9 - Division B - Part 6
9 - Division B - Part 6
Part 6
Heatihgr Ventilating and Air-conditioning
Section 6.1. General
6.1.1. Application 6-3
6.1.2. Reserved 6-3
6.1.3. Plans and Specifications 6-3
Part 6
Heating, Ventilating and Air-conditioning
Section 6.1. General
6.1.{. Application
[Link]. Scope
1 ) The scope of this Part shall be as described in Subsectio n 1.3.3 . of Division A.
[Link]. Application
1) This Part applies to systems and equipment for heating, ventilating and air-conditioning seryices.
6.2.1 . General
6.2.1,1. Good Engineering Practice
(See Note A-[Link].)
1) Heating, ventilating and air-conditioning systems, including mechanical refrigeration equipment, shall be
designed, constructed and installed in conformance with good engineering practice such as that described in, but not
limited to,
a) the ASHRAE Handbooks and Standards,
i) EPA 6251R-921016, "Radon Prevention in the Design and Construction of Schools and Other Large
Buildings."
2) Reserved.
3) Reserved.
[Link]. Asbestos
1) fubestos shall not be used in HVAC systems and equipment.
6.2.2. lncinerators
6.2.2,,1. Applicable Standard
1 ) The design, construction, installation and aberation of every indoor incinerator shall conform to NFPA 82,
b) buildings of industrial occupanc! where the nature of the processes contained therein permits or requires the
use of large openings in the building envelope even during the winter, and
a) limit the concentration of carbon monoxide to not more than 100 parts per million parts of air,
b) limit rhe concentration of nitrogen dioxide to not more than 3 parts per million parts of air, where the
majority of the vehicles stored are powered by diesel-fuelled engines, or
c) provide, during operating hours, a continuous supply of outdoor air at a rate of not less than 3.9 Ll s for each
square metre of floor area (see Article 3 .3 .l .20.) .
(See also Sentence [Link].(4).) (See Note A-[Link].(l).)
2) Mechanical ventilation systems provided in accordance with Clause (l)(a) shall be controlled by carbon
monoxide monitoring devices, and systems provided in accordance with Clause (1)(b) shall be controlled by nitrogen
dioxide or other acceptable monitoring devices. (See Note A-[Link].(2).)
3) Mechanical ventilation systems provided in accordance with Sentence (1) shall be designed such that the
pressure in the storage garage is less than the pressure in adjoining buildings of other occupanc!, or in adjacent portions
of the same [Link] a different occupanq).
4l lnstoragegaragessubjecttotherequirementsofSentences(l)and(2),wheremotorvehiclesareparkedby
mechanical means, the ventilation requirements may be reduced by one half.
5) Except as provided in Sentence (6), ticket and attendant booths of storage garages shall be pressurized with a
supply of uncontaminated air.
6) The requirements of Sentences ( I ) to (5) shall not apply to open-air storeys in a storage garage.
2) Systems serving spaces that contain sources of contamination and systems serving other occupied parts of the
[Link] in or running through spaces that contain sources of contamination shall be designed in such a
manner as to prevent the spread of such contamination to other occupied parts of the building.
3) Heating, ventilating and air-conditioning systems shall be designed to minimize the growth and spread of
bio-contaminants.
heating, vendlating and air-conditioning systems other than those in dwelling units covered by Part 9.
2) Ducts that are used in a location where they may be subjected to excessive moisture shall have no appreciable
loss of strength when wet and shall be resistant to moisture-induced corrosion.
3) All ductwork and fittings shall be constructed and installed as recommended in SMACNA Manuals and
ASHRAE Standards.
4) All duct materials shall be suitable for exposure to the temperature and humidiry of the air being carried and
shall be resistant to corrosion caused by contaminants in the air being conveyed in the duct,
[Link]. lnterconnectionofSystems
1) In a care or residential occupanry, air from one suite shall not be circulated to any other suite or to apublic
corridor.
2)Except as permitted by Sentences (3) and [Link].(6), air duct systems serving storage garages shall not be
directly interconnected with other parts of the building.
