Regenerative Pumps for Cold Water Standards
Regenerative Pumps for Cold Water Standards
*m
Y
w - y1w4 wE*m;ft+rmm
mqf*m)
Indian Standard
PUMPS -REGENERATIVEFORCLEAR,COLD
WATER- SPECIFICATION
( First Revision )
ICS 23.080
0 BIS 1998
FOREWORD
This Indian standard (First Revision) was adopted by the Bureau of Indian Standards, after the draft finalized
by the Pumps Sectional Committee had been approved by the Heavy Mechanical Engineering Division Council.
This standard was first published in 1977. Since then 2 amendments were issued in 1980,and 1987 respectively.
The present revision has been taken up to align the method of verification of guarantee with the other pump
standard like IS 9079, IS 8034 and IS 6595. Also the requirements of self miming characteristics in case of self-
priming and semi-self-priming pumps have been incorporated.
For the purpose of deciding whether a particular requirement of this standard is complied with, the final value,
observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance with IS 2 :
1960 ‘Rules for rounding off numerical values (revised)‘. The number of significant places retained in the
rounded off value should be the same as that of the specified value in this standard.
IS 8472 : 1998
Indian Standard
PUMPS -REGENERATIVEFORCLEAR,COLD
WATER- SPECIFICATION
(First Revision)
1 SCOPE 5.2 Manometric Suction Lift
This standard specifies the technical requirements for It is the vacuum gauge/suction manometer reading in
regenerative, that is, repeated centrifugal action metre of water column.
pumps for handling clear, cold water. The pumps may
be constructed as bare pumps or monosets in single-or 5.3 Static Suction Lift
multi-stage construction.
It is the vertical distance between the centre line of the
2 REFERENCES horizontal portion of the suction pipe line and the
water level (see Fig. 6, 7, 8 and 12).
The Indian Standards listed in Annex A are necessary
adjuncts to this standard. 6 CHARACTERISTICS OF CLEAR, COLD
3 TYPES WATER
Regenerative pump designs are mainly of two types: Characteristics of clear, cold water are specified
below:
a) Side channel type, and
b) Peripheral type. a) Turbidity 50 ppm (silica scale), MUX
b) Chlorides 500 ppm, MUX
In terms oftheir design capabilities, the pumps may be
c) Total solids 3 000 ppm, MUX
categorized as:
d) pH value 6.5 to 8.5
i) non-self-priming, e) Temperature 33’C:, Max
ii) semi-self-priming, and f) Specific gravity 1.004, Max
iii) self-priming. g) Hardness (as Ca Cog) 300 mg, MUX
3.1 Non-self-Priming (drinking water)
NOTES
It is that type of regenerative pump which cannot
I If the range of pH value of the wafer pumped is between 6.5
prime without a foot valve. and 7.5 and also the chloride content is less than 100 ppm, the
pump may be made of any hronLe. However, if the range ofpH
3.2 Semi-self-Priming
is between65and8Sandthechloridecontentexceeds 1OOppm.
only zinc-free bronze fitted construction or stainless steel
It is that type of regenerative pump which is capable
construction shall be ,permitted.
of priming up to 1.5 m static suction lift without foot
2 If any other characteristics of the water differ from those
valve, at rated head and discharge. specified in 6, the pump details shall have to be agreed between
the manufacturer/supplier and the user and shall be specified in
3.3 Self-Priming
the order.
It is that type of regenerative pump which is capable
of priming up to 3 m static suction lift without a foot 7 NOMENCLATURE
valve, at rated head and discharge.
Nomenclature of the pump parts commonly used for
4 PRINCIPLE OF OPERATION regenerative pumps shall be as given in Fig. I, 2, 3,4
and 5. Nomenclature of the motor parts shall be as
In these pumps, the energy transfer takes place by
given in IS 1885 (Part 35).
centrifugal regeneration in series of impeller pockets
and the peripheral of- side channel casing. 8 MATERIALS OF CONSTRUCTION
5 UNITS, TERMINOLOGY AND It is recognized that a number of materials 01‘
CLASSIFICATION construction are available to meet the needs for pumps
5.1 Units, terminology and classification relating to handling clear, cold water. A few typical materials are
pumps shall be as specified in IS 5 120 and for motors indicated below merely for the guidance of the
as specified in IS 996 and IS 7538. manufacturers and the users.
