+GF+ SIGNET 5600 Batch Controller Guide
+GF+ SIGNET 5600 Batch Controller Guide
3-5600.090-1
B-1/98
CAUTION!
• Refer to this instruction manual for more details.
• Remove power to unit before wiring input and output connections.
• Follow instructions carefully to avoid personal injury.
Contents
1. Dial Selection 9. 5600 Operation Modes
2. Power Connection 10. Menu Functions
3. Compatible Sensor Wiring 11. Parts and Accessories
4. Batch Contact Wiring 12. Specifications
5. Remote Control Wiring 13. Quick Reference Menu Parameters
6. End of Batch/Counter Pulse Output Wiring 14. Maintenance
7. Option Contact Wiring Options 15. Troubleshooting
8. Current Output Wiring Options
5600
0-
100
ALA
RM
1
%
12-24 V Terminals
Ba 10 W
100 tch
External power
ALA
RM
D
2
0 = Double Insulated
supply
= DC or AC power
+ -
A B
C - 12 - 24 VDC
OR
12 - 24 VAC
ALA
+
RM
1
%
Bat
0 ch ALA
RM
2
100
Technical Notes:
• Maximum 4-20 mA loop impedance (sec. 8A) is affected by the
ENTE
R
supply voltage.
• To reduce the possibility of noise interference, isolate AC power
lines from signal lines.
Freq. IN
Sen. Pwr.
Iso. Gnd
flow
Std. Sensor valve
Open Collector
Sensor
5600
Terminals
Gnd
Rsm
RTN
Start
Stop
second 5600 (sec. 7C). 5600
Rsm
RTN
Start
Stop
+
Gnd
Terminals CNT/EOB
Remote
Remote output
• End of batch current pulse from a CNT/EOB
second 5600 (sec. 8C). output 5600
Terminals First 5600 Second 5600
A. Two Stage Shutdown (advanced mode only, sec. 9.2) A. Batch Completion (simple or advanced mode, sec. 9)
Fuse** 4 - 20 mA
5600
Terminals
1/8A
+
Option Batch *
NO C NC NO C NC -
+ - 5600
AC or DC
power Current
Terminals
output
Bypass line
B. Missing Signal Alarm (simple or advanced mode, sec. 9) OR B. Valve Control (advanced mode only, sec. 9.2)
Overrun Alarm (advanced mode only, sec. 9.2)
#5 ( + )
5600 4 - 20 mA
Terminals #6 ( - )
Option Batch
NO C NC NO C NC + - 5600
Terminals George Fischer electronic
Current
Alarm AC or DC output actuator with PE 22P
device power
positioner required
C. End of Batch Pulse (advanced mode only, sec. 9.2) C. End of Batch Pulse (advanced mode only, sec. 9.2)
Daisy chaining two 5600 batch controllers together for a second Daisy chaining two 5600 batch controllers together for a second
batching stage. batching stage.
5600
Option Batch
Terminals
NO C NC NO C NC
Rsm
RTN
Start
Stop
Terminals
Current
Rsm
RTN
Start
Stop
output Remote
Second
Remote
5600
First 5600 Second 5600
Technical Notes: Technical Notes:
• Use 2-conductor shielded twisted-pair cable for contact lines up to • Wiring MUST be connected exactly as shown.
30 m (100 ft.) max. • Use 2-conductor shielded twisted-pair cable for output lines up to
30 m (100 ft) max.
• Counter/End of Batch Pulse Output (sec. 6): In simple mode, the output is configured as a counter pulse output. The output emits a
130 millisecond pulse for each engineering (total) unit measured. The output is a open collector type which requires an external pull up resistor
and power supply for external counter use (sec. 6).
Batch started...
• Option Contact - Missing Signal Alarm (sec. 7B): This function provides alarm capability if flow is not detected
Sensor input
in 30 seconds after a batch cycle starts. If the flow sensor signal is missing, the option contact energizes and the
front panel contact indicator turns on, signaling the missing sensor signal. The batch contact also option contact
de-energizes, closing the flow control valve and stopping the batch. The alarm condition will remain until the front
batch contact
panel ENTER key is pressed or a remote contact closure is made to the rear STOP terminal (sec. 5).
4 mA
• Counter/End of Batch Pulse Output (sec. 6): In advanced mode, the output can be configured as either a counter pulse output (sec. 9.1) or as
an end of batch pulse output. When configured as an end of batch pulse, the output emits a 500 millisecond pulse at the completion of every
batch. The output is a open collector type which requires an external pull up resistor and power supply for external counter use (sec. 6).