3l Exhaust ducts rcferred to in Sentence [Link].(10) are permitted to exhaust through an enclosed storage
garage prior to exhausting to the outdoors, provided
c) a leakage smokeff re damper rated in accordance with CAN/ULC-S ll2.l, "Leakaee Rated Dampers for
rate 1
Use in Smoke Control Systems," is provided near the duct outlet location in the storage garage to prevent air
from the storage garage from entering the exhaust ducrwork system in the event the building's exhaust fan is
shut down.
Table [Link].
Minimum Distances of Air lntakes from Sources of Gontaminants
Forming Part of Sentence 6,3.2.9.(2)
Source of Contaminants Minimum Distance of Outdoor Air lntake, m
Garage entry of a garage for 5 or more motor vehicles, automobile loading area and
4.5
drive-in queue
Discharge from evaporative cooling tower, evaporative fluid cooler and evaporative
7,6
condenser
3) Outdoor air intakes shall be installed not less than 0.3 m above roofs, landscape grades or other surfaces,
taking into account anticipated snow accumulation levels.
4) Exterior openings for outdoor air intakes and exhaust outlets shall be shielded from the entry ofsnow and
rain and shall be fitted with corrosion-resistant screens of mesh having openings not larger than I 5 mm, except where
experience has shown that climatic conditions require larger openings to prevent the screen openings from icing over
5)
Except as permitted in Sentence (6), exhaust systems shall discharge directly to the outdoors. (See
Note 4-[Link].(5) and (6).)
6) Exhaust systems are permitted to exhaust into a storage garage, provided
a) they serve rooms that are accessible only from that storage garage,
b) the exhaust contains no contaminants that would adversely affect the air qualiry in the storage garage
(see Note A-[Link].(6)(b)), and
c)they are designed in accordance with Sentence [Link].(3).
(See Note A-[Link].(5) and (6).)
7l Exhaux ducts connected to laundry-drying equipment shall be
a) independent ofother exhaust ducts,
b) accessible for inspection and cleaning, and
c) constructed of a smooth corrosion-resistant material.
(See Note A-[Link].(7) and (8).)
8) \flhere collective venting of multiple installations of laundry-drying equipment is used, the ventilation
system shall
a) be connected to a common exhaust duct that is vented by one central exhaust fan and incorporates one central
Iint trap,
b) include an interlock to activate the central exhaust fan when laundry-drying equipment is in use, and
c)be provided with make-up air.
(See Note A-[Link].(7) and (8).)
9l Exhaust dulrr or vents connected to laundry-drying equipment shall discharge directly to the outdoors.
10) Except as provided in Sentence (I2) and except for self-contained systems serving individual dwellingunits,
exhaust ducts serving rooms containing water closets, urinals, basins, showers or slop sinks shall be independent of
other exhaust ducts.
1 1) Except as provided in Sentence (12) and except for self-contained systems serving individual duelling units,
exhau$ ducts serving rooms containing residential cooking equipment shall be independent of other exhaust ducts.
12) TwoormoreexhaustsystemsdescribedinSentences(10)and(11)maybeinterconnectedorconnectedwith
exhaust ducts serving other areas of the building, provided
a) the connections are made at the inlet of an exhaust fan, and all interconnected systems are equipped with
suitable back pressure devices to prevent the passage of odours from one system to another when the fan is
not in operation, or
b) the exhaust ducts discharse to a shaft that is served by an exhaust fan having a capacity that is equal to or
greater than the combined capacity of the exhaust fans dischargingto the plenunt mtltiplied by the operation
diversiry factor, provided that the exhaust fan serving the shaft operates continuously (see
Note A.-6.3.2. 10.(l2Xb)).
1 3) \Mhere exhaust ducts containing air from conditioned spaces pass through or are adjacent to unconditioned
spaces, the ducts shall be constructed to prevent condensation from forming on the inside or outside ofthe ducts.
6.3.2.{3. Filters
1) Air filters for air duct systems shall conform to the requirements for Class 2 air filter units as described in
CAN/ULC-S111, "Fire Tests for Air Filter Units."
2) \Vhen elecrrostatic-rype filters are used, they shall be installed so as to ensure that the electric circuit is
automatically de-energized when filter access doors are opened or, in dwelling units, when rhe furnace circulation fan
is not operating.
I [Link]. Reserved
3) Make-up water connections shall be equipped with backflow prevention devices that conform to
Article [Link]. of Division B of the Book II. (Plumbing Systems). of this code.
