Generator Room Design Guidelines
Generator Room Design Guidelines
Generator installations with acoustic The dimension "E" as indicated on the layout diagrams is
treatment to achieve 85dBA at 1 metre based upon using standard manufacturers silencers to
achieve 85dBA at 1m, please ensure that the intended
Note:- The layout drawings provided are intended as a
silencers to be used can be positioned as indicated as
guide and to form the basis of the installation design, but
this dimension affects the builders works such as
before the room design is finalised please ensure you
apertures to the walls for the exhaust outlet.
have a "project specific" generator general arrangement
drawing. Certain ambient temperatures or specific site The exhaust run as indicated exits via the side wall
requirements can affect the finalised generator build, through a wall sleeve, packed with a heat resistant
layout configuration and room dimensions. medium and closed to the weather with wall plates.
Should the generator room, internally or externally, be
Room size allowance
constructed with plastic coated profiled steel sheet
The dimensions as indicated A & B allow for good cladding, it is important to ensure that the wall sections
maintenance/escape access around the generator. at the exhaust outlet are isolated from the high exhaust
Ideally you should allow a minimum distance of 1 metre pipe temperature and sealed by a specialist cladder. The
from any wall, tank or panel within the room. same applies for any exhaust going through or near any
Machine access timber or plastic guttering.
It is important to remember that the generator has to be It is good installation practice for the exhaust system
moved into the constructed generator room, therefore within the generator room to be insulated with a
the personnel access door has to be of a sufficient size minimum of 50mm. of high density, high temperature
to allow access alternatively the inlet/outlet attenuator mineral insulation covered by an aluminium overclad.
aperture should be extended to the finished floor level, This reduces the possibility of operator burn injury and
with the bottom uplift section built when the generator is reduces the heat being radiated to the operating
in the room. generator room.
Inlet and outlet attenuators with weather louvres Cable systems
The inlet and outlet attenuators should be installed within The layout drawings assumes that the change-over
a wooden frame and are based on 100mm. airways with switch-gear is external to the generator room and
200mm. acoustic modules. The attenuators should be located in the power distribution room. Specific project
fitted with weather louvres with a minimum 50% free requirements can affect this layout.
area, good airflow profile and afford low restriction The power output cables from the generator output
airflow access. The noise level of 85dB(A) at 1m will breaker to the distribution panel must be of a flexible
comply with minimum EEC Regulations. To achieve construction:-
lower levels attenuator size can more than double in
EPR/CSP (6381TQ)
length.
PCP (H07RNF)
The weather louvres should have bird/vermin mesh
screens fitted on the inside, but these screens must not Should the cable route length from the generator to the
impede the free flow of cooling and aspiration air. distribution room be extensive the flexible cables can be
terminated to a load terminal close box to the generator
The outlet attenuator should be connected to the radiator
and then extended to the distribution room with
ducting flange with a heat and oil resistant flexible
armoured multi-core cables. (See typical load terminal
connection.
box layout).
Exhaust systems The flexible power cables as installed should be laid up
The exhaust systems shown on the layout drawings are in trefoil, placed on support trays/ladder rack in the
supported from the ceiling. Should the building trench with the recommended inter-spacing and
construction be such that the roof supports were unable segregated from the system control cables.
to support the exhaust system, a floor standing steel The cables should be correctly supported and rated for
exhaust stand will be needed. Exhaust pipes should the installation/ambient conditions.
terminate at least 2.3m above floor level to make it
The flexible single core power cables when entering any
reasonably safe for anyone passing or accidentally
panel must pass through a non ferrous gland plate.
touching.
It is recommended that stainless steel bellows be fitted
to the engine exhaust manifold followed by rigid
pipework to the silencer.
B4
ROOM DESIGN GUIDANCE NOTES Section B
Control panel
Note:
Alternator If flexible cable is used
terminal box DMC between switchboard,
remote panel and generator,
a load terminal box
is un-neccessary
To changeover
switchboard
Load terminal box must be used
if connecting cable is PVC/SWA/PVC
CUMMINS ENGINE POWERED 37 kVA - 511 kVA GENERATING SETS WITHOUT ACOUSTIC TREATMENT.
SINGLE SETS.
