0% found this document useful (0 votes)
41 views4 pages

Intelligent Power Control Hardware Solutions

Uploaded by

jegc2993
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views4 pages

Intelligent Power Control Hardware Solutions

Uploaded by

jegc2993
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Intelligent and secure controller hardware ensures compliance with local grid code and

standards. ePPC leverages a model-driven electrical digital twin for visualization, predictive
calculations, optimization, and management of renewable and conventional power plants.

Active Power Control


Active power can be limited or controlled at POI
based on operator or TSO schedule commands.
Rule-based or optimal dispatch can be used to
minimize import power cost, limit exported power
to the grid, take benefit of price arbitrage,
maximize peak shaving, and more.

Reactive Power Control


Reactive power control function allows
Q, V, PF, Q(V) control at the point of
interconnection.

Ramp Rate Control Planned Islanding


Ramp rate control are applicable to both active Seamlessly island plant at the planned time by preparing plant
and reactive power control. resources as well as controlling POI active and reactive power.

Islanded Management and control Synchronization


Manage and control plant assets in an islanded Detects stable grid availability and initiate synchro checking at
mode of operation. POI and monitor status of reconnection.

Renewable / Load Smoothing


Active and reactive power control at POI, Grid code support, renewable smoothing, peak shaving, rate control
and more.

Controller Options:

High Compute Medium Compute Low Compute IO Expansion

50 MW + 10 to 50 MW Less than 10 MW Protocol Expansion


Hardwire IO

Public
General Hardware Specifications for High / Medium Compute
Default Communication Protocols
• DNP3
19” Rack Mount
• Modbus TCP

Certifications
• CE, FCC, CCC,
• Electricity IV level for China,
• IEC-61850-3,
• IEEE-1613,
• UL, CB, LVD

IO Interface Hardware
• LAN: 8x10/100/1000 Base-T RJ45ports

Power Supply Requirements Physical Specifications


• Redundant Power Supply Configuration • Dimensions (W x D x H) 440 x 280 x 88 mm
• Power1: 100 ~ 240 VAC, 100 ~ 240 VDC • Enclosure SECC and aluminum
• Power2: 100 ~ 240 VAC, 100 ~ 240 VDC • Weight 6.0 Kg
• Power Consumption 25 W • Mounting 2U Rackmount
• System Design Fanless

Environment
• Operating Temperature -20 ~ 60°C (-4 ~ 140°F) @ 5 ~ 85% RH with 0.7 m/s airflow
• Storage Temperature -40 ~ 85°C (-40 ~ 185°F)
• Relative Humidity 10 ~ 95% RH @ 40°C, non-condensing
• Shock Protection Operating, IEC 60068-2-27, 50G, half sine, 11 ms
• Vibration Protection Operating, IEC 60068-2-64, 3 Grms, random, 5 ~ 500 Hz, 1hr/axis (mSATA)
Ingress Protection IP40

System Hardware
High Compute Medium Compute

• CPU: Intel Xeon E3 Processor • CPU: Intel Core i7 1.7 GHz Processor
• Memory: 32 GB RAM • Memory: 16 GB RAM
• Storage: SG 500G 2.5" SATAIII 5KRPM • Storage: SG 500G 2.5" SATAIII 5KRPM
• SSD: SQF 2.5" 820 128G MLC (40~85°C)UL, CB, • SSD: SQF 2.5" 820 128G MLC (40~85°C) UL,
LVD CB, LVD
• Display:DB15 VGA Connector, 1xDVI • Display:DB15 VGA Connector, 1xDVI

Public
General Hardware Specifications for Low Compute
Default Communication
• DNP3
• Modbus TCP

Certifications
• CE, FCC, CCC, UL, BSMI

IO Interface Hardware
• 4 x RJ45, 10/100/1000 Mbps IEEE 802.3u
1000Base-T Fast Ethernet

Power Supply Requirements


• Power Requirement: 10 - 36 VDC
• Power Consumption: 55W (Typical), 95.2W
(Max)

System Hardware Physical Specifications


• CPU: i7-7600U, 2.8GHz • Dimensions (W x D x H) 200 x 140 x 40 mm
• Memory: 8GB DDR4 2133 MHz • Enclosure Aluminum Housing
• Storage: SG 500G 2.5" SATAIII 5KRPM • Mounting Stand, Wall, VESA, DIN-rail
• Display: 1 x HDMI supports 1920 x 1080 • Weight (Net) Single stack: 1.4kg (3.09lbs)
@60Hz, 1 x DP supports 3840 x 2160 @30Hz

Environment
• Operating Temperature -20 ~ 60°C (-4 ~ 140°F) @ 5 ~ 85% RH with 0.7 m/s airflow
• Storage Temperature -40 ~ 85°C (-40 ~ 185°F) ƒ Relative Humidity 10 ~ 95% RH @ 40°C, non-
condensing
• Shock Protection Operating, IEC 60068-2-27, 50G, half sine, 11 ms
• Vibration Protection Operating, IEC 60068-2-64, 3 Grms, random, 5 ~ 500 Hz, 1hr/axis (mSATA)
• Ingress Protection IP40

Public
IO Expansion Programable Unit
Communication Protocols Power Supply: wide range, 32 - 250Vdc / 80 -
• IEC 60870-5-101,102,103,104 250Vac (2.5kVrms isolation) 24: 19.5-60Vdc
• IEC 61850 MMS, GOOSE (2.5kVrms isolation)
• DNP3.0 Serial & TCP
• Modbus RTU/TCP Physical Dimensions: 173 x 137 x 78.4mm
• Profibus DP DIN Rail mounting
• Procome
• DLMS Digital inputs - D1: (24) digital inputs.
• SNMP Combined I/O - C1: (8) digital inputs,
Logic Programing (4) relay outputs
• IEC61131-3 (2) DC current analog inputs

Communication Ports Options


• Serial ports: up to (4) ports with RS-232/RS-485/RS-422 selected by software
• Wireless connection: internal 4G(LTE), 3G and GPRS modem
• Ethernet: (2) 10/100BaseTX ports with independent MAC addresses
• Internal Ethernet Switch: up to (4) 10/100BaseTX ports with RJ45 connection and (2) FX100 with ST, SC
connectors or SFP interface, and supporting RSTP, HSR and PRP configurations

Additional I/O Expandability


Auxiliary units provide additional input and output ports for data acquisition and control capabilities. Each I/O
board is equipped with a RS-422 serial expansion port or a duel Ethernet ST/SC connector to communicate with
data collection servers, SCADA servers and other I/O modules.
• 48 Digital Inputs
• 24 Digital Inputs + 8 Digital Outputs
• 24 Digital Inputs + 8 Analog Inputs (0-20mA)
• 16 Digital Outputs
• 16 Analog Inputs
• Other configurations upon request

Public

You might also like