4) \flater treatment equipment for biological growth control shall be provided in accordance with
Sub-Section 7.6.2. of ASHRAE Guideline 12, "Minimizing the fusk of Legionellosis Associated with Building
'S7'ater
Systems."
5) Drains, overflows and blow-downs shall be connected to the building's drainage system in accordance with
Claurrc2.4.2.L (1)(e) of Division B of the Book II. (Plumbing Systems). of this code.
6) Evaporative cooling towers, evaporative fluid coolers and evaporative condensers shall be provided with access
ports, service platforms, fixed ladders and restraint connections to allow visual inspection, maintenance and testing.
[Link]. Evaporative Air Goolers, Misters, Atomizers, Air Washers and Humidifiers
1) The fflter and water evaporation medium of every air washer and evaporative air cooler enclosed within a
building shall be made of noncombustibh material.
2) Sumps for air washers and evaporative air coolers shall be constructed and installed so that they can be flushed
and drained.
3) Evaporative air coolers, misters, atomizers, air washers and humidifiers shall be designed in accordance with
Sections 8 and 9 of ASHRAE Guideline 12, "Minimizing the Risk of Legionellosis Associated with Building
\Vater Systems."
6.3.2.{8. VibrationlsolationGonnectors
1) Vibration isolation connectors in air duct systems shall comply with Article [Link].
6.3.2.{9. Tape
1 ) Tape used for sealing joints in air ducts, p lenums and other parts of air duct systems shall comply with
Article [Link].
2) Except as provided in Article [Link]., vented products of combustion, other than those referred to in
Sentence (l), shall be discharged away from the building, so as not to re-enter it, to a distance not less than
a) 2.15 m above sidewalks and driveways,
b) a - from outdoor air intakes,
c) 3 m horizontally or vertically from doors and operable windows, and
d) 3 m horizontally or vertically from occupiable outdoor spaces, excluding maintenance spaces.
(See Note A-[Link].(2).)
b) fireplaces.
2l Masonry or conoete chimneys other than those described in Sentence (1) shall be designed and installed in
conformance with the appropriate requirements in NFPA 211, "Chimneys, Fireplaces, Vents, and Solid
Fuel-Burning Appliances. "
2) Rungs for external ladders shall begin at not less than 2.5 m from ground level.
a) conform to NFPA 9I , "Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible
Particulate Solids,"
b) provide conrinuous exhaust ventilation at an air velocity sufficient to prevent the accumulation of combustible
or reacrive deposits in the power-ventilated enclosure and its exhaust duct system,
c) confine dangerous goods vapours and particles to the area where they are generated and exhaust them to the
outdoors,
d) not return the exhausted air to the building, and
e) be provided with well identified control switches that are
i) located outside of the power-ventilated enclosure, and
ii) readily accessible in case of an emergency.
a) except as provided in Sentences (2) and (3), be constructed of noncornbustible materials compatible with and
chemically resistant to the dangerous goods vapours and particles being exhausted, and
b) be provided with access doors to permit inspection and maintenance of the fan assembly and exhaust ducts.
3l The [Link]+pread rating required by Sentence (2) is permitted to be greater than 25 if an automatic fire
suppression system is provided inside the power-ventilated enclosure and its exhaust duct system.
)
Section 6.7. Piping Systems
6.7.1. Piping for Heating and Gooling Systems
[Link]. Piping Materials and lnstallation
1 ) Piping shall be made from materials designed to withstand the effects of temperatures and pressures that may
occur in the system. (See Articles [Link].,[Link].,[Link]. and9.10.9.7. for fire safery requirements.)
2l Every pipe used in a heating or air-conditioning system shall be installed to allow for expansion and
contraction due to temperature changes.
3) Supports and anchors for piping in a heating or air-conditioning system shall be designed and installed to
ensure that undue stress is not placed on the supporting structure.
[Link]. Glearances
1 ) Clearances berween combustible material and bare pipes carrying steam or hot water shall conform to
Table [Link].
Table [Link].