Prime Type Room dimensions Set Set C/L Exhaust Outlet Inlet
Rating of 2000 1999 Length width height back position Offset Height Louvre Uplift Louvre Cable trench position
KVA ENGINE Model Model A B C D P E X F G H J K L M N
32.5 B3.3G1 26 DGGC CP30-5 3100 3000 2600 400 1500 159 2300 650 700 650 750 800 420 400 1165
50 B3.3G2 40 DGHC CP50-5 3100 3000 2600 400 1500 275 2300 750 800 650 900 900 420 400 1165
38 4B3.9G 30 DGBC CP40-5 3100 3000 2600 400 1500 141 2300 650 750 600 750 850 520 400 1325
52 4BT3.9G1 42 DGCA CP50-5 3200 3000 2600 400 1500 194 2300 650 750 600 750 850 520 400 1325
64 4BT3.9G2 51 DGCB CP60-5 3200 3000 2600 400 1500 194 2300 650 750 600 750 850 520 400 1325
70 4BTA3.9G1 56 DGCC CP70-5 3250 3000 2600 400 1500 194 2300 650 750 600 750 850 520 400 1410
96 6BT5.9G2 77 DGDB CP90-5 3500 3000 2600 400 1500 168 2300 700 860 540 800 800 520 400 1630
106 6BT5.9G2 85 DGDF CP100-5 3500 3000 2600 400 1500 168 2300 700 860 540 800 800 520 400 1630
129 6CT8.3G2 103 DGEA CP125-5 3850 3000 2700 400 1500 255 2300 850 1025 600 1000 1150 520 400 1910
153 6CTA8.3G 122 DGFA CP150-5 3850 3000 2700 400 1500 255 2300 850 1025 600 1000 1150 520 400 1910
185 6CTA8.3G 148 DGFB CP180-5 3850 3000 2700 400 1500 255 2300 850 1025 600 1000 1150 520 400 2070
200 6CTAA8.3G 163 DGFC CP200-5 3950 3000 2700 400 1500 255 2300 850 1025 600 1000 1150 520 400 2070
233 LTA10G2 186 DFAB CP200-5 4850 3250 2800 500 1625 361 2300 1000 1075 520 1150 1250 625 400 2285
252 LTA10G3 202 DFAC CP250-5 4850 3250 2800 500 1625 361 2300 1000 1075 520 1150 1250 625 400 2285
315 NT855G6 252 DFBH CP300-5 4850 3200 2700 500 1600 284 2300 1000 1300 700 1250 1400 625 400 2525
350 NTA855G4 280 DFCC CP350-5 4850 3200 2700 500 1600 284 2300 1000 1300 700 1250 1400 625 400 2525
431* NTA855G6 340 DFCE CS450-5 4850 3200 2700 500 1600 284 2300 1000 1300 700 1250 1400 625 400 2630
431 KTA19G3 345 DFEC CP400-5 5275 3400 3000 500 1700 320 2500 1400 1450 700 1600 1675 775 400 2815
450 KTA19G3 360 DFEL CP450-5 5275 3400 3000 500 1700 320 2500 1400 1450 700 1600 1675 775 400 2815
511 KTA19G4 409 DFED CP500-5 5275 3400 3000 500 1700 320 2500 1400 1450 700 1600 1675 775 400 2815
Before finalising the generator room layout please ensure you read the guidance notes.
*Standby rating only.
B6
a P
X
F
aa
RECOMMENDED ROOM SIZES
SEE NOTES
SET
SET
CANVAS
DUCTING
EXHAUST
H
AIR
FLOW
DATUM
SET
DATUM
N
FUEL TRANSFER
TRENCH IF BULK
TANK INCLUDED
A
M
CABLE TRENCH
FLEXIBLE EXHAUST
BELLOWS
B7
AIR
FLOW
600
TRENCH
Section B
PANEL PC005
(IF SUPPLIED)
TRENCH TO
SWITCHROOM
SEE NOTES
RE PLANT ACCESS
WEATHER LOUVRE
SEE NOTES
H
B
C
RECOMMENDED ROOM SIZES Section B
CUMMINS ENGINE POWERED 37 kVA – 511 kVA GENERATING SETS WITH ACOUSTIC TREATMENT.
SINGLE SETS.
