SpaceLogic RP-C 24 V Controller Models Installation Sheet

This document provides installation instructions for SpaceLogic RP-C 24 V controller models. It contains information on safety, technical literature, dimensions, installation orientation, mounting on DIN rails or flat surfaces, connecting optional covers, wiring connections, part numbers, and specifications. Connecting devices must have SELV/PELV inputs/outputs and the input power polarity and voltage must match the controller specifications to avoid damage.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
223 views4 pages

SpaceLogic RP-C 24 V Controller Models Installation Sheet

This document provides installation instructions for SpaceLogic RP-C 24 V controller models. It contains information on safety, technical literature, dimensions, installation orientation, mounting on DIN rails or flat surfaces, connecting optional covers, wiring connections, part numbers, and specifications. Connecting devices must have SELV/PELV inputs/outputs and the input power polarity and voltage must match the controller specifications to avoid damage.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Installation Sheet 02-40057-04-en, April 2023 | 1

SpaceLogic™ RP-C 24 V
Controller Models
Part numbers: SXWRCF12A10002, SXWRCF12B10002, SXWRCF12C10002, and SXWRCF16B10001
Safety Information
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this material.
Carefully read these instructions and all information relevant for this product before trying to install it. See the list of technical literature.
Technical Literature
• SpaceLogic and EasyLogic - Hardware Reference Guide, 04-XX001-XX-en
The technical literature and declarations of conformity can be accessed on the Schneider Electric extranet, ecoxpert.se.com. Contact your
local Schneider Electric sales office for a hard copy of the documentation or for additional information.
Dimensions
mm 180 (7.1) 64 (2.5)
(inches) 50 (2.0)
Optional
cover

110
(4.3) 44
117 (1.7)
(4.6)
164
(6.5)

12 (0.5)

44 (1.7)

Installation Orientation Restrictions Installing the Device on a DIN Rail


Normal operation, 0 to 50 °C (32 to 122 °F):
NOTICE
CONTROLLER DAMAGE
Use the DIN rail end clip when you install the controller on a
vertical DIN rail.
Failure to follow these instructions can result in equipment
damage.

1
Rooftop application, -40 to +60 °C (-40 to +140 °F):

2
02-40057-04-en, April 2023 | 2

Installing the Device on a Flat Surface

72 (2.8)

mm (inches)

Drill
Template 5 (0.2)

Scale 1:1
Wall Anchor (3x)
(Optional)

86
(3.4) No. 8 or M4 (4 mm)
Pan Head Self-tapping
Screw (3x)

1 inch = 25.4 mm

Important:
When printing this
template on paper, use
the scale marks above
to verify the template
is printed correctly.

Installing and Removing the Optional Covers


Installation: Removable knockouts

1
2 3
Click!

4 Repeat steps 1 to 3
Removal:
2
Insert tool here
1
3

Connections

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Disconnect all line voltage connected to the controller and its relay outputs before working on the device.
• More than one disconnect switch may be required to de-energize this equipment before servicing.
• Connect only devices with safe extra low voltage equipment (SELV/PELV) inputs/outputs to the controller universal inputs/outputs.
Failure to follow these instructions will result in death or serious injury.
02-40057-04-en, April 2023 | 3

Connections, continued

NOTICE
CONTROLLER DAMAGE
Before powering up RP-C, ensure that the input power polarity is correct and that the voltage level meets the specifications of the controller.
Failure to follow these instructions can result in equipment damage.

