Timers
Multifunction
Types DMC01, PMC01
• Time range 0.1 s to 100 h
• 7 knob selectable functions
Op - Delay on operate, manual start
Oa - Delay on operate, automatic and manual start
In - Interval, manual start
Ia - Interval, automatic and manual start
Nr - Interval with no time reset, manual start
Na - Interval with no time reset, automatic and
manual start
Dr - Delay on release
• Knob selection of time range
• Knob adjustable time setting
• External adjustable time setting available
DMC01C DMC01D PMC01 • Repeatability: ≤ 0.2%
• DC supply for PNP/NPN and Namur sensors
• Output: 8 A SPDT or 2 x 8 A SPDT relay
• For mounting on DIN-rail in accordance with DIN/EN
50 022 or Plug-in
• 22.5 mm or 45 mm Euronorm or 36 mm Plug-in
module housing
• LED indication for relay status and power supply ON
Product Description Ordering key DMC 01 C B23
Multi-voltage timer with 7 15 VDC, 10 mA (1 relay) or 24 Housing
knob selectable functions VDC, 15 mA (2 relays) supply Function
and 7 knob selectable time for PNP/NPN sensors and 8.2 Type
ranges within 0.1s and VDC supply for Namur sensor. Item number
100h. Remote time setting For mounting on DIN-rail Output
available. (DMC01) or Plug-in (PMC01). Power Supply
Type Selection
Mounting Output Housing Supply: 24 VDC Supply: 24 or 48 VAC Supply: 115 or 230 VAC
For DIN-rail 1 x SPDT D - 22.5 mm DMC 01 C 724 DMC 01 C B48 DMC 01 C B23
For DIN-rail 2 x SPDT D - 45 mm DMC 01 D 724 DMC 01 D B48 DMC 01 D B23
Mounting Output Housing Supply: 24 VDC Supply: 24 VAC Supply: 115 VAC Supply: 230 VAC
Plug-in 1 x SPDT P - Housing PMC 01 C 724 PMC 01 C 024 PMC 01 C 115 PMC 01 C 230
Plug-in 2 x SPDT P - Housing PMC 01 D 724 PMC 01 D 024 PMC 01 D 115 PMC 01 D 230
Time Specifications
Time ranges Reset
Knob selectable 0.1 to 1 s Manual reset of time
1 to 10 s and/or relay Close the trigger contact
6 to 60 s Pulse duration ≥ 10 ms
60 to 600 s Power supply interruption
0.1 to 1 h 1 relay versions: ≥ 700 ms
1 to 10 h 2 relays versions: ≥ 200 ms
10 to 100 h PNP/NPN sensor supply output
Setting accuracy ≤ 5% 1 relay versions: 15 VDC, 10 mA
Repeatability ≤ 0.2% 2 relays versions: 24 VDC, 15 mA
pins + and - or 6 and 7
Time variation pin + or 6 positive
Within rated power supply ≤ 0.05%/V
Within ambient temperature ≤ 0.2%/°C Namur sensor connection 8.2 VDC, 1kΩ
pins + and S or 6 and 5
External time setting pin + or 6 positive
Linear remote potentiometer 10 kΩ
Max length of pot. cable 3m
Specifications are subject to change without notice (18.06.07) 1
DMC01, PMC01
Output Specifications General Specifications
Output 1 or 2 x SPDT relay Power ON delay ≤ 100 ms
Rated insulation voltage 250 VAC (RMS) Reaction time from trigger
Contact Ratings (AgSnO2) µ Delayed contact(s) < 10 ms
Resistive loads AC 1 8 A @ 250 VAC Instantaneous contcat < 20 ms
DC 12 5 A @ 24 VDC Indication for
Small inductive loads AC 15 2.5 A @ 250 VAC Power supply ON LED, green
DC 13 2.5 A @ 24 VDC Output relays ON LED, yellow (flashing when
Mechanical life ≥ 30 x 106 operations timing)
Electrical life ≥ 105 operations Environment (EN 60529)
(at 8 A, 250 V, cos ϕ = 1) Degree of protection IP 20
Pollution degree 3 (DMC01), 2 (PMC01)
Operating frequency < 7200 operations / h (IEC 60664)
Dielectric strength Operating temperature -20 to 60 °C, R.H. < 95%
Dielectric voltage 2 kVAC (RMS) Storage temperature -30 to 80 °C, R.H. < 95%
Rated impulse withstand volt. 4 kV (1.2/50 µs) Housing
Dimensions DMC01C 22.5 x 80 x 99.5 mm
DMC01D 45 x 80 x 99.5 mm
Supply Specifications PMC01 36 x 80 x 94 mm
Power supply Overvoltage cat. III Weight 120 to 260g depending on
Rated operational voltage (IEC 60664, IEC 60038) model