• Option Contact - Overrun Alarm (sec. 7B): This function provides overrun alarm Batch running... Overrun
Option Contact: 100%
Overrun Alarm capability for detecting a leaky or stuck valve. If the programmed batch overrun volume is 0%
Option contact
measured after the batch ends, the option contact is energized and the front panel contact
indicator turns on, alarming the operator that the flow shut off valve is leaking or stuck open. To cancel alarm,
batch contact
press the ENTER key (or remote STOP switch) once. The overrun alarm will retrigger if the condition persists.
• Option Contact - End of Batch Pulse (sec. 7C): This function is designed to trigger an Batch running... 100%
Option Contact:
0% 500ms
End of Batch external batch counter or second 5600 Batch Controller at the end of a batch. The option
Option contact
contact is energized for 500 milliseconds at the end of every batch cycle. An external
power supply switched through the option contact's common (COM) and normally open (NO) terminal provides
batch contact
a pulse for triggering these devices.
Option Contact: • Option Contact - Missing Signal Alarm (sec. 7B): The missing signal alarm represents a missing sensor signal after batch
Missing Signal start-up. An adjustable time delay entry (in seconds) is offered which specifies how long the instrument will wait after batch
start-up before initiating the missing signal alarm. See simple operation mode (sec. 9.1) for alarm operation details.
Option Contact: • Option Contact On/Off (sec. 10.4H): This function enables or disables the option contact and front panel option LED.
Off When the option contact is configured "Off", the option contact and front panel LED are disabled.
Current Output: • Current Output - Batch Completion (sec. 8A): In advanced mode, the current output functions identical to the simple
Batch Completion operation mode. See the simple operation mode explanation above.
Current Output: • Current Output - Valve Control (sec. 8B): This function is designed for use with a George
Valve Control Fischer electric actuator with PE 22P positioner for preventing overflow or minimizing water Batch running...
hammer. When a batch starts, the current output is held at 20 mA, forcing the PE 22P 0% 100%
valve
positioner to the full open valve position. Near batch end, the output gradually ramps downward to slow the
20 mA valve
flowrate, then drops to 4 mA closing the valve and ending the batch. Front keypad and remote START, STOP,
and RESUME inputs also control the output (sec. 5). A STOP command any time during a batch sequence will 4 mA
force the output to 4 mA and close the PE 22P positioner. (Note: for optimum performance, the batch process
should last at least 1 minute!)
Current Output: • Current Output - End of Batch (sec. 8C): This function is designed to trigger a second Batch running...
100%
End of Batch 5600 batch controller's remote START input for a second batching stage. When the batch
starts, the current output remains at 0 mA until the end of the batch, then jumps to 20 mA for 0% 20 mA
500 milliseconds. The 500 millisecond current pulse triggers the second 5600's remote START terminal to start 500ms
0 mA
the second batch stage.
OR Permanent Total
Batch Volume:
200.500 Gallons
To exit without
changes:
Overrun: Manual
2. Enter volume E. 0.00000 Gallons E. Shown only when "advanced" mode is chosen
quick (sec. 10.4E)
press Overrun compensation
3. ENTER Save
To step C → ← To step A
1 2 3
Choose: Change: Save: ←Back to step C
G↓
Batch Units: Set batch units: Batch K-Factor: Set batch
Batch Units: Aa - Zz, 0 - 9, Batch K-Factor:
A. Gallons >
Liter D. 60.000 >
3456.7 K-Factor:
/, _ 0.0001 - 99999.
Batch units Batch K-Factor (see note*)
5600
Requirements: 40 60 Batch contact terminals (sec. 4) OR
A. The flow sensor must be installed in the actual batch pipeline. Batch
20 Batch % 80
Option
normally open (NO) batch contact terminals (sec. 4) or the current ENTER
100
80
60
40
20
0
Reference Container
WARNING!
The auto calibration procedure generates a custom batch K-Factor. The batch and Totalizer K-Factors are independent from one
another. ALWAYS reenter your totalizer K-Factor after performing the auto calibration procedure.
Downloaded from www.Manualslib.com manuals search engine
10.4 OPTIONS Menu (factory defaults shown in menu column 1)
1 2 3 ←Back to step F
Menu Navigation
• Advanced mode chosen (step E): menu continues, steps F - I. NOT shown if Missing Signal Alarm is Off (step H)
• Simple mode chosen (step E): down arrow key advances to top of Set missing
Missing Signal
menu (step A). I. Missing Signal signal time
Delay: 30.0 sec > Delay: 25.0 sec
delay: 0.10 -
Option Contact 999. sec.
