0% found this document useful (0 votes)
100 views52 pages

PCA-M50-140KA Service Manual OCH659

Uploaded by

Alexandre Conde
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views52 pages

PCA-M50-140KA Service Manual OCH659

Uploaded by

Alexandre Conde
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

SPLIT-TYPE, AIR CONDITIONERS


March 2017
No. OCH659

SERVICE MANUAL
R32/R410A
Indoor unit
[Model Name] [Service Ref.]
PCA-M35KA Notes:
PCA-M35KA • This manual describes service
data of the indoor units only.
• RoHS compliant products
PCA-M50KA have <G> mark on the spec
PCA-M50KA name plate.

PCA-M60KA
PCA-M60KA
PCA-M71KA
PCA-M71KA
PCA-M100KA
PCA-M100KA
PCA-M125KA
PCA-M125KA
PCA-M140KA
PCA-M140KA
  CONTENTS
1. REFERENCE MANUAL................................... 2
2. SAFETY PRECAUTION................................... 3
3. PARTS NAMES AND FUNCTIONS................. 8
4. SPECIFICATIONS.......................................... 13
5. NOISE CRITERION CURVES ....................... 17
6. OUTLINES AND DIMENSIONS..................... 19
7. WIRING DIAGRAM............................................. 23
8. REFRIGERANT SYSTEM DIAGRAM............. 24
9. TROUBLESHOOTING................................... 25
10. FUNCTION SETTING..................................... 41
11. SPECIAL FUNCTION..................................... 42
12. DISASSEMBLY PROCEDURE.......................46
INDOOR UNIT Model name
indication PARTS CATALOG (OCB659)
1 REFERENCE MANUAL

1-1. OUTDOOR UNIT’S SERVICE MANUAL


Model name Service Ref. Service manual No.
MXZ-3E54VA-E1/ET1/ER1 MXZ-3E54VA-E1/ET1/ER1
MXZ-3E68VA-E1/ET1/ER1 MXZ-3E68VA-E1/ET1/ER1
MXZ-4E72VA-E1/ET1/ER1 MXZ-4E72VA-E1/ET1/ER1 OBH723
MXZ-4E83VA-E1/ER1 MXZ-4E83VA-E1/ER1 OBB723
MXZ-5E102VA-E1/ER1 MXZ-5E102VA-E1/ER1
MXZ-4E83VAHZ-E1 MXZ-4E83VAHZ-E1
OBH626
MXZ-6D122VA-E1 MXZ-6D122VA-E1
OBB626
PAC-MK32/52BC PAC-MK32/52BC OCH589
PAC-MK32/52BCB PAC-MK32/52BCB OCB589
PUMY-P112/125/140VKM(-BS) PUMY-P112/125/140VKM(-BS) OCH593
PUMY-P112/125/140YKM(-BS) PUMY-P112/125/140YKM(-BS) OCB593
PUZ-ZM35/50/60VKA PUZ-ZM35/50/60VKA OCH653
PUZ-ZM71VHA PUZ-ZM71VHA OCB653
PUZ-ZM100/125/140VKA PUZ-ZM100/125/[Link] OCH654
PUZ-ZM100/125/140YKA PUZ-ZM100/125/[Link] OCB654
PUHZ-ZRP35/50VKA2 PUHZ-ZRP35/50VKA2(-ER/ET)
OCH635
PUHZ-ZRP71VHA2 PUHZ-ZRP71VHA2(-ER/ET)
OCB635
PUHZ-ZRP60VHA2 PUHZ-ZRP60VHA2(-ER/ET)
PUHZ-ZRP100/[Link]
PUHZ-ZRP100/140VKA3
PUHZ-ZRP100/[Link]
PUHZ-ZRP100/140YKA3 OCH645
PUHZ-ZRP200/[Link]
PUHZ-ZRP200/250YKA2 OCB645
[Link]
PUHZ-ZRP125V/YKA3
[Link]
TCH004
SUZ-KA35/50/60/71VA6 SUZ-KA35/50/60/[Link]
TCB004
PUHZ-P100VHA5 [Link]
PUHZ-P125/140VHA4 PUHZ-P125/[Link] OCH646
PUHZ-P100YHA3 [Link] OCB646
PUHZ-P125/140YHA2 PUHZ-P/[Link]
OCH647
PUHZ-P200/250YKA2 PUHZ-P200/[Link]
OCB647

OCH544
PUHZ-FRP71VHA PUHZ-FRP71VHA
OCB544

1-2. TECHNICAL DATA BOOK

Series (Outdoor unit) Manual No.

SUZ-KA • VA OCS03
PUHZ-RP • HA4
OCS16
PUHZ-RP • KA
SUZ-KA• VA3 OCS22/OCS25
SUZ-KA • VA4 OCS26

OCH659 2
2 SAFETY PRECAUTION
MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT
This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit.
WARNING

Read the OPERATION MANUAL carefully before operation.

Service personnel are required to carefully read the OPERATION MANUAL and INSTALLATION MANUAL before operation.

