T Series - Field converters
T201DCH100-LP - T201DCH300-LP
EN Contact-less direct and alternating
TRMS current transducer
General Specifications
Direct and alternating current transducer
galvanically insulated from the measuring circuit
Measurement principle: Hall Effect
Possibility to measure the direct and alternating
component of TRMS current
No shunt, no wasted power of primary current
Circuit and no dissipation.
Unipolar or bipolar measurement.
High measurement accuracy: 0.5% 1%.
Suitable for Seneca modules with power supply
sensors at 12V and input 4 - 20 mA.
Two DIP-Switches selectable ranges.
Damping filter availability to improve stable
reading.
Suitable for batteries, battery chargers, solar
panels, power units and generic dc loads.
Compact dimensions: 96,5 x 68 x 26 mm.
SENECA s.r.l.
Via Austria, 26 – 35127 – PADOVA – ITALY
Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287
Manuals and configuration software are available at website:
www.seneca.it/products/t201dch100-lp and www.seneca.it/products/t201dch300-lp
Technical support: [email protected] Product Informations: sales@seneca.
This document is property of SENECA Srl. Duplication and reproduction are forbidden, if not authorized.
Contents of the present documentation refers to products and technologies described in it.
All technical data contained in the document may be modified without prior notice.
Content of this documentation is subject to periodical revision.
MI00450-1-EN ENGLISH - 1/4
Technical features
INPUT
Measure type AC / DC TRMS or Bipolar DC.
Range T201DCH100- 0 – 50A or 0 – 100A TRMS; -50 – +50A or -100 – +100A Bipolar
LP 0 – 300A or 0 – 150A TRMS; -150 – +150A or -300 – +300A Bipolar
Range T201DCH300- (selectable by dip-switch.).
Peak factor 1.3
Bandwidth 1 kHz
When a sheathed wire is used, the insulation voltage is set by
Insulation
sheath properties. On a bare wire, it’s stated to 3 kV .
Over-current 2000 A impulsive, 500 A permanent.
OUTPUT AND POWER SUPPLY
Type 4 – 20 mA, max. load RLOAD=600 Ω. Screw terminals: and .
Terminals Screw terminal pitch 5.08mm for max 2.5 mm2 cables.
Hole diameter 20.8 mm
Power supply 9 – 28 V (between and )
- Polarity reversal
Protections
- Over-Voltage
Fail indication < 3.8 mA
Max. indication < 22 mA
PRECISION
Range Precision Precision
Over the 2% 100 A or 300 A 0.5% of end scale. 1% of end scale.
of End of Scale 50 A or 150 A 1% of end scale. 2% of end scale.
Under the 2% 100 A or 300 A 1% of end scale. 2% of end scale.
of End of Scale 50 A or 150 A 2% of end scale. 4% of end scale.
Resolution Output: 10 bit (1000 points) Input: 12 bit (4000 points).
Temperature coefficient < 200 ppm/°C.
Error due to EMI < 1%
- Fast filter: 500 ms.
Response time
- Slow filter: 1000 ms.
Measure hysteresis 0.3% of the end scale (typical)
OVERVOLTAGE CATEGORY
Bare conductor CAT. III 300V
Insulated conductor CAT. III 600V
MI00450-1-EN ENGLISH - 2/4
OPERATING CONDITION
Protection degree IP20.
Operating temperature -20 – +70 °C.
Storage Temperature -40 – +85 °C.
Humidity 10 – 90 % non-condensing.
Altitude Up to 2000 m a.s.l.
CASE
Weight 47 g.
Overall dimensions 96,5 x 68 x 26 mm (without terminals)
Box material PA6, black color
STANDARDS
EN61326 (EMC requirements)
EN61010-1 (safety)
DIP-switches
Range Filter (10% – 90%) Mode Not Used
1 DCH100 DCH300 2 DCH100 - 300 3 DCH100 - 300 4 DCH100 - 300
0 – 100A 0 – 300A Filter = 500ms TRMS /
Filter = 1000ms
Must be OFF
0 – 50A 0 – 150A Bipolar
In the table the symbol corresponds to the switch in the ON position.
The instrument is factory delivered with range:
100A (T201DCH100-LP) or 300A (T201DCH300-LP), 800ms filter and RMS mode.
TRMS Output (mA)
output (mA)
20 20
Bipolar
12 12
4 ±50 ±100 -100 -50 4 +50 +100
±150 ±300 -300 -150 +150 +300
Input (A) Input (A)
MI00450-1-EN ENGLISH - 3/4
Mounting
The device can be located in any position and place, in accordance with the operating
conditions above stated. Use the included holder bracket when fixing to a DIN rail.
WARNING: High-strength magnetic fields may change the measured output value:
Let avoid closeness to permanent magnets, electromagnets or iron bulks that cause
such a modification of the surrounding magnetic field; try a different arrangement or
orientation if zero error was greater than expected.
Multi-turn primary winding to improve sensibility
You can increase the sensibility of the device simply passing several times in the hole
w i t h t h e m e a s u r i n g c u r r e n t , r e a l i z i n g t u r n s w i t h m u l t i p l i c a t i v e e ff e c t :
For example, passing 5 times in the hole, as to see 4 turns, choosing a 50 A range,
you get an equivalent sensibility of 10 A full-scale. When you make this, let dispose the
turns with symmetry in order to preserve accuracy: use diametric contraposition with 2
turns, cross disposition with 4 turns, with 6 turns at 60° and so on.
Disposal of electrical & electronic equipment (applicable throughout the EU and other countries
with separate collection programs). This symbol, found on your product or on its packaging,
indicates that this product should not be treated as household waste when you wish to
dispose of it.Instead,it should be handed over to an applicable collection point for the recycling
of electrical and electronic equipment. By ensuring this product is disposed of correctly, you will
help prevent potential negative consequences to the environment and human health, which could
otherwise be caused by inappropriate disposal of it. The recycling of materials will help to conserve
natural resources. For more detailed information about the recycling of this product, please contact
your local city office, waste disposal service or the retail store where you purchased this product.
MI00450-1-EN ENGLISH - 4/4