FHC - Hydraulic Calculation Report

Submitted by FHC user number: Project: EX1


Project Ref ---
Area Ref: 1F
Inst. Number: 1

Tel:
Fax:

Project Data and Design Parameters


Project name : EX1
Area reference : 1F
Address / location : ---
Project number : ---
Installation number(s) : 1
Drawing number(s) : ---
Issue no / date : ---
Designers reference : ---
Project Data File : EX1.FHC
Hazard classification : 1
Design authority : NFPA 13 : 2016 - Installation of Sprinkler S
Insurance company : ---
Specified density of discharge : 24.00 mm/min (l/min/m2)
Assumed maximum area of operation : 81.00 m2
Number of operating sprinkler heads : 9 + 1 hydrant(s)
Maximum area covered per head : 9.00 m2
Highest head / nozzle above source : 11.20 m
Number of pipes in system : 29 from 25 to 100 mm
Pressure loss equation used : Hazen-Williams
Fluid : Water
Pipe Data Table : STD_PIPE.PDT
Maximum fluid velocity : 19.34 m/s in pipe 310 320
Volume of pipework and fittings : 1.56 m3
Elbows are welded for : 0 mm and above
Comment : ---
Checked by & Date :

Source duty = 2516.7 l/min @ 12.894 bar at node no 100

Canute FHC Ver: 1.8.4 Tuesday, October 1, 2024 - 15:54


www.canutesoft.com Page: 1/3
FHC - Hydraulic Calculation Report
Submitted by user number: Project: EX1
Project Ref ---
Tel: Area Ref: 1F
Fax: Inst. Number: 1

Operating Sprinkler Heads, Nozzles and Hydrants


Head|Node| Size | 'K' |F l o w|A r e a|Density mm/min|Pressure bar|Heights|Pipe
no | no | mm | factor| l/min | m2 |Req.d Actual| Min Actual| m | no
1 270 20.0 161.30 289.7 9.000 24.00 32.19 0.50 3.226 11.200 17
2 280 20.0 161.30 233.1 9.000 24.00 25.90 0.50 2.088 11.200 18
3 290 20.0 161.30 216.0 9.000 24.00 24.00 0.50 1.794 11.200 19
4 311 20.0 161.30 289.7 9.000 24.00 32.18 0.50 3.225 11.200 22
5 321 20.0 161.30 233.0 9.000 24.00 25.89 0.50 2.087 11.200 23
6 331 20.0 161.30 216.0 9.000 24.00 24.00 0.50 1.793 11.200 24
7 320 20.0 161.30 289.9 9.000 24.00 32.21 0.50 3.229 11.200 25
8 330 20.0 161.30 233.2 9.000 24.00 25.91 0.50 2.090 11.200 26
9 340 20.0 161.30 216.1 9.000 24.00 24.02 0.50 1.796 11.200 27
220 300.0 Hydrant 9.943 7.200 12

0 heads are under the required density / minimum pressures

Canute FHC Ver: 1.8.4 Tuesday, October 1, 2024 - 15:54


www.canutesoft.com Page: 2/3
FHC - Hydraulic Calculation Report
Submitted by user number: Project: EX1
Project Ref ---
Tel: Area Ref: 1F
Fax: Inst. Number: 1