Torque: 0.56 to 0.79 Nm (5 to 7 lbf.in)

RP-C-12A-F-24V
B

B Cable tie anchor point (x4)

RP-C-12B-F-24V
B

RP-C-12C-F-24V
B

RP-C-16B-F-24V
B

B
02-40057-04-en, April 2023 | 4

Wiring
Recommended screw tightening torque: 0.56 to 0.79 Nm (5 to 7 lbf.in)
For information on wiring, see the SpaceLogic and EasyLogic - Hardware Reference Guide.
Part Numbers
Product Part number

RP-C-12A-F-24V SXWRCF12A10002

RP-C-12B-F-24V SXWRCF12B10002

RP-C-12C-F-24V SXWRCF12C10002

RP-C-16B-F-24V SXWRCF16B10001

Optional covers SXWRPCCOV10001

DIN-rail end clip, 25 pieces SXWDINEND10001

Isolated RS-485 adapter (cable not included) SXWISORS48510001

Non-isolated RS-485 adapter (cable not included) SXWNISORS48510001

RS-485 power adapter (cable not included) SXWNISORS485P10001

For more information on the RS-485 adapters and the cable required, see the RS-485 Adapter and RS-485 Power Adapter Installation Sheets.

Specifications
AC input Approved external antenna (optional) Voltage output rating
Nominal voltage Manufacturer: Linx Technologies, Model: 0 to 10 VDC , 2.4 kohm (min.)
24 VAC 50/60 Hz ANT-2.4-WRT-MON-SMA, Gain: 0.8 dBi, Channels
Power consumption Type: Monopole, Impedance: 50 ohm, RP-C-12A: 8; -12B: 8; -12C: 4; -16B: 8
RP-C-12A: 23 VA; -12B: 23 VA; -12C: 23 VA; Connector: SMA
-16B: 30 VA DO – Relay outputs
Operation environment Relay contact rating
DC input Ambient temperature, operating Pilot Duty (C300)
Nominal voltage 0 to 50 °C (32 to 122 °F) at normal operation Min. current: 100 mA (5 VDC)
24 to 30 VDC -40 to +60 °C (-40 to +140 °F) for rooftop Resistive: 250 VAC / 30 VDC ,
Power consumption applications, horizontal installation only 4 A (cos phi = 1)
RP-C-12A: 14 W; -12B: 14 W; -12C: 14 W; See section Installation Orientation Inductive: 250 VAC / 30 VDC ,
-16B: 16 W Restrictions. 4 A (cos phi = 0.4)
Humidity Channels
Port types Maximum 95 % RH non-condensing RP-C-12A: 0; -12B: 3; -12C: 3; -16B: 3
USB device port
Mini-B Mechanical DO – High power relay outputs
USB host port Ingress protection rating Relay contact rating
Type-A, 5 VDC, 0.5 A IP 20 Pilot Duty (B300)
Ethernet port 1 and 2 Plastic flame rating Normally Open, resistive: 250 VAC
10/100BASE-TX RJ45 UL94-5VB / 24 VDC , 12 A (cos phi = 1)
RS-485 port Com A and Com B Plenum rating Normally Closed, inductive: 250 VAC
24 VDC, 3 W, RS-485 (RJ45) UL 2043 (Approved for plenum installations) / 24 VDC , 3 A (cos phi = 0.4)
Channels
Wireless connectivity IP networking RP-C-12A: 0; -12B: 1; -12C: 1; -16B: 1
Bluetooth® Low Energy (Bluetooth® 5) IP address assignment methods
2.402 to 2.480 GHz, max. 10 dBm output Static, DHCP (default), Auto-IP (address DO – Solid-state relay outputs
power, 100 m (328 ft) line-of-sight range range 169.254.0.1 to 169.254.255.254, Output rating
Antenna subnet mask 255.255.0.0) 30 VAC / 30 VDC ,2A
Integrated antenna Max. 4 A total load
Ub – Universal I/O Channels
Input rating RP-C-12A: 4; -12B: 0; -12C: 4; -16B: 4
24 VDC , 2.4 mA
Differences from Previous Hardware Versions
For information on differences from previous versions, see the SpaceLogic and EasyLogic - Hardware Reference Guide.
Addendum - California Proposition 65 Warning Statement for California Residents
WARNING: This product can expose you to chemicals including lead which is known to the State of California
to cause cancer and which is known to the State of California to cause birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov

© 2023 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
www.se.com/buildings