Glearance Between Steam or Hot Water Pipes and Combustible Material
Forming Part of Articles [Link]. and 6.7.1 .2., and Sentence [Link].(2)
oC
Steam or Water Temperature, Minimum Clearance, mm
Up to 95 No clearance
Above 95 to 120 15
Above 120 25
[Link]. Protection
1) \iflhere a pipe carrying steam or hot water at a temperature above 120'C passes through a combustible floor,
ceiling or wall, the construction shall be protected by a sleeve of metal or other noncombustible material not less than
50 mm larger in diameter than the pipe.
2) \XZlrenindoor piping for Class I flammable liquids is installed in a trench, the trench shall be
a) provided with positive ventilation to the outdoors, or
b) designed to prevent the accumulation of flammable vapours.
5) For each suiteof residential occupancy or suite of care occu?anc! that shares a wall or floor/ceiling assembly with
a storage garage or that is adjacent to an attic or crawl space to which the storage garage is also adjacent, a CO alarm
shall be installed
[Link]. Fireplaces
1) Fireplaces shall conform to the requirements of Section9.22.
Table [Link].
Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6
Forming Part of Sentence [Link].(1)
Functional Statements and Objectives(t)
(a),(b),(c),(e),(f),(s),(h) [F50,F51,F52,F54,F63-oH1.2,0H1.3]
1F31,F50,F51,F52,F54,F63-053.2,OS3.41
(d)[F01-0s1.1]
(1) 1F20.0s3.21
(1) lF23-OS3.1l
1F51,F63,F50-0H1.1,0H1.2,0H1.31
(1) lF43-0S1.11
lF43-0S3.41
lF43-OP1.1l
(1) lF82-OS1.1l
lF82-OS3.4l
lF82-0P1.11
(2) lF31-0S3.1I
lF81-OS1.1l
[Link]. Asbestos
(1) 1F43,0H1.11
(1) lF81-OS1.1l
(1) lF30-oH2.1l
(2) lF01-0s1.1I
lFo1-0P1.11
(1) 1F50,F31,F63,F51,F54,F52-0S1.1 l
1F50,F31,F63,F51,F54,F52-0P1.1 l
(2) lF50-0H1.11
(4) lF50-0H1.11
(1) 1F61,F63,F41-0H1.1,OH1.3I
(1) lF50-0H1.11
(2) lF50-oH1.1I
(1) 1F50,F44-0S3.41
(2) lF44-0S3.41
(3) lF44-OS3.4l
(4) 1F50,F44-0S3.41
(5) 1F50,F44-0H1.11
1F50,F44-OS3.4l
(1) lF44-0S3.41
[F44.OH1.1l
(2) lF44-OH1.1l
(3) lF52-0H1.11
(1) 1F01,F44-OS1.1l
1F01,F44-OP1.1l
(3) 1F81,F44-0S3,4I
lF81-0H1.11
(1) lF81-0H1.1,0H1.21
1F81,F44-0S3.41
(2) lF81-0H1.1,0H1.21
lF81-0S1.11
lF81-0P1.1I
(1) lF44-OS1.1l
lF4o-oH1,1l
(2) 1F81,F44-OH1.1l
lF81 ,F44-0S1.'rl
lF81 ,F44-0P1.11
(3) 1F81,F44-0H1.11
(1) 1F50,F81-OH1.1l
1F44,F81-OS3.4l
(2) lF81-OH1.1l
1F81,F44-0S3.41
(3) lF81-OH1.2l
(1) lF30-os3.1l
lF81-OH1.2l
(2) 1F44,F81-0H1,11
1F81,F44-OS3.4l
(3) 1F44,F81-OH1.1l
1F44,F81-OS3.4l
(4) lF81-OH1.1l
(5) 1F82,F81-OH1.1l
lF82-OS3.4l
(1) lF44-OH1.1l
(2) [F44-OH1.1l
(3) lF81-OH1.1l
lF81-OH1.2l
(4) lF81-OH1.1I
lF81-OH1.2l
(5) lF81-0H1.11
(6) lF81-OH1.1l
(7) lF81-OS1.1l
lF01-os1.1l
lFo1-oP1.1l
(e) 1F40, F44,F50,F52-OH1.1l
lF01-os1.1l
lF01-oP1.1l
(1 0) lF81-OH1.1l
(1 1) 1F81,F44-0H1.11
1F81,F44-0S1.11
(12) 1F81,F44-0H1.11
(1 3) lF81-0H1.21
1F81,F44-0H1.11
(3) lF10-0s1.51
(b)[F44,F81-0H1.1]