through terminals: Screw terminals (DMC01)
A1, A2 or A1, A3 (DMC01) Tightening torque Max 0.5 Nm according to
B48 24 or 48 VAC ± 15% IEC EN 60947
45 to 65 Hz
B23 115 or 230 VAC ± 15% Approval UL, CSA
45 to 65 Hz CE Marking Yes
724 24 VDC ± 20% EMC Electromagnetic Compatibility
2, 10 (PMC01) Immunity According to EN 61000-6-2
024 24 VAC ± 15%,45 to 65 Hz Emission According to EN 61000-6-3
115 115 VAC ± 15%,45 to 65 Hz Timer Specifications According to EN 61812-1
230 230 VAC ± 15%,45 to 65 Hz
724 24 VDC ± 20%
Voltage interruption ≤ 10 ms
Rated operational power
AC supply: 5 VA
DC supply: 2W
Function/Range/Time Setting
Adjust the function setting To access the DIP switches In - Interval, manual start scale: 1 to 10 with respect
the DIP switches 1 to 6 as open the grey plastic cover Ia - Interval, automatic to the chosen range.
shown below (1 to 4 for using a screwdriver as and manual start
Lower knob:
DMC01Cxxx). shown below. Nr - Interval with no time
Setting of time range
Note 1: DIP switch 5 must reset, manual start
Upper knob: External potentiometer
be kept ON when using Na - Interval with no time
Selection of function: (DMC01D, PMC01C):
PMC01Dxxx. reset, automatic and
Op - Delay on operate, Time setting on relative
manual start
Note 2: DIP switch 6 does manual start scale: 1 to 10 with respect
Dr - Delay on release
not have any effect on the Oa - Delay on operate, to the chosen range.
PMC01Cxxx working mode. automatic and manual Centre knob:
start Time setting on relative
DMC01D, Sensor type selection
PMC01C, ON ON OFF OFF: PNP/NPN sensor,
PMC01D Open collector DMC01C
or contact
OFF OFF ON ON: Namur sensor
Time setting (DMC01D and PMC01C)
ON: Centre knob on front
OFF: External trimmer
Second relay
ON: Instantaneous
OFF: DPDT
2 Specifications are subject to change without notice (18.06.07)
DMC01, PMC01
Mode of Operation
Function Op: Delay on Function Ia: Interval, auto- Function Dr: Delay on Example 2: Interval with
operate, manual start matic and manual start release NPN or Namur proximity
sensor.
The time period begins as The relay operates and the The relay operates as soon
soon as the trigger contact time period begins as soon as the trigger contact is Using the Interval function
is closed. as the power supply is con- closed. The time period and a NPN or Namur prox-
At the end of the set delay nected. begins when the trigger con- imity sensor, DMC01 and
time the relay operates and The relay releases at the end tact is opened. The relay PMC01 can be used to
doesn't release until the trig- of this period or when the releases at the end of the monitor the actual presence
ger contact is closed again power supply is disconnect- set delay time or when the of an object (i.e. a can) in
or the power supply is dis- ed. The relay operates again power supply is disconnect- the right place on a convejor
connected. When the trigger when the trigger contact is ed. The relay operates again belt. In fact the sensor trig-
contact is closed, the relay closed. If the trigger contact when the input contact is gers the timer each time it
releases and a new time is closed before the end of closed again. If it is closed detects an object on the
period starts. the delay time, the relay before the end of the delay belt, so the relay keeps ON
keeps ON and a new time time the relay keeps ON, a as long as there is no gap
period starts. new time period begins as on the belt. As soon as there
Function Oa: Delay on soon as the contact is is a gap on the belt, the
operate, automatic and opened again. relay switches OFF and an
manual start Function Nr: Interval with alarm can be activated.
