SIVACON S8plus Arc fault protection
in low-voltage switchboards
Unrestricted | © Siemens 2024 | SI EA
Testing under arc fault protection
Not required in IEC 61439-1/2
These is a voluntary tests either at the discretion of the manufacturer or the
subject of an agreement between the manufacturer and the user
Seite 2 Unrestricted | © Siemens 2024 | SI EA
Arc fault in low-voltage
switchboards
Origin and impact
Seite 3 Unrestricted | © Siemens 2024 | SI EA
Definition of arc fault
free burning short-circuit through air arising from a fault between live parts of different potential
and/or between live parts and other conductive parts within an assembly.
Serial arc faults Parallel arc faults
Origin LX -LX LX - Land LX -ON
Temperature Up to approx. 6 000° C Up to approx. 13 000°C (base points approx. 20 000°C)
Current In the range of the nominal Up to the level of short-circuit current
current
Seite 4 Unrestricted | © Siemens 2024 | SI EA
Origin and effects of arc faults
Seite 5 Unrestricted | © Siemens 2024 | SI EA
Effects of an arc fault as part of an arc fault test
Seite 6 Unrestricted | © Siemens 2024 | SI EA
Causes of arc faults in low-voltage switchgear
Seite 7 Unrestricted | © Siemens 2024 | SI EA
Impact of an arc flash
for assembly
and operator
Unrestricted | © Siemens 2024 | SI EA
Downtime costs
8.000 – Costs on average for an
unplanned shutdown in Oil &
Gas or Automotive Industry.
€20,000/
min
Quelle: senseye.io The True Cost of Downtime 2022
Seite 9 Unrestricted | © Siemens 2024 | SI EA
What does the IEC have to say?
Unrestricted | © Siemens 2024 | SI EA
Standards - Technical Report
IEC/TR 61641
Enclosed low-voltage switchgear
and controlgear assemblies
Guide for testing under conditions of
arcing due to internal fault
Seite 11 Unrestricted | © Siemens 2024 | SI EA
Arc fault zones according to standard
Arc tested zone
Part of a circuit or compartment where the ignition of
an arc is made and all selected criteria
for the assessment of the test(s) are fulfilled
Arc ignition protected zone Part of a circuit within an assembly where specific
measures are provided to ensure the initiation of an
arcing fault is a remote possibility
Seite 12 Unrestricted | © Siemens 2024 | SI EA
Arc fault protection according to standard
Personnel protection
Assembly protection
Seite 13 Unrestricted | © Siemens 2024 | SI EA
Limiting effects of an internal arcing to a defined area
Seite 14 Unrestricted | © Siemens 2024 | SI EA
Test setup of an arc fault test
Seite 15 Unrestricted | © Siemens 2024 | SI EA
Criteria according to IEC/TR 61641
Criteria
1 Doors and covers do not open Arcing class A Arcing class B Arcing class C Arcing
Personnel Personnel Personnel class I
2 No parts of the switchgear combination are
protection protection and protection and
thrown away assembly assembly
protection protection
3 No holes due to burnout of the arc fault on the
outer parts of the housing designated as freely
accessible
4 The indicators do not ignite
5 The protective conductor circuit for touchable
parts of the enclosure is still effective
6 The arc fault is limited to the defined area of
the switchgear and switchgear combination
7
After the fault has been rectified or after the
affected functional units have been
disconnected or removed in the defined area,
emergency operation of the remaining
switchgear combination is possible
Seite 16 Unrestricted | © Siemens 2024 | SI EA
Preventive and passive
Protective measures
Unrestricted | © Siemens 2024 | SI EA
Preventive measures to avoid arc faults
Proper planning in SIMARIS project/curves
Seite 18 Unrestricted | © Siemens 2024 | SI EA
Terms and definitions
• Rated operating voltage Ue
• Design short-term resistance Icw
• Switching capacity of the incoming breakers, or outgoing breakers Icu
• Permissible short-circuit current under arcing conditions Ip arc
• Permissible arc duration tarc or test duration td
• Permissible conditional short-circuit current under arcing conditions Ipc arc
• Permissible short-circuit current under self-extinguishing arcing conditions Ips arc
Seite 19 Unrestricted | © Siemens 2024 | SI EA
Measure to avoid electric arc faults
Uniform operating concept
Seite 20 Unrestricted | © Siemens 2024 | SI EA