IS 8472 : 1998
Component Muterials oj’Construction IS 11346 except for pumps with vertical axis suction
port - the test set-up shall then be as in Fig. 7. In ’
Pump Casing/chamber Casting grade FG200 of
addition hydrostatic and self-priming tests shall also
IS210,LTB2ofIS318
be carried out as specified in 13.3 and 13.5.
Impeller Bronze Grade LTB2 of
13.2 Sampling
IS 3 18, HTB I/HTB2 of
IS 304 The sampling and criteria of conformity shall be
according to IS 10572.
Shaft Stainless Steel Grades
X04Cr12, X12Crl2 and 13.3 Hydrostatic Test
X20Crl3 of IS 6603
Pump casing shall be of robust construction and shall
9 DIRECTION OF ROTATION be tested to withstand the shut-off pressure for at least
15 s.
9.1 The direction of rotation of pumps is designated
clockwise or anti-clockwise as observed when looking 13.4 The pump shall be capable to perform as per
at the pump shaft from the driving end. guaranteed duty point at the manometric suction lift
of4m.
9.2 The direction of rotation shall be clearly marked
either by incorporating an arrow in the casting or by a 13.5 Self-Priming Test (for Self-Priming and
separate metal plate arrow fitted to the pumps at a Semi- Self-Priming Pumps only)
place clearly visible.
The pump shall be tested for self-priming time at a
9.3 The direction of inlet and outlet of the pumps shall minimum static suction lift of 1.5 m for semi-self-
be marked on the castings. priming and minimum static suction lift of 3 m for self-
priming pump.
10 FACTORS AFFECTING PUMP
PERFORMANCE The test procedure shall be as follows:
10.1 The degree of compliance of pump components No check or foot valve or any other external means of
and assembly to the specified requirements affect the priming shall be installed in the suction piping. Fill
pump performance since the dimensional tolerances pump casing with water and start the unit. The priming
and clearances required by these pumps are critical. time shall be the total elapsed time between starting
the unit and the time required to obtain a continuous
10.2 Under identical suction conditions with increase
flow through the discharge pipe (Fig. 12).
in usage of such pumps or wear of impeller and
casings, the self-priming time increases; and the head 13.6 The observations of tests shall be recorded in a
and discharge decrease. test record sheet. A specimen sheet is given in
Annex B.
11 DESIGN FEATURES FOR MONOSET
13.7 Bare pumps shall be tested using calibrated
11.1 Voltage and Frequency Variation
prime movers.
Motor of the monoset pump shall be capable of
delivering the rated output: 14 TEST FOR ELECTRICAL PERFORMANCE
a) With the terminal voltage differing from its The routine and type tests on monoset shall be
rated value by not more than + 6 percent and performed as specified in 14.1 and 14.2. The general
- 15 percent. requirements of the motor with regard to types 01‘
b) The frequency differing from its rated value by enclosures, methods of cooling, duly rating anti
not more than 3 percent. earthing shall be in accordance with IS 996 or IS 75.18.
c) Any combination of (a) and (b).
14.1 Single Phase Monoset
12 END CONNECTIONS
2
IS 8472 : 1998
[Link] Temperature-rise test a) discharge, total head, input power at the guran-
teed duty point and the full load current in the
[Link].1 Temperature rise test at rated voltage shall operating head range. The full load current
be conducted for the maximum current in the operating declared shall be less than or equal to the value
head range with rated voltage and supply frequency. of full load current, MUXspecified in IS 996 or
The temperature rise shall not exceed the limits IS 7538. Where such values of full load current
specified in Table 6 of IS 996. are not specified, the same shall be declared by
[Link].2 Temperature-rise test at reduced voltage the manufacturer.
shall be conducted at 85 percent of the rated voltage b) maximum self-priming static suction lift at
and supply frequency with the same load as mean sea level.
in [Link].1. The temperature rise shall not exceed c) maximum self-priming time at minimum
the limits specified in Table 6 of IS 996 by more than 1.5 m static suction lift for semiself-priming
10”c. pumps and minimum 3 m static suction lift for
self-priming pumps.