38 4B3.9G 30 DGBC CP40-5 4920 3000 2700 400 1500 168 2300 900 900 1000 400 520 400 1325
52 4BT3.9G1 42 DGCA CP50-5 5000 3000 2700 400 1500 221 2300 900 900 1000 400 520 400 1325
64 4BT3.9G2 51 DGCB CP60-5 5000 3000 2700 400 1500 221 2300 900 900 1000 400 520 400 1325
70 4BTA3.9G1 56 DGCC CP70-5 5000 3000 2700 400 1500 221 2300 900 900 1000 400 520 400 1410
96 6BT5.9G2 77 DGDB CP90-5 5600 3000 2700 400 1500 208 2300 900 1200 1000 400 520 400 1630
106 6BT5.9G2 85 DGDF CP100-5 5600 3000 2700 400 1500 208 2300 900 1200 1000 400 520 400 1630
129 6CT8.3G2 103 DGEA CP125-5 6300 3000 2800 400 1500 320 2300 900 1200 1200 400 520 400 1910
153 6CTA8.3G 122 DGFA CP150-5 6300 3000 2800 400 1500 320 2300 900 1200 1200 400 520 400 1910
185 6CTA8.3G 148 DGFB CP180-5 6300 3000 2800 400 1500 320 2300 900 1200 1200 400 520 400 2070
200 6CTAA8.3G 163 DGFC CP200-5 6450 3000 2800 400 1500 320 2300 1200 1200 1200 400 520 400 2070
233 LTA10G2 186 DFAB CP200-5 7100 3250 2900 500 1625 426 2400 1200 1200 1200 300 625 400 2285
252 LTA10G3 202 DFAC CP250-5 7100 3250 2900 500 1625 426 2400 1200 1200 1200 300 625 400 2285
315 NT855G6 252 DFBH CP300-5 7240 3200 3000 500 1600 362 2500 1200 1200 1600 400 625 400 2525
350 NTA855G4 280 DFCC CP350-5 7240 3200 3000 500 1600 362 2500 1200 1200 1600 400 625 400 2525
431* NTA855G6 340 DFCE CS450-5 7360 3200 3200 500 1600 362 2700 1500 1200 1800 400 625 400 2630
431 KTA19G3 345 DFEC CP400-5 7775 3400 3250 500 1700 420 2750 1500 1200 1850 400 775 400 2815
450 KTA19G3 360 DFEL CP450-5 7775 3400 3250 500 1700 420 2750 1500 1200 1850 400 775 400 2815
511 KTA19G4 409 DFED CP500-5 7775 3400 3250 500 1700 420 2750 1500 1200 1850 400 775 400 2815
Before finalising the generator room layout please ensure you read the guidance notes.
The attenuator dimensions indicated are based on 100mm. airways and 200mm acoustic modules.
In free field conditions we would expect this treatment to achieve 85dBA at 1 metre.
*Standby rating only.
B8
a P
F
aa
RECOMMENDED ROOM SIZES
SEE NOTES
SET
EXHAUST
H
AIR
FLOW
OUTLET
ATTENUATOR
DATUM
SET
SET
DATUM
N
A
FUEL TRANSFER
TRENCH IF BULK
TANK INCLUDED
M
CABLE TRENCH
FLEXIBLE EXHAUST
BELLOWS
B9
AIR
FLOW
600
L
INLET
INLET
Y
ATTENUATOR
TRENCH
Section B
TRENCH TO
SWITCHROOM
ACOUSTIC DOOR
SEE NOTES
RE PLANT ACCESS
WEATHER LOUVRE
SEE NOTES
H
B
C
RECOMMENDED ROOM SIZES Section B
CUMMINS ENGINE POWERED 575 kVA – 2000 kVA GENERATING SETS WITHOUT ACOUSTIC TREATMENT.
SINGLE SETS.