Further information is available in the OPERATION MANUAL, INSTALLATION MANUAL, and the like.

2-1. ALWAYS OBSERVE FOR SAFETY


Before obtaining access to terminal, all supply
circuits must be disconnected.

2-2. CAUTIONS RELATED TO NEW REFRIGERANT


Cautions for units utilising refrigerant R32/R410A

Use a vacuum pump with a reverse flow check


Use new refrigerant pipes.
valve.
In case of using the existing pipes for R22, be careful with Vacuum pump oil may flow back into refrigerant cycle and
the following: that can cause deterioration of refrigerant oil, etc.
· Be sure to clean the pipes and make sure that the insides
of the pipes are clean.
Use the following tools specifically designed for
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
use with R32/R410A refrigerant.
· Avoid using thin pipes. The following tools are necessary to use R32/R410A refrigerant.
Tools for R32/R410A
Gauge manifold Flare tool
Make sure that the inside and outside of refrige-
Charge hose Size adjustment gauge
rant piping is clean and it has no contaminants
Gas leak detector Vacuum pump adaptor
such as sulfur, oxides, dirt, shaving particles, etc,
Torque wrench Electronic refrigerant
which are hazard to refrigerant cycle. charging scale
In addition, use pipes with specified thickness.

Contamination inside refrigerant piping can cause deterio-


ration of refrigerant oil, etc. Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can
Store the piping indoors, and keep both ends of cause deterioration of refrigerant oil or malfunction of com-
the piping sealed until just before brazing. pressor.
(Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can Do not use a charging cylinder.
cause deterioration of refrigerant oil or malfunction of com-
pressor. If a charging cylinder is used, the composition of refrigera-
nt will change and the efficiency will be lowered.
The refrigerant oil applied to flare and flange
connections must be ester oil, ether oil or Use the specified refrigerant only.
alkylbenzene oil in a small amount.
Never use any refrigerant other than that specified.
If large amount of mineral oil enters, that can cause deterio-
Doing so may cause a burst, an explosion, or fire when the
ration of refrigerant oil, etc.
unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the
Charge refrigerant from liquid phase of gas spec labels provided with our products.
cylinder. We will not be held responsible for mechanical failure,
system malfunction, unit breakdown or accidents caused
If the refrigerant is charged from gas phase, composition
by failure to follow the instructions.
change may occur in refrigerant and the efficiency will be
lowered.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
Do not use refrigerant other than R32/R410A. a flame, poisonous gases will be released.
If other refrigerant (R22, etc.) is used, chlorine in refrige-
rant can cause deterioration of refrigerant oil, etc.

OCH659 3
[1] Warning for service
(1) Do not alter the unit.
(2) For installation and relocation work, follow the instructions in the Installation Manual and use tools and pipe
components specifically made for use with refrigerant specified in the outdoor unit installation manual.
(3) Ask a dealer or an authorized technician to install, relocate and repair the unit.
(4) This unit should be installed in rooms which exceed the floor space specified in outdoor unit installation manual.
Refer to outdoor unit installation manual.
(5) For appliances not accessible to the general public.
(6) Refrigerant pipes connection shall be accessible for maintenance purposes.
(7) If the air conditioner is installed in a small room or closed room, measures must be taken to prevent the refrig-
erant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Should the
refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may
result.
(8) Keep gas-burning appliances, electric heaters, and other fire sources (ignition sources) away from the location
where installation, repair, and other air conditioner work will be performed.
If refrigerant comes into contact with a flame, poisonous gases will be released.
(9) When installing or relocating, or servicing the air conditioner, use only the specified refrigerant written on out-
door unit to charge the refrigerant lines.
Do not mix it with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and
may result in an explosion and other hazards.
(10) After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes
into contact with the flame of a heater or portable cooking range, poisonous gases will be released.
(11) Do not use low temperature solder alloy in case of brazing the refrigerant pipes.
(12) When performing brazing work, be sure to ventilate the room sufficiently. Make sure that there are no hazardous
or flammable materials nearby.
When performing the work in a closed room, small room, or similar location, make sure that there are no refriger-
ant leaks before performing the work.
If refrigerant leaks and accumulates, it may ignite or poisonous gases may be released.
(13) Do not install the unit in places where refrigerant may build-up or places with poor ventilation such as a semi-
basement or a sunken place in outdoor: Refrigerant is heavier than air, and inclined to fall away from the leak
source.
(14) Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manu-
facturer.
(15) The appliance shall be stored in a room without continuously operating ignition sources (for example: open
flames, an operating gas appliance or an operating electric heater).
(16) Do not pierce or burn.
(17) Be aware that refrigerants may not contain an odour.
(18) Pipe-work shall be protected from physical damage.
(19) The installation of pipe-work shall be kept to a minimum.
(20) Compliance with national gas regulations shall be observed.
(21) Keep any required ventilation openings clear of obstruction.
(22) Servicing shall be performed only as recommended by the manufacturer.
(23) The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as
specified for operation.
(24) Maintenance, service and repair operations shall be performed by authorized technician with required qualifica-
tion.

