SGL 2000

The document summarizes the NOTIFIER SGL-2000 fire alarm control panel. It is a two-zone panel that complies with NFPA standards and UL listing. It has features like discrete component design, built-in surge suppression, low battery monitoring, and compatible with two-wire smoke detectors. It is intended for small to medium commercial buildings and will annunciate alarms with LEDs and optional modules that can send signals to remote stations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views2 pages

SGL 2000

The document summarizes the NOTIFIER SGL-2000 fire alarm control panel. It is a two-zone panel that complies with NFPA standards and UL listing. It has features like discrete component design, built-in surge suppression, low battery monitoring, and compatible with two-wire smoke detectors. It is intended for small to medium commercial buildings and will annunciate alarms with LEDs and optional modules that can send signals to remote stations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

November 5, 1999 B-310

SGL-2000
Fire Alarm Control Panel
Section: Conventional Fire Alarm Control Panels

GENERAL California
State Fire
The NOTIFIER SGL-2000 is a cost-effective two-zone fire Marshal
alarm control panel. It is designed in accordance with
National Fire Protection Association (NFPA) Standards for 7165-0028:143
Protective Signaling Systems: 72 (Local), 72 (Remote S635 CS68
Station). The compact SGL-2000 control panel was tested
as a fire protective signaling system control unit under
Underwriters Laboratories Inc., Standard for Safety UL 864.

FEATURES
• Discrete component solid state design.
• Two-zone non-expandable construction.
• Class B (Style B) initiating circuits.
• Built-in surge suppression.
• Built-in brown-out circuitry.
• Single audible Style Y (Class B) circuit rated at 0.75 A.
• Low current drain of panel minimizes battery Amp/Hour
requirements.
• Supervision of battery.
• Float charger network.
• Two-wire smoke detector compatible.
• DC power tap rated at 100 milliamps.
• Dead-front construction.
• Trouble silence with resound.
• Ground fault circuit.
• Disable switch.
• Power-limited for use with limited-energy cable.
• In-panel signaling provides:
— Short pulse = Trouble.
— Long pulse = Resound.
— Steady signal = Alarm. 0380cov.wmf
• Trouble circuit monitors the following fault conditions:
— Open detector loop(s).
• Detection loop:
— Low battery voltage.
— Missing or disconnected battery. — Compatible with many types of two-wire detectors.
— Ground fault. — Power-limited for limited-energy cable.
— Low AC voltage (brown out). — Supervised Style B (Class B) operation.
— Loss of AC power. • Supervised Class B (Style Y) audible/visual signaling cir-
— “Off Normal” switch position. cuit.
— Open or shorted signaling (bell) circuit. • Compact solid state design.
• Control switches: • Automatic float charger.
— “Reset” for control and detectors. • Piezoelectric transducer for audible trouble signal.
— “Trouble Silence” with resound. • Panel will accept one of the following optional modules:
— “Disable” switch. — Supplementary alarm contacts, two Form-C.
• LED indicating lamps: — Supplementary alarm and trouble contacts,
— “Alarm 1” and “Alarm 2”. Form-C alarm, Form-C trouble (one each).
— “System Trouble”. — Remote station output, alarm only.
— “A.C. Power”. — Remote station output, alarm and trouble.

This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or ISO-9001
anticipate all requirements. All specifications are subject to change without notice. For Engineering and Manufacturing
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118 Quality System Certified to
International Standard ISO-9001 Made in the U.S.A.
One Fire-Lite Place, Northford, Connecticut 06472

DN-380 — Page 1 of 2
APPLICATIONS
The SGL-2000 fire alarm control panel is intended for use Always use two-wire detectors which have been listed
in small or medium sized commercial, industrial, and insti- by Underwriters Laboratories Inc. for use with this con-
tutional buildings. trol panel. For a list of compatible UL-listed smoke
detectors, please refer to the Installation Manual for
OPERATION this control panel.
Activation of a compatible two-wire detector or any nor-
mally open fire alarm initiating device will sound audible
signaling devices, illu-
minate an indicating 0380bd.wmf

LED at the control


panel, and operate an
optional module. The
optional modules can
be used to notify a re-
mote station, or initiate
a supplementary con-
trol function.

MAJOR
COMPONENT
& TERMINAL
LOCATIONS

OPTIONAL MODULES — Choose only ONE per control panel.


MP-AC24
Auxiliary Module MP-TR24
Transmitter Module
transmits Alarm to
responding authority.
0380mpac.wmf

0380mptr.wmf

MP-AC24 Notes: 1) For wiring, refer to UL power-limited re- MP-TR24 Notes: Connect to compatible UL listed polarity-sensi-
quirements. 2) Both sets of contacts must be connected to ei- tive remote station receiver. Output signal 18 to 28 VDC. 1) For
ther a non-power-limited or a power-limited circuit. DO NOT mix wiring, refer to UL power-limited requirements. 2) This circuit is
sets of contacts. 3) Refer to the Protected Premises Unit label suitable to leave the building. 3) This output is power-limited.
(located on the system door) and mark the dry contacts used as
non-power-limited circuits.
MP-TRT24
MP-AT24 Transmitter Module
transmits both Alarm
Auxiliary Module and Trouble to
responding authority.
0380mtrt.wmf
0380mpat.wmf

MP-AT24 Notes: *1) *Indicates non-trouble state. 2) All con- MP-TRT24 Notes: Connect to compatible UL listed polarity-sen-
tacts rated 3 A, 120 VAC/30 VDC. 3) For wiring, refer to UL sitive remote station receiver. Output signal 18 to 28 VDC. 1)
power-limited requirements. 4) Both sets of contacts must be For wiring, refer to UL power-limited requirements. 2) The MP-
connected to either a non-power-limited or a power-limited cir- TRT24 module DOES NOT comply with the requirement for sepa-
cuit. DO NOT mix sets of contacts. 5) Refer to the Protected rate trouble/alarm signal transmission. 3) This circuit is suitable
Premises Unit label (located on the system door) and mark the to leave the building. 4) This output is power-limited.
dry contacts used as non-power-limited circuits.
Page 2 of 2 — DN-380