Prime Type Room dimensions Set Set C/L Exhaust Outlet Inlet
Rating of 2000 1999 Length width height back position Offset Height Louvre Uplift Louvre Cable trench position
KVA ENGINE Model Model A B C D P E X F G H J K L M N
575 VTA28G5 460 DFGA CP575-5 5300 3450 3200 400 1725 300 2700 1500 1800 600 1800 2000 775 500 3150
640 VTA28G5 512 DFGB CP625-5 5300 3450 3200 400 1725 300 2700 1500 1800 600 1800 2000 775 500 3150
725 QST30G1 580 DFHA CP700-5 5960 3640 3400 500 1820 300 2950 1500 1850 600 1850 2000 920 500 3575
800 QST30G2 640 DFHB CP800-5 5960 3640 3400 500 1820 300 2950 1500 1850 600 1850 2000 920 500 3575
939 QST30G3 751 DFHC CP900-5 5960 3640 3400 500 1820 300 2950 1500 1850 600 1850 2000 920 500 1665
1000 QST30G4 800 DFHD CP1000-5 6050 3640 3500 500 1820 350 3000 1800 2150 600 2200 2350 920 600 3825
936 KTA38G3 748 DFJC CP900 -5 6050 3800 3400 500 1900 350 3000 1800 2150 600 2200 2350 920 500 3655
1019 KTA38G5 815 DFJD CP100-5 6050 3800 3500 500 1900 350 3000 1800 2150 600 2200 2350 920 600 3655
1256 KTA50G3 1005 DFLC CP1250-5 6800 3800 3500 500 1900 350 3000 2100 2150 600 2200 2350 920 600 4375
1405 KTA50G8 1125 DFLE CP1400-5 7500 4000 3500 500 2000 350 3000 2100 2150 600 2300 2600 920 600 5000
1688 QSK60G3 1350 DQKB CP1700-5 7850 4500 4400 600 2250 693 3720 2750 3000 525 3300 3300 600
1875* QSK60G3 1500 DQKC CP1875-5 7850 4500 4400 600 2250 693 3720 2750 3000 525 3300 3300 600
Before finalising the generator room layout design please ensure you read the guidance notes.
*Note: Prime rating now extends up to 2000 kVA.
a P
X
F
SET
EXHAUST
APPROX
SEE
NOTE
aa
Generator room layout without Acoustic Treatment
D
SET
H
AIR
FLOW
DATUM
CANVAS
DUCTING
SET
DATUM
N
FUEL TRANSFER
TRENCH IF BULK
TANK INCLUDED
B11
A
CABLE TRENCH
FLEXIBLE EXHAUST
BELLOWS
SUB BASE
FUEL TANK
TRENCH
L
AIR
FLOW
M
PANEL PC005
H
TRENCH TO
SWITCHROOM
J
Section B
(IF SUPPLIED)
WEATHER LOUVRE
SEE NOTES
CUMMINS ENGINE POWERED 575 kVA – 2000 kVA GENERATING SETS WITH ACOUSTIC TREATMENT.
SINGLE SETS.
Prime Type Room dimensions Set Set C/L Exhaust Exhaust Attenuator
Rating of 2000 1999 length width height back position offset height Dimensions uplift Cable trench position.
KVA ENGINE Model Model A B C D P E X F Y G H L M N
575 VTA28G5 460 DFGA CP575-5 8400 3450 3450 400 1725 400 2950 1500 1500 2000 400 775 500 5150
640 VTA28G5 512 DFGB CP625-5 8400 3450 3450 400 1725 400 2950 1500 1500 2000 400 775 500 5150
725 QST30G1 580 DFHA CP700-5 8400 3640 3700 500 1820 400 3150 2400 1200 2400 400 920 500 5100
800 QST30G2 640 DFHB CP800-5 8400 3640 3700 500 1820 400 3150 2400 1200 2400 400 920 500 5100
939 QST30G3 751 DFHC CP900-5 8400 3640 3700 500 1820 400 3150 2400 1200 2400 400 920 500 5100
1000 QST30G4 800 DFHD CP1000-5 8450 3640 3800 500 1820 450 3150 2700 1200 2400 200 920 500 5100
936 KTA38G3 748 DFJC CP900-5 9500 3800 3800 500 1900 450 3100 1950 1800 2200 200 920 500 3655
1019 KTA38G5 815 DFJD CP1000-5 9500 3800 3800 500 1900 450 3100 1950 1800 2200 200 920 600 3655
1256 KTA50G3 1005 DFLC CP1250-5 10360 3800 3800 500 1900 450 3100 1950 1800 2200 200 920 600 4375
1405 KTA50G8 1125 DFLE CP1400-5 11700 4000 4500 500 2000 500 3500 2450 2100 2600 200 920 600 5000
1688 QSK60G3 1350 DQKB CP1700-5 12650 4500 4500 600 2250 693 3720 2800 2400 2600 525 600
1875* QSK60G3 1500 DQKC CP1875-5 12650 4500 4500 600 2250 693 3720 2800 2400 2600 525 600
Before finalising the generator room layout design please ensure you read the guidance notes.
The attenuator dimensions indicated are based on 100mm airways and 200mm acoustic modules.
In free field conditions we would expect this treatment to achieve 85dBA at 1 metre.
*Note: Prime rating now extends up to 2000 kVA.