[2] Cautions for service


(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.

[3] Additional refrigerant charge


When charging directly from cylinder
(1) Check that cylinder for R32/R410A available on the market is a syphon type.
(2) Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)

OCH659 4
[4] Cautions for unit using R32 refrigerant
Basic work procedures are the same as those for conventional units using refrigerant R410A. However, pay careful
attention to the following points.
(1) Information on servicing
(1-1) Checks on the Area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the
risk of ignition is minimized.
For repair to the refrigerating systems, (1-3) to (1-7) shall be completed prior to conducting work on the systems.
(1-2) Work Procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being
present while the work is being performed.
(1-3) General Work Area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out.
Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the con-
ditions within the area have been made safe by control of flammable material.
(1-4) Checking for Presence of Refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is
aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable
for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
(1-5) Presence of Fire Extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing
equipment shall be available to hand.
Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
(1-6) No Ignition Sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall use any
sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, includ-
ing cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal,
during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around
the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs
shall be displayed.
(1-7) Ventilated Area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any
hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should
safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
(1-8) Checks on the Refrigeration Equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all
times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer’s
technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
• The charge size is in accordance with the room size within which the refrigerant containing parts are installed.
• The ventilation machinery and outlets are operating adequately and are not obstructed.
• Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.
• Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance
which may corrode refrigerant containing components, unless the components are constructed of materials which are
inherently resistant to being corroded or are suitably protected against being corroded.
(1-9) Checks on Electrical Devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection proce-
dures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is
satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an ade-
quate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include that:
• capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
• no live electrical components and wiring are exposed while charging, recovering or purging the system;
• there is continuity of earth bonding
(2) Repairs to Sealed Components
(2-1) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked
upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment
during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn
of a potentially hazardous situation.
(2-2) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not
altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of
connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.
Ensure that the apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of prevent-
ing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer’s specifications.

OCH659 5
(3) Repair to intrinsically Safe Components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the
permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmos-
phere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in
the atmosphere from a leak.
(4) Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse
environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such
as compressors or fans.
(5) Detection of Flammable Refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks.
A halide torch (or any other detector using a naked flame) shall not be used.
(6) Leak Detection Methods
Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity
may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.)
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equip-
ment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the
appropriate percentage of gas (25% maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be
avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or
isolated (by means of shut off valves) in a part of the system remote from the leak. For appliances containing flammable
refrigerants, oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing pro-
cess.
(7) Removal and Evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose conventional procedures shall be
used. However, for flammable refrigerants it is important that best practice is followed since flammability is a considera-
tion. The following procedure shall be adhered to:
• remove refrigerant
• purge the circuit with inert gas
• evacuate
• purge again with inert gas
• open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrig-
erants, the system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several
times.
Compressed air or oxygen shall not be used for purging refrigerant systems.
For appliances containing flammable refrigerants, flushing shall be achieved by breaking the vacuum in the system with
OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to
a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used,
the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital
if brazing operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and that ventilation is available.
(8) Charging Procedures
In addition to conventional charging procedures, the following requirements shall be followed:
• Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines
shall be as short as possible to minimize the amount of refrigerant contained in them.
• Cylinders shall be kept upright.
• Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
• Label the system when charging is complete (if not already).
• Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-
tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the
site.
(9) Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its
detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an
oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential
that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.

Continued to the next page


OCH659 6
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:
• mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• all personal protective equipment is available and being used correctly;
• the recovery process is supervised at all times by a competent person;
• recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equip-
ment are removed from site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
(10) Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be
dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stat-
ing the equipment contains flammable refrigerant.
(11) Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice
that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrig-
erant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge
are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e.
special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated
shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery
occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at
hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, flammable refriger-
ants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be com-
plete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in
satisfactory working order, has been properly maintained and that any associated electrical components are sealed to
prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant
waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or
compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that
flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning
the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this pro-
cess. When oil is drained from a system, it shall be carried out safely.

OCH659 7
Unit

Electronic weighing scale

[5] Service tools


Use the below service tools as exclusive tools for R32/R410A refrigerant.

No. Tool name Specifications


1. Gauge manifold · Use the existing fitting specifications. (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
2. Charge hose · Use pressure performance of 5.09MPa·G or over.
3. Electronic weighing scale ―
4. Gas leak detector · Use the detector for R32 or R410A.
5. Adaptor for reverse flow check · Attach on vacuum pump.
6. Refrigerant charge base ―
7. Refrigerant cylinder · Top of cylinder (R32 or R410A refrigerant)
· Cylinder with syphon
8. Refrigerant recovery equipment ―

3 PARTS NAMES AND FUNCTIONS


3-1. Indoor Unit

Louver
Air outlet

Vane
Filter
Air intake (Inside of Air intake)

OCH659 8
3-2. Wireless remote controller (OPTION)
The functions which can be used are restricted according to each model.