(c) [F44,F81-0H1.1]
(2) lF81-OH1.1,0H1.2,OH1.31
[Link]. Filters
(1) lF80-0s1.11
lF80-0P1.11
(2) lF30-os3.3l
1F81,F43-0H1.11
6.3,2.15. Evaporative Gooling Towers, Evaporative Fluid Coolers and Evaporative Condensers
(1) 1F41,F44-0H1.11
(2) 1F41,F44-OH1.1l
(3) 1F46,F81-0H2.21
(4) 1F41,F44-OH1.1l
1F46,F81-OH2.2l
(5) lF81-OH2.1l
(6) [F82-OH1.1l
6,3.2.16. Evaporative Air Coolers, Misters, Atomizers, Air Washers and Humidifiers
(1) 1F80,F81-OS1.1l
1F80,F81-OP1.1l
(2) [F82-OH1.1l
(3) lF44-0H1.11
(1) 1F81,F44-OH1.1l
1F81,F44-0S3.41
(2) lF81-OH1.1l
(2) [F01-0s1.1]
lFO1-0P1.11
(1) lF01-0s1.11
lFo1-0P1.11
(1) 1F20,F80-0s3.11
(2) lF30-os3.1l
(c) [F02-0P1.2]
(2) [F11,F81-OS1.1l
(b)[F02-0P1.2]
) (e) [F12-0P1.1,0P1.2]
(a) [F02-0P1.2]
(e) [F12-0S1.1,0S1.2]
(a) [F02-0S1.2]
(a)[F01-0S1.1]
(1) (a) [F02-OS1 .2] Applies to portion of Code text: "... be constructed of noncombustible materials . .."
(b)[F02-0P1.2]
(a) [F02-0P1 .2] Applies to portion of Code text ".,. be constructed of noncombustible materials ..."
(a) [F80-0S3.4] Applies to portion of Code text: ". . . be constructed of . .. materials . . . chemically resistant to the dangerous goods vapours and
particles being exhausted ..."
(a) [F80-0S1.1] Applies to portion of Code text: "... be constructed of ... materials .,, chemically resistant to the dangerous goods vapours and
particles being exhausted ..."
(a) [F01-0S1.1] Applies to portion of Code text: "... be constructed of ... materials compatible with ... the dangerous goods vapours and
particles being exhausted ..."
(3) lF02-0s1.21
lF02-0P1.21
(1) lF81-0P1.11
lF81-OH1,1l
lF81-OS1.1I
[Link]. Clearances
(1) lF01-oP1.1l
lF01-os1.1l
(1) lF01-os1.1l
lF01-oP1.1l
(2) lF01-os1.1I
(3) lF31-OS3.2l
(1) 1F43,F81-OS3.4l
(1) lF20-0s3.2,0s3.41
(2) lF21-OH1.1l
(3) lF20-0s2.21
[Link]. Glearances
(1) lF01-os1.1l
lF01-oP1.1l
(1) lF31-0S3.21
[Link]. Protection
(1) lF01-os1.1l
lF01-oP1.1l
(2) lF01-os1.1l
lF01-oP1.1l
(1) lF36-0S3.61
(1) lF81-OH1.1,OH1.21
1F81,F44-OS3.4l
(2) lF82-0S1.11
(1) lF82-0H1.11
(2) lF82-0H1.11
(1) lFO1-0P1.11
lF01-0s1.11
(2) lF01-0s1.11
lFo1-0P1.11
(1) 1F02,F81-OS1.2l
1F02,F81-OP1.2l
(3) lF44-0S3.41
(4) lF44-0S3.41
(5) lF44-0S3.41
(1) lF01-os1,1l
lF01-oP1.1l
(2) lF01-os1.1l
lFo1-0P1.11
Notes to Part 6
Heatihgr Ventilating and Air-conditioning
A-[Link]. Good Engineering Practice.
Building Pressurization
New buildings tend to be considerably more airdght than older ones. Consequently, these buildings may have a reduced
pressurization requirement compared to the normal requirement in order to limit drafts and provide a reasonable level of comfort.
The humidification and relative pressurization of buildings and individual spaces in buildings can be significant factors in
compromising the ongoing performance of the building envelope and other environmental separators.