Good example of purpose made building to house two 1000 kVA generators with sound attenuators extending to the
outside.
B12
RECOMMENDED ROOM SIZES
a P
F
X
SET
EXHAUST
APPROX
SEE
NOTE
AIR
FLOW
E
aa
Cummins Generator Sets 575 - 2000 kVA
Generator room layout with Acoustic Treatment to Achieve 85dBA @ 1 metre
H
OUTLET
SET
DATUM
ATTENUATOR
DATUM
SET
D
N
FUEL TRANSFER
TRENCH IF BULK
TANK INCLUDED
A
L
FLEXIBLE EXHAUST
BELLOWS
B13
TRENCH
M
CABLE TRENCH
SUB BASE
FUEL TANK
AIR
FLOW
INLET
ATTENUATOR
INLET
ATTENUATOR
TRENCH TO
SWITCHROOM
G
B
ACOUSTIC DOOR
SEE NOTE RE.
MACHINE ACCESS
WEATHER LOUVRE
SEE NOTES
RECOMMENDED ROOM SIZES Section B
315 NT855G6 252 DFBH CP300-5 4850 6200 2700 2200 500 2425 284 2300 1000 1300 700 1250 1400 625 400 2525
350 NTA855G4 280 DFCC CP350-5 4850 6200 2700 2200 500 2425 284 2300 1000 1300 700 1250 1400 625 400 2525
431* NTA855G6 340 DFCE CS450-5 4850 6200 2700 2200 500 2425 284 2300 1000 1300 700 1250 1400 625 400 2630
431 KTA19G3 345 DFEC CP400-5 5275 6600 3000 2400 400 2500 320 2500 1400 1450 700 1600 1675 775 400 2815
450 KTA19G3 360 DFEL CP450-5 5275 6600 3000 2400 400 2500 320 2500 1400 1450 700 1600 1675 775 400 2815
511 KTA19G4 409 DFED CP500-5 5275 6600 3000 2400 400 2500 320 2500 1400 1450 700 1600 1675 775 400 2815
Before finalising the generator room layout please ensure you read the guidance notes.
*Standby rating only.
Twin CP1000-5 sets (1000kVA) with QST30 G4 engines, PCC control and DMC autosync cubicle in a typical
installation.
B14
RECOMMENDED ROOM SIZES
a Z
P
F
X
SET
SEE
NOTE
aa
Cummins Generating Sets 233 - 511 kVA
2 Set installation without Acoustic Treatment
FUEL TRANSFER
H
AIR
FLOW
SET
TRENCH IF BULK
TANK INCLUDED
DATUM
CANVAS
DUCTS
SET
DATUM
N
A
SET
FLEXIBLE EXHAUST
BELLOWS
B15
SEE NOTE RE.
M
MACHINE ACCESS
SUB BASE
FUEL TANK
TRENCH
AIR
FLOW
MIN
600
J
POWER COMMAND
PARALLELING PANEL
TRENCH TO
SWITCHROOM
WEATHER
LOUVRE
SEE
NOTES
H
K
C
Section B
B
RECOMMENDED ROOM SIZES Section B
315 NT855G6 252 DFBH CP300-5 7840 6200 3000 2200 500 2425 362 2500 1200 1500 1600 400 625 400 2525
350 NTA855G4 280 DFCC CP350-5 7840 6200 3000 2200 500 2425 362 2500 1200 1500 1600 400 625 400 2525
431* NTA855G6 340 DFCE CS450-5 7960 6200 3200 2200 500 2425 362 2700 1500 1500 1800 400 625 400 2630
431 KTA19G3 345 DFEC CP400-5 8375 6600 3250 2400 400 2500 420 2750 1500 1500 1850 400 775 400 2815
450 KTA19G3 360 DFEL CP450-5 8375 6600 3250 2400 400 2500 420 2750 1500 1500 1850 400 775 400 2815
511 KTA19G4 409 DFED CP500-5 8375 6600 3250 2400 400 2500 420 2750 1500 1500 1850 400 775 400 2815
Before finalising the generator room layout please ensure you read the guidance notes.
The attenuator dimensions indicated are based on 100mm. airways and 200mm acoustic modules.
In free field conditions we would expect this treatment to achieve 85dBA at 1 metre.
*Standby rating only.