CHECK TEST RUN display


CHECK and TEST RUN display indicate that
the unit is being checked or test-run.

MODEL SELECT display


Blinks when model is selected.

display
Lights up while the signal is transmitted to
the indoor unit when the button is pressed.

display
SET TEMP. display indicates the desired
temperature which is set.

display CLOCK display


OPERATION MODE display Displays the current time.
Operation mode display indicates which
operation mode is in effect. TIMER display
CHECK TEST RUN
MODEL SELECT °C Displays when in timer operation or when
AMPM setting timer.

“ ”“ ” display
AMPM
Displays the order of timer operation.
NOT AVAILABLE

display “ ”“ ” display
ON/OFF TEMP Displays whether timer is on or off.
The vertical direction of air flow is indicated.

display
FAN SPEED display indicates which fan
buttons
speed has been selected. SET TEMPERATURE button sets any desired
room temperature.
FAN AUTO STOP
ON/OFF button
The unit is turned ON and OFF alternately MODE VANE AUTO START
each time the button is pressed. TIMER CONTROL buttons
CHECK LOUVER h AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be
FAN SPEED SELECT button automatically stopped at the preset time.
Used to change the fan speed. TEST RUN min AUTO START (ON timer): when this switch is
set, the air conditioner will be automatically
started at the preset time.
MODE SELECT button SET RESET CLOCK

Used to switch the operation mode between


cooling, drying, heating, auto and fan mode. “h” and “min” buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.

LOUVER button
CHECK-TEST RUN buttons
Changes left/right airflow direction.
Only press this button to perform an (Not available for this model.)
inspection check or test operation.
Do not use it for normal operation.

CLOCK button
VANE CONTROL button
RESET button
Used to change the air flow direction.
SET button

OCH659 9
3-3. Wired remote controller (Option) <PAR-32MAA>
The functions which can be used are restricted according to each model.
Display The main display can be displayed in 2 different modes: "Full" and "Basic."
The initial setting is "Full."
1 Operation mode 13
Indoor unit operation mode appears here. Appears when the On/Off timer or Night setback
18 function is enabled.
13 15 2 Preset temperature
Full mode 12 14 16 17 19
14
Preset temperature appears here.
Appears when the Weekly timer is enabled.

3 3 Clock
Fri 15
(See the Installation Manual.)
6 20
Current time appears here. Appears while the units are operated in the
7 energy-save mode.
8
9 Room 21 4 Fan speed
10 16
Cool Set temp. Auto Fan speed setting appears here. Appears while the outdoor units are operated in
1 4 the silent mode.
5 Button function guide
11 Functions of the corresponding buttons appear
17
Mode Temp. Fan here. Appears when the built-in thermistor on the
remote controller is activated to monitor the
6 room temperature (a).
22 2
Appears when the ON/OFF operation is centrally
controlled. appears when the thermistor on the
5 indoor unit is activated to monitor the room
7 temperature.
Appears when the operation mode is centrally 18
Basic mode 2 controlled.
Appears when the units are operated in the
8 energy-save mode with 3D i-see Sensor.
Fri 3 Appears when the preset temperature is centrally
controlled. 19
9 Indicates the vane setting.
Cool Set temp. Auto
1 4 Appears when the filter reset function is centrally
controlled. 20
10 Indicates the louver setting.

Indicates when filter needs maintenance. 21


Mode Temp. Fan
11 Room temperature Indicates the ventilation setting.
(See the Installation Manual.) 22
5 Current room temperature appears here.
Note: All icons are displayed for explanation. Appears when the preset temperature range is
12 restricted.

Appears when the buttons are locked.

Controller interface 1 ON/OFF button The functions of the function buttons


change depending on the screen. Refer
Press to turn ON/OFF the indoor unit. to the button function guide that appears
at the bottom of the LCD for the functions
they serve on a given screen.
2 SELECT button When the system is centrally controlled,
the button function guide that
Press to save the setting. corresponds to the locked button will not
appear.

3 RETURN button
Main display Main menu
5 Press to return to the previous screen. Fri Main Main menu
Vane·Louver·Vent. (Lossnay)
High power
Room Timer
Cool Set temp. Auto Weekly timer
OU silent mode

4 MENU button Mode Temp. Fan


Main display:
Cursor Page

Press to bring up the Main menu.


7 8 9 0 7 8 9 0
Function guide
6 5 Backlit LCD
Operation settings will appear. 7 Function button F1
When the backlight is off, pressing any Main display: Press to change the operation
button turns the backlight on and it mode.
will stay lit for a certain period of time Main menu: Press to move the cursor down.
depending on the screen.
4 3 2 1 8 Function button F2
Function buttons 6 ON/OFF lamp Main display: Press to decrease temperature.
Main menu: Press to move the cursor up.
This lamp lights up in green while the unit
is in operation. It blinks while the remote
9 Function button F3
7 8 9 10 controller is starting up or when there is
an error. Main display: Press to increase temperature.
Main menu: Press to go to the previous page.

