0% found this document useful (0 votes)
82 views10 pages

pm800 Technical Datasheet

Uploaded by

Rodrigo Silva
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views10 pages

pm800 Technical Datasheet

Uploaded by

Rodrigo Silva
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

The PowerLogic PM800 series meters offers many high-performance capabilities

PE86134

needed to meter and monitor an electrical installation in a compact 96 x 96 mm unit.


All models include an easy-to-read display that presents measurements for all three
phases and neutral at the same time, an RS-485 Modbus communication port, one
digital input, one KY-type digital output, total harmonic distortion (THD) metering,
and alarming on critical conditions. Four models offer an incremental choice of
custom logging and power quality analysis capabilities. Expand any model with

outputs, analogue inputs and outputs, and Ethernet port.

Applications
Panel instrumentation
Sub-billing, cost allocation and energy management
Remote monitoring of an electrical installation
Power quality analysis

Front view of PowerLogic PM800 series meter with Characteristics


integrated display.
Easy to install
Mounts using two clips, with no tools required. Direct connect the voltage inputs, with
no need for potential transformers (PTs) up to 600 VAC.
Easy to operate
Intuitive navigation with self-guided, language-selectable menus.
PB101823-50

System status at a glance


Large, anti-glare display with back-light provides summary screens with multiple
values. Bar charts graphically represent system loading and I/O.
Custom alarming with time stamping
Over 50 alarm conditions, including over or under conditions, digital input changes,
phase unbalance and more. The models PM850 and PM870 offer boolean logic that
can be used to combine up to four alarms.
Power quality analysis
The PM800 series offers an incremental range of features for troubleshooting and
preventing power quality related problems. All models offer THD metering. The
PM810 with PM810LOG option and PM820 offer individual current and voltage
harmonics readings. The PM850 and PM870 offer waveform capture (PM870 is

-ITI(CBEMA)/SEMI F-47 standards. The PM870 offers voltage and current


Rear view of PowerLogic PM800 series meter. disturbance (sag/swell) detection.
Extensive on-board memory

data logs, all stored in non-volatile memory (PM810 requires PM810LOG option).
ANSI 12.20 Class 0.2S and IEC 62053-22 Class 0.5S accuracy for active energy
PE86229

Accurate energy measurement for sub-billing and cost allocation.


PMD-S IEC61557-12 performance standard
Meets PMD/SD/K70/0.5 and PMD/SS/K70/0.5 requirements for combined
Performance Measuring and monitoring Devices (PMD).
Trend curves and short-term forecasting
The models PM850 and PM870 offer trend logging and forecasting of energy and
demand readings to help compare load characteristics and manage energy costs.
Expandable I/O capabilities
Use the on-board or optional digital inputs for pulse counting, status/position
monitoring, demand synchronisation or control (gating) of the conditional energy
metering. Use the on-board or optional digital outputs for equipment control or
interfacing, controllable by internal alarms or externally through digital input status.
PowerLogic PM800 series meter display Use the optional analogue inputs and outputs for equipment monitoring or
screen showing bar graphs.
interfacing.
Metering of other utilities (WAGES)

steam utilities (WAGES) through the pulse counting capabilities of the digital inputs.
Pulses from multiple inputs can be summed through a single channel.
Modular and upgradeable
All models offer easy-to-install option modules (memory, I/O and communications)

Remote display
The optional remote display can be mounted as far as 10 m from the metering unit.
The adapter includes an additional 2- or 4-wire RS-485/RS-232 communication port.

2 2014
PB101814 -36

Part Numbers
Description
Meter without display
Use the base meter unit without display to comply with voltage limitations for local regulations
when door mounting is not possible, or when meter voltage exceeds regulations, or when local

communications port is limited to the default (address 1, 9600 baud, parity even). Requires
software to read data.
PowerLogic PM800 series meter without display. PM810 meter unit only, no display, PM810UMG
basic instrumentation, THD, alarming, 80 kB logging
(with PM810LOG)
PM820 meter unit only, no display, PM820UMG
basic instrumentation, THD, alarming, 80 kB logging

PM850 meter unit only, no display, PM850UMG


basic instrumentation, THD, alarming, 800 kB
PE86134

logging, waveform capture


PM870 meter unit only, no display, PM870UMG
basic instrumentation, THD, alarming, 800 kB

disturbance detection.
Meter with integrated display
Use the meter with integrated display for panel mounting when door space is available and when
voltage usage is within the local regulation limits.
PowerLogic PM800 series meter with integrated display. PM810 meter with integrated display, PM810MG