B16
Z
P
a X
F
SEE
NOTE
aa
RECOMMENDED ROOM SIZES
H
Y D
DATUM
SET
CANVAS
DUCTS
FUEL TRANSFER
TRENCH IF BULK
TANK INCLUDED
AIR
FLOW
SET
DATUM
N
A
FLEXIBLE EXHAUST
BELLOWS
B17
SET
M
SUB BASE
FUEL TANK
TRENCH
AIR
FLOW
MIN
600
INLET
300
Y
POWER COMMAND
Section B
PARALLELING PANEL
TRENCH TO SWITCHROOM
F
WEATHER
LOUVRE
SEE
NOTES
H
B
C
RECOMMENDED ROOM SIZES Section B
725 QST30G1 580 DFHA CP700-5 5960 7080 3400 2640 500 2620 300 2950 1500 1850 600 1850 2000 920 500 3900
800 QST30G2 640 DFHB CP800-5 5960 7080 3400 2640 500 2620 300 2950 1500 1850 600 1850 2000 920 500 3900
939 QST30G3 751 DFHC CP900-5 5960 7080 3400 2640 500 2620 300 2950 1500 1850 600 1850 2000 920 500 3900
1000 QST30G4 800 DFHD CP1000-5 6050 7080 3500 2640 500 2620 350 3000 1800 2150 600 2200 2350 920 600 4200
936 KTA38G3 748 DFJC CP900-5 6050 7400 3500 2800 500 2700 350 3000 1800 2150 600 2200 2350 920 500 3655
1019 KTA38G5 815 DFJD CP1000-5 6200 7400 3500 2800 500 2700 350 3000 1800 2150 600 2200 2350 920 600 3655
1256 KTA50G3 1005 DFLC CP1250-5 6800 7400 3500 2800 500 2700 350 3000 1800 2150 600 2200 2350 920 600 5000
1405 KTA50G8 1125 DFLE CP1400-5 7500 7800 3500 3000 600 2800 350 3000 2100 2150 600 2300 2600 920 600 5700
1688 QSK60G3 1350 DQKB CP1700-5 7850 8800 4400 3500 600 3050 693 3720 2750 3000 525 3300 3300 645 600 4805
1875* QSK60G3 1500 DQKC CP1875-5 7850 8800 4400 3500 600 3050 693 3720 2750 3000 525 3300 3300 645 600 4805
Before finalising the generator room layout design please ensure you read the guidance notes.
*Note: Prime rating now extends up to 2000 kVA.
Three 1250 kVA standby sets with Cummins KTA50G engines provide backup to 150
computer centres in Norway.
B18
RECOMMENDED ROOM SIZES
a Z
P
F
X
SET
SEE
NOTE
aa
Cummins Generating Sets 575 - 2000 kVA
Room layout for 2 Set installation without Acoustic Treatment
FUEL TRANSFER
TANK INCLUDED
DATUM
SET
TRENCH IF BULK
CANVAS
DUCTS
H
AIR
FLOW
SET
DATUM
N
A
SET
FLEXIBLE EXHAUST
BELLOWS
B19
M
SUB BASE
FUEL TANK
TRENCH
M
AIR
FLOW
MIN
600
WEATHER
LOUVRE
SEE NOTES
300
POWER COMMAND
PARALLELING PANEL
TRENCH TO
SWITCHROOM
WEATHER
LOUVRE
SEE
NOTES
DEPTH TO SUIT
CABLE SIZE
K
C
Section B
B
RECOMMENDED ROOM SIZES Section B
725 QST30G1 580 DFHA CP700-5 9000 7080 3700 2640 500 2620 400 3150 2400 1500 2400 400 920 500 3900
800 QST30G2 640 DFHB CP800-5 9000 7080 3700 2640 500 2620 400 3150 2400 1500 2400 400 920 500 3900
939 QST30G3 751 DFHC CP900-5 9000 7080 3700 2640 500 2620 400 3150 2400 1500 2400 400 920 500 3900
1000 QST30G4 800 DFHD CP1000-5 9050 7080 3800 2640 500 2620 450 3150 2700 1500 2400 200 920 500 4200
936 KTA38G3 748 DFJC CP900-5 10100 7400 3800 2800 500 2700 450 3100 1950 2100 2200 200 920 500 3655
1016 KTA38G5 815 DFJD CP1000-5 10100 7400 3800 2800 500 2700 500 3100 1950 2100 2200 200 920 600 3655
1256 KTA50G3 1005 DFLC CP1250-5 10960 7400 3800 2800 500 2700 450 3100 1950 2100 2200 200 920 600 5000
1405 KTA50G8 1125 DFLE CP1400-5 12300 7800 4500 3000 600 2800 500 3500 2450 2400 2600 200 920 600 5700
1688 QSK60G3 1350 DQKB CP1700-5 12650 8800 4500 3500 600 3050 693 3720 2800 2400 2600 525 645 600 4805
1875* QSK60G3 1500 DQKC CP1875-5 12650 8800 4500 3500 600 3050 693 3720 2800 2400 2600 525 645 600 4805
Before finalising the generator room layout design please ensure you read the guidance notes.
