pm800 Technical Datasheet
pm800 Technical Datasheet
PE86134
Applications
Panel instrumentation
Sub-billing, cost allocation and energy management
Remote monitoring of an electrical installation
Power quality analysis
data logs, all stored in non-volatile memory (PM810 requires PM810LOG option).
ANSI 12.20 Class 0.2S and IEC 62053-22 Class 0.5S accuracy for active energy
PE86229
steam utilities (WAGES) through the pulse counting capabilities of the digital inputs.
Pulses from multiple inputs can be summed through a single channel.
Modular and upgradeable
All models offer easy-to-install option modules (memory, I/O and communications)
Remote display
The optional remote display can be mounted as far as 10 m from the metering unit.
The adapter includes an additional 2- or 4-wire RS-485/RS-232 communication port.
2 2014
PB101814 -36
Part Numbers
Description
Meter without display
Use the base meter unit without display to comply with voltage limitations for local regulations
when door mounting is not possible, or when meter voltage exceeds regulations, or when local
communications port is limited to the default (address 1, 9600 baud, parity even). Requires
software to read data.
PowerLogic PM800 series meter without display. PM810 meter unit only, no display, PM810UMG
basic instrumentation, THD, alarming, 80 kB logging
(with PM810LOG)
PM820 meter unit only, no display, PM820UMG
basic instrumentation, THD, alarming, 80 kB logging
disturbance detection.
Meter with integrated display
Use the meter with integrated display for panel mounting when door space is available and when
voltage usage is within the local regulation limits.
PowerLogic PM800 series meter with integrated display. PM810 meter with integrated display, PM810MG
2014 3
Part Numbers - continued
DB119011
Description
Optional modules
Ethernet communication module provides a 10/100BaseTx UTP port, PM8ECC
an RS-485 Modbus serial master port, Ethernet-to-serial line gateway
functionality, and an embedded web server that is fully compliant with
Transparent Ready - Level 1 (TRe1) systems.
The PM8ECC supports a private host PM8ECC MIB. Use of this MIB allows
4 2014
Selection guide PM810 PM820 PM850 PM870
Performance standard
Demand values
Current Present & max.
Active, reactive, apparent Present & max.
power
Predicted active, reactive, apparent power
Synchronisation of the measurement window
Demand calculation modeBlock, sliding, thermal
Other measurements
Hour counter
Power quality measurements
Harmonic distortion Current & voltage
Individual harmonics Current & voltage 31 (1) 31 63 63
(2)
Waveform capture - -
(4)
PM8ECC module
10/100BaseTx UTP port, RS-485 Modbus serial master port, Ethernet to serial line gateway,
embedded web server
Input/Output modules PM8M22 PM8M26* PM8M2222
Relay outputs 2 2 2
Digital inputs 2 6 2
Analogue outputs 4-20 mA 2
Analogue inputs 0-5 Vdc or 4-20 mA 2
* Includes a 24 Vdc Power Supply that can be used to power the digital inputs
Power Meters supports up to two option modules. When PM8M2222 & PM8ECC are mounted together
PowerLogic PM800 series meter with I/O module.
2014 5
Electrical characteristics
Type of measurement 63rd harmonic, 128 samples per cycle
Measurement accuracy standard PMD-S IEC 61557-12 compliant
Current 0.5% from 0.5 A to 10 A
Voltage 0.2% 10 V - 277 V
Power Factor +/- 0.002 from 0.500 leading to 0.500 lagging
Active Power 0.2%
Frequency
6 2014
Electromagnetic compatibility
Electrostatic discharge Level III (IEC 61000-4-2)
Level III (IEC 61000-4-3)
Immunity to fast transients Level III (IEC 61000-4-4)
Immunity to impulse waves Level III (IEC 61000-4-5)
Conducted immunity Level III (IEC 61000-4-6)
Level III (IEC 61000-4-8)
Immunity to voltage dips Level III (IEC 61000-4-11)
Conducted and radiated
emissions
Harmonics emissions IEC 61000-3-2
Flicker emissions IEC 61000-3-3
Surge immunity IEC 61000-4-12
Surge withstand capability (SWC)
Safety
(1)
Europe , as per IEC 61010-1
U.S. and Canada
Control Equipment)
Onboard communications
RS 485 port 2-wire, up to 38400 baud, Modbus
Model-dependent characteristics
Data Logs PM810 with PM810LOG, PM820, PM850 and PM870:
- 1 billing log
- 1 customisable log
PM850 and PM870 only: 2 additional custom logs
Min./max. Worst min. and max. with phase indication for Voltages,
Currents, Voltage unbalance, and THD. Min. and max. values
for power factor (True and Displacement), power (P, Q, S) and
frequency
One event log Time stamping to 1 second
Trend curves Four trend curves: 1 minute, 1 hour, 1 day and 1 month. Min./
(PM850 and PM870 only) max./avg. values recorded for eight parameters:
- every second for one minute for the 1-minute curve
- every minute for one hour for the 1-hour curve
- every hour for one day for the 1-day curve
- every day for one month for the 1-month curve
Hour counter Load running time in days, hours and minutes
Energy per shift
Available for all models (the PM810 requires the PM810LOG
module)
Forecasting Forecasting of the values for the trended parameters for the
(PM850 and PM870 only) next four hours and next four days
PM850 waveform capture Triggered manually or by alarm, 3-cycle, 128 samples/cycle on
PM870 enhanced waveform From 185 cycles on 1 channel at 16 samples per cycle up to
capture 3 cycles on 6 channels at 128 samples per cycle
Alarms Adjustable pickup and dropout setpoints and time delays,
numerous activation levels possible for a given type of alarm
Historical and active alarm screens with time stamping
Response time: 1 second
Boolean combination of four alarms is possible using
PM870
Digital alarms: status change of digital inputs
Memory available for logging 80 kbytes in PM810 with PM810LOG and PM820
and waveform capture (2) 800 kbytes in PM850 and PM870
Firmware update (all models) Update via the communication ports
File download available free from [Link]
Bar graphs (all models) Graphical representation of system performance
Display characteristics
Languages English, French, Spanish, German, Russian, Turkish and
Portuguese.
Display screen Back-lit white LCD (6 lines total, 4 concurrent values)
Dimensions Display screen viewable area 73 x 69 mm
Integrated display Overall 96 x 96 mm
Depth meter + display 69.4 mm + 17.8 mm
Remote display Overall 96 x 96 x 40 mm
Weight Meter with remote display adapter 0.81 kg
Remote display 0.23 kg
2014 7
Power meter with integrated display
Dimensions
DB111765
DB111766
DB111767
DB111770
8 2014
Remote display door mounting
Flush mounting
DB111792
Surface mount
DB111793
2014 9
ART / © 2014 - Schneider Electric - All rights reserved
04-2014