PM820 meter with integrated display PM820MG

PM850 meter with integrated display PM850MG


PB101822 -68

PM870 meter with integrated display PM870MG

Meter with remote display


Conveniently packaged kit consist of a base meter (810, 820, 850 or 870) with a remote display,
remote display adapter, and remote display cable 3 m ([Link] 10 inches).
PM810 meter with remote display PM810RDMG

PM820 meter with remote display PM820RDMG


PowerLogic PM800 series meter with remote display.
PM850 meter with remote display PM850RDMG
PE86135

PM870 meter with remote display PM870RDMG

Parts and accessories


Remote display adapter with remote display and PM8RDMG
a 3 m (9 ft 10 inch) cable
Use this combination of remote display, adapter, and
3 m cable to equip a base meter unit for use with a
remote display. In addition, the display can be carried
from meter to meter, enabling you to purchase one
display for multiple meters. Each base unit meter
must be equipped with a remote display adapter
Remote display adapter with display and cable. (PM8RDA).
Remote display adapter alone PM8RDA
When added to the front of the base unit (PM8xxU),
PB101819 -32

the adapter brings two additional communication


ports: one for the remote display and one 4-wire/2-
wire RS 485/RS 232.

Part number list continued on next page.

Remote display adaptor alone.

2014 3
Part Numbers - continued
DB119011

Description
Optional modules
Ethernet communication module provides a 10/100BaseTx UTP port, PM8ECC
an RS-485 Modbus serial master port, Ethernet-to-serial line gateway
functionality, and an embedded web server that is fully compliant with
Transparent Ready - Level 1 (TRe1) systems.

The PM8ECC supports a private host PM8ECC MIB. Use of this MIB allows

PowerLogic PM870 with ECC module (bottom view


to any PM8 on-board alarms.
DB119012

2 relay outputs, 2 digital inputs PM8M22


DB119013

2 relay outputs, 6 digital inputs PM8M26


2 relay outputs, 2 digital inputs, 2 analogue outputs, PM8M2222
2 analogue inputs
PM810 optional logging module for on-board data recording, uses a PM810LOG
non-volatile, battery-backed internal clock
RJ11 Extender kit to mount RJ11 jack in panel door RJ11EXT
(for use with PM800, CM3000, and CM4000 series meters)
ECC module (front view) ECC module (side view Cable for remote display adapter 1.25 m (4 ft) CAB4
showing LED indicators).
Cable for remote display adapter 3 m (9 ft 10 inch) CAB12
Cable for remote display adapter 9.14 m (30 ft) CAB30
PB1018216 -34

PowerLogic PM8M26 module.


PB101824 -50

PowerLogic PM800 with PM8M22 and


PM8M26 modules.

4 2014
Selection guide PM810 PM820 PM850 PM870
Performance standard

PMD-S IEC 61557-12 PMD/SD/K70/0.5 and PMD/SS/


K70/0.5
General
Use on LV and HV systems
Current and voltage accuracy 0.5 %/0.2% 0.5 %/0.2% 0.5 %/0.2% 0.2 %/0.2%
Active energy accuracy (5% to 200% of load) 0.2 % 0.2 % 0.2% 0.2%
128 128 128 128
Instantaneous rms values
Current, voltage, frequency
Active, reactive,apparent power Total & per phase

Power factor Total & per phase


Energy values
Active, reactive, apparent energy

Demand values
Current Present & max.
Active, reactive, apparent Present & max.
power
Predicted active, reactive, apparent power
Synchronisation of the measurement window
Demand calculation modeBlock, sliding, thermal
Other measurements
Hour counter
Power quality measurements
Harmonic distortion Current & voltage
Individual harmonics Current & voltage 31 (1) 31 63 63
(2)
Waveform capture - -
(4)

Sag and swell detection - - -


Data recording
Min/max of instantaneous values
Data logs 2 (1) 2 4 4
Event logs -
PowerLogic PM800 series connectors. Trending / forecasting - -
1. Control power. GPS synchronisation (1)

2. Voltage inputs. Alarms


3. Digital input/output. Time stamping (1)

4. RS 485 port. Display and I/O


5. Option module connector. White backlit LCD display
6. Current inputs. Multilingual
7. Mounting clips. Digital input (standard/optional) 1/12 1/12 1/12 1/12
Digital output (standard/optional) 1 KY/4 RY 1 KY/4 RY 1 KY/4 RY 1 KY/4 RY
Analogue inputs (standard/optional) 0/4 0/4 0/4 0/4
Analogue outputs (standard/optional) 0/4 0/4 0/4 0/4
Input metering capability (number of channels) 5 5 5 5
Communication
RS 485 port 2-wire 2-wire 2-wire 2-wire
Modbus protocol
RS 232/RS 485, 2- or 4-wire Modbus RTU/
ASCII (with addition of PM8RDA module)
Ethernet 10/100Base Tx UTP port and RS485
DB109269

Modbus serial master port with PM8ECC


Option modules selection guide
(3)

PM8ECC module
10/100BaseTx UTP port, RS-485 Modbus serial master port, Ethernet to serial line gateway,
embedded web server
Input/Output modules PM8M22 PM8M26* PM8M2222
Relay outputs 2 2 2
Digital inputs 2 6 2
Analogue outputs 4-20 mA 2
Analogue inputs 0-5 Vdc or 4-20 mA 2
* Includes a 24 Vdc Power Supply that can be used to power the digital inputs

Power Meters supports up to two option modules. When PM8M2222 & PM8ECC are mounted together
PowerLogic PM800 series meter with I/O module.

2014 5
Electrical characteristics
Type of measurement 63rd harmonic, 128 samples per cycle
Measurement accuracy standard PMD-S IEC 61557-12 compliant
Current 0.5% from 0.5 A to 10 A
Voltage 0.2% 10 V - 277 V
Power Factor +/- 0.002 from 0.500 leading to 0.500 lagging
Active Power 0.2%
Frequency

Active Energy IEC 62053-22 Class 0.5S and

Reactive Energy IEC 62053-23 Class 2


Data update 1s
rate
Input-voltage Measured voltage 0 to 600 V AC (direct L-L)
characteristics
up to 3.2 MV AC (with external VT)
Metering over-range 1.5 Un
Impedance 5 MW
Frequency measurement range
Input-current CT ratings Primary Adjustable from 5 A to 32767 A
characteristics Secondary 1 A or 5 A
Measurement input range 5 mA to 10 A AC
Permissible overload 15 A continuous
50 A for 10 seconds per hour
500 A for 1 second per hour
Impedance < 0.1 W
Load < 0.15 VA
Control Power AC 115 to 415 ±10 % V AC, 15 VA with options at

DC 125 to 250 ±20 % V DC, 10 W with options


Ride-through time 45 ms at 120 V AC or 125 V DC
Inputs/Outputs (2)
Standard 1 digital KY pulse output 6 to 220 V AC ± 10% or 3 to 250 V DC ± 10%,
(meter unit) 100 mA max. at 25 °C, 1350 V rms isolation
1 digital input 24 to 125 V AC/DC ±10 %, < 5 mA maximum
burden, 1350 Vrms isolation
PM8M22 2 relay outputs (1) 6 to 240 V AC or 6 to 30 V DC
option 2 A rms, 5 A max. for 10 seconds per hour
2 digital inputs 19 to 30 V DC, 5 mA max. at 24 V DC
PM8M26 2 relay outputs (1) 6 to 240 V AC, 6 to 30 V DC
option 2 A rms, 5 A max. for 10 seconds per hour
6 digital inputs 20 to 150 V AC/DC, 2 mA max.
24 V internal supply 20 - 34 V DC, 10 mA max. (feeds 6 digital inputs)
PM8M2222 2 relay outputs (1) 6 to 240 V AC, 6 to 30 V DC
option 2 A rms, 5 A max. for 10 seconds per hour
2 digital inputs 20 to 150 V AC/DC, 2 mA max.
2 analogue outputs 4 to 20 mA dc into 600 ohms maximum
2 analogue inputs Adjustable from 0 to 5 V DC or 4-20 mA
Switching Standard Input/output
frequency PM8M22 Input/output
(digital I/O) PM8M26 and Input
PM8M2222 Output
Mechanical characteristics
Weight (meter with integrated display) 0.6 kg
IP degree of protection (IEC 60529) IP52 integrated display. Type 12 compliant
remote display (with gasket). IP30 meter body
Dimensions Without options 96 x 96 x 70 mm (mounting surface)
With 1 option 96 x 96 x 90 mm (mounting surface)
Environmental conditions
Operating Meter -25 °C to +70 °C (2)
temperature Display -10 °C to +50 °C
Storage temp. Meter + display -40 °C to +85 °C
Humidity rating 5 to 95 % RH at 40 °C (non-condensing)
Pollution degree 2
Installation category
600 V AC L-L
Dielectric withstand
Altitude 3000 m max.
(

° °C. Same is true when using two PM8M2222.