Measures to prevent and limit arc faults
Preventive protective measures
• Prevention of operator errors due to interlocks
• Insulation of live parts
• Main busbar, customer connection
• Use of shutters
• Withdrawable units, ACB 3WA
• Coding of withdrawable units
Reactive protective measures
• Arc-proof hinge and locking systems
• Protective measures on front ventilation openings
• Pressure relief dampers in the roof
• Arc Fault Barriers
Seite 21 Unrestricted | © Siemens 2024 | SI EA
Test under arcing condition
Seite 22 Unrestricted | © Siemens 2024 | SI EA
Thermal effects over time
Seite 23 Unrestricted | © Siemens 2024 | SI EA
Active arc fault protection
Unrestricted | © Siemens 2024 | SI EA
Arc Detection
Integration and testing according to IEC/TS 63107
Components
02 02 02 02 02 02
01 Basic unit AQ110 for
12 Sensor (IACD)
02 02 Optical Sensors (light)
05
03 Current transformer (in incomer)
04
04
Circuit breaker (incomer)
with voltage release 5 % ED
01
05 Arc quenching device (AQD)
02 03
Combined sensor
06 (Light and Pressure)
02 02 02 02 02 06
Seite 25 Unrestricted | © Siemens 2024 | SI EA
Effects of pressure over time
Seite 26 Unrestricted | © Siemens 2024 | SI EA
Design of AQD
Seite 27 Unrestricted | © Siemens 2024 | SI EA
Limitation of active measures to pressure and temperature
IACD+AQD
IACD+AQD
IACD+ACB
Seite 28 Unrestricted | © Siemens 2024 | SI EA
Test with activated arc quenching device
Seite 29 Unrestricted | © Siemens 2024 | SI EA
Advantages of AQD
Reusable
Two full-load operations under
fault conditions
with simple reset mechanism
Testable
up to 100 test cycles
Seite 30 Unrestricted | © Siemens 2024 | SI EA
Summary – Conclusion
Unrestricted | © Siemens 2024 | SI EA
Summary – Conclusion
Arc fault as a worst-case Conversion of large amounts of energy in Effects: Flash of light, large current surge,
in an assembly the shortest possible time – considerable explosive pressure surge
potential of damage
Considerable downtime costs possible –
Definition by IEC 61439-2, IEC/TR 61641, Differentiation according to arc flash avoidance/limitation of the arc fault
IEC/TS 63107 categories (A, B, C, I) necessary
Active arc fault mitigation
Preventive, passive and with IACD+AQD Measures to reduce/minimize damage
active measures Active arc fault detection with IAMS and downtime costs
Seite 32 Unrestricted | © Siemens 2024 | SI EA
Whitepaper
Arc fault prevention and protection
Download Whitepaper
Seite 33 Unrestricted | © Siemens 2024 | SI EA
Visit us at the Hannover fair
© Deutsche Messe AG
22/04/24 – 26/04/24 Hall 9
Seite 34 Unrestricted | © Siemens 2024 | SI EA
Contact
Siemens AG Siemens AG
Andreas Stoecker Martin Sichting
Product Manager SIVACON S8plus Promoter SIVACON S8plus
Suedstr. 74 Schützenstr. 4-10
04178 Leipzig 04103 Leipzig
GERMANY GERMANY
+49 (152) 28864828 +49 (152) 02385384
[email protected] [email protected]Seite 35 Unrestricted | © Siemens 2024 | SI EA
Thank you for attending the webinar
If you are interested in our upcoming
Watch
or past webinars register for free here:
our past
https://www.siemens.com/electrification-automation-webinars
webinars
Stay up to date with subscriptions?
www.siemens.com/ea-subscriptions
Subscribe
Looking for trainings?
Visit our http://www.siemens.com/poweracademy
trainings
Seite 36 Unrestricted | © Siemens 2024 | SI EA
Contact / Disclaimer
Published by Siemens 2024
Smart Infrastructure
Electrification & Automation
Mozartstraße 31 C
91052 Erlangen
Germany
For the U.S. published by
Siemens Industry Inc.
100 Technology Drive
Alpharetta, GA 30005
United States
© Siemens 2024
Subject to changes and errors. The information given in this
document/video only contains general descriptions and/or performance
features which may not always specifically reflect those described, or
which may undergo modification in the course of further development of
the products. The requested performance features are binding only
when they are expressly agreed upon in the concluded contract.
All product designations may be trademarks or other rights of Siemens,
its affiliated companies or other companies whose use by third parties
for their own purposes could violate the rights of the respective owner.
Unrestricted | © Siemens 2024 | SI EA