE 1 POWER (kW) 0.4

DIFFUSER TEST REPORT

LOCATION REGISTER, GRILLE, DIFFUSER DESIGN FINAL


OR
ADDRESS NUMBER TYPE SIZE FLOW (CFM) FLOW (CFM)

Washroom 1 Disk Valve 6" Dia 80 42

Washroom 2 Disk Valve 6" Dia 80 35

Washroom 3 Disk Valve 6" Dia 80 37

Washroom 4 Disk Valve 6" Dia 80 51

Washroom 5 Disk Valve 6" Dia 80 34

Washroom 6 Disk Valve 6" Dia 80 50

Washroom 7 Disk Valve 6" Dia 80 73

Washroom 8 Disk Valve 6" Dia 80 42

Washroom 9 Disk Valve 6" Dia 80 49

TOTAL 720 413

REMARKS:
No VCD are given in exhaust duct

Technician Name: Jamal TEST DATE : 21-12-2020