• When the backlight is off, pressing any button turns the backlight on and
10 Function button F4
does not perform its function. (except for the ON/OFF button)
• Most settings (except ON/OFF, mode, fan speed, temperature) can be Main display: Press to change the fan speed.
made from the Menu screen. Main menu: Press to go to the next page.

OCH659 10
Menu structure

Press the MENU button.


Main menu Move the cursor to the desired item with the F1 and F2 buttons, and press the SELECT button.

Vane · Louver · Vent. (Lossnay)


High power

Timer
ON/OFF timer
Auto-OFF timer

Weekly timer

Restriction
Temp. range
Operation lock

Energy saving
Auto return
Schedule

Night setback

Filter information
Error information

Maintenance
Auto descending panel
Manual vane angle
3D i-see Sensor
Initial setting
Main/Sub
Clock
Main display
Contrast
Display details
Auto mode
Administrator password
Language selection

Service
Test run
Input maintenance info.
Function setting
Check
Self check
Maintenance password
Remote controller check

Not all functions are available on all models of indoor units.

OCH659 11
Setting and display items Setting details
Vane · Louver · Vent. Use to set the vane angle.
(Lossnay) • Select a desired vane setting from 5 different settings.
Use to turn ON/OFF the louver.
• Select a desired setting from "ON" and "OFF."
Use to set the amount of ventilation.
• Select a desired setting from "OFF," "Low," and "High."
High power Use to reach the comfortable room temperature quickly.
• Units can be operated in the High-power mode for up to 30 minutes.
Timer ON/OFF timer* Use to set the operation ON/OFF times.
• Time can be set in 5-minute increments.
Auto-Off timer Use to set the Auto-OFF time.
• Time can be set to a value from 30 to 240 in 10-minute increments.
Filter information Use to check the filter status.
• The filter sign can be reset.
Error information Use to check error information when an error occurs.
• Check code, error source, refrigerant address, unit model, manufacturing number, contact information (dealer's phone
number) can be displayed.
(The unit model, manufacturing number, and contact information need to be registered in advance to be displayed.)
Weekly timer* Use to set the weekly operation ON/OFF times.
• Up to 8 operation patterns can be set for each day.
(Not valid when the ON/OFF timer is enabled.)
Energy saving Auto return Use to get the units to operate at the preset temperature after performing energy-save operation for a specified
time period.
• Time can be set to a value from 30 and 120 in 10-minute increments.
(This function will not be valid when the preset temperature ranges are restricted.)
Schedule* Set the start/stop times to operate the units in the energy-save mode for each day of the week, and set the
energy-saving rate.
• Up to 4 energy-save operation patterns can be set for each day.
• Time can be set in 5-minute increments.
• Energy-saving rate can be set to a value from 0% and 50 to 90% in 10% increments.
Night setback* Use to make Night setback settings.
• Select "Yes" to enable the setting, and "No" to disable the setting. The temperature range and the start/stop times can be set.
Restriction Temp. range Use to restrict the preset temperature range.
• Different temperature ranges can be set for different operation modes.
Operation lock Use to lock selected functions.
• The locked functions cannot be operated.
Maintenance Auto descending panel Auto descending panel (Optional parts) UP/DOWN you can do.
Manual vane angle Use to set the vane angle for each vane to a fixed position.
3D i-see Sensor Use to set the following functions for 3D i-see Sensor.
• Air distribution • Energy saving option • Seasonal airflow
Initial setting Main/Sub When connecting 2 remote controllers, one of them needs to be designated as a sub controller.
Clock Use to set the current time.
Main display Use to switch between "Full" and "Basic" modes for the Main display.
• The initial setting is "Full."
Contrast Use to adjust screen contrast.
Initial setting Display details Make the settings for the remote controller related items as necessary.
Clock: The initial settings are "Yes" and "24h" format.
Temperature: Set either Celsius (°C) or Fahrenheit (°F).
Room temp. : Set Show or Hide.
Auto mode: Set the Auto mode display or Only Auto display.
Auto mode Whether or not to use the AUTO mode can be selected by using the button.
This setting is valid only when indoor units with the AUTO mode function are connected.
Administrator pass- The administrator password is required to make the settings for the following items.
word • Timer setting • Energy-save setting • Weekly timer setting
• Restriction setting • Outdoor unit silent mode setting • Night set back
Language selection Use to select the desired language.
Service Test run Select "Test run" from the Service menu to bring up the Test run menu.
• Test run • Drain pump test run
Input maintenance Select "Input maintenance Info." from the Service menu to bring up the Maintenance information screen.
The following settings can be made from the Maintenance Information screen.
• Model name input • Serial No. input • Dealer information input
Function setting Make the settings for the indoor unit functions via the remote controller as necessary.
LOSSNAY setting This setting is required only when the operation of City Multi units is interlocked with LOSSNAY units.
(City Multi only)
Check Error history: Display the error history and execute "delete error history".
Refrigerant leak check: Refrigerant leaks can be judged.
Smooth maintenance: The indoor and outdoor maintenance data can be displayed.
Request code: Details of the operation data including each thermistor temperature and error history can be checked.
Self check Error history of each unit can be checked via the remote controller.
Maintenance password Use to change the maintenance password.
Remote controller When the remote controller does not work properly, use the remote controller checking function to trouble-
check shoot the problem.
* Clock setting is required.