The attenuator dimensions indicated are based on 100mm airways and 200mm acoustic modules.
In free field conditions we would expect this treatment to achieve 85dBA at 1 metre.
*Note: Prime rating now extends up to 2000 kVA.
B20
a Z
X
F
SEE
NOTE
aa
RECOMMENDED ROOM SIZES
SEE NOTES
H
Y D
FUEL TRANSFER
TRENCH IF BULK
TANK INCLUDED
AIR
FLOW
DATUM
SET
CANVAS
DUCTS
SET
DATUM
N
A
SET
SET
FLEXIBLE EXHAUST
BELLOWS
B21
SEE NOTE RE.
L
MACHINE ACCESS
SUB BASE
FUEL TANK
TRENCH
M
AIR
FLOW
MIN
600
INLET
300
Section B
POWER COMMAND
PARALLELING PANEL
TRENCH TO SWITCHROOM
DEPTH TO SUIT
CABLE SIZE
WEATHER
LOUVRE
SEE
NOTES
F
H
B
C
RECOMMENDED ROOM SIZES Section B
725 QST30G1 580 DFHA CP700-5 9300 9720 3700 2640 400 2620 400 3150 2400 1650 2400 400 920 500 3900
800 QST30G2 640 DFHB CP800-5 9300 9720 3700 2640 400 2620 400 3150 2400 1650 2400 400 920 500 3900
939 QST30G3 751 DFHC CP900-5 9300 9720 3700 2640 400 2620 400 3150 2400 1650 2400 400 920 500 3900
1000 QST30G4 800 DFHD CP1000-5 9350 9720 3800 2640 450 2620 450 3150 2700 1650 2400 200 920 500 4200
936 KTA38G3 748 DFJC CP700-5 10400 10200 3800 2800 450 2700 450 3100 1950 2000 2200 200 920 500 3655
1016 KTA38G3 815 DFJD CP1000-5 10400 10200 3800 2800 500 2700 450 3100 1950 2000 2200 200 920 600 3655
1256 KTA50G3 1005 DFLC CP1250-5 11260 10200 3800 2800 450 2700 450 3100 1950 2250 2200 200 920 600 5000
1405 KTA50G8 1125 DFLE CP1400-5 12600 10800 4500 3000 500 2800 500 3500 2450 2550 2600 200 920 600 5700
1688 QSK60G3 1300 DQKB CP1700-5 12650 12300 4500 3500 600 3050 693 3720 2800 2400 2600 525 645 600 4805
1875* QSK60G3 1500 DQKC CP1875-5 12650 12300 4500 3500 600 3050 693 3720 2800 2400 2600 525 645 600 4805
Before finalising the generator room layout design please ensure you read the guidance notes.
The attenuator dimensions indicated are based on 100mm airways and 200mm acoustic modules.
In free field conditions we would expect this treatment to achieve 85dBA at 1 metre.
*Note: Prime rating now extends up to 2000 kVA.
725 QST30G1 580 DFHA CP700-5 9600 12360 3700 2640 500 2620 400 3150 2400 1800 2400 400 920 500 3900
800 QST30G2 640 DFHB CP800-5 9600 12360 3700 2640 500 2620 400 3150 2400 1800 2400 400 920 500 3900
939 QST30G3 751 DFHC CP900-5 9600 12360 3700 2640 500 2620 400 3150 2400 1800 2400 400 920 500 3900
1000 QST30G4 800 DFHD CP1000-5 9650 12360 3800 2640 500 2620 450 3150 2700 1800 2400 200 920 500 4200
936 KTA38G3 748 DFJC CP900-5 10400 13000 3800 2800 500 2700 450 3100 1950 2000 2200 200 920 500 3655
1016 KTA38G3 815 DFJD CP1000-5 10400 13000 3800 2800 500 2700 450 3100 1950 2000 2200 200 920 600 3655
1256 KTA50G3 1005 DFLC CP1250-5 11560 13000 3800 2800 500 2700 450 3100 1950 2400 2200 200 920 600 5000
1405 KTA50G8 1125 DFLE CP1400-5 12900 13800 4500 3000 600 2800 500 3500 2450 2700 2600 200 920 600 5700
1688 QSK60G3 1300 DQKB CP1700-5 12650 15800 4500 3500 600 3050 693 3720 2800 2400 2600 525 645 600 4805
1875* QSK60G3 1500 DQKC CP1875-5 12650 15800 4500 3500 600 3050 693 3720 2800 2400 2600 525 645 600 4805
Before finalising the generator room layout design please ensure you read the guidance notes.
