OPzV SERIES Tubular Gel Battery

6OPzV600 (2V600AH)

Specification
Nomial Voltage 2V
Capacity 600.0Ah@10hr to 1.80V/cell
Length 145 2mm (5.17 inches)
Width 206 3mm (8.11 inches)
Dimension
Container Height 646 3mm (25.4 inches)
Total Height (with Terminal) 681 3mm (26.8 inches)
Approx Weight Approx 46.0 kg (101.4bs)
Container Material ABS(UL94-V0 optional)
600 AH/60.0A (10hr,1.80V/cell,200 C/680 F)
520 A H/104A (5hr,1.75V/cell,200 C/680 F)
Rated Capacity
456 AH/152A (3hr,1.75V/cell,200 C/680 F)
0 0
341 AH/341A (1hr,1.60V/cell,20 C/68 F)
Max. Discharge Current 4800A (5s) Applications
Internal Resistance Approx 0.62mΩ
Solar energy, wind energy
Discharge : -20 55 0C (-4 131 0F)
Electric power, nuclear power
Operating Temp.Range Charge : 0 40 C0 (32 104 F0 )
Communication
Storage : -20 500C (-4 122 0F)
Ship, maritime affairs
Initial Charging Current less than 150.0A.Voltage UPS, medical facilities and emergency
Cycle Use
2.40V~2.50V at 20 0 C(68 0F)Temp. Coefficient -5mV/ 0C lighting
No limit on Initial Charging Current Voltage Situation with high environmental
Standby Use 0 0 0 protection and energy-saving
2.25V~2.30V at 20 C(68 F)Temp. Coefficient -3mV/ C
Better safety performance and reliability
Self-discharge <2% pre month @ 20 0 C(68 0 F) Designed service life of 20 years

Main Technical Advantages


Plate: positive plate adopts tubular plate which can prevent active material falling, and adopts multi-component alloy frame.
have fine corrosion-resisting performance and long service life. Negative plate adopts special radiated structure.
Separator: adopt special micro-pore PVC-SiO 2 separator from Europe AMER-SIL Company, separator have big porosity and low resistance.
Electrolyte: adopts Germany gas silicon dioxide,electrolyte in gel state in the battery without flowing,leakage and lamination can be avoided.
Safety valve: adopt Germany technology,constant opening and closing,accumulator case expansion,damage and electrolyte dry up can be avoided.

Constant Current Discharge (Amperes) at 20 0 C (68 0F )


F.V/Time 10min 15min 30min 1h 2h 3h 5h 8h 10h
1.85V/cell 409 389 335 267 177 137 94.2 65.8 56.2
1.80V/cell 503 470 390 301 195 149 102 70.5 60.0
1.75V/cell 595 526 416 313 200 152 104 71.7 60.9
1.70V/cell 668 574 440 325 205 156 105 72.6 61.6
1.65V/cell 717 607 458 335 209 158 107 73.5 62.3
1.60V/cell 750 628 469 341 212 160 108 74.1 62.7

Constant Power Discharge (Watts) at 20 0 C (68 0F )


F.V/Time 10min 15min 30min 1h 2h 3h 5h 8h 10h
1.85V/cell 761 730 640 517 344 268 185 130 112
1.80V/cell 919 871 738 578 376 290 199 139 119
1.75V/cell 1069 962 779 598 385 295 202 141 121
1.70V/cell 1178 1034 816 617 393 300 205 143 122
1.65V/cell 1243 1076 840 631 399 304 207 144 123
1.60V/cell 1276 1098 853 637 402 306 208 145 124

Specifications subject to change without notice. Page·1


Dimensions

T11 Terminal

Discharge Characteristics Charging Characteristics


2.50 25
A
2.45 0.1C 10
Charge voltage (V/cell)

Charging time in hours


20 B
Equaling charge voltage
2.40
for max. 16 hours
2.35
A
2.30 0.2C 10 B
10
2.25
Float voltage +/- 1%
2.20

2.15

2.10
0
-10 10 20 30 40 50 0 50 100
-20 0
Temperature( C) 0 Depth of discharge in % of C10
For continuous charging we recommend a voltage of 2.25 V. Charge voltage:
The charging voltage must be compensated to the curve for A 2.25 V/cell B 2.40 V/cell
acontinuously different battery ambient temperature. State of charge 100 % State of charge 90 %

Temperature Effects in Relation to Battery Capacity Effect of Temperature on Long Term Float Life

110
105 22
100
20
Life expectancy (year)

95
Available capacity( % )

90 18
Charging voltage
85 16
80 2.25V/cell
14
75
70 12
65
C 10 10
60 C5
55 C3 5
50
45
C1
40
35
30 20 30 40 50 0
O
C
-20 -15 -10 -5 0 5 10 15 20 25 30 68 86 104 122 F
Ambienttemperature( ) Battery temperature

Cycle Life in Relation to Depth of Discharge General Relation of Capacity VS. Storage Time
0 0
Acc.to IEC 896-2 (25 C / 77 F)
Residual average capacity in % of C10
100 120
90
100
Available capacity / %
Extracted capacity in %

80

70 80
10
60
60
50
40 30
20
40 40
30
20
20

10 0 5 10 15 20 25
1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500
Number of Cycles Storage time (months)