OCH659 12
4 SPECIFICATIONS

4-1. SPECIFICATIONS
Service Ref. PCA-M35KA

Mode Cooling Heating


Power supply (phase, cycle, voltage) Single phase, 50Hz, 230V
Input kW 0.04 0.04
Running current A 0.29 0.27
External finish Munsell 6.4Y 8.9/0.4
INDOOR UNIT

Heat exchanger Plate fin coil


Fan Fan (drive) × No. Sirocco fan (direct) × 2
Fan motor output kW 0.090
Airflow (Low-Medium2-Medium1-High) K/min (CFM) 10-11-12-14 (355-390-460-497)
External static pressure Pa (mmAq) 0 (direct blow)
Operation control & Thermostat Remote controller & built-in
Noise level (Low-Medium2-Medium1-High) dB 31-33-36-39
Field drain pipe O.D. mm (inch) 26 (1)
Dimensions W mm (inch) 960 (37-13/16)
D mm (inch) 680 (26-3/4)
H mm (inch) 230 (9-1/16)
Weight kg (lb) 25 (55)

Service Ref. PCA-M50KA

Mode Cooling Heating


Power supply (phase, cycle, voltage) Single phase, 50Hz, 230V
Input kW 0.05 0.05
Running current A 0.37 0.37
External finish Munsell 6.4Y 8.9/0.4
INDOOR UNIT

Heat exchanger Plate fin coil


Fan Fan (drive) × No. Sirocco fan (direct) × 2
Fan motor output kW 0.090
Airflow (Low-Medium2-Medium1-High) K/min (CFM) 10-11-13-15 (355-390-460-530)
External static pressure Pa (mmAq) 0 (direct blow)
Operation control & Thermostat Remote controller & built-in
Noise level (Low-Medium2-Medium1-High) dB 32-34-37-40
Field drain pipe O.D. mm (inch) 26 (1)
Dimensions W mm (inch) 960 (37-13/16)
D mm (inch) 680 (26-3/4)
H mm (inch) 230 (9-1/16)
Weight kg (lb) 26 (57)

Service Ref. PCA-M60KA


Mode Cooling Heating
Power supply (phase, cycle, voltage) Single phase, 50Hz, 230V
Input kW 0.06 0.06
Running current A 0.39 0.39
External finish Munsell 6.4Y 8.9/0.4
INDOOR UNIT

Heat exchanger Plate fin coil


Fan Fan (drive) × No. Sirocco fan (direct) × 3
Fan motor output kW 0.095
Airflow (Low-Medium2-Medium1-High) K/min (CFM) 15-16-17-19 (530-565-600-670)
External static pressure Pa (mmAq) 0 (direct blow)
Operation control & Thermostat Remote controller & built-in
Noise level (Low-Medium2-Medium1-High) dB 33-35-37-40
Field drain pipe O.D. mm (inch) 26 (1)
Dimensions W mm (inch) 1,280 (50-3/8)
D mm (inch) 680 (26-3/4)
H mm (inch) 230 (9-1/16)
Weight kg (lb) 32 (71)

OCH659 13
Service Ref. PCA-M71KA
Mode Cooling Heating
Power supply (phase, cycle, voltage) Single phase, 50Hz, 230V
Input kW 0.06 0.06
Running current A 0.42 0.42
External finish Munsell 6.4Y 8.9/0.4
INDOOR UNIT

Heat exchanger Plate fin coil


Fan Fan (drive) × No. Sirocco fan (direct) × 3
Fan motor output kW 0.095
Airflow (Low-Medium2-Medium1-High) K/min (CFM) 16-17-18-20 (565-600-635-705)
External static pressure Pa (mmAq) 0 (direct blow)
Operation control & Thermostat Remote controller & built-in
Noise level (Low-Medium2-Medium1-High) dB 35-37-39-41
Field drain pipe O.D. mm (inch) 26 (1)
Dimensions W mm (inch) 1,280 (50-3/8)
D mm (inch) 680 (26-3/4)
H mm (inch) 230 (9-1/16)
Weight kg (lb) 32 (71)

Service Ref. PCA-M100KA

Mode Cooling Heating


Power supply (phase, cycle, voltage) Single phase, 50Hz, 230V
Input kW 0.09 0.09
Running current A 0.65 0.65
External finish Munsell 6.4Y 8.9/0.4
INDOOR UNIT

Heat exchanger Plate fin coil


Fan Fan (drive) × No. Sirocco fan (direct) × 4
Fan motor output kW 0.160
Airflow (Low-Medium2-Medium1-High) K/min (CFM) 22-24-26-28 (775-850-920-990)
External static pressure Pa (mmAq) 0 (direct blow)
Operation control & Thermostat Remote controller & built-in
Noise level (Low-Medium2-Medium1-High) dB 37-39-41-43
Field drain pipe O.D. mm (inch) 26 (1)
Dimensions W mm (inch) 1,600 (63)
D mm (inch) 680 (26-3/4)
H mm (inch) 230 (9-1/16)
Weight kg (lb) 37 (82)