14.2 Three-Phase Monoset
NOTE - The pump performance shall be declared at the rated
speed of the prime mover. In case of bare pumps the rated speed
14.2.1 Routine Test
shall be declared by the manufacturer.
Shall comprise (a), (c), (e) and (f) of 22.3.2ofIS 7538.
16.2.2 While carrying out verification of performance
14.2.2 T)lppeTest as per 13.4, 16.2.1(b) and (c), corrections shall be
applied for altitude at the test place and water
Shall comprise (b), (c), (d), (e), (m) and (n) of 22.3.1
temperature other than 33’C. The corrections to be
of IS 7538 and the temperature-rise test given below.
applied as per IS 11346.
[Link] Temperuture-rise test
16.3 Tolerances
[Link].1 Temperature-rise test at rated voltage shall
be conducted for maximum current in the operating 16.3.1 At rated speed the pump shall give a minimum
head range with rated voltage and supply frequency. of 90 percent of rated total head at a minimum of 90
The temperature rise shall not exceed the limits percent of rated discharge. The pump shall not take
specified in Table I of IS 12802. more than 110 percent of the declared power input at
the guaranteed duty point.
[Link].2 Temperature-rise test at reduced voltage
shall be conducted at 85 percent of the rated voltage 16.3.2 The motor shall not get overloaded in the
and supply frequency with the same load as operating head range of + 25 percent of rated head at
in [Link].1. The temperature rise shall not exceed rated voltage when the supply frequency is within the
the limits specified in Table 1 of IS 12802 by more limits f 3 percent of the rated frequency. The
than l@C. maximum allowable current shall be 1.07 times the
15 PRIME MOVERS FOR BARE PUMPS declared full load current, defined in 16.2.1(a).
The motor shall conform to IS 996 or IS 7.538. Test readings of Q, H and IP corrected for rated
4
16 GUARANTEE ON PUMP PERFORMANCE speed shall be plotted on a graph and con-
AND TOLERANCES tinuous curves drawn. Plot guaranteed duty
point Qg Hg on this graph (see Fig. 9). If the
16.1 Guarantee of Workmanship and Material guaranteed duty point lies below the Q-h
The pumps shall be guaranteed by the manufacturer curve pumps shall be deemed to have con
against defects in material and workmanship. When formed to the head and discharge require-
used under the conditions specified in this standard, ments.
for a period of at least IS months from the date of b) For verification of input power draw a straight
despatch or 12 months from the date of commissioning line through the origin and Qg Hg to intersect
whichever is earlier. the Q-H curve. Draw a vertical line through the
point of intersection so that it intersects the
16.2 Guarantee of Performance Q-IP curve. The value of IP at the point of
16.2.1 When tested in accordance with 13 the pumps intersection shall be within the limit specified
shall be guaranteed for their performance of: in 16.3.1.
3
IS 8472 : 1998
c) Test readings of Q, H and 1 shall be plotted on allowances for belt losses may be taken as 6 and 3
a graph and continuous curves drawn. percent, respectively.
Horizontal lines shall be drawn at duty point
17 MARKING AND PARAMETERS TO BE
head +25 percent and duty point head -25
DECLARED BY THE MANUFACTURER
percent to intersect the Q-Hcurve (see Fig. 10).
Vertical lines shall be drawn through the points 17.1 The monoset pump shall be marked with the
of intersection to intersect the Q-I curve. If the following parameters, which shall be declared by the
maximum value between the points of inter- manufacturer:
section on the Q-l curve is not more than the Model, size and serial number of the pump;
4
value specified in 16.3.2, the prime mover is
b) Rated speed, total head and discharge at the
not overloaded. guaranteed duty point;
d) If the guaranteed duty point lies above the test
Q-H curve then a point 0.90 Qg,O.90 Hg shall
c> Range of head;
4 Motor rating(kW)/Prime mover rating;
be plotted. Then, if this point lies on or below
the curve (see Fig. 11) the guarantee condition
e> Rated voltage;
f) Rated frequency;
in respect of head and discharge shall be
g) Number of phases;
deemed to have been met, otherwise not.
h) Winding connection;
16.4.2 In the case of bare pumps a calibrated prime 9 Maximum current in amperes;
mover shall be used. When tested with such prime k) Class of insulation of motor;
movers the power consumption by the pump shall not m> Manufacturer’s name/trade-mark;
exceed the recommended prime mover rating in the n) Power input in kW;
specified operating head range with the tolerance P) Classification;
specified in 16.3.1. Correction shall be made for 4) Number of stages in case of multi stage; and
losses between the driving element and the pump as r) Self-priming time at I .5 m or 3 m static suction
lift.
follows.
