2003-Detailed CFD Modeling of Engine Cooling Fan Systems
2003-Detailed CFD Modeling of Engine Cooling Fan Systems
net/publication/280387221
CITATIONS READS
6 2,228
3 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Stéphane Moreau on 26 July 2015.
0.14
0.1
11TA45Mot#1
11TA45Mot#2
Pressure
dp in inH2O
0.06
0.04
0.02
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
flow cfm
Flow rate
Figure 3. CATIA design of fan hub with swept ribs
2
EXPERIMENTAL INVESTIGATIONS – The previously built
fan prototypes were then assembled with the same
support and several instrumented compact electrical
motors (shown in figure 5). Each resulting fan system was
then put on the same set of heat exchangers and tested
in a climate cell at an ambient temperature of 100°C.
Temperatures were measured with thermocouples at
several key locations within the electrical motor: the
brushes, the bushing on the back plate, the bearing on
the front plate and the diode on the plastic brush holder.
Strong temperature differences were found between the
reference small ribs fan and the above four prototypes: the
large ribs decreased the local temperatures by 5 to 10
degrees. Yet little temperature difference was found
between the radial and the curved ribs. The latter result
was a further incentive for a more detailed CFD analysis of
the internal flow under the fan hub.
0.14
y = 0.0048x2
drop
0.1
11TA45Mot#1
11TA45Mot#2
dp in inH2O
Pressure
0.08 Polynomial (11TA
Polynomial (11TA
0.06
0.04
0.02
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
flow cfm
Flow rate
Figure 11. Internal hub topology and mesh At the solid boundaries wall laws have been applied to
reduce the number of nodes close to the walls. All
SUPPORT MODEL AND ASSEMBLY – The final part of computations have been performed at a rotational speed
the under-fan-hub model is the support. It involves the of 2500 rpm and a volumetric flow rate of 2500 m3/h.
central ring of the support with the actual clearance with
the motor case. It fits exactly in the previous fan system RESULTS
topology: under the blue part (stator feet) of figure 7. The
grid is a simple H-grid topology whose node density is Figures 13 and 14 show the induced flow topology in the
meant to match the node density of the fan system and hub and around the motor case for the large and straight
hub templates as closely as possible. No-slip condition is rib case. As already seen in the initial simplified CFD
imposed on the ring. One-to-one periodic boundary model, the ribs act as centrifugal pumps that drain air
conditions are imposed on the periodic faces. GGI from the back of the motor into the hub. Figure 13 shows
interfaces are set at the fluid boundaries with the other the streamlines colored by speed within the hub with the
templates. motor and the support removed from the plot for sake of
clarity. It emphasizes that the large ribs induce a
For the final assembly, all the above parts are located in significant flow field (large speeds) and therefore a
the same reference frame with their proper relative position significant mass flow rate into the electrical motor.
to yield the topology shown in figure 12. The Moreover significant momentum fluxes are injected in the
corresponding partial grids are attached to yield the final hub boundary layer at the blade root as conjectured in [8]
simulation grid. The same grid quality has been targeted and measured by LDV. A comparison with the initial small
for the different cases according to previous test rig ribs show similar patterns but with a much smaller flow
simulations with medium resolution [4-5]. This has led to rate. Figure 14 is a velocity vector plot in a meridional cut
5
through the electrical motor case, the fan hub and the Rib Radial 160-90 160-110 160-130
support ring between two ribs. It first points out that the Qmotor 12.35 12.93 12.7 12.21
inlet flow rate splits between a main flow rate that enters (m3/h)
the back of the motor and a secondary leakage flow Gain % base 4.70 2.83 -1.13
between the support ring and the motor case. The latter Table 1: Volumetric flow rates in the electrical motor
goes back all the way to the front plate of the motor. The
outlet flow is all concentrated between the ring and hub When comparing the mean flow velocity through the
end. Figure 14 also shows that several secondary flow motor, all four large rib designs lie around 5 m/s whereas
patterns happen in the hub: a large flow recirculation in the initial small rib design lie 25% lower at about 4 m/s.
the hub corner and another one in front of the support ring. The corresponding aerodynamic operating points of the
electrical motor are shown in figure 15. These results
closely correlate with the temperature measurements in
climate cells described above. The flow field in the portion
of the rib lying along the hub edge can explain the
marginal increase in flow rate observed with the swept
ribs. This second centrifugal pump currently operates off-
design in a quasi-stalled mode. On the contrary, the inlet
angle of the first centrifugal pump is improved over the
radial design yielding the marginal efficiency improvement.