In new construction, HVAC designers should take this issue into consideration and confer with those responsible for the design of
the environmental separators so as to limit unintended effects on the environmental separators. In existing buildings, the abiliry of
the environmental separators to resist or accommodate increases in pressure differential or moisture loading should be considered
before changes are made to the HVAC system.
Radon Control
Measures may be necessary to reduce the radon concentration to a level below the guideline specified by Health Canada.
Further information on reducing the indoor concentration of radon can be found in the following Health Canada publications:
. "Guide for Radon Measurements in Public Buildings (Schools, Hospitals, Care Facilities, Detention Centres)," and
. "Radon: A Guide for Canadian Homeowners."
A-6.2.1 .2.(21 Outdoor Design Gonditions. In the past, the practice of ventilating buildings with outdoor air assumed that
the outdoor air was of better qualiry than the indoor air. It has become evident that the outdoor air in some areas of Canada may not
be of an acceptable qualiry for ventilating buildings unless certain particles and gases are first removed or reduced. For particulate
matter, the maximum acceptable level is the 98th percentile of the average 24hov values; for ozone, the maximum acceptable level is
the average of the average 8 hour values. A recent estimate suggests that many Canadians are exposed to contaminated outdoor air via
buildings' ventilation systems, which may lead to health problems such as cardiovascular and cerebral vascular diseases, respiratory
irritation and illnesses, asthma, allergies, cancer, mucus membrane disorders and possibly death.
In order to manage the air quality of a building's indoor environment, thus reducing the potential for adverse effects on occupants'
health, the qualiry of outdoor air for building ventilation purposes must be addressed. The air pollutants for which standards have been
developed are particulate matter and ground-level ozone. Senten ce [Link].(2) sets limits on the maximum acceptable levels of these
particles and gas that a building's ventilation system should introduce direcdy to the indoor environment. These limits form part of the
Canada-wide Standards for Particulate Matter (PM) and Ozone, which were established pursuant to the 1998 Canada-wide Accord on
Environmental Harmonization of the Canadian Council of Ministers of the Environment (CCME) and its Canada-wide
Environmental Standards Sub-Agreement. Information on related regulations is available from Environment Canada and the
provincial/territorial ministries of the environment. A database of particle measurements for certain Canadian locations is available
from the National Air Pollution Surveillance Nerwork (NAPS), which is run by Environment Canada in conjunction with the
provinces and territories. (See Subsection 1.3.2. for contact information for CCME, Environment Canada and NAPS.)
A-6.2.'l .4. Structural Movement. This Article is intended to remind designers and installe rs of mechanical systems of one
aspectof the "good engineering practice" referred to in Article 6.2.L.I.
In determining how to accommodate structural movement, there are rwo important principles to bear in mind:
. The prime concern of the British Columbia Building Code is the safety of people in and around the building, as opposed to
protection of the mechanical systems and equipment.
. The nature of the accommodation will vary with the type of movement being considered, taking into account particularly how
often the movement is likely to be encountered over the life of the building.
For example, a gas line supported on columns that also support a crane must be installed in such a way that the movement of the
columns, which occurs many times daily, does not cause the lines to break, thus creating ahazard. Even if the gas line installation could
somehow be designed to break in a non-hazardous manner, it would hardly be recognized as good engineering practice if movement
that occurs so frequently could disrupt the operation of the mechanical system.
On the other hand, earthquakes occur far less frequently and it would not be surprising to have a non-critical mechanical system fail as
a result of an earthquake. However, even in this situation, the failure must occur in a manner that does not create ahazard to building
occupanrs. For example, heavy mechanical equipment should be properly anchored so that it does not topple on building occupants
during an earthquake. The design of the anchors should take into account accelerations consistent with the seismic data given in
Appendix C for the location of the buildin g. Parr 4 provides guidance on the calculation of the loads such equipment would exert on
the building srructure during an earthquake; these same loads can be used in designing the anchors.
important component of post-disaster life safety systems. In these cases, the measures needed to
Some mechanical equipment can be an
accommodare the movements caused by an earthquake become even more critical since failure of the equipment would not be
acceptable.
Clearly, complying with this requirement will, in most cases, necessitate close coordination beween the mechanical designer and the
structural designer.