6 2014
Electromagnetic compatibility
Electrostatic discharge Level III (IEC 61000-4-2)
Level III (IEC 61000-4-3)
Immunity to fast transients Level III (IEC 61000-4-4)
Immunity to impulse waves Level III (IEC 61000-4-5)
Conducted immunity Level III (IEC 61000-4-6)
Level III (IEC 61000-4-8)
Immunity to voltage dips Level III (IEC 61000-4-11)
Conducted and radiated
emissions
Harmonics emissions IEC 61000-3-2
Flicker emissions IEC 61000-3-3
Surge immunity IEC 61000-4-12
Surge withstand capability (SWC)
Safety
(1)
Europe , as per IEC 61010-1
U.S. and Canada
Control Equipment)
Onboard communications
RS 485 port 2-wire, up to 38400 baud, Modbus
Model-dependent characteristics
Data Logs PM810 with PM810LOG, PM820, PM850 and PM870:
- 1 billing log
- 1 customisable log
PM850 and PM870 only: 2 additional custom logs
Min./max. Worst min. and max. with phase indication for Voltages,
Currents, Voltage unbalance, and THD. Min. and max. values
for power factor (True and Displacement), power (P, Q, S) and
frequency
One event log Time stamping to 1 second
Trend curves Four trend curves: 1 minute, 1 hour, 1 day and 1 month. Min./
(PM850 and PM870 only) max./avg. values recorded for eight parameters:
- every second for one minute for the 1-minute curve
- every minute for one hour for the 1-hour curve
- every hour for one day for the 1-day curve
- every day for one month for the 1-month curve
Hour counter Load running time in days, hours and minutes
Energy per shift
Available for all models (the PM810 requires the PM810LOG
module)
Forecasting Forecasting of the values for the trended parameters for the
(PM850 and PM870 only) next four hours and next four days
PM850 waveform capture Triggered manually or by alarm, 3-cycle, 128 samples/cycle on

PM870 enhanced waveform From 185 cycles on 1 channel at 16 samples per cycle up to
capture 3 cycles on 6 channels at 128 samples per cycle
Alarms Adjustable pickup and dropout setpoints and time delays,
numerous activation levels possible for a given type of alarm
Historical and active alarm screens with time stamping
Response time: 1 second
Boolean combination of four alarms is possible using

PM870
Digital alarms: status change of digital inputs
Memory available for logging 80 kbytes in PM810 with PM810LOG and PM820
and waveform capture (2) 800 kbytes in PM850 and PM870
Firmware update (all models) Update via the communication ports
File download available free from [Link]
Bar graphs (all models) Graphical representation of system performance
Display characteristics
Languages English, French, Spanish, German, Russian, Turkish and
Portuguese.
Display screen Back-lit white LCD (6 lines total, 4 concurrent values)
Dimensions Display screen viewable area 73 x 69 mm
Integrated display Overall 96 x 96 mm
Depth meter + display 69.4 mm + 17.8 mm
Remote display Overall 96 x 96 x 40 mm
Weight Meter with remote display adapter 0.81 kg
Remote display 0.23 kg

2014 7
Power meter with integrated display
Dimensions

DB111765

DB111766
DB111767

Front-panel mounting (meter with integrated display)


DB111768

Spacing between units


DB111769

DB111770

8 2014
Remote display door mounting
Flush mounting

DB111792

Surface mount
DB111793

Mounting in a Ø102 cutout (replace analogue device: ammeter, voltmeter, etc.)


DB111794

2014 9
ART / © 2014 - Schneider Electric - All rights reserved

Schneider Electric Industries SAS


35, Rue Joseph Monier,
CS 30323
F - 92506 Rueil Malmaison Cedex

Design: Schneider Electric


Capital social 896 313 776 Photos: Schneider Electric