The attenuator dimensions indicated are based on 100mm airways and 200mm acoustic modules.
In free field conditions we would expect this treatment to achieve 85dBA at 1 metre.
*Note: Prime rating now extends up to 2000 kVA.
B22
RECOMMENDED ROOM SIZES
a Z
P
F
X
SEE
NOTE
aa
Cummins Generating Sets 575 - 2000 kVA (up to 4.5 MW installation)
Room layout for Multiple Set installation with Acoustic Treatment to Achieve 85dBA @ 1 metre
H
Y D
FUEL TRANSFER
TRENCH IF BULK
TANK INCLUDED
AIR
FLOW
SET
DATUM
N
BELLOWS
B23
SET
SET
SET
SET
MACHINE ACCESS
FLEXIBLE EXHAUST
SUB BASE
FUEL TANK
TRENCH
AIR
FLOW
MIN
600
INLET
INLET
INLET
INLET
300
POWER COMMAND
PARALLELING PANEL
TRENCH TO SWITCHROOM
WEATHER
LOUVRE
SEE
NOTES
H
F
G
Section B
C
B
RECOMMENDED ROOM SIZES Section B
4 x 800 kVA Gen Sets in a ground level room installation with simple but effective exhaust run.
Four 1500 kVA sets with KTA50 engines running on base load operation in Saudi Arabia.
B24
R O O F T O P I N S TA L L AT I O N Section B
B25
R O O F T O P I N S TA L L AT I O N Section B
Where possible a
packaged set,
300 kVA as shown
in picture, on a base
frame provides a
faster installation.
Silenced enclosure
drops over unit.
Note prepared steel
structure support
base.
B26
R O O F T O P I N S TA L L AT I O N Section B
Two roof mounted super-silenced 1000 KVA sets with extended attenuators for a superstore provide a clean
installation.
B28
POWER PLANT PROJECT GUIDE Section B
Recommended room sizes for Natural The external structure of the building may be made of
Gas Generating Sets 1400 to 2000 kVA steel with insulating material or of concrete.
Sufficiently large maintenance doors should be provided
Power station with silencing treatment and designed
to allow generator set removal from the building.
for tropical climates and prime/continuous operation.
Combustion air is taken into the generator set room from
Main features, with soundproofing outside by a fan through a sound trap. The air outlet is
This power plant room is designed for temperate climates soundproofed and the exhaust line is equipped with two
or hot climate countries. Enhanced for sound attenuation high efficiency residential silencers.
the residual noise level is 50 dBA @ 50 metres. Power cables may be routed in trenches or on overhead
Maintenance areas are provided around the generator cable trays.
sets, providing the ability to repair each generator set
individually without breakout noise.
B29
POWER PLANT PROJECT GUIDE Section B
B30
POWER PLANT PROJECT GUIDE Section B
B31
POWER PLANT PROJECT GUIDE Section B
B32
POWER PLANT PROJECT GUIDE Section B
Recommended buildings room sizes for The electrical room should be built in masonry to prevent
Natural Gas generating sets 1400 to temperature changes and condensation effects. Placed
2000 kVA in the middle of the building it will shorten power and
control lines. Power cables may be routed in trenches or
Basic Power Station without sound attenuation on overhead cable trays.
treatment Radiators are grouped together to prevent hot air
Main features recirculating. It is recommended to place them 10 metres
This power plant is designed for cost effective (30 ft) from the power station.
installation, providing fast commissioning and simplified
servicing.
B33
POWER PLANT PROJECT GUIDE Section B
6.6 MW installation.
Fuel piping and auxiliary
cabling runs.
Three 2.2MW HV standby sets in specially prepared plant room. Note height required to accommodate large silencers.
B34