Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Ground area 19.44 m² Clearance height 2.800 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.500 m

1
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 515 lx ≥ 500 lx WP1

Uo (g1 ) 0.68 ≥ 0.60 WP1

Lighting power density 28.32 W/m² –

5.50 W/m²/100 lx –

Energy estimation(2) Consumption [505.28 - 801.90] kWh/a max. 700 kWh/a

Room Lighting power density 16.67 W/m² –

3.24 W/m²/100 lx –

(1) Based on a rectangular space of 3.600 m x 5.400 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

20 Philips BDS559 FG T25 1 xLED20-4S/830 DX51 DF – 16.2 W 902 lm 55.7 lm/W