←To step A
To return To restore original value:
to VIEW:
quick quick
press press
12. Specifications
General Agency Approvals
Sensor compatibility: All +GF+ SIGNET flow sensors • CE
Accuracy: ± 0.5% of batch reading • Manufactured under ISO 9001
Input: Optically isolated
Enclosure: Electrical
• Rating: NEMA 4X/IP65 front Power:
• Dimensions: 1/4 DIN, 96 x 96 x 88 mm (3.8 x 3.8 x 3.5 in.) • 12 to 24 VDC or 12 to 24 VAC, unregulated, 50-60 Hz,
• Case materials: ABS plastic 10 W max.
• Keypad material: Sealed 4-key silicone rubber
• Weight: Approximately 500 g (18 oz.)
Contacts (2 sets):
• Mechanical SPDT contacts
Display: • Maximum voltage rating: 5 A @ 30 VDC, 5 A @ 125 VAC, or
• Type: Microprocessor controlled air-core meter movement and 3 A @ 250 VAC, (power factor = 1.0)
alphanumeric 2 x 16 LCD
• Update rate: <200 ms
• Contrast: User selected Current output:
• Alarm annunciators: green batch LED (left), red option LED (right) • 4 to 20 mA, non-isolated, internally powered
• Update rate: <200 ms
• Max loop impedance: 350 Ω max with a 12 V instrument supply
Totalizers: voltage, 950 Ω max with a 24 V instrument supply voltage
• 8-digit resettable with security option • Accuracy: ±0.1% of max range
• 8-digit non-resettable
Environmental GND
Operating temp.: -10 to 55 °C (14 to 131 °F), 50 °C (122 °F)
max. with optional rear cover
Storage temp.: -15 to 80 °C (5 to 176 °F)
Relative humidity: 0 to 95%, non-condensing Noise immunity: EN50082-2
Altitude: 4000 m max. Noise emissions: EN55011
Pollution degree: 2 Safety: EN61010-1
Panel
96 mm (3.8 in.) Optional Splashproof Rear Cover (sec. 11)
Gasket
40 60 Mounting Panel
Batch % Option
96 mm
20 Batch 80 (3.8 in.)
Mounting Clamp (2 ea.)
0 100
96 mm 88 mm
(3.8 in.) (3.5 in.)
91 mm
(3.6 in.)
SIDE VIEW
ENTER
Front
+GF+ SIGNET
View
76 mm (3 in.)
96 mm (3.8 in.)
88 mm (3.5 in.)
88 mm (3.5 in.)
+ + -
Iso. Gnd
Gnd
Freq. IN
Freq. IN
Rsm
Sen. Pwr.
RTN
Start
Stop
Batch
CNT/EOB Current
output Remote output
Patent No. D 376,328
Std. Sensor
88 mm
Open Collector
92 x
(3.62 92 mm
Sensor
(3.5 in.)
12-24 V
x 3.6
10 W
Option Batch 2 in.)
+GF+ SIGNET
Model #3-5600 + - NO C NC NO C NC
Rear Panel
View cutout
_ = blank display
Batch Units: Batch units Aa - Zz, 0 - 9, /, _ _Gallons
A. digit option
Gallons > (8-digits max.)
15. Troubleshooting
Time Left - - - min Remaining batch time greater than Display will show actual remaining minutes after the remaining batch time
<ENTER> to Stop 999 minutes (overrange) is less than 999 minutes
-0001.8 Gallons Flow rate detected after batch end Repair leaky or stuck flow shuttoff valve.
<ENTER> to Start
Flow K-Factor Flow (batch) display K-Factor dan not Enter K-Factor greater than zero (sec. 10.2D)
can not be zero be zero
Total K-Factor Totalizer K-Factor can not be Enter K-Factor greater than zero (sec. 9.2E)
can not be zero zero
Must be between Missing signal time delay must be set Enter missing signal time delay within 0.10 - 999 seconds (sec. 10.4I)
0.10 - 999 for 0.10 - 999 seconds
Overrun Volume Overrun alarm volumetric setting Enter overrun alarm volumetric setpoint within 0.00100 - 999999.)
can not be zero must be within 0.00100 - 999999. engineering units (sec. 10.4H
engineering units
Power Failure Instrument power interrupted during Use RIGHT arrow key to select "Resume" or "Clear". Selecting resume will
Resume Clear active batch process continue the batch from the point where the power interruption occurred.
Selecting clear will clear the power failure. After your selection has been
made, press ENTER to continue.
SETUP READ ERROR Power fault occurred while saving Press any key to reload factory defaults then reprogram flow system setup
Press any Key setup menu entry parameters. Note: Totalizer displays remain undistrubed and will
resume after instrument reset.
Notes: