MCS BMS Communication Manual
MCS BMS Communication Manual
6
August 4, 2023
BMS COMMUNICATION
MCS-BMS-GATEWAY
5580 Enterprise Pkwy.
For Interfacing MCS-MAGNUM to:
Fort Myers, FL 33905 Building Automation Systems Protocols:
Office: 239-694-0089 Modbus RTU, Ethernet
Fax: 239-694-0031 BACnet MS/TP, Johnson N2, LonWORKS
www.mcscontrols.com
Modbus RTU to Modbus TCP/IP
MCS-BMS-Gateway Models
• MCS-BMS-GATEWAY
RS485
MCS-MAGNUM
OR
• MCS-BMS-GATEWAY-N54
(NO LonWorks)
RS485
Building
Management
System
Internet
Ethernet
Router
MCS Total
Solution MCS-Touch
All information contained within this document is considered to be proprietary information of Micro Control Systems, Inc.
No information or data from this document shall be published, used, reproduced, transmitted, or disclosed to others outside your
organization without the prior expressed written consent of Micro Control Systems, Inc. This document and the information
contained herein shall be treated as proprietary. Reasonable provisions shall be provided to ensure that this information
remains proprietary by your employees, agents, and other personnel that may have access to this document.
Copyright ©2023
2
Table of Contents
Chapter - 1. MCS-BMS-GATEWAYS ........................................................................................................5
1.1. MCS-BMS-GATEWAY (Model with LonTALK) ..............................................................................................5
1.1.1 LonTALK Protocol................................................................................................................................5
1.2. MCS-BMS-GATEWAY-N54 (NO LonTALK) ..................................................................................................5
Chapter - 2. WIRING MCS-BMS GATEWAY ........................................................................................6
2.1. WIRING BACnet IP OR MODBUS IP TO BMS OVER ETHERNET..............................................................6
2.2. WIRING for MCS-BMS-GATEWAY for BACnet MSTP, Johnson N2, or LonTalk to BMS.............................7
2.3. EXAMPLE NETWORK..................................................................................................................................8
2.3.1 Standalone MCS-Magnum (using Modbus RTU Protocol)..................................................................8
Chapter - 3. MCS-CONFIG-RS485 & ETHERNET COMMUNICATION ....................................9
3.1. Setting up Communication in MCS-CONFIG - RS485 or ETHERNET..........................................................9
3.2. Setting ETHERNET to Communicate to a BMS System...............................................................................9
3.3. Understanding the BMS setup in MCS-CONFIG for Points........................................................................10
3.4. Viewing and printing a list of the Modbus IP/RTU Registers):.....................................................................10
3.5. Print Report from the MCS-CONFIG BMS COMMUNICATION SCREEN..................................................11
Chapter - 4. SETUP PROTOCOLS IN MCS-CONNECT .................................................................12
4.1. MCS-MAGNUM BMS PROTOCOL (Modbus TCP/IP)................................................................................12
4.1.1 Communication to MCS-MAGNUM over Ethernet (MODBUS RTU).................................................12
4.1.2 ETHERNET OVER (MODBUS RTU) PROTOCOL............................................................................13
4.2. MCS-BMS-GATEWAY PROTOCOLS..........................................................................................................14
4.2.1 Protocols MCS controllers support:...................................................................................................14
Chapter - 5. MCS-BMS-GATEWAY FIELDSERVER TOOLBOX .............................................15
Chapter - 6. Setup-MCS-BMS-GATEWAY .........................................................................................18
6.1. Record Identification Data...........................................................................................................................18
6.2. Configuring Device Communications..........................................................................................................18
6.2.1 Set COM settings on all Devices Connected to the MCS-BMS-GATEWAY......................................18
6.2.2 Set IP Address for each MCS-MAGNUM connected to the MCS-BMS-GATEWAY..........................18
6.3. BMS Network Settings: ...............................................................................................................................19
6.3.1 BACnet MS/TP, N2 and Modbus IP / RTU.........................................................................................19
Figure 5 Protocol Selection Switch Tables.........................................................................................................19
6.3.2 BACnet MS/TP: Setting the MAC Address for BMS Network............................................................20
6.3.3 BACnet MS/TP and BACnet/IP: Setting the Device Instance ...........................................................20
6.3.4 Johnson N2: Setting the Node-ID......................................................................................................20
6.3.5 BACnet MS/TP: Setting the Serial Baud Rate for BMS Network.......................................................20
6.3.5.1. Baud Rate DIP Switch Selection...........................................................................................21
Chapter - 7. Interfacing MCS-BMS-GATEWAY ...............................................................................22
7.1. MCS-BMS-GATEWAY Connection Ports.....................................................................................................22
7.2. Device Connections to MCS-BMS-GATEWAY............................................................................................23
7.3. MCS-MAGNUM Address Settings...............................................................................................................23
7.4. Biasing the RS-485 Device Network...........................................................................................................26
7.5. End of Line Termination Switch for the Modbus RS-485 Device Network...................................................26
7.6. Power-Up MCS-BMS-GATEWAY................................................................................................................26
Chapter - 8. BMS-GATEWAY SWITCH SETTINGS .........................................................................28
8.1. BMS Address DIP Switch Settings..............................................................................................................28
Chapter - 9. Installing the MCS-BMS-GATEWAY-N54 .................................................................34
9.1. Termination Resistor....................................................................................................................................34
9.2. Connecting the R1 & R2 Ports....................................................................................................................34
9.3. Wiring..........................................................................................................................................................35
9.4. Power up the MCS-BMS-GATEWAY-N54...................................................................................................35
9.5. Connect the PC to the MCS-BMS-GATEWAY-N54.....................................................................................36
9.5.1 Connecting to the Gateway via Ethernet...........................................................................................36
9.5.2 Changing the Subnet of the Connected PC.......................................................................................36
9.6. Navigate to the ProtoNode Login Page.......................................................................................................37
3
9.7. Setup Web Server Security.........................................................................................................................37
9.7.1 Login to the FieldServer.....................................................................................................................37
9.8. Select the Security Mode.............................................................................................................................39
9.9. HTTPS with Own Trusted TLS Certificate...................................................................................................39
Chapter - 10. APPENDIX - INPUT / OUTPUT POINTS / STATES ...............................................40
10.1. Sensor Input Points.....................................................................................................................................40
10.2. Relay Output Points.....................................................................................................................................41
10.3. ANALOG Output Points...............................................................................................................................42
10.4. Setpoints......................................................................................................................................................42
10.5. Chiller/Compressor States...........................................................................................................................42
10.6. Other Points.................................................................................................................................................43
10.7. Network inputs to MCS-MAGNUM..............................................................................................................46
10.8. MCS Capacity Control State Chart..............................................................................................................47
10.9. MCS Compressor Control State Chart........................................................................................................47
Chapter - 11. ALARMS- UNIT/COMPRESSOR / MODBUS ...........................................................48
11.1. Unit Alarms..................................................................................................................................................48
11.2. Compressor Alarms.....................................................................................................................................49
11.3. MODBUS Alarms.........................................................................................................................................51
Chapter - 12. APP085 USING MCS-CONFIG .....................................................................................56
4
Chapter - 1. MCS-BMS-GATEWAYS
The MCS-BMS-GATEWAY is a microprocessor based communication device that provides protocol translation from
difference protocols. Information that can be transmitted includes the status of control points, alarm information, digital
inputs, analog inputs or setpoints.
The MCS-BMS-GATEWAY protocol is field selectable by setting jumper on the device.
Using MCS-CONFIG and the CONFIG file for the MCS-MAGNUM, you can automatically create the program that is re-
quired by the MCS-BMS-GATEWAY. Then using a web browser you can download the program into the unit.
The MCS-BMS-GATEWAY can receive changes from the network to enable or disable the Network Run/Stop indicator.
Adjustments can also be made to the Cooling Target (Setpoint #1) of a MCS-MAGNUM.
5
Chapter - 2. WIRING MCS-BMS GATEWAY
2.1. WIRING BACnet IP OR MODBUS IP TO BMS OVER ETHERNET
In this configuration the MCS-BMS-GATEWAY provides Ethernet RJ45 Cat5 connection to the BMS using
BACnet IP or Modbus IP.
The MCS-BMS-GATEWAY in this configuration connects to the MCS-MAGNUM RS485 port, using MODBUS
RTU protocol with baud rate of 9600, Modbus slave 1.
TO BMS
.MCS-BMS-GATEWAY Wiring Diagram RS485 LonWorks, Bacnet MSTP, Johnson N2.pdf - S:Products/MCS-BMS-GATEWAY/Drawings 5-18-2023 -3:00pm-dew
6
2.2. WIRING for MCS-BMS-GATEWAY for BACnet MSTP, Johnson N2, or LonTalk to BMS
In this configuration the MCS-BMS-GATEWAY provides a RX485 port for BACnet MSTP or Johnson N2 and
uses the port for LonTalk as shown in the drawing below.
The MCS-BMS-GATEWAY in this configuration connects to the MCS-MAGNUM using a Ethernet RJ45 Cat5
connection talking BACnet IP.
CROSSOVER CABLE
BACnet MSTP
RS485 - or
RS485 + Johnson N2
MCS-BMS-GATEWAY Wiring Diagram LonWorks, Bacnet MSTP, Johnson N2 REV 01-06-2023 - S:Manufacturing/Stuff/MCS-Magnum-N-12 REV 11.1 - 5/18/2023
7
2.3. EXAMPLE NETWORK
2.3.1 Standalone MCS-Magnum (using Modbus RTU Protocol)
MCS INDUSTRIAL CONTROL PANEL with a MCS-MAGNUM controller using an Ethernet cable to
communicate to the MCS-BMS-GATEWAY over BACnet IP.
MCS-BMS-GATEWAY hardwired to BMS Management System using:
1. BACnet MS/TP protocol or
2. Johnston N2 protocol or
3. LonTalk protocol using the LonWorks port
Communication from
MCS-MAGNUM using
BACnet IP over Ethernet
to MCS-BMS-GATEWAY
Ethernet BACnet IP
MCS-BMS-Gateway
or hardwired
ed from
LonWorks
to BMS System
tem
RS485
BACnet MS/TP
or Johnson N2
hardwired to
BMS System
Building
Management
System
8
Chapter - 3. MCS-CONFIG-RS485 & ETHERNET COMMUNICATION
9
3.3. Understanding the BMS setup in MCS-CONFIG for Points
The number of data bit is 8, stop bit is 1 and parity is none (these parameter
are not adjustable).
The sensors inputs are 16 bit signed values. (Read input Registers, Function code = 4)
• The Analog sensor inputs values typically have 1 assumed decimal place, meaning a value of 12.3
will be transmitted as value 123. The # of decimal point depending on the sensor type define in
the MCS-MAGNUM CONFIG. Most sensor types are 1 decimal place.
But take care there are a few 2 decimal and a few zero decimal place types.
The BMS point list has a column which indicates how many assumed decimal are contained in the
value.
• The digital sensor inputs values will be 0 or 1, 0 = off and 1 = on.
The analog outputs are 16 bit signed values. (Read Input Registers, Function code = 4)
• The analog output have 1 assumed decimal place, meaning a value of 12.3 will be transmitted as value 123.
The relay outputs are 16 bit packed values. (Read Coil Status , Function code = 1)
• Each bit within the 16 bits can contains a relay output. A bit value of 0 = relay off, 1 = relay on.
The number of packed bit depends on the requesting Modbus message.
If only one coil is asked for, then only bit 0 will contains a relay status value and bit 1 thru 7 are do
not care.
If two relays are asked for, then bit 0 and bit 1 will contains values and bit 2 thru 7 are do not care.
The setpoints are 16 bit signed values. (Read Holding Registers, Function code = 3)
• The setpoints values typically have 1 assumed decimal place, meaning a value of 12.3 will be trans-
mitted as value 123.
The # of decimal point depending on the setpoint type defined in the MCS-MAGNUM CONFIG.
10
3.5. Print Report from the MCS-CONFIG BMS COMMUNICATION SCREEN
1. Click on ‘FILE’ or the printer ‘ICON’ on the top of the screen.
2. Choose the report you need, in this case we want to see the BMS Points Built Into MCS-MAGNUM.
MCS-CONNECT
SERVICE WINDOW
RS485 SETUP
The following changes can be made using the Keypad or can be made using MCS-CONNECT
SERVICE WINDOW.
The BACnet IP address can be verified and changed (if authorized) from the Keypad/LCD. The following steps will
display the BACnet IP Network address, and the TCP/IP port:
Press the Menu key, select Serv Tools, and then press the Enter key.
Use arrow to BACnet Setting then press Enter.
Select address then press Enter. Change the address so it matches the last two digits of the device
ID then press Enter.
Use arrow to tab to the TCP/IP address.
Select address then press Enter. Change the address and port to match your device.
MCS-CONNECT
SERVICE WINDOW
BACNET SETUP
12
4.1.2 ETHERNET OVER (MODBUS RTU) PROTOCOL
The following steps will display the ETHERNET NETWORK settings:
MCS-CONNECT
SERVICE WINDOW
ETHERNET SETUP
ETHERNET SETUP
SHOWS USING
STATIC SETTING
If you are going to manually assign the IP Address, Subnet Mask, and Default Gateway.
Press the Menu key, select Serv Tools, and then press the Enter key.
Select Ethernet Network then press Enter.
Set “DYNAMIC IP” to NO.
Set the “IP Address”.
Set the “Subnet Mask”.
Set “Default Gateway”.
Reset Magnum for change to take effect.
If you are going to let your network assign the IP Address, Subnet Mask, and Default Gateway:
Press the Menu key, select Serv Tools, and then press the Enter key.
Select Ethernet Network then press Enter.
Set “DYNAMIC IP” to YES.
Connect the MCS-Magnum to the network and power up the board.
13
4.2. MCS-BMS-GATEWAY PROTOCOLS
BACnet MSTP
Johnson N2
Modbus TCP/IP
BACnet IP
LonTalk
The MCS-BMS-GATEWAY is a microprocessor based communication device that enables MCS equipment to connect
to various industrial, building, and machine automation protocols.
Information that can be transmitted includes the status of control points, alarm information, digital inputs, analog inputs
or setpoints.
Network protocols are formatting rules that specify how data is sent and received between devices.
Protocols are necessary for devices to interact with each other.
= Built in Support
MCS IP MCS-Ethernet-RS485
Modbus RTU
MCS 485
BACnet MS/TP MCS-BMS-Gateway
Johnson N2 MCS-BMS-Gateway MCS-BMS-Gateway
14
Chapter - 5. MCS-BMS-GATEWAY FIELDSERVER TOOLBOX
Revision: 2.A
The latest update to the user interface utility called FieldServer Toolbox has been introduced. This updated utility
is available on the web for all FieldServer Gateways and enables users to easily:
1. Search the local network for any connected FieldServers.
2. Select the FieldServer and launch either the current user-friendly browser-based interface to help set-up, config-
ure and diagnose the FieldServer.
NOTE: The ProtoCast gateway is not supported by the FS Toolbox. For gateways updated with FieldSafe, diag-
nostic captures cannot be taken with the FieldServer Toolbox but has been integrated into the FS-GUI configura-
tion page.
The following information is viewable for connected FieldServers found by the FieldServer Toolbox:
DEVICES – Lists the device name.
IP ADDRESS – Shows the IP Address of the listed device.
MAC ADDRESS – Shows the MAC Address of the listed device.
FAVORITE – Click to mark this as a favorite device. The device information will show whether the device is found
or not.
CONNECTIVITY – The light shows the level of connectivity for the device. Green is full connectivity. Yellow is
limited connectivity. Blue is limited IP connectivity. And red is connectivity lost.
BUTTONS – These buttons allow multiple functions. The Connect button jumping straight into a device’s FS-GUI
or Web Configuration page via default Internet browser. The Heartbeat button allows taking diagnostics for the
device.
NOTE: For detailed descriptions on any of these items or additional information check the help menu.
Download the MCS-BMS-GATEWAY - FS Toolbox at:
https://mcscontrols.com/communications.html - “FieldServer Toolbox-1.08aC-Setup.exe
15
Home
Allows the user to check the status of the FieldServer gateway, including the configuration code, version, memory,
gateway type and more. Under “Settings” the user has access to important network information.
NOTE: The “System Restart” button at the bottom of the page is used to restart the FieldServer gateway (only on
the Home page).
About
Allows the user to check current firmware of the FieldServer gateway plus version identification of the interface
and skin, plus con- tact information. Skin is either the default FieldServer template or it can be a specific template
specified by the OEM customer.
Setup
Select “File Transfer” to upload files to the FieldServer gateway including configuration files, firmware upgrades
and more. Select “Network Settings” to access and modify network connection.
View
Select “Connections” to view activity of devices connected to the FieldServer gateway ports.
Select “Data Arrays” to view the Data Arrays setup in the gateway and the user can click on the specific Data
Array for detailed information.
Select “Nodes” to view the Nodes setup in the gateway and the user can click on the specific node for Node
detailed information. On the Nodes details page tabs across the top allow access to settings, status, info stats and
error stats.
16
Select “Map Descriptors” to view the Map Descriptors setup in the gateway and clicking on the specific map
descriptor will access the Map Descriptors detail page. Again, tabs across the top of the page provide quick
access to settings, status, info stats, and error stats.
User Messages
Allows access to error messages, info messages and driver messages.
Diagnostics
Used to create diagnostics captures to assist technical support. Allows capture of Ethernet or Wi-Fi conne
17
*Customer ProtoCarrier Startup Guide
Go to > >
Right-click on Local Area Connection > Properties
Highlight >
Go to > >
> >
Right-click on Local Area Connection > Properties
Highlight >
Page 23 of 38
18
*Customer ProtoCarrier Startup Guide
• For Windows 7 / 10, select: Use the following IP Address
x For Windows XP and Windows 7, select: Use the following IP Address
192 . 168 . 18 . 1
x Click twice
x Open a web browser and go to the following address: [IP Address of ProtoCarrier]/fserver.xif
6.3. BMS Network Settings:
o Example: 192.168.1.24/fserver.xif
• Selecting Stored Configurations, Setting the MAC Address, Device Instance, and Baud Rate
x If the web •browser
Selecting Configuration
prompts to save theFiles
file,forsave
Devices:
the file“S” Bank
onto theDIP
PC.Switches S0browser
If the web – S3 displays
Thexif
the S file
bank asof
a DIP
web switches (S0the
page, save - S3) are used
file onto to select
the local PC as and load a configuration file from a group of
fserver.xif
pretested/preloaded configuration files which are stored in the MCS-BMS-GATEWAY FPC-ED4.
Off On
Fig 3 S3
Shows setting for S2
BACnet MS/TP
Dip switch S0 ‘ON’ S1
as per the Figure 5
chart below S0
S0 – S3 DIP
S Bank DIP Switch Location
Switches
Figure 3: S Bank DIP Switches
Page 24 of 38
19
6.3.2 BACnet MS/TP: Setting the MAC Address for BMS Network
Only 1 MAC address is set for MCS-BMS-GATEWAY regardless of how many devices are connected to MCS-
BMS-GATEWAY.
Set the BACnet MS/TP MAC addresses of the MCS-BMS-GATEWAY to a value between 1 to 127 (MAC Master
Addresses); this is so that the BMS Front End can find the MCS-BMS-GATEWAY via BACnet auto discovery.
NOTE: Never set a BACnet MS/TP MAC Address from 128 to 255. Addresses from 128 to 255 are Slave
Addresses and can not be discovered by BMS Front Ends that support auto discovery of BACnet MS/TP
devices.
Set DIP switches A0 – A7 to assign MAC Address for BACnet MS/TP for the MCS-BMS-GATEWAY FPC-ED4.
Please refer to Appendix A.1 for the complete range of MAC Addresses and DIP switch settings.
NOTE: When using Johnson N2 and Modbus TCP/IP, the ‘A’ Bank of DIP
switches are disabled and not used. They should be set to OFF.
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.
6.3.3 BACnet MS/TP and BACnet/IP: Setting the Device Instance
• The ‘A’ Bank of DIP switches are used for two purposes:
• For BACnet MS/TP, they are used to set the BACnet MS/TP MAC address (Section 3.3.2)
• For both BACnet MS/TP and BACnet/IP, they are also used to determine the BACnet Device In-
stance values
• The BACnet Device Instance can range from 1 to 4,194,303.
• The BACnet device instances will be calculated by taking the Node Offset (default is 18100)
found in Web Configurator and adding it to the value of the ‘A’ Bank DIP switches.
When more than one device is connected to the MCS-BMS-GATEWAY, the subsequent BACnet Device In-
stance values will be sequential from the first/previous device.
For example:
• Given that Device Instance = Node_Offset + A Bank DIP switch value = Default Node_Offset
value = 18150 = ‘A’ Bank DIP switch value = 03 (as per Appendix A.10 DIP Switch Setting)
• Then the Device Instance values for the devices are: = Device 1 Instance = 18153 = Device 2
Instance = 18154
6.3.4 Johnson N2: Setting the Node-ID
• Set DIP switches A0 – A7 to assign a Node-ID for Johnson N2 to the MCS-BMS-GATEWAY.
• Node-ID’s range from 1-255.
• Refer to Appendix A.10 for the full range of addresses for setting Node ID.
6.3.5 BACnet MS/TP: Setting the Serial Baud Rate for BMS Network
DIP Switches B0 – B3 can be used to set the serial baud rate to match the baud rate required by the Building
Management System for BACnet MS/TP.
Off On Off On
A0 B0 Fig 5
Shows setting for
A1 B1 19200 Baud Rate
Fig 4 A2 B2
Shows setting for 03 BMS Address
as found in A.1 appendix A3
B3
in the rear of this manual A4
A5
A6 Figure 5: Baud Rate DIP Switches
A7
20
• The baud rate on MCS-BMS-GATEWAY for Johnson N2 is set for 9600. DIP Switches B0 – B3
are disabled for Johnson N2.
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.
6.3.5.1. Baud Rate DIP Switch Selection
Baud B0 B1 B2 B3
Auto Off Off Off Off
110 On Off Off Off
300 Off On Off Off
600 On On Off Off
1200 Off Off On Off
2400 On Off On Off
4800 Off On On Off
9600 On On On Off
19200 Off Off Off On
20833 On Off Off On
28800 Off On Off On
38400 On On Off On
57600 Off Off On On
76800 On Off On On
115200 Off On On On
21
Chapter - 7. Interfacing MCS-BMS-GATEWAY
22
7.2. Device Connections to MCS-BMS-GATEWAY
MCS-BMS-GATEWAY6 Pin Phoenix connector for RS-485 Devices.
MCS-BMS-GATEWAY-
Device Pins Pin Assignment
Pin #
Pin RS-485 + Pin 1 RS-485 +
Pin RS-485 - Pin 2 RS-485 -
Pin GND Pin 3 RS-485 GND
Power In (+) Pin 4 V+
Power In (-) Pin 5 V-
Frame Ground Pin 6 FRAME GND
23
The MCS-MAGNUM BACnet DEVICE ID can be verified and changed (with the proper authorization code)
from MCS-Magnum’s keypad the keypad/LCD of a live unit.
1. To get authorized on Magnum do the following:
2. Press ‘Menu’
3. Using , , , or position curser to ‘Passwords’
4. Press key.
5. Enter 4 digit password & press .
6. Press ‘Menu’ to make next selection.
1. \Press the MENU key and then Using , , , or position curser to Serv Tools then press the ENTER key.
2. then Using , , , or position curser to BACnet Setting then press Enter.
3. Use , , curser to change the BACnet Device ID.
4. Set your desired address then press Enter.
5. Reset or cycle power to the magnum for the change to take effect.
The MCS-MAGNUM IP must be set to the address specified on the MCS-BMS-GATEWAY’s label
(Example - 192.168.18.101). Range of default settings: 101-150
The MCS-MAGNUM IP address can be verified and changed (with the proper authorization code) from the
MCS-Magnum’s Keypad/LCD of a live unit.
The following steps will display the IP Address settings:
(to change the address you first must be authorized)
6. Press the MENU key and then Using ↑, ↓, , or position curser to Serv Tools then press the ENTER key.
7. Then Using, , or position curser to Serv Tools then press Enter.
8. Then Using,, , or position curser to Ethernet Network then press Enter.
9. Then Using↑, , , or position curser to IP address then press Enter.
24
10. Using , to increase and decrease the first set of values then use the to select the next set of num-
bers and use , to increase and decrease the second value and repeat the previous steps for rest
of the ip address.
11. Once you have set the desired address press the Enter key.
12. Reset or cycle power to the magnum for the change to take effect.
The MCS-MAGNUM IP address can be verified and changed (with the proper authorization code) from
MCS-CONNECT of a live unit.
RS-485
EOL Switch
(off)
Leave in Position A
25
7.4. Biasing the RS-485 Device Network
• An RS-485 network with more than one device needs to have biasing to ensure proper communi-
cation. The biasing only needs to be done on one device.
• The MCS-BMS-GATEWAY has 510 Ohm resistors that can be used to set the biasing.
• The MCS-BMS-GATEWAY’s default positions from the factory for the Biasing jumpers are OFF.
• The OFF position is when the 2 RED biasing jumpers straddle the 4 pins closest to the outside of
the board of the MCS-BMS-GATEWAY. (Figure 9)
• Only turn biasing ON:
• IF the BMS cannot see more than one device connected to the MCS-BMS-GATEWAY AND all
the settings (wiring, and DIP switches) have been checked.
• To turn biasing ON, move the 2 RED biasing jumpers to straddle the 4 pins closest to the inside
of the board of the MCS-BMS-GATEWAY.
RS-485 Bias
Switch
(off)
7.5. End of Line Termination Switch for the Modbus RS-485 Device Network
• On long RS-485 cabling runs, the RS-485 trunk must be properly terminated at each end.
• The MCS-BMS-GATEWAY has an End of Line (EOL) blue jumper. The default setting for this
Blue EOL switch is OFF with the jumper straddling the pins closest to the inside of the board of
the MCS-BMS-GATEWAY.
• On short cabling runs the EOL switch does not to need to be turned ON
• If the MCS-BMS-GATEWAY is placed at one of the ends of the trunk, set the blue EOL jumper to
the ON position straddling the pins closest to the outside of the board of the MCS-BMS-GATE-
WAY.
• Always leave the single Red Jumper in the A position (default factory setting).
7.6. Power-Up MCS-BMS-GATEWAY
Apply power to MCS-BMS-GATEWAYas show below in Figure 13. Ensure that the power supply used complies
with the specifications provided in chapter 9.
6. MCS-BMS-GATEWAY accepts either 9-30VDC or 12-24 VAC on pins 4 and 5.
7. Frame GND should be connected.
26
FPC – ED4 (Typical) 210mA 130mA 90mA
FPC – ED4 (Maximum) 250mA 170mA 110mA
NOTE: These values are ‘nominal’ and a safety margin should be added to the power supply of the host system.
A safety margin of 25% is recommended.
Figure 12: Required current draw for the MCS-BMS-GATEWAY
27
Chapter - 8. BMS-GATEWAY SWITCH SETTINGS
33
Chapter - 9. Installing the MCS-BMS-GATEWAY-N54
9.1. Termination Resistor
If the MCS-BMS-GATEWAY-N54 is the last device on the serial trunk, then the End-Of-Line Termination
Switch needs to be enabled. To enable the Termination Resistor, move the TERM dip switch to the right in the
orientation shown in Figure 4.
Termination resistor is also used to reduce noise. It pulls the two lines of an idle bus together. However, the
resistor would override the effect of any bias resistors if connected.
NOTE: The R1 and R2 DIP Switches apply settings to the respective serial port.
NOTE: If the gateway is already powered on, DIP switch settings will not take effect unless the unit is power
cycled.
34
Figure 5: R1 & R2 Connection Ports
3.2.1 Wiring
RS-485 RS-232
BMS RS-485 Gateway Pin BMS RS-232 Gateway Pin
Wiring Assignment Wiring Assignment
RS-485 + TX + RS-232 - TX +
RS-485 - RX - RS-232 + RX -
GND GND GND GND Power up
NOTE: Use standard grounding principles for GND.
9.4. Power up the MCS-BMS-GATEWAY-N54 Power up
4 Power up the ProtoNode
Check
Check power requirements
power requirements in the
in the table table below:
below:
4 Power
Powerup the ProtoNode
Requirement for ProtoNode External Gateway
Check power requirements in the table below: Current Draw Type
ProtoNode Family
Power Requirement for ProtoNode External Gateway 12VDC 24VDC/AC
FPC – N54 (Typical) 250mA
Current Draw Type 125mA
NOTE: These values are ‘nominal’ and a safety margin should be added to the power supply
ProtoNode Family 12VDC 24VDC/AC
of the host system. A safety margin of 25% is recommended.
FPC – N54 (Typical) 250mA 125mA
Figure 6: Required Current Draw for the Gateway
NOTE: These values are ‘nominal’ and a safety margin should be added to the power supply
of the host
Apply system.
power A safety
to the margin
ProtoNode of 25%below
as shown is recommended.
in Figure 7. Ensure that the power supply used complies
with the specifications provided
Figure 6: in SectionCurrent
Required 10.4. Draw for the Gateway
Apply power to the MCS-BMS-GATEWAY-N54 as shown below in Figure 7. Ensure that the power supply
• toThethegateway
used
Apply complies
power withaccepts
the
ProtoNode
ProtoNode 9-30VDC
as shown or in
specifications 24VAC
Start-up
below on7.pins
provided
Guide
Figure L+ and
Ensure N-.
in that
Section
11 10.4.
the power supply used complies
with the specifications
• Frame GND provided Section
in be
should 10.4.
connected.
•• The gateway accepts 9-30VDC or 24VAC on pins L+ and N-.
The gateway accepts 9-30VDC or 24VAC on pins L+ and N-.
•• Frame
Frame GND
GND should
should be connected.
be connected.
35
9.5. Connect the PC to the MCS-BMS-GATEWAY-N54
9.5.1 Connecting to the Gateway via Ethernet
Connect a Cat-5 Ethernet cable (straight through or cross-over) between the local PC and MCS-BMS-
GATEWAY-N54
Ethernet Port
• Click the Okay button to close the Internet Protocol window and the Close button to close the Ethernet
Properties window.
36
9.6. Navigate to the ProtoNode Login Page
• Open a web browser and connect to the ProtoNode’s default IP Address. The default IP Address of the
FieldServer is 192.168.2.101, Subnet Mask is 255.255.255.0.
• If the PC and the ProtoNode are on different IP networks, assign a static IP Address to the PC on the
192.168.2.X network.
• When the warning that “Your connection is not private” appears, click the advanced button on the bottom
left corner of the screen.
37
• Additional text will expand below the warning, click the underlined text to go to the IP Address. In the
Figure 11 example this text is “Proceed to 10.40.50.94 (unsafe)”.
• When the login screen appears, put in the Username (default is “admin”) and the Password (found on the
label of the FieldServer).
PASSWORD ON LABEL
NOTE: A user has 5 attempts to login then there will be a 10-minute lockout. There is no timeout on the Field-
Server to enter a password.
38
9.8. Select the Security Mode
On the first login to the FieldServer, the following screen will appear that allows the user to select which mode
the FieldServer should use.
Figure 14: Security Mode Selection Screen – Certificate & Private Key
• Copy and paste the Certificate and Private Key text into their respective fields. If the Private Key is en-
crypted type in the associated Passphrase.
• Click Save.
• A “Redirecting” message will appear. After a short time, the FieldServer GUI will open.
39
Chapter - 10. APPENDIX - INPUT / OUTPUT POINTS / STATES
Sensor M-1 AI: 1 Refer to Config *30001 *AI: 1 Sensor 2-9 AI:41 Refer to Config *30041 *AI: 41
Sensor M-2 AI: 2 Refer to Config *30002 *AI: 2 Sensor 2-10 AI:42 Refer to Config *30042 *AI: 42
Sensor M-3 AI: 3 Refer to Config *30003 *AI: 3 Sensor 2-11 AI:43 Refer to Config *30043 *AI: 43
Sensor M-4 AI: 4 Refer to Config *30004 *AI: 4 Sensor 2-12 AI:44 Refer to Config *30044 *AI: 44
Sensor M-5 AI: 5 Refer to Config *30005 *AI: 5 Sensor 2-13 AI:45 Refer to Config *30045 *AI: 45
Sensor M-6 AI: 6 Refer to Config *30006 *AI: 6 Sensor 2-14 AI:46 Refer to Config *30046 *AI: 46
Sensor M-7 AI: 7 Refer to Config *30007 *AI: 7 Sensor 2-15 AI:47 Refer to Config *30047 *AI: 47
Sensor M-8 AI: 8 Refer to Config *30008 *AI: 8 Sensor 2-16 AI:48 Refer to Config *30048 *AI: 48
Sensor M-9 AI: 9 Refer to Config *30009 *AI: 9 Sensor 3-1 AI:49 Refer to Config *30049 *AI:49
Sensor M-10 AI:10 Refer to Config *30010 *AI: 10 Sensor 3-2 AI:50 Refer to Config *30050 *AI: 50
Sensor M-11 AI:11 Refer to Config *30011 *AI: 11 Sensor 3-3 AI:51 Refer to Config *30051 *AI: 51
Sensor M-12 AI:12 Refer to Config *30012 *AI: 12 Sensor 3-4 AI:52 Refer to Config *30052 *AI: 52
Sensor M-13 AI:13 Refer to Config *30013 *AI: 13 Sensor 3-5 AI:53 Refer to Config *30053 *AI: 53
Sensor M-14 AI:14 Refer to Config *30014 *AI: 14 Sensor 3-6 AI:54 Refer to Config *30054 *AI: 54
Sensor M-15 AI:15 Refer to Config *30015 *AI: 15 Sensor 3-7 AI:55 Refer to Config *30055 *AI: 55
Sensor M-16 AI:16 Refer to Config *30016 *AI: 16 Sensor 3-8 AI:56 Refer to Config *30056 *AI: 56
Sensor 1-1 AI:17 Refer to Config *30017 *AI: 17 Sensor 3-9 AI:57 Refer to Config *30057 *AI: 57
Sensor 1-2 AI:18 Refer to Config *30018 *AI: 18 Sensor 3-10 AI:58 Refer to Config *30058 *AI: 58
Sensor 1-3 AI:19 Refer to Config *30019 *AI: 19 Sensor 3-11 AI:59 Refer to Config *30059 *AI: 59
Sensor 1-4 AI:20 Refer to Config *30020 *AI: 20 Sensor 3-12 AI:60 Refer to Config *30060 *AI: 60
Sensor 1-5 AI:21 Refer to Config *30021 *AI: 21 Sensor 3-13 AI:61 Refer to Config *30061 *AI: 61
Sensor 1-6 AI:22 Refer to Config *30022 *AI: 22 Sensor 3-14 AI:62 Refer to Config *30062 *AI: 62
Sensor 1-7 AI:23 Refer to Config *30023 *AI: 23 Sensor 3-15 AI:63 Refer to Config *30063 *AI: 63
Sensor 1-8 AI:24 Refer to Config *30024 *AI: 24 Sensor 3-16 AI:64 Refer to Config *30064 *AI: 64
Sensor 1-9 AI:25 Refer to Config *30025 *AI: 25 Sensor 4-1 AI:65 Refer to Config *30065 *AI: 65
Sensor 1-10 AI:26 Refer to Config *30026 *AI: 26 Sensor 4-2 AI:66 Refer to Config *30066 *AI: 66
Sensor 1-11 AI:27 Refer to Config *30027 *AI: 27 Sensor 4-3 AI:67 Refer to Config *30067 *AI: 67
Sensor 1-12 AI:28 Refer to Config *30028 *AI: 28 Sensor 4-4 AI:68 Refer to Config *30068 *AI: 68
Sensor 1-13 AI:29 Refer to Config *30029 *AI: 29 Sensor 4-5 AI:69 Refer to Config *30069 *AI: 69
Sensor 1-14 AI:30 Refer to Config *30030 *AI: 30 Sensor 4-6 AI:70 Refer to Config *30070 *AI: 70
Sensor 1-15 AI:31 Refer to Config *30031 *AI: 31 Sensor 4-7 AI:71 Refer to Config *30071 *AI: 71
Sensor 1-16 AI:32 Refer to Config *30032 *AI: 32 Sensor 4-8 AI:72 Refer to Config *30072 *AI: 72
Sensor 2-1 AI:33 Refer to Config *30033 *AI: 33 Sensor 4-9 AI:73 Refer to Config *30073 *AI: 73
Sensor 2-2 AI:34 Refer to Config *30034 *AI: 34 Sensor 4-10 AI:74 Refer to Config *30074 *AI: 74
Sensor 2-3 AI:35 Refer to Config *30035 *AI: 35 Sensor 4-11 AI:75 Refer to Config *30075 *AI: 75
Sensor 2-4 AI:36 Refer to Config *30036 *AI: 36 Sensor 4-12 AI:76 Refer to Config *30076 *AI: 76
Sensor 2-5 AI:37 Refer to Config *30037 *AI: 37 Sensor 4-13 AI:77 Refer to Config *30077 *AI: 77
Sensor 2-6 AI:38 Refer to Config *30038 *AI: 38 Sensor 4-14 AI:78 Refer to Config *30078 *AI: 78
Sensor 2-7 AI:39 Refer to Config *30039 *AI: 39 Sensor 4-15 AI:79 Refer to Config *30079 *AI: 79
Sensor 2-8 AI:40 Refer to Config *30040 *AI: 40 Sensor 4-16 AI:80 Refer to Config *30080 *AI: 80
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
40
10.2. Relay Output Points
Relay Output points are read-only. Output numbering is based upon MCS-RO-10 (MCS-RO BASE, MCS-RO-EXT) hard-
ware type board.
Magnum BACnet ID BACnet Name Modbus N2 Magnum BACnet ID BACnet Name Modbus N2
Relay M–1 BO: 1 Refer to Config 00001 BO: 1 Relay 4–1 BO:41 Refer to Config 00041 BO: 41
Relay M–2 BO: 2 Refer to Config 00002 BO: 2 Relay 4–2 BO:42 Refer to Config 00042 BO: 42
Relay M–3 BO: 3 Refer to Config 00003 BO: 3 Relay 4–3 BO:43 Refer to Config 00043 BO: 43
Relay M–4 BO: 4 Refer to Config 00004 BO: 4 Relay 4–4 BO:44 Refer to Config 00044 BO: 44
Relay M–5 BO: 5 Refer to Config 00005 BO: 5 Relay 4–5 BO:45 Refer to Config 00045 BO: 45
Relay M–6 BO: 6 Refer to Config 00006 BO: 6 Relay 4–6 BO:46 Refer to Config 00046 BO: 46
Relay M–7 BO: 7 Refer to Config 00007 BO: 7 Relay 4–7 BO:47 Refer to Config 00047 BO: 47
Relay M–8 BO: 8 Refer to Config 00008 BO: 8 Relay 4–8 BO:48 Refer to Config 00048 BO: 48
Relay M–9 BO: 9 Refer to Config 00009 BO: 9 Relay 4–9 BO:49 Refer to Config 00049 BO: 49
Relay M-10 BO:10 Refer to Config 00010 BO: 10 Relay 4 -10 BO:50 Refer to Config 00050 BO: 50
Relay 1–1 BO:11 Refer to Config 00011 BO: 11 Relay 5–1 BO:51 Refer to Config 00051 BO: 51
Relay 1–2 BO:12 Refer to Config 00012 BO: 12 Relay 5–2 BO:52 Refer to Config 00052 BO: 52
Relay 1–3 BO:13 Refer to Config 00013 BO: 13 Relay 5–3 BO:53 Refer to Config 00053 BO: 53
Relay 1–4 BO:14 Refer to Config 00014 BO: 14 Relay 5–4 BO:54 Refer to Config 00054 BO: 54
Relay 1–5 BO:15 Refer to Config 00015 BO: 15 Relay 5–5 BO:55 Refer to Config 00055 BO: 55
Relay 1–6 BO:16 Refer to Config 00016 BO: 16 Relay 5–6 BO:56 Refer to Config 00056 BO: 56
Relay 1–7 BO:17 Refer to Config 00017 BO: 17 Relay 5–7 BO:57 Refer to Config 00057 BO: 57
Relay 1–8 BO:18 Refer to Config 00018 BO: 18 Relay 5–8 BO:58 Refer to Config 00058 BO: 58
Relay 1–9 BO:19 Refer to Config 00019 BO: 19 Relay 5–9 BO:59 Refer to Config 00059 BO: 59
Relay 1- 10 BO:20 Refer to Config 00020 BO: 20 Relay 5 -10 BO:60 Refer to Config 00060 BO: 60
Relay 2–1 BO:21 Refer to Config 00021 BO: 21 Relay 6–1 BO:61 Refer to Config 00061 BO: 61
Relay 2–2 BO:22 Refer to Config 00022 BO: 22 Relay 6–2 BO:62 Refer to Config 00062 BO: 62
Relay 2–3 BO:23 Refer to Config 00023 BO: 23 Relay 6–3 BO:63 Refer to Config 00063 BO: 63
Relay 2–4 BO:24 Refer to Config 00024 BO: 24 Relay 6–4 BO:64 Refer to Config 00064 BO: 64
Relay 2–5 BO:25 Refer to Config 00025 BO: 25 Relay 6–5 BO:65 Refer to Config 00065 BO: 65
Relay 2–6 BO:26 Refer to Config 00026 BO: 26 Relay 6- 6 BO:66 Refer to Config 00066 BO: 66
Relay 2–7 BO:27 Refer to Config 00027 BO: 27 Relay 6–7 BO:67 Refer to Config 00067 BO: 67
Relay 2–8 BO:28 Refer to Config 00028 BO: 28 Relay 6–8 BO:68 Refer to Config 00068 BO: 68
Relay 2–9 BO:29 Refer to Config 00029 BO: 29 Relay 6–9 BO:69 Refer to Config 00069 BO: 69
Relay 2 -10 BO:30 Refer to Config 00030 BO: 30 Relay 6–10 BO:70 Refer to Config 00760 BO: 70
Relay 3–1 BO:31 Refer to Config 00031 BO: 31 Relay 7–1 BO:71 Refer to Config 00071 BO: 71
Relay 3–2 BO:32 Refer to Config 00032 BO: 32 Relay 7–2 BO:72 Refer to Config 00072 BO: 72
Relay 3–3 BO:33 Refer to Config 00033 BO: 33 Relay 7–3 BO:73 Refer to Config 00073 BO: 73
Relay 3–4 BO:34 Refer to Config 00034 BO: 34 Relay 7–4 BO:74 Refer to Config 00074 BO: 74
Relay 3–5 BO:35 Refer to Config 00035 BO: 35 Relay 7–5 BO:75 Refer to Config 00075 BO: 75
Relay 3- 6 BO:36 Refer to Config 00036 BO: 36 Relay 7–6 BO:76 Refer to Config 00076 BO: 76
Relay 3–7 BO:37 Refer to Config 00037 BO: 37 Relay 7–7 BO:77 Refer to Config 00077 BO: 77
Relay 3–8 BO:38 Refer to Config 00038 BO: 38 Relay 7–8 BO:78 Refer to Config 00078 BO: 78
Relay 3–9 BO:39 Refer to Config 00039 BO: 39 Relay 7–9 BO:79 Refer to Config 00079 BO: 79
Relay 3–10 BO:40 Refer to Config 00040 BO: 40 Relay 7–10 BO:80 Refer to Config 00070 BO: 80
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
41
10.3. ANALOG Output Points
Analog Output Points are read-only. Output numbering is based upon SI16-AO4 (SI-Base and SI-EXT) hardware type
board. Notable BACnet properties available: Units
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
10.4. Setpoints
Setpoints are read-only. Notable BACnet properties available: Units
Magnum BACnet ID BACnet Name Modbus N2
Setpoint #1 AV:0 STP# 1-<Setpoint name> 40301 ADF:1
Setpoint #21 AV:88 STP# 21-<Setpoint name> 40321 ADF:89
STP# 163-<Setpoint
Setpoint #163 AV:230 40463 ADF:231
name>
42
Magnum BACnet ID BACnet Name Modbus Register N2
Compressor #3 State MV:3 COMPRESSOR #3 STATE 30309 BYT:4
Compressor #4 State MV:4 COMPRESSOR #4 STATE 30310 BYT:5
Compressor #5 State MV:5 COMPRESSOR #5 STATE 30311 BYT:6
Compressor #6 State MV:6 COMPRESSOR #6 STATE 30312 BYT:7
Compressor #7 State MV:7 COMPRESSOR #7 STATE 30313 BYT:8
Compressor #8 State MV:8 COMPRESSOR #8 STATE 30314 BYT:9
Compressor #9 State MV:130 COMPRESSOR #9 STATE 30560 BYT:131
Compressor #10 State MV:131 COMPRESSOR #10 STATE 30561 BYT:132
Compressor #11 State MV:132 COMPRESSOR #11 STATE 30562 BYT:133
Compressor #12 State MV:133 COMPRESSOR #12 STATE 30563 BYT:134
Compressor #13 State MV:134 COMPRESSOR #13 STATE 30564 BYT:135
Compressor #14 State MV:135 COMPRESSOR #14 STATE 30565 BYT:136
Compressor #15 State MV:136 COMPRESSOR #15 STATE 30566 BYT:137
Compressor #16 State MV:137 COMPRESSOR #16 STATE 30567 BYT:138
Compressor #17 State MV:138 COMPRESSOR #17 STATE 30568 BYT:139
Compressor #18 State MV:139 COMPRESSOR #18 STATE 30569 BYT:140
Compressor #19 State MV:140 COMPRESSOR #19 STATE 30570 BYT:141
Compressor #20 State MV:141 COMPRESSOR #20 STATE 30571 BYT:142
43
Magnum BACnet ID BACnet Name Modbus N2
Compressor #4 Disch SH AV:33 C4_Disch SH *30342 *ADF:34
Compressor #4 Suct SH AV:34 C4_Suct SH *30340 *ADF:35
Compressor #4 Oil Pres Diff AV:66 C4_Oil Pres Diff *30378 *ADF:67
Compressor #5 FLA% AV:35 C5_FLA% *30323 *ADF:36
Compressor #5 Sat Suction AV:38 C5_Sat Suct *30343 *ADF:39
Compressor #5 Sat Disch AV:39 C5_ Sat Disch *30345 *ADF:40
Compressor #5 Disch SH AV:40 C5_Disch SH *30346 *ADF:41
Compressor #5 Suct SH AV:41 C5_Suct SH *30344 *ADF:42
Compressor #5 Oil Pres Diff AV:67 C5_Oil Pres Diff *30379 *ADF:68
Compressor #6 FLA% AV:42 C6_FLA% *30324 *ADF:43
Compressor #6 Sat Suction AV:45 C6_Sat Suct *30347 *ADF:46
Compressor #6 Sat Disch AV:46 C6_ Sat Disch *30349 *ADF:47
Compressor #6 Disch SH AV:47 C6_Disch SH *30350 *ADF:48
Compressor #6 Suct SH AV:48 C6_Suct SH *30348 *ADF:49
Compressor #6 Oil Pres Diff AV:68 C6_Oil Pres Diff *30380 *ADF:69
Compressor #7 FLA% AV:49 C7_FLA% *30325 *ADF:50
Compressor #7 Sat Suction AV:52 C7_Sat Suct *30351 *ADF:53
Compressor #7 Sat Disch AV:53 C7_ Sat Disch *30353 *ADF:54
Compressor #7 Disch SH AV:54 C7_Disch SH *30354 *ADF:55
Compressor #7 Suct SH AV:55 C7_Suct SH *30352 *ADF:56
Compressor #7 Oil Pres Diff AV:69 C7_Oil Pres Diff *30381 *ADF:70
Compressor #8 FLA% AV:56 C8_FLA% *30326 *ADF:57
Compressor #8 Sat Suction AV:59 C8_Sat Suct *30352 *ADF:53
Compressor #8 Sat Suction AV:59 C8_Sat Suct *30355 *ADF:60
Compressor #8 Sat Disch AV:60 C8_ Sat Disch *30357 *ADF:61
Compressor #8 Disch SH AV:61 C8_Disch SH *30358 *ADF:62
Compressor #8 Suct SH AV:62 C8_Suct SH *30356 *ADF:63
Compressor #8 Oil Pres Diff AV:70 C8_Oil Pres Diff *30382 *ADF:71
Compressor #9 FLA% AV:440 C9_FLA% *30572 *ADF:441
Compressor #9 Sat Suction AV: 443 C9_Sat Suct *30584 *ADF: 442
Compressor #9 Sat Disch AV: 444 C9_ Sat Disch *30586 *ADF: 443
Compressor #9 Disch SH AV: 445 C9_Disch SH *30587 *ADF: 444
Compressor #9 Suct SH AV: 446 C9_Suct SH *30585 *ADF: 445
Compressor #9 Oil Pres Diff AV:524 C9_Oil Pres Diff *30656 *ADF:525
Compressor #10 FLA% AV:447 C10_FLA% *30573 *ADF:448
Compressor #10 Sat Suction AV: 450 C10_Sat Suct *30588 *ADF: 451
Compressor #10 Sat Disch AV: 451 C10_ Sat Disch *30590 *ADF: 452
Compressor #10 Disch SH AV: 452 C10_Disch SH *30591 *ADF: 453
Compressor #10 Suct SH AV: 453 C10_Suct SH *30589 *ADF: 454
Compressor #10 Oil Pres Diff AV:525 C10_Oil Pres Diff *30657 *ADF:526
Compressor #11 FLA% AV:454 C11_FLA% *30574 *ADF:455
Compressor #11 Sat Suction AV: 457 C11_Sat Suct *30592 *ADF: 458
Compressor #11 Sat Disch AV: 458 C11_ Sat Disch *30594 *ADF: 459
Compressor #11 Disch SH AV: 459 C11_Disch SH *30595 *ADF: 460
Compressor #11 Suct SH AV: 460 C11_Suct SH *30593 *ADF: 461
Compressor #11 Oil Pres Diff AV: 526 C11_Oil Pres Diff *30658 *ADF: 527
Compressor #12 FLA% AV: 461 C12_FLA% *30575 *ADF: 462
Compressor #12 Sat Suction AV: 464 C12_Sat Suct *30596 *ADF: 465
Compressor #12 Sat Disch AV: 465 C12_ Sat Disch *30598 *ADF: 466
Compressor #12 Disch SH AV: 466 C12_Disch SH *30599 *ADF: 467
Compressor #12 Suct SH AV: 467 C12_Suct SH *30597 *ADF 468
Compressor #12 Oil Pres Diff AV:527 C12_Oil Pres Diff *30659 *ADF:528
44
Magnum BACnet ID BACnet Name Modbus N2
Compressor #13 FLA% AV:468 C13_FLA% *30576 *ADF:469
Compressor #13 Sat Suction AV: 471 C13_Sat Suct *30600 *ADF: 470
Compressor #13 Sat Disch AV: 472 C13_ Sat Disch *30602 *ADF: 473
Compressor #13 Disch SH AV: 473 C13_Disch SH *30603 *ADF: 474
Compressor #13 Suct SH AV: 474 C13_Suct SH *30600 *ADF: 475
Compressor #13 Oil Pres Diff AV: 528 C13_Oil Pres Diff *30661 *ADF: 529
Compressor #14 FLA% AV: 475 C14_FLA% *30577 *ADF: 476
Compressor #14 Sat Suction AV: 478 C14_Sat Suct *30604 *ADF: 479
Compressor #14 Sat Disch AV: 479 C14_ Sat Disch *30606 *ADF: 480
Compressor #14 Disch SH AV: 480 C14_Disch SH *30607 *ADF: 481
Compressor #14 Suct SH AV: 481 C14_Suct SH *30605 *ADF: 482
Compressor #14 Oil Pres Diff AV: 529 C14_Oil Pres Diff *30661 *ADF: 530
Compressor #15 FLA% AV: 482 C15_FLA% *30578 *ADF: 483
Compressor #15 Sat Suction AV: 485 C15_Sat Suct *30608 *ADF: 486
Compressor #15 Sat Disch AV: 486 C15_ Sat Disch *30610 *ADF: 487
Compressor #15 Disch SH AV: 487 C15_Disch SH *30611 *ADF: 488
Compressor #15 Suct SH AV: 488 C15_Suct SH *30609 *ADF: 489
Compressor #15 Oil Pres Diff AV: 530 C15_Oil Pres Diff *3062 *ADF: 531
Compressor #16 FLA% AV: 489 C16_FLA% *30579 *ADF: 490
Compressor #16 Sat Suction AV: 492 C16_Sat Suct *30612 *ADF: 493
Compressor #16 Sat Disch AV: 493 C16_ Sat Disch *30614 *ADF: 494
Compressor #16 Disch SH AV: 494 C16_Disch SH *30615 *ADF: 495
Compressor #16 Suct SH AV: 495 C16_Suct SH *30613 *ADF: 496
Compressor #16 Oil Pres Diff AV: 531 C16_Oil Pres Diff *30663 *ADF: 532
Compressor #17 FLA% AV: 496 C17_FLA% *30580 *ADF: 497
Compressor #17 Sat Suction AV: 499 C17_Sat Suct *30616 *ADF: 500
Compressor #17 Sat Disch AV: 500 C17_ Sat Disch *30618 *ADF: 501
Compressor #17 Disch SH AV: 501 C17_Disch SH *30619 *ADF: 502
Compressor #17 Suct SH AV: 502 C17_Suct SH *30617 *ADF: 503
Compressor #17 Oil Pres Diff AV: 532 C17_Oil Pres Diff *30664 *ADF: 533
Compressor #18 FLA% AV: 503 C18_FLA% *30581 *ADF: 504
Compressor #18 Sat Suction AV: 506 C18_Sat Suct *30620 *ADF: 507
Compressor #18 Sat Disch AV: 507 C18_ Sat Disch *30622 *ADF: 508
Compressor #18 Disch SH AV: 508 C18_Disch SH *30623 *ADF: 509
Compressor #18 Suct SH AV: 509 C18_Suct SH *30621 *ADF: 510
Compressor #18 Oil Pres Diff AV: 533 C18_Oil Pres Diff *30665 *ADF: 534
Compressor #19 FLA% AV: 510 C19_FLA% *30582 *ADF: 511
Compressor #19 Sat Suction AV: 513 C19_Sat Suct *30624 *ADF: 514
Compressor #19 Sat Disch AV: 514 C19_ Sat Disch *30626 *ADF: 515
Compressor #19 Disch SH AV: 515 C19_Disch SH *30627 *ADF: 516
Compressor #19 Suct SH AV: 516 C19_Suct SH *30625 *ADF: 517
Compressor #19 Oil Pres Diff AV: 534 C19_Oil Pres Diff *30666 *ADF: 535
Compressor #20 FLA% AV: 517 C20_FLA% *30583 *ADF: 518
Compressor #20 Sat Suction AV: 520 C20_Sat Suct *30628 *ADF: 521
Compressor #20 Sat Disch AV: 521 C20_ Sat Disch *30630 *ADF: 522
Compressor #20 Disch SH AV: 522 C20_Disch SH *30631 *ADF: 523
Compressor #20 Suct SH AV: 523 C20_Suct SH *30629 *ADF: 524
Compressor #20 Oil Pres Diff AV: 535 C20_Oil Pres Diff *30667 *ADF: 536
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
45
10.7. Network inputs to MCS-MAGNUM
The MCS-Magnum can receive changes from the network to enable or disable the Network Run/Stop, Network Target
Reset (adjustments to the Cooling Target, Setpoint #1, based on Setpoint #21), Network Demand FLA, and Network
Demand Steps.
The MCS-Magnum must be set up to accept these inputs. The configuration file must contain a Network Run/Stop,
Network Target, Network Demand FLA, and Network Demand Steps sensors.
Magnum BACnet ID BACnet Name Modbus N2
Network Run/Stop AV:246 Net_R/S 40201 BO:247
Network Target/Reset AV:247 Net_Tar/Res 40202 AO:248
Network Demand/FLA AV:248 Net_Demad_FLA 40204 AO:249
Network Demand/Steps AV:249 Net_Demad_Steps 40205 AO:250
Note the following Information panel has a Network Run/Stop, and /or Network Target Reset sensors inputs indicated.
This is an example of how MCS-Config must be setup in the General Information and Evaporator Information panels.
The sensors must be set up as follows (This is only an example)
46
10.8. MCS Capacity Control State Chart
The values exposed in the capacity state relate to the descriptions in this table.
State Number Description 12 RESERVED
0 “UNIT IN POWER UP” 13 “AMBIENT OFF “
1 RESERVED 14 “PROCESS HEAT OFF”
2 “NO RUN- I/O LOST” 15 “UNIT IS UNLOADED”
3 “UNIT IN LOCKOUT “ 16 “UNIT IS LOADED “
4 “UNIT IS OFF “ 17 “OFF TMP-ICE MADE “
5 “UNIT IS HOLDING “ 18 “ECONOMIZER ONLY “
6 “UNIT UNLOADING “ 19 “SWITCHING MODES “
7 “UNIT IS LOADING “ 20 “UNIT SMOKE UNLDG”
8 “NO RUN–SAFETY “ 21 “UNIT OFF UNLDING”
9 “RUN/STOP SW OFF “ 22 “UNIT DMD UNLDING”
10 “SCHEDULED OFF “ 23 “UNIT HEAT UNLDNG”
11 “OFF-NO FLOW(s)”
47
Chapter - 11. ALARMS- UNIT/COMPRESSOR / MODBUS
48
11.2. Compressor Alarms
49
V17 Frimware Supporting Alarm Indicators
Compressor Alarms
Relay output Modbus BACnet
Discharge Temperature Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Suction Pressure Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Discharge Pressure Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Oil Pressure Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Oil Temperature Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Motor Temperature Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Evap Refrigerant Temperature Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Evap Refrigerant Level Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Oil Seal Temperature Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Pre-Oil Filter Pressure Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
Circuit Leaving Water Sensor Fault HVAC/RTU HVAC/RTU HVAC/RTU
50
51
Modbus Register
Modbus Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp.
Alarms
Function Type #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 #13 #14 #15 #16 #17 #18 #19 #20
LOW_SUCTION 04:input Register 31201 31252 31303 31354 31405 31456 31507 31558 31609 31660 31711 31762 31813 31864 31915 31966 32017 32068 32119 32170
UNSAFE_SUCTION 04:input Register 31202 31253 31304 31355 31406 31457 31508 31559 31610 31661 31712 31763 31814 31865 31916 31967 32018 32069 32120 32171
HIGH_DISCHARGE_PSI 04:input Register 31203 31254 31305 31356 31407 31458 31509 31560 31611 31662 31713 31764 31815 31866 31917 31968 32019 32070 32121 32172
HIGH_DISCHARGE_TEMP 04:input Register 31204 31255 31306 31357 31408 31459 31510 31561 31612 31663 31714 31765 31816 31867 31918 31969 32020 32071 32122 32173
LOW_OIL_PSI 04:input Register 31205 31256 31307 31358 31409 31460 31511 31562 31613 31664 31715 31766 31817 31868 31919 31970 32021 32072 32123 32174
UNSAFE_OIL_PSI 04:input Register 31206 31257 31308 31359 31410 31461 31512 31563 31614 31665 31716 31767 31818 31869 31920 31971 32022 32073 32124 32175
HIGH_OIL_TEMP 04:input Register 31207 31258 31309 31360 31411 31462 31513 31564 31615 31666 31717 31768 31819 31870 31921 31972 32023 32074 32125 32176
11.3. MODBUS Alarms
DIRTY_OIL_FILTER 04:input Register 31208 31259 31310 31361 31412 31463 31514 31565 31616 31667 31718 31769 31820 31871 31922 31973 32024 32075 32126 32177
HIGH_OIL_SEAL_TEMP 04:input Register 31209 31260 31311 31362 31413 31464 31515 31566 31617 31668 31719 31770 31821 31872 31923 31974 32025 32076 32127 32178
NO_CRANK_CASE_HEATER_PROOF 04:input Register 31210 31261 31312 31363 31414 31465 31516 31567 31618 31669 31720 31771 31822 31873 31924 31975 32026 32077 32128 32179
HIGH_AMPS 04:input Register 31211 31262 31313 31364 31415 31466 31517 31568 31619 31670 31721 31772 31823 31874 31925 31976 32027 32078 32129 32180
LOW_AMPS 04:input Register 31212 31263 31314 31365 31416 31467 31518 31569 31620 31671 31722 31773 31824 31875 31926 31977 32028 32079 32130 32181
HIGH_MOTOR_TEMP 04:input Register 31213 31264 31315 31366 31417 31468 31519 31570 31621 31672 31723 31774 31825 31876 31927 31978 32029 32080 32131 32182
NO_COMPRESSOR_PROOF 04:input Register 31214 31265 31316 31367 31418 31469 31520 31571 31622 31673 31724 31775 31826 31877 31928 31979 32030 32081 32132 32183
LOW_OIL_SUPERHEAT 04:input Register 31215 31266 31317 31368 31419 31470 31521 31572 31623 31674 31725 31776 31827 31878 31929 31980 32031 32082 32133 32184
PUMP_DOWN 04:input Register 31216 31267 31318 31369 31420 31471 31522 31573 31624 31675 31726 31777 31828 31879 31930 31981 32032 32083 32134 32185
LOW_DISCHARGE_PSI 04:input Register 31217 31268 31319 31370 31421 31472 31523 31574 31625 31676 31727 31778 31829 31880 31931 31982 32033 32084 32135 32186
LUBE_OIL_TEMP 04:input Register 31218 31269 31320 31371 31422 31473 31524 31575 31626 31677 31728 31779 31830 31881 31932 31983 32034 32085 32136 32187
LUBE_OIL_PSI 04:input Register 31219 31270 31321 31372 31423 31474 31525 31576 31627 31678 31729 31780 31831 31882 31933 31984 32035 32086 32137 32188
LUBE_OIL_TIME 04:input Register 31220 31271 31322 31373 31424 31475 31526 31577 31628 31679 31730 31781 31832 31883 31934 31985 32036 32087 32138 32189
REFRIGERATION_LEAK 04:input Register 31221 31272 31323 31374 31425 31476 31527 31578 31629 31680 31731 31782 31833 31884 31935 31986 32037 32088 32139 32190
LOW_REFRIGERATION_TEMP 04:input Register 31222 31273 31324 31375 31426 31477 31528 31579 31630 31681 31732 31783 31834 31885 31936 31987 32038 32089 32140 32191
TOO_MANY_PURGES 04:input Register 31223 31274 31325 31376 31427 31478 31529 31580 31631 31682 31733 31784 31835 31886 31937 31988 32039 32090 32141 32192
EXCESS_PURGING_TIME 04:input Register 31224 31275 31326 31377 31428 31479 31530 31581 31632 31683 31734 31785 31836 31887 31938 31989 32040 32091 32142 32193
PURGE_FLOAT_ERROR 04:input Register 31225 31276 31327 31378 31429 31480 31531 31582 31633 31684 31735 31786 31837 31888 31939 31990 32041 32092 32143 32194
LOW_DIFFERENTIAL_PSI_RATIO 04:input Register 31226 31277 31328 31379 31430 31481 31532 31583 31634 31685 31736 31787 31838 31889 31940 31991 32042 32093 32144 32195
LOW_SUPERHEAT 04:input Register 31227 31278 31329 31380 31431 31482 31533 31584 31635 31686 31737 31788 31839 31890 31941 31992 32043 32094 32145 32196
LOW_DISCHARGE_SUPERHEAT 04:input Register 31228 31279 31330 31381 31432 31483 31534 31585 31636 31687 31738 31789 31840 31891 31942 31993 32044 32095 32146 32197
LOST_LEG_PART_WINDING 04:input Register 31229 31280 31331 31382 31433 31484 31535 31586 31637 31688 31739 31790 31841 31892 31943 31994 32045 32096 32147 32198
HIGH_PARTS_PER_MILLION_LEAK 04:input Register 31230 31281 31332 31383 31434 31485 31536 31587 31638 31689 31740 31791 31842 31893 31944 31995 32046 32097 32148 32199
HIGH_REFRIGERATION_LEVEL 04:input Register 31231 31282 31333 31384 31435 31486 31537 31588 31639 31690 31741 31792 31843 31894 31945 31996 32047 32098 32149 32200
LOW_OIL_LEVEL 04:input Register 31232 31283 31334 31385 31436 31487 31538 31589 31640 31691 31742 31793 31844 31895 31946 31997 32048 32099 32150 32201
NO_FLOW 04:input Register 31233 31284 31335 31386 31437 31488 31539 31590 31641 31692 31743 31794 31845 31896 31947 31998 32049 32100 32151 32202
OIL_FLOW 04:input Register 31234 31285 31336 31387 31438 31489 31540 31591 31642 31693 31744 31795 31846 31897 31948 31999 32050 32101 32152 32203
52
Modbus Register
Modbus Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp.
Alarms
Function Type #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 #13 #14 #15 #16 #17 #18 #19 #20
COMPRESSOR_SPEED_FAULT 04:input Register 31235 31286 31337 31388 31439 31490 31541 31592 31643 31694 31745 31796 31847 31898 31949 32000 32051 32102 32153 32204
LOW_TANDEM_SUPERHEAT 04:input Register 31236 31287 31338 31389 31440 31491 31542 31593 31644 31695 31746 31797 31848 31899 31950 32001 32052 32103 32154 32205
HIGH_TANDEM_SUPERHEAT 04:input Register 31237 31288 31339 31390 31441 31492 31543 31594 31645 31696 31747 31798 31849 31900 31951 32002 32053 32104 32155 32206
EXCESS_SURGES 04:input Register 31238 31289 31340 31391 31442 31493 31544 31595 31646 31697 31748 31799 31850 31901 31952 32003 32054 32105 32156 32207
HIGH_SUPERHEAT 04:input Register 31239 31290 31341 31392 31443 31494 31545 31596 31647 31698 31749 31800 31851 31902 31953 32004 32055 32106 32157 32208
Suction Temperature Sensor Fault 04:input Register 31240 31291 31342 31393 31444 31495 31546 31597 31648 31699 31750 31801 31852 31903 31954 32005 32056 32107 32158 32209
Discharge Temperature Sensor Fault 04:input Register 31241 31292 31343 31394 31445 31496 31547 31598 31649 31700 31751 31802 31853 31904 31955 32006 32057 32108 32159 32210
Suction Pressure Sensor Fault 04:input Register 31242 31293 31344 31395 31446 31497 31548 31599 31650 31701 31752 31803 31854 31905 31956 32007 32058 32109 32160 32211
Discharge Pressure Sensor Fault 04:input Register 31243 31294 31345 31396 31447 31498 31549 31600 31651 31702 31753 31804 31855 31906 31957 32008 32059 32110 32161 32212
Oil Pressure Sensor Sensor Fault 04:input Register 31244 31295 31346 31397 31448 31499 31550 31601 31652 31703 31754 31805 31856 31907 31958 32009 32060 32111 32162 32213
Oil Temperature Sensor Fault 04:input Register 31245 31296 31347 31398 31449 31500 31551 31602 31653 31704 31755 31806 31857 31908 31959 32010 32061 32112 32163 32214
Motor Temperature Sensor Fault 04:input Register 31246 31297 31348 31399 31450 31501 31552 31603 31654 31705 31756 31807 31858 31909 31960 32011 32062 32113 32164 32215
Evap Refrigerant Temp. Sensor Fault 04:input Register 31247 31298 31349 31400 31451 31502 31553 31604 31655 31706 31757 31808 31859 31910 31961 32012 32063 32114 32165 32216
Evap Refrigerant Level Sensor Fault 04:input Register 31248 31299 31350 31401 31452 31503 31554 31605 31656 31707 31758 31809 31860 31911 31962 32013 32064 32115 32166 32217
Oil Seal Temperature Sensor Fault 04:input Register 31249 31300 31351 31402 31453 31504 31555 31606 31657 31708 31759 31810 31861 31912 31963 32014 32065 32116 32167 32218
Pre-Oil Filter Presssure Sensor Fault 04:input Register 31250 31301 31352 31403 31454 31505 31556 31607 31658 31709 31760 31811 31862 31913 31964 32015 32066 32117 32168 32219
Circuit Leaving Water Sensor Fault 04:input Register 31251 31302 31353 31404 31455 31506 31557 31608 31659 31710 31761 31812 31863 31914 31965 32016 32067 32118 32169 32220
53
BACnet Object Identifier
BACnet Object Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp.
Alarms
Type #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 #13 #14 #15 #16 #17 #18 #19 #20
LOW_SUCTION Analog Value 1396 1447 1498 1549 1600 1651 1702 1753 1804 1855 1906 1957 2008 2059 2110 2161 2212 2263 2314 2365
UNSAFE_SUCTION Analog Value 1397 1448 1499 1550 1601 1652 1703 1754 1805 1856 1907 1958 2009 2060 2111 2162 2213 2264 2315 2366
HIGH_DISCHARGE_PSI Analog Value 1398 1449 1500 1551 1602 1653 1704 1755 1806 1857 1908 1959 2010 2061 2112 2163 2214 2265 2316 2367
HIGH_DISCHARGE_TEMP Analog Value 1399 1450 1501 1552 1603 1654 1705 1756 1807 1858 1909 1960 2011 2062 2113 2164 2215 2266 2317 2368
LOW_OIL_PSI Analog Value 1400 1451 1502 1553 1604 1655 1706 1757 1808 1859 1910 1961 2012 2063 2114 2165 2216 2267 2318 2369
UNSAFE_OIL_PSI Analog Value 1401 1452 1503 1554 1605 1656 1707 1758 1809 1860 1911 1962 2013 2064 2115 2166 2217 2268 2319 2370
HIGH_OIL_TEMP Analog Value 1402 1453 1504 1555 1606 1657 1708 1759 1810 1861 1912 1963 2014 2065 2116 2167 2218 2269 2320 2371
DIRTY_OIL_FILTER Analog Value 1403 1454 1505 1556 1607 1658 1709 1760 1811 1862 1913 1964 2015 2066 2117 2168 2219 2270 2321 2372
HIGH_OIL_SEAL_TEMP Analog Value 1404 1455 1506 1557 1608 1659 1710 1761 1812 1863 1914 1965 2016 2067 2118 2169 2220 2271 2322 2373
NO_CRANK_CASE_HEATER_PROOF Analog Value 1405 1456 1507 1558 1609 1660 1711 1762 1813 1864 1915 1966 2017 2068 2119 2170 2221 2272 2323 2374
HIGH_AMPS Analog Value 1406 1457 1508 1559 1610 1661 1712 1763 1814 1865 1916 1967 2018 2069 2120 2171 2222 2273 2324 2375
LOW_AMPS Analog Value 1407 1458 1509 1560 1611 1662 1713 1764 1815 1866 1917 1968 2019 2070 2121 2172 2223 2274 2325 2376
HIGH_MOTOR_TEMP Analog Value 1408 1459 1510 1561 1612 1663 1714 1765 1816 1867 1918 1969 2020 2071 2122 2173 2224 2275 2326 2377
NO_COMPRESSOR_PROOF Analog Value 1409 1460 1511 1562 1613 1664 1715 1766 1817 1868 1919 1970 2021 2072 2123 2174 2225 2276 2327 2378
LOW_OIL_SUPERHEAT Analog Value 1410 1461 1512 1563 1614 1665 1716 1767 1818 1869 1920 1971 2022 2073 2124 2175 2226 2277 2328 2379
PUMP_DOWN Analog Value 1411 1462 1513 1564 1615 1666 1717 1768 1819 1870 1921 1972 2023 2074 2125 2176 2227 2278 2329 2380
LOW_DISCHARGE_PSI Analog Value 1412 1463 1514 1565 1616 1667 1718 1769 1820 1871 1922 1973 2024 2075 2126 2177 2228 2279 2330 2381
LUBE_OIL_TEMP Analog Value 1413 1464 1515 1566 1617 1668 1719 1770 1821 1872 1923 1974 2025 2076 2127 2178 2229 2280 2331 2382
LUBE_OIL_PSI Analog Value 1414 1465 1516 1567 1618 1669 1720 1771 1822 1873 1924 1975 2026 2077 2128 2179 2230 2281 2332 2383
LUBE_OIL_TIME Analog Value 1415 1466 1517 1568 1619 1670 1721 1772 1823 1874 1925 1976 2027 2078 2129 2180 2231 2282 2333 2384
REFRIGERATION_LEAK Analog Value 1416 1467 1518 1569 1620 1671 1722 1773 1824 1875 1926 1977 2028 2079 2130 2181 2232 2283 2334 2385
LOW_REFRIGERATION_TEMP Analog Value 1417 1468 1519 1570 1621 1672 1723 1774 1825 1876 1927 1978 2029 2080 2131 2182 2233 2284 2335 2386
TOO_MANY_PURGES Analog Value 1418 1469 1520 1571 1622 1673 1724 1775 1826 1877 1928 1979 2030 2081 2132 2183 2234 2285 2336 2387
EXCESS_PURGING_TIME Analog Value 1419 1470 1521 1572 1623 1674 1725 1776 1827 1878 1929 1980 2031 2082 2133 2184 2235 2286 2337 2388
PURGE_FLOAT_ERROR Analog Value 1420 1471 1522 1573 1624 1675 1726 1777 1828 1879 1930 1981 2032 2083 2134 2185 2236 2287 2338 2389
LOW_DIFFERENTIAL_PSI_RATIO Analog Value 1421 1472 1523 1574 1625 1676 1727 1778 1829 1880 1931 1982 2033 2084 2135 2186 2237 2288 2339 2390
LOW_SUPERHEAT Analog Value 1422 1473 1524 1575 1626 1677 1728 1779 1830 1881 1932 1983 2034 2085 2136 2187 2238 2289 2340 2391
LOW_DISCHARGE_SUPERHEAT Analog Value 1423 1474 1525 1576 1627 1678 1729 1780 1831 1882 1933 1984 2035 2086 2137 2188 2239 2290 2341 2392
LOST_LEG_PART_WINDING Analog Value 1424 1475 1526 1577 1628 1679 1730 1781 1832 1883 1934 1985 2036 2087 2138 2189 2240 2291 2342 2393
HIGH_PARTS_PER_MILLION_LEAK Analog Value 1425 1476 1527 1578 1629 1680 1731 1782 1833 1884 1935 1986 2037 2088 2139 2190 2241 2292 2343 2394
HIGH_REFRIGERATION_LEVEL Analog Value 1426 1477 1528 1579 1630 1681 1732 1783 1834 1885 1936 1987 2038 2089 2140 2191 2242 2293 2344 2395
LOW_OIL_LEVEL Analog Value 1427 1478 1529 1580 1631 1682 1733 1784 1835 1886 1937 1988 2039 2090 2141 2192 2243 2294 2345 2396
NO_FLOW Analog Value 1428 1479 1530 1581 1632 1683 1734 1785 1836 1887 1938 1989 2040 2091 2142 2193 2244 2295 2346 2397
OIL_FLOW Analog Value 1429 1480 1531 1582 1633 1684 1735 1786 1837 1888 1939 1990 2041 2092 2143 2194 2245 2296 2347 2398
54
BACnet Object Identifier
BACnet Object Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp.
Alarms
Type #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 #13 #14 #15 #16 #17 #18 #19 #20
LOW_SUCTION Analog Value 1396 1447 1498 1549 1600 1651 1702 1753 1804 1855 1906 1957 2008 2059 2110 2161 2212 2263 2314 2365
UNSAFE_SUCTION Analog Value 1397 1448 1499 1550 1601 1652 1703 1754 1805 1856 1907 1958 2009 2060 2111 2162 2213 2264 2315 2366
HIGH_DISCHARGE_PSI Analog Value 1398 1449 1500 1551 1602 1653 1704 1755 1806 1857 1908 1959 2010 2061 2112 2163 2214 2265 2316 2367
HIGH_DISCHARGE_TEMP Analog Value 1399 1450 1501 1552 1603 1654 1705 1756 1807 1858 1909 1960 2011 2062 2113 2164 2215 2266 2317 2368
LOW_OIL_PSI Analog Value 1400 1451 1502 1553 1604 1655 1706 1757 1808 1859 1910 1961 2012 2063 2114 2165 2216 2267 2318 2369
UNSAFE_OIL_PSI Analog Value 1401 1452 1503 1554 1605 1656 1707 1758 1809 1860 1911 1962 2013 2064 2115 2166 2217 2268 2319 2370
HIGH_OIL_TEMP Analog Value 1402 1453 1504 1555 1606 1657 1708 1759 1810 1861 1912 1963 2014 2065 2116 2167 2218 2269 2320 2371
DIRTY_OIL_FILTER Analog Value 1403 1454 1505 1556 1607 1658 1709 1760 1811 1862 1913 1964 2015 2066 2117 2168 2219 2270 2321 2372
HIGH_OIL_SEAL_TEMP Analog Value 1404 1455 1506 1557 1608 1659 1710 1761 1812 1863 1914 1965 2016 2067 2118 2169 2220 2271 2322 2373
NO_CRANK_CASE_HEATER_PROOF Analog Value 1405 1456 1507 1558 1609 1660 1711 1762 1813 1864 1915 1966 2017 2068 2119 2170 2221 2272 2323 2374
HIGH_AMPS Analog Value 1406 1457 1508 1559 1610 1661 1712 1763 1814 1865 1916 1967 2018 2069 2120 2171 2222 2273 2324 2375
LOW_AMPS Analog Value 1407 1458 1509 1560 1611 1662 1713 1764 1815 1866 1917 1968 2019 2070 2121 2172 2223 2274 2325 2376
HIGH_MOTOR_TEMP Analog Value 1408 1459 1510 1561 1612 1663 1714 1765 1816 1867 1918 1969 2020 2071 2122 2173 2224 2275 2326 2377
NO_COMPRESSOR_PROOF Analog Value 1409 1460 1511 1562 1613 1664 1715 1766 1817 1868 1919 1970 2021 2072 2123 2174 2225 2276 2327 2378
LOW_OIL_SUPERHEAT Analog Value 1410 1461 1512 1563 1614 1665 1716 1767 1818 1869 1920 1971 2022 2073 2124 2175 2226 2277 2328 2379
PUMP_DOWN Analog Value 1411 1462 1513 1564 1615 1666 1717 1768 1819 1870 1921 1972 2023 2074 2125 2176 2227 2278 2329 2380
LOW_DISCHARGE_PSI Analog Value 1412 1463 1514 1565 1616 1667 1718 1769 1820 1871 1922 1973 2024 2075 2126 2177 2228 2279 2330 2381
LUBE_OIL_TEMP Analog Value 1413 1464 1515 1566 1617 1668 1719 1770 1821 1872 1923 1974 2025 2076 2127 2178 2229 2280 2331 2382
LUBE_OIL_PSI Analog Value 1414 1465 1516 1567 1618 1669 1720 1771 1822 1873 1924 1975 2026 2077 2128 2179 2230 2281 2332 2383
LUBE_OIL_TIME Analog Value 1415 1466 1517 1568 1619 1670 1721 1772 1823 1874 1925 1976 2027 2078 2129 2180 2231 2282 2333 2384
REFRIGERATION_LEAK Analog Value 1416 1467 1518 1569 1620 1671 1722 1773 1824 1875 1926 1977 2028 2079 2130 2181 2232 2283 2334 2385
LOW_REFRIGERATION_TEMP Analog Value 1417 1468 1519 1570 1621 1672 1723 1774 1825 1876 1927 1978 2029 2080 2131 2182 2233 2284 2335 2386
TOO_MANY_PURGES Analog Value 1418 1469 1520 1571 1622 1673 1724 1775 1826 1877 1928 1979 2030 2081 2132 2183 2234 2285 2336 2387
EXCESS_PURGING_TIME Analog Value 1419 1470 1521 1572 1623 1674 1725 1776 1827 1878 1929 1980 2031 2082 2133 2184 2235 2286 2337 2388
PURGE_FLOAT_ERROR Analog Value 1420 1471 1522 1573 1624 1675 1726 1777 1828 1879 1930 1981 2032 2083 2134 2185 2236 2287 2338 2389
LOW_DIFFERENTIAL_PSI_RATIO Analog Value 1421 1472 1523 1574 1625 1676 1727 1778 1829 1880 1931 1982 2033 2084 2135 2186 2237 2288 2339 2390
LOW_SUPERHEAT Analog Value 1422 1473 1524 1575 1626 1677 1728 1779 1830 1881 1932 1983 2034 2085 2136 2187 2238 2289 2340 2391
LOW_DISCHARGE_SUPERHEAT Analog Value 1423 1474 1525 1576 1627 1678 1729 1780 1831 1882 1933 1984 2035 2086 2137 2188 2239 2290 2341 2392
LOST_LEG_PART_WINDING Analog Value 1424 1475 1526 1577 1628 1679 1730 1781 1832 1883 1934 1985 2036 2087 2138 2189 2240 2291 2342 2393
HIGH_PARTS_PER_MILLION_LEAK Analog Value 1425 1476 1527 1578 1629 1680 1731 1782 1833 1884 1935 1986 2037 2088 2139 2190 2241 2292 2343 2394
HIGH_REFRIGERATION_LEVEL Analog Value 1426 1477 1528 1579 1630 1681 1732 1783 1834 1885 1936 1987 2038 2089 2140 2191 2242 2293 2344 2395
LOW_OIL_LEVEL Analog Value 1427 1478 1529 1580 1631 1682 1733 1784 1835 1886 1937 1988 2039 2090 2141 2192 2243 2294 2345 2396
NO_FLOW Analog Value 1428 1479 1530 1581 1632 1683 1734 1785 1836 1887 1938 1989 2040 2091 2142 2193 2244 2295 2346 2397
OIL_FLOW Analog Value 1429 1480 1531 1582 1633 1684 1735 1786 1837 1888 1939 1990 2041 2092 2143 2194 2245 2296 2347 2398
55
BACnet Object Identifier
BACnet Object Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp. Comp.
Alarms
Type #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 #13 #14 #15 #16 #17 #18 #19 #20
COMPRESSOR_SPEED_FAULT Analog Value 1430 1481 1532 1583 1634 1685 1736 1787 1838 1889 1940 1991 2042 2093 2144 2195 2246 2297 2348 2399
LOW_TANDEM_SUPERHEAT Analog Value 1431 1482 1533 1584 1635 1686 1737 1788 1839 1890 1941 1992 2043 2094 2145 2196 2247 2298 2349 2400
HIGH_TANDEM_SUPERHEAT Analog Value 1432 1483 1534 1585 1636 1687 1738 1789 1840 1891 1942 1993 2044 2095 2146 2197 2248 2299 2350 2401
EXCESS_SURGES Analog Value 1433 1484 1535 1586 1637 1688 1739 1790 1841 1892 1943 1994 2045 2096 2147 2198 2249 2300 2351 2402
HIGH_SUPERHEAT Analog Value 1434 1485 1536 1587 1638 1689 1740 1791 1842 1893 1944 1995 2046 2097 2148 2199 2250 2301 2352 2403
Suction Temperature Sensor Fault Analog Value 1435 1486 1537 1588 1639 1690 1741 1792 1843 1894 1945 1996 2047 2098 2149 2200 2251 2302 2353 2404
Discharge Temperature Sensor Fault Analog Value 1436 1487 1538 1589 1640 1691 1742 1793 1844 1895 1946 1997 2048 2099 2150 2201 2252 2303 2354 2405
Suction Pressure Sensor Fault Analog Value 1437 1488 1539 1590 1641 1692 1743 1794 1845 1896 1947 1998 2049 2100 2151 2202 2253 2304 2355 2406
Discharge Pressure Sensor Fault Analog Value 1438 1489 1540 1591 1642 1693 1744 1795 1846 1897 1948 1999 2050 2101 2152 2203 2254 2305 2356 2407
Oil Pressure Sensor Sensor Fault Analog Value 1439 1490 1541 1592 1643 1694 1745 1796 1847 1898 1949 2000 2051 2102 2153 2204 2255 2306 2357 2408
Oil Temperature Sensor Fault Analog Value 1440 1491 1542 1593 1644 1695 1746 1797 1848 1899 1950 2001 2052 2103 2154 2205 2256 2307 2358 2409
Motor Temperature Sensor Fault Analog Value 1441 1492 1543 1594 1645 1696 1747 1798 1849 1900 1951 2002 2053 2104 2155 2206 2257 2308 2359 2410
Evap Refrigerant Temp. Sensor Fault Analog Value 1442 1493 1544 1595 1646 1697 1748 1799 1850 1901 1952 2003 2054 2105 2156 2207 2258 2309 2360 2411
Evap Refrigerant Level Sensor Fault Analog Value 1443 1494 1545 1596 1647 1698 1749 1800 1851 1902 1953 2004 2055 2106 2157 2208 2259 2310 2361 2412
Oil Seal Temperature Sensor Fault Analog Value 1444 1495 1546 1597 1648 1699 1750 1801 1852 1903 1954 2005 2056 2107 2158 2209 2260 2311 2362 2413
Pre-Oil Filter Presssure Sensor Fault Analog Value 1445 1496 1547 1598 1649 1700 1751 1802 1853 1904 1955 2006 2057 2108 2159 2210 2261 2312 2363 2414
Circuit Leaving Water Sensor Fault Analog Value 1446 1497 1548 1599 1650 1701 1752 1803 1854 1905 1956 2007 2058 2109 2160 2211 2262 2313 2364 2415
Chapter - 12. APP085 USING MCS-CONFIG
APPLICATION NOTE
APP #085
MCS-BMS-GATEWAY
A BMS GATEWAY is needed to support the following protocols;
BACnet IP, Modbus IP, BACnet MS/TP, Johnson N2
and LonTalk
MCS-BMS-GATEWAY
56
USING MCS-CONFIG
If you are licensed to use MCS-CONFIG follow the instruction below to start building a file for your
MCS-BMS-GATEWAY.
MCS-Config version 18.13 or greater is required to create the csv files for Bacnet IP and Modbus IP.
CREATING CSV FILES USING MCS-CONFIG
1. Open MCS-Config program and load the config you are working on.
2. Click on Setup.
NOTE:
The Ethernet IP, ETC settings do not need to be set
when using RS485 connection.
3. Click on BMS-POINTS
2 Revision 08-03-2023-09:27 AM
57
5. Choose BMS type:
a. BMS-GATEWAY-(default - with LonTalk)
b. BMS-GATEWAY-N54
6. Click 'CREATE MCS-BMS-GATEWAY CSV FILES'
7. Drop down window shows Fixed BACnet ID;
a. Default - 'DIP Switch field-selectable BACnet ID 181xx'
b. Customer Specified BACnet ID (custom BACnet number can be added)
Default setting
Add Customer's
BACnet ID
58
3 Revision 08-03-2023-09:27 AM
9. When popup window comes up click ok.
NOTE:
When prompted, select the file location where you want to save the csv files. This would be the time
to name the CSV files, there is a 15 character maximum not including the file extension.
If you do not name the file it will default to the first 15 characters of the config name as shown below.
10. MCS-Config will create CSV file: (CONFIG.CSV) and files needed for BMS-GATEWAY.
11. Click to save files (choose where you want to save the file)
4 59 Revision 08-03-2023-09:27 AM
Setting up and Programming a MCS-BMS-GATEWAY
A. Field Server Toolbox program installed on a computer (download from mcscontrols.com).
B. An Ethernet Cable. (crossover cable is only required when connected from MCS-BMS Gateway
to MCS-MAGNUM)
C. CSV files created from the MCS-MAGNUM Controller supplied by MCS or OEM / Contractor.
1. Connect PC to a powered BMS-GATEWAY with an Ethernet Cable or crossover cable, your PC must be
logged in as administrator.
2. Open Field Server Toolbox Program. (If running program for the first time click on ‘DISCOVER
NOW’, (unclick 'Show on startup' at bottom when closing program). The MCS-BMS-GATEWAY
you’re connected will show up on the top line giving you the IP address and MAC address. Also you may
need to right click and run as Administrator if the Gateway did not show up.
3. Look at CONNECTIVITY column lights,
a. If Blue, it is a NEW CONNECTION
b. If GREEN, click Connect (shows that this is on the same network)
c. If YELLOW, it is not on same network, go to 'Note at bottom of this page'
Loading CSV file the MCS-BMS-GATEWAY
4. Click 'CONNECT'
a. Log in using 'admin' as user name.
b. Password is located on the label of the ethernet jack on the MCS-BMS-GATEWAY.
c. Enter the password, select HTTP (not secure, vulnerable to man-in-the-middle attacks) unless in region
of install.
4. Click Diagnostics and Debugging.
5. Click Setup.
6. Click File Transfer.
7. Click the Configuration tab, then click Choose Files.
8. In Pop Up file browser, navigate to the saved CSV files, select Config and click open .
9. Click Submit.
10. Click the General Tab, then click Choose Files
11. Select the correct BMS protocol file, than click open.
a. bac for BacNet MS/TP
b. jn2 for Johnson N2
c. lon for Lontalk (not available on MCS-BMS-GATEWAY-NL or BMS-GATEWAY-N54)
d. mod for Modbus over IP
e. modbac for RTU to BACnet
12. Click Submit.
13. Click System Restart to reboot the BMS GATEWAY card and refresh the web browser.
14. Close the web browser and the Field Server Toolbox.
15. Reconnect the BMS GATEWAY card to the MCS MAGNUM and have the building management system
discover the card.
01-26-2023 DEW Update drawing, made changes to pages changing how we hook up gateway
61