NOTE-For prime-movers other than electric motor items (e),
(f), (g),(h),(j), (k) and (n) shall not be apphcable.
Power delivered to the pump shaft when directly
connected shall be the power output of the driving 17.2 In case of bare pumps the parameters mentioned
element. When not directly connected, correction shall at 17.1 (a), (b), (c), and (m) and prime mover rating
be made for the losses between the driving element and shall be declared by the manufacturer and shall be
the pump. In the case of flat belt and V-belt drives, the marked on the pump.
IS 8472 : 1998
r
PUMP CASING
SUCTION
/-VERY)
SEALING
M IMPELI .ER
FIG. I TYPICALREGENERATIVE
SELF-PRIMING
MONOSETPUMP(PERIPHERAL
TYPE)
IS 8472 : 1998
PRIME MOVER
LER
SEALING ARRANGEMENT/
LANGE
HAMBER
ADAPTOR
DEL.
SHA FT
BRACKET
PRIME MOVER
_ ____.-_-_--
r=- TO
DISCHARGE
DEVICE
MEASURING
STAl
FIG. 6 NON-SELF-PRIMING
MONOSETTESTSET-UP
TO
DISCHARGE MEASURING
DEVICE
CONNECT10
IS 8472 : 1998
TO
DELIVERY GAUGE
DISCHARGE MEASURING ’
DEVICE
SEL .F
STA .TI
-_--___
--_--__
____________
____--_-____
=-z,_-z_-z_~y_~~y_~y_-_
FIG. 8 SELF-PRIMING
MONOSETTESTSET-UP
I I I I I r
cl-)_
FIG. 9 CURVESFORVERIFICATION
OFGUARANTEEQ-H, Q-IP AT RATEDSPEED
IS 8472 : 1998
t
-
ANNEX A
(Clause 2)
LIST OF REFERRED INDIAN STANDARDS
210 : 1993 Grey iron castings vourth revision) 7347 : 1974 Performance of small size spark
ignition engines for agricultural
304 : 1981 High tensile brass ingots and cast-
sprayers and similar applications
ings (second revision)
7538 : 1996 Three phase squirrel cage induction
318 : 1981 Leaded tin bronze ingots and cast-
ings (second revision) motors for centrifugal pumps for
agricultural applications (first
996 : 1979 Single-phase small ac and universal revision)
electric motors (second revision)
10572: 1983 Methods of sampling pumps
1239 (Part 1) : Mild steel tubes, tubulars and other
10805 : 1986 Footvalves, retlux valves or non-
1990 wrought steel fittings: Part 1 Mild
return valves and bore valves to be
steel tubes ($3/r revision)
used in suction lines of agricultural
1885 (Part 35) : Electrotechnical vocabulary: Part pumping systems (first revision)
1993 35 Rotating machinery (first
11170: 1985 Performance requirements for con-
revision)
stant speed compression ignition
4984 : 1995 Specification for high density (diesel) engines for agricultural pur-
polyethylene pipes for potable poses (up to 20 kW)
water supplies (fourth revision)
11346 : 1985 Testing set-up for agricultural
4985 : 1988 Unplasticized PVC pipes for potable
pumps
water supplies (second revision)
12231 : 1987 UPVC (rigid) pipes for use in suc-
5120: 1977 Technical requirements for tion and delivery lines of agricul-
rotodynamic special purpose tural pumps
pumps (first revision)
12802 : 1989 Temperature rise measurement of
6603 : 1972 Stainless steel bars and flats rotating electrical machines
12
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publication), BIS.
Amendments arc issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue
of ‘BTS Handbook’ and ‘Standards Monthly Additions’.
This Indian Standard has been developed from Dot: No. HMD 20 ( 0276 ).
(Front cover puge and page 1, Tide) — Substi~te the following for the
existing title:
‘Indian Standard :
(ME20)
Reprography
UnikBIS, New Delhi, India
,. ,
.
.,.