For additional information on the rypes of structural movement that may be encountered, see futicle [Link]., Sentence [Link].(2)
and Subsection 4.1.8.
A-[Link].(1) lnstallation - General. Ducts or pipes without dampers or valves are generally not considered to constitute
"equipment" and are therefore not subject to this requirement.
A-[Link].(4) Ventilation Air Supplied to Suites. The indirect supply of required outdoor ventilation air to normally
occupied spaces through corridor pressurization or other indirect systems is not permitted.
A-[Link].(1) Ventilation and Venting of Crawl Spaces and Attic or Roof Spaces. The cross-reference to Part 5
pertains ro unconditione d and unoccupied crawl spaces, and attic or roof spaces, which are effectively within the building e nvelope.
That is, unconditioned and unoccupied attic or roof spaces are located beween the roof deck and roofing above, and the insulation,
air barrier system and vapour barrier below. Unconditioned and unoccupied crawl spaces are located berween the ground cover below
and the insularion, air barrier system and vapour barrier above . Venting of these spaces has implications for the performance of the
building envelope rather than having direct effects on indoor conditions. The ventilation ofconditioned or occupied crawl spaces and
attic or roof spaces must comply with Part 6.
The requirements in Part 5 are stated in terms of loads that must be resisted rather than in terms of building elements. Thus, the Code
user will nor find explicit references in Part 5 to crawl spaces, or attic or roofspaces. Part 5 makes reference to the need for venting
environmental separators, i.e., the dissipation of heat or moistute.
Sentence [Link].(l) requires that crawl spaces be ventilated either by natural (above-grade only) or mechanical means. High moisture
levels within the crawl space can lead to problems such as the formation of mould, lifting of flooring or long-term damage to structural
components.
Crawl space ventilation cannot be expected to correct moisture-related problems caused by other factors like inadequate surface
drainage from the foundation walls or improper protection against moisture from the ground. These conditions must be properly
addressed so that crawl space ventilation can meet its intended objectives.
Several factors favour the use ofmechanical ventilation rather than reliance on natural drafts. Local conditions, such as areas with high
water tables, may dictate the need for mechanical ventilation to remove excessive moisture.
Crawl spaces should be maintained at a negative pressure relative to the conditioned area above to prevent the migration of moisture
into occupied areas. This can be achieved through the use ofan exhaust fan and relying on air uansfer through floor penetrations,
such as pipes.
A-[Link].(1) Storage Garages, Car dealership showrooms are not considered as storage garages.
A-[Link].(2) Ventilation of Storage Garages. Storage garages are ventilated to protect occupantsfrom exposure to carbon
monoxide and other vehicular exhaust fumes. In certain small rwo- or three-bay storage garages that are used for
cases, such as
occasional vehicle srorage, and where occupants are not present, carbon monoxide or nitrogen dioxide monitoring devices may be
omitted if the ventilation system is interlocked with a local light switch or other controls to ensure continuous system operation
whenever the area is occupied. In any event, the ventilation system capaciry must be designed to limit the concentrations of carbon
monoxide or nitrogen dioxide at or below the prescribed values.
A-[Link]. lndoorAirContaminants.
Gontaminants of Concern
Indoor air can contain complex mixtures of contaminants of concern such as formaldehyde, legionella, mould and emissions from
building materials.'$fhile some contaminants may be knowingly introduced - as in the case of processing and manufacturing
environments - others may be unintentionally released into indoor environments. "Industrial Ventilation: A Manual of Recommended
Practice for Design," published by the ACGIH, and the "Exposure Guidelines for Residential Indoor Air Qualiry," published by
Health Canada, are useful references on the control of contaminants in industrial workplace environments and residential settings,
respectively. These and other guidelines and manuals should be interpreted while keeping in mind the settings and purposes for which
they were developed compared to those to which they will be applied. Note that such documents do not necessarily consider the
interactions between various contaminants.
A-6.3,2.5. Duct Coverings and Linings. The TIAC "Mechanical Insulation Best Practices Guide" is a comprehensive
source of information on the selection, installation and proper use of thermal insulation materials. (Nore that Section 4 of this Guide
is not included in the scope of this Note as it contains information on proprietary products, which are not within the mandate of
the Code.)