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size Type| L/min | Length VJ|Dir. | Eq.len | Start | Start Frict
no | End |Bore 'C'| Vel m/s |EL T VT|Slope| mbar/m | End | End Static
1 100 100mm MW 2516.7 4.000 Up 4.00 2.000 12.894 -0.096
110 105.14 120 4.8 0 0 90.0 24.0 6.000 12.406 -0.392
2 110 100mm MW 2516.7 2.000 270 4.09 6.000 12.406 -0.098
120 105.14 120 4.8 1 0 0.0 24.0 6.000 12.307 +0.000
3 120 100mm MW 2516.7 0.500 270 0.50 6.000 12.307 -0.012
130 105.14 120 4.8 0 0 0.0 24.0 6.000 12.295 +0.000
4 130 100mm MW 2516.7 2.000 180 4.09 6.000 12.295 -0.098
140 105.14 120 4.8 1 0 0.0 24.0 6.000 12.197 +0.000
5 140 100mm MW 2516.7 6.000 Dn 8.09 6.000 12.197 -0.195
150 105.14 120 4.8 1 0 -90.0 24.0 0.000 12.590 +0.588
6 150 100mm MW 2516.7 35.000 270 37.09 0.000 12.590 -0.891
160 105.14 120 4.8 1 0 0.0 24.0 0.000 11.699 +0.000
7 160 100mm MW 2516.7 6.000 0 8.09 0.000 11.699 -0.195
170 105.14 120 4.8 1 0 0.0 24.0 0.000 11.504 +0.000
8 170 100mm MW 2516.7 7.200 Up 9.29 0.000 11.504 -0.223
180 105.14 120 4.8 1 0 90.0 24.0 7.200 10.576 -0.705
9 180 100mm MW 2516.7 2.000 0 4.09 7.200 10.576 -0.098
190 105.14 120 4.8 1 0 0.0 24.0 7.200 10.477 +0.000
10 190 100mm MW 2516.7 9.100 0 9.10 7.200 10.477 -0.219
200 105.14 120 4.8 0 0 0.0 24.0 7.200 10.259 +0.000
11 200 100mm MW 1294.0 9.500 0 9.50 7.200 10.259 -0.067
210 105.14 120 2.5 0 0 0.0 7.0 7.200 10.192 +0.000
12 210 100mm MW 1294.0 33.400 270 35.49 7.200 10.192 -0.249
220 105.14 120 2.5 1 0 0.0 7.0 7.200 9.943 +0.000
13 220 100mm MW 994.0 16.400 270 16.40 7.200 9.943 -0.071
230 105.14 120 1.9 0 0 0.0 4.3 7.200 9.872 +0.000
14 230 100mm MW 994.0 9.500 180 11.59 7.200 9.872 -0.050
240 105.14 120 1.9 1 0 0.0 4.3 7.200 9.822 +0.000
15 240 80mm BM 994.0 6.000 Up 7.99 7.200 9.822 -0.113
250 75.74 150 3.7 1 0 90.0 14.1 13.200 9.122 -0.588
16 250 80mm BM 994.0 12.400 90 14.39 13.200 9.122 -0.203
260 75.74 150 3.7 1 0 0.0 14.1 13.200 8.919 +0.000
17 260 25mm BM 738.8 3.000 180 5.97 13.200 8.919 -5.692
270 28.48 150 19.3 0 1 0.0 953.0 13.200 3.227 +0.000
18 270 25mm BM 449.1 3.000 180 3.00 13.200 3.227 -1.139
280 28.48 150 11.8 0 0 0.0 379.4 13.200 2.088 +0.000
19 280 25mm BM 216.0 3.000 180 3.00 13.200 2.088 -0.294
290 28.48 150 5.7 0 0 0.0 98.0 13.200 1.794 +0.000
20 260 80mm BM 255.2 3.000 90 3.00 13.200 8.919 -0.003
300 75.74 150 0.9 0 0 0.0 1.1 13.200 8.915 +0.000
21 300 80mm BM -483.5 3.000 90 3.00 13.200 8.915 +0.011
310 75.74 150 1.8 0 0 0.0 3.7 13.200 8.927 +0.000
22 300 25mm BM 738.7 3.000 180 5.97 13.200 8.915 -5.690
311 28.48 150 19.3 0 1 0.0 952.7 13.200 3.225 +0.000
23 311 25mm BM 449.0 3.000 180 3.00 13.200 3.225 -1.138
321 28.48 150 11.7 0 0 0.0 379.3 13.200 2.087 +0.000
24 321 25mm BM 216.0 3.000 180 3.00 13.200 2.087 -0.294
331 28.48 150 5.7 0 0 0.0 97.9 13.200 1.793 +0.000
25 310 25mm BM 739.2 3.000 180 5.97 13.200 8.927 -5.697
320 28.48 150 19.3 0 1 0.0 953.8 13.200 3.229 +0.000
26 320 25mm BM 449.3 3.000 180 3.00 13.200 3.229 -1.140
330 28.48 150 11.8 0 0 0.0 379.7 13.200 2.090 +0.000
27 330 25mm BM 216.1 3.000 180 3.00 13.200 2.090 -0.294
340 28.48 150 5.7 0 0 0.0 98.1 13.200 1.796 +0.000
28 200 100mm MW 1222.7 6.000 Up 15.07 7.200 10.259 -0.095
350 105.14 120 2.3 1 1 90.0 6.3 13.200 9.575 -0.588
29 310 80mm BM -1222.7 31.400 90 31.40 13.200 8.927 +0.649
350 75.74 150 4.5 0 0 0.0 20.7 13.200 9.575 +0.000
Maximum flow rate error at nodes : 0.01104 L/min
Maximum pressure drop error at nodes : 0.00061 bar
Maximum pressure
Canute FHC Ver: 1.8.4 drop error in loops : 0.00000 bar Tuesday, October 1, 2024 - 15:54
Overall head flow balance error :
www.canutesoft.com 0.00144 % Page: 3/3