Dp dans le moteur
120.00
100.00
80.00
Optimized ribs (+25%)
Dp (Pa)
60.00
Essais
Curve fit
Figure 13. Streamlines colored by speed with the support
20.00 Test data
valeurs essais
removed
Simulations
Obtenu calcu K98l
0.00
0 1 2 3 4 5 6 7 8 9
V (m/s)
Hub
Figure 15. Electrical motor operating conditions
Figure 14. Velocity vectors in a cut between the ribs Gain % base -0.04 -0.25 -0.28
Table 2: Fan pressure rise and torque
The next step has been to simulate and compare the
different rib designs. Similar flow patterns as figure 14 are CONCLUSION
obtained in all cases. Table 1 shows that quantitatively
the flow rates achieved in the motor with the four large The extensive use of CFD for fan design has been
designs are very similar with a marginal increase of 5% for extended to the full fan systems with both the external
the 160-90 configuration. flow field through the fan blades and the internal flow field
under the fan hub through the electrical motor. Previous
6
work had involved automatic grid templates for three kinds 4. “On the use of CFD in the Automotive Engine Cooling
of topologies, respectively the in-duct configuration, the Fan System Design,” E. Coggiola, B. Dessale, S.
virtual test rig and the rotor-stator configuration. The latter Moreau, and R. Broberg, AIAA 98-0772 paper, Reno,
included some new relevant local effects as the detailed January 1998.
tip clearance labyrinth and the electrical motor presence. 5. “Latest Improvements of CFD Models of Engine
Based on this upgraded topology, a new automatic grid Cooling Axial Fan Systems,” M. Henner, S. Kessaci
template for the under-fan-hub configuration has been and S. Moreau, SAE-02HX-36 paper, Detroit,
developed which exactly fits in the previous template. It is February 2002.
designed to cover a wide range of rib design with high 6. “Modélisation du transfert de chaleur au sein des
sweep and potentially various profiles and stacking. machines électriques tournantes. Dimensionnement
et Optimisation de leur système de refroidissement,”
Four different large rib designs with increasing sweep and C. Vasilescu, PhD dissertation, Université Paris VI,
therefore geometrical difficulty were used to test this new 2002.
grid capability. They involved the same fan used in 7. “Unsteady Rotor-Stator Interactions in Automotive
previous studies. No stator blades have been included to Engine Cooling Fan Systems,” M. Henner, M.
limit the model size. All four geometry was meshed Stanciu, S. Moreau, S. Aubert and P. Ferrand,
successfully with an equivalent grid quality of about Proceedings of the ISUAAAT 2000 Conference,
600000 nodes designed to capture the main relevant flow Ecully, September 2000.
features. 8. “Evaluating CFD Models of Axial Fans by
Comparisons with Phase-Averaged Experimental
A second step was to develop a simple realistic electrical Data,” D. Neal, S. Moreau, M. Henner and J. Foss,
model that bore most of its aerodynamic characteristics. VTMS5-01-89 paper, Nashville, May 2001.
A best fit of the available measured pressure drop was
then supplied to the flow solver as a porous medium
external subroutine. The flow simulations were then easy
and fast enough to provide a detailed investigation of the
four different rib shapes and to compare then to the initial
small rib design. Gains of about 25% in flow rates with
respect to the reference fan system were estimated for
each large rib case at a single operating condition. That
confirmed the trend observed in earlier temperature
measurements made in climate cells in key locations
within the electrical motor. The numerical comparison of
various fan system internal configurations is now effective
at an early stage of the product design process.
Future work will include more elaborate rib design that will
address the second pump stall issue. Additional flow
rates will also be run to assess the sensitivity of the
internal flow rates to the external flow rates. Finally results
from [8] will be revisited to study the impact of the ribs on
the wake topology of this nine-blade fan mounted in the
MSU test rig.
REFERENCES