A-[Link],(5) and (6) Exhausting to Garages. A frequent pracrice in the design of ventilation systems serving buildings
which have associated parking garages is to discharge exhaust air from the building to the garage in order to reduce the cost ofheating
the garage or reduce the length of the exhaust ducts. However, this practice entails a certain amount of risk since, when the exhaust
system is not running, stack effect may turn the exhaust oudets into intakes and exhaust fumes (including carbon monoxide) can be
drawn from the garage into the building. Incorporating a backdraft damper at the exhaust outlet provides some additional protection
but backdraft dampers are generally not regarded as being very reliable. Therefore this practice is only permitted in very limited
circumstances.
A-[Link].(6Xb) Air Contaminants. For the purpose of Clause 6.3.2,10.(6)(b), washroom exhaust air is not considered to
contain contaminants that would adversely affect the air qualiry in the storage garage.
A-[Link].(7) and (8) Exhaust Ducts Connected to Laundry-Drying Equipment. Clothes dryers are a major cause
of fires in buildings often due to a build-up of lint in the system, which then ignites or obstructs the venting or venrilarion.
Proper cleaning and regular maintenance of lint traps is directly proportional to the ease of access ro rhe linr traps. It is therefore
important to ensure that lint traps in multiple installations of laundry-drying equipment are installed in such a way as to allow easy
access for inspection, maintenance, repair and cleaning.
A-[Link].(12Xb) Operation Diversity Factor. The operation diversity factor has to be assessed for each specific
application. Good engineering practice (see Article [Link].) design guidelines can provide information on the subject.
Figure A-[Link].(12)(b), which originates from ASHRAE handbooks, provides an example of factors that can be used for
general applications.
/
./
a
c(u
12
a
(', 10
./
c
F(u
c)
o_ 8
,/
o
o 6
./
-o
E ,/
4
o
-o
(U
-o 2
o
L
10 20 30 40
A-[Link].(2) Requirement for Venting. Sentence 6.3.3.I.(2) 'requires that vented products of combustion from appliances
be discharged a minimum distance away from certain outdoor spaces and building components in cases where the vented products
could contaminate rhe air of occupiable spaces. These minimum distances may need to be increased due to local conditions such as
prevailing winds, adjacenr structures, special processes being carried out, specific contaminants or effluent discharges, all of which
would require further analysis.
"Occupiable ourdoor spaces" refers to areas that could be occupied for a duration of more than fifteen minutes at any time' but does
not include mainrenance spaces. Occupiable outdoor spaces are located adjacent to an indoor space and are considered to be an
extension of this indoor space: e.g. main entries, balconies, patios, decks, green roofs and other public assembly areas. Although
sidewalks and driveways are mentioned in the provision, these areas are not considered as occupiable outdoor spaces since they are used
as transporr roures ro and from the building, and people are not expected to remain there for extended periods of time.
The requirements of Senten ce [Link].(2) are not meant to override similar requirements found in the installation standards referenced
in futicle [Link]. that address identical situations.
A-[Link],(3) Temperature of Exposed Piping. Normally piping carrying steam or high-temperature hot water at pressures
above atmospheric (corresponding temperature 100'C or above) will be insulated to reduce heat losses as an economy measure'
Above a remperarure of approximady 70"C, however, a bare pipe can cause a burn to human flesh coming in contact with the pipe'
If pipes above this temperature are normally out of reach of all persons other than maintenance personnel or are properly guarded, it
would be expected that no insulation would be needed for public safery.
A-[Link].(1) NFPA Publications Pertaining to the Heating, Ventilating and Air-Conditioning of Spaces
Containing Hazardous Gases, Dusts or Liquids.
NFPA 30, "Flammable and Combustible Liquids Code"
NFPA 30A, "Motor Fuel Dispensing Facilities and Repair Garages"
NFPA 32, "Drycleaning Plants"
NFPA 33, "Spray Application Using Flammable or Combustible Materials"
NFPA 34, "Dipping, Coating, and Printing Processes Using Flammable or Combustible Liquids"
NFPA 35, "Manufacture of Organic Coatings"
NFPA 36, "Solvent Extraction Plants"
NFPA 40, "storage and Handling of Cellulose Nitrate Film"
NFPA 5 1, "Design and Installation of Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied Processes"