no time reset, manual start
The time period begins as Example1: Delay on
soon as the power supply is The relay operates and the operate with remote Yellow LED working mode
connected. time period begins as soon control time setting:
At the end of the set delay as the trigger contact is Timing:
time the relay operates and closed. The relay releases at Using the delay on operate Slow blinking
doesn't release until the trig- the end of this period or function, DMC01D or Relay ON:
ger contact is closed or the when the power supply is PMC01C can be used to set See operation diagrams
power supply is disconnect- disconnected. The relay the working delay of an Incorrect knobs position:
ed. When the trigger contact operates again when the equipment (i.e. a pump) by a Fast blinking
is closed, the relay releases trigger contact is closed knob placed on a panel. It is
and a new time period again. only necessary to connect
starts. an external potentiometer to
the suitable pins (T1, T2, T3
Function Na: Interval with for DMC01D or 8. 9. 11 for
Function In: Interval, no time reset, automatic PMC01C) and mount the
manual start and manual start knob on the control panel.
The relay operates and the The relay operates and the
time period begins as soon time period begins as soon Note:
as the trigger contact is as the power supply is con-
closed. The relay releases at nected. The external potentiometer
the end of this period or The relay releases at the end must be connected before
when the power supply is of this period or when the the product operates. The
disconnected. The relay power supply is disconnect- cable length must be below
operates again when the ed. The relay operates again 3m
trigger contact is closed when the trigger contact is
again. If the trigger contact closed.
is closed before the end of
the delay time, the relay
keeps ON and a new time
period starts.
Specifications are subject to change without notice (18.06.07) 3
DMC01, PMC01
Operation Diagrams
Function Op - Delay on operate, manual start Function Oa - Delay on operate, automatic and manual start
Power supply Power supply
Trigger input Trigger input
ON ON
Relay 1 ON Relay 1 ON
OFF OFF
Relay 2 ON ON Relay 2 ON ON
(delayed) (delayed)
OFF OFF
Relay 2 ON ON Relay 2 ON ON
(instant.) (instant.)
OFF OFF
LED LED
Function In - Interval, manual start Function Ia - Interval, automatic and manual start
Power supply Power supply
Trigger input Trigger input
ON ON
Relay 1 ON Relay 1 ON
OFF OFF
Relay 2 ON ON Relay 2 ON ON
(delayed) (delayed)
OFF OFF
Relay 2 ON Relay 2 ON
ON ON
(instant.) (instant.)
OFF OFF
LED LED
Function Nr - Interval with no time reset, manual start Function Na - Interval with no time reset, automatic and manual start
Power supply Power supply
Trigger input Trigger input
ON
Relay 1 ON ON
Relay 1 ON
OFF OFF
Relay 2 ON Relay 2 ON
ON
(delayed) (delayed) ON
OFF OFF
Relay 2 ON Relay 2 ON
(instant.) ON (instant.) ON
OFF OFF
LED LED
Function Dr - Delay on release
Power supply
Trigger input
Relay 1 ON ON
OFF
Relay 2 ON
(delayed) ON
OFF
Relay 2 ON
(instant.) ON
OFF
LED
4 Specifications are subject to change without notice (18.06.07)
DMC01, PMC01
Wiring Diagrams
DMC01C - Contact input PMC01C - Contact input
DMC01C - Open collector input PMC01C - Open collector input
DMC01D - PNP / NPN sensor input PMC01D - PNP / NPN sensor input
DMC01D - Namur sensor input PMC01D - Namur sensor input
Specifications are subject to change without notice (18.06.07) 5
DMC01, PMC01
Dimensions
DIN-rail DIN-rail
22.5 99.5
99.5 45
83.5
80
83.5
63
80
63
28.5 28.5
Plug-in
94
36 90
63
80
28.5
6 Specifications are subject to change without notice (18.06.07)