Service Ref. PCA-M125KA


Mode Cooling Heating
Power supply (phase, cycle, voltage) Single phase, 50Hz, 230V
Input kW 0.11 0.11
Running current A 0.76 0.76
External finish Munsell 6.4Y 8.9/0.4
INDOOR UNIT

Heat exchanger Plate fin coil


Fan Fan (drive) × No. Sirocco fan (direct) × 4
Fan motor output kW 0.160
Airflow (Low-Medium2-Medium1-High) K/min (CFM) 23-25-27-29 (810-885-955-1025)
External static pressure Pa (mmAq) 0 (direct blow)
Operation control & Thermostat Remote controller & built-in
Noise level (Low-Medium2-Medium1-High) dB 39-41-43-45
Field drain pipe O.D. mm (inch) 26 (1)
Dimensions W mm (inch) 1,600 (63)
D mm (inch) 680 (26-3/4)
H mm (inch) 230 (9-1/16)
Weight kg (lb) 38 (84)

OCH659 14
Service Ref. PCA-M140KA
Mode Cooling Heating
Power supply (phase, cycle, voltage) Single phase, 50Hz, 230V
Input kW 0.14 0.14
Running current A 0.90 0.90
External finish Munsell 6.4Y 8.9/0.4
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan (drive) × No. Sirocco fan (direct) × 4


Fan motor output kW 0.160
Airflow (Low-Medium2-Medium1-High) K/min (CFM) 24-26-29-32(850-920-1025-1130)
External static pressure Pa (mmAq) 0 (direct blow)
Operation control & Thermostat Remote controller & built-in
Noise level (Low-Medium2-Medium1-High) dB 41-43-45-48
Field drain pipe O.D. mm (inch) 26 (1)
Dimensions W mm (inch) 1,600 (63)
D mm (inch) 680 (26-3/4)
H mm (inch) 230 (9-1/16)
Weight kg (lb) 40 (88)

OCH659 15
4-2. FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS

■ PCA-M35KA ■ PCA-M60KA
PCA-M50KA PCA-M71KA
50
50
0
0

Static pressure[Pa]
−50
Static pressure[Pa]

−50
−100
−100
−150
−150
−200
−200
−250
−250
−300
−300 0 1 2 3 4
0 1 2 3 4
Airflow rate[m³/min]
Airflow rate[m³/min]

■ PCA-M100KA
PCA-M125KA How to read curves
PCA-M140KA Duct characteristics
Curve in the at site
1
graphs
Q…Designed amount of fresh air intake
0
<m3/min>

A
50

C
0 A…Static pressure loss of fresh air

B
Q intake duct system with airflow
Static pressure[Pa]

−50 amount Q <Pa>


−100 2 B…Forced static pressure at air conditioner
inlet with airflow amount Q <Pa>
−150
A
C

C…Static pressure of booster fan with


−200 airflow amount Q <Pa>
E

−250 Q D…Static pressure loss increase amount


of fresh air intake duct system for
−300
0 1 2 3 4 airflow amount Q <Pa>
3
E…Static pressure of indoor unit with
D

Airflow rate[m³/min] airflow amount Q <Pa>


Qa … Estimated amount of fresh air
A

Q
intake without D <m3/min>
Qa

OCH659 16
5 NOISE CRITERION CURVES

PCA-M35KA NOTCH SPL(dB) LINE PCA-M50KA NOTCH SPL(dB) LINE


High 39 High 40
Medium1 36 Medium1 37
Medium2 33 Medium2 34
Low 31 Low 32

90 90

80 80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)


70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 APPROXIMATE APPROXIMATE
THRESHOLD OF
20
THRESHOLD OF
HEARING FOR HEARING FOR
CONTINUOUS
NC-20 NC-20
CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

PCA-M60KA NOTCH SPL(dB) LINE PCA-M71KA NOTCH SPL(dB) LINE


High 40 High 41
Medium1 37 Medium1 39
Medium2 35 Medium2 37
Low 33 Low 35

90
90

80
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)

70
NC-70 70
NC-70

60
60
NC-60
NC-60

50
50
NC-50
NC-50

40
40
NC-40
NC-40

30
30
NC-30
NC-30

20 APPROXIMATE
THRESHOLD OF 20 APPROXIMATE
HEARING FOR THRESHOLD OF
NC-20 HEARING FOR
CONTINUOUS
CONTINUOUS
NC-20
NOISE
NOISE
10
10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

OCH659 17
PCA-M100KA NOTCH SPL(dB) LINE PCA-M125KA NOTCH SPL(dB) LINE
High 43 High 45
Medium1 41 Medium1 43
Medium2 39 Medium2 41
Low 37 Low 39

90 90

80 80

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)


OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 APPROXIMATE 20 APPROXIMATE
THRESHOLD OF THRESHOLD OF
HEARING FOR HEARING FOR
CONTINUOUS
NC-20 CONTINUOUS
NC-20
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

PCA-M140KA NOTCH SPL(dB) LINE


High 48
Medium1 45
Medium2 43
Low 41

90

80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)

70
NC-70

60
NC-60 1m Ceiling

50 1m Main unit
NC-50 about 1.4m

40
NC-40
MICROPHONE

30
NC-30

20 APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NC-20
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz

OCH659 18
6

[FRONT VIEW]
1 917(Suspension bolt pitch)
5 4 140 62

OCH659
Electrical box 8 6

18
24 260

150
3 38 85 86 2
2

1
80
120°
Ceiling

76
126

190
190

169

124
320

46
680

37
75

121
38 18

(71)
25 138
When electrical box ø1
461 387
is pulled down
9 7
PCA-M35KA PCA-M50KA

In case of the rear pipe arrangement, make sure to


remove the shaded portions from the independent piece.
Then put the independent piece back in initial position. 51
(The heat exchanger might be clogged because of dust) 2 960 2 10
8 48 853 5

Electrical box

19
236

230
195
84 88
2
233 When drain socket Air outlet 184
is installed (liquid ø6.35)
246 203 (gas ø12.7)
(Drainage)
OUTLINES AND DIMENSIONS

233 When drain socket


is installed
246 (Drainage)
1 Drainage pipe connection(26mmI.D.)
57

2 Drainage pipe connection(for the left arrangement)


3 Knockout hole for left drain-piping arrangement
680

4 Refrigerant-pipe connection(gas pipe side/flared connection)


NOTES.
476

5 Refrigerant-pipe connection(liquid pipe side/flared connection)


6 Knockout hole for upper drain pipe arrangement [Link] M10 or W3/8 screw for anchor bolt.
254

7 Knockout hole for fresh air intake ø100 [Link] be sure when installing the
8 Knockout hole for wiring arrangement 2-ø22 drain pump (option parts),
9 Knockout hole for wiring arrangement 2-ø26 Air intake 182 85 refrigerant pipe will be only upward.
878
Accessory···Drain socket (I.D. 26)
Unit: mm
[FRONT VIEW] 1 1237(Suspension bolt pitch)
5 4
Electrical box 8 140 62
24 260 6

18
3

150
2
38 85 86 2

1
Ceiling 120°

80

OCH659
126

190
190

169
124 76
320

46
680

(71)

37
75 38 18

121
25 138
ø1
When electrical box 461 387
is pulled down
9 7
In case of the rear pipe arrangement, make sure to M60 M71
PCA-M60KA PCA-M71KA

remove the shaded portions from the independent piece. A 179 180
Then put the independent piece back in initial position. 51
(The heat exchanger might be clogged because of dust) B 203 200
2 1280 2 10
8 48
1173 5
Electrical box
236

230
195
84 88

20
2 233 When drain socket
is installed Air outlet A
246 (liquid )
(Drainage) B
(gas ø15.88)
233 When drain socket
is installed
246
1 (Drainage)
Drainage pipe connection(26mmI.D.)
57

2 NOTES.
Drainage pipe connection(for the left arrangement)
[Link] M10 or W3/8 screw for anchor bolt.
3 Knockout hole for left drain-piping arrangement
[Link] be sure when installing the
680

4 Refrigerant-pipe connection(gas pipe side/flared connection) drain pump (option parts),


476

5 Refrigerant-pipe connection(liquid pipe side/flared connection) refrigerant pipe will be only upward.
6 Knockout hole for upper drain pipe arrangement
254

Use the current nuts meeting the pipe size of the outdoor unit.
7 Knockout hole for fresh air intake ø100 Available pipe size
8 Knockout hole for wiring arrangement 2-ø22 M60 M71
9 Knockout hole for wiring arrangement 2-ø26 Air intake 182 85 5 LIQUID SIDE ø6.35
1198
Accessory···Drain socket (I.D. 26) ø9.52 ø9.52
Flare nut ø6.35 (M60 only) 4 GAS SIDE ø15.88 ø15.88
:Initial flare nut size
Unit: mm
1
[FRONT VIEW] 5 4
8 1557 (Suspension bolt pitch)
24 260

OCH659
2 3 140 62
Electrical box 38 85 86 2 6

1
18

76
Ceiling

150
120° PCA-M140KA
PCA-M125KA
PCA-M100KA

80

126

190
190

169
124

46
71
320

37
38 18

121
75
25 138

680
When electrical box ø1
is pulled down 461 387

9 7
In case of the rear pipe arrangement, make sure to
remove the shaded portions from the independent piece.
Then put the independent piece back in initial position.
(The heat exchanger might be clogged because of dust) 51
2 1600 2 10
8 48
1493 5
Electrical box
230
236

195
84 88

21
2 233 When drain socket
is installed
246 Air outlet 180 (liquid ø9.52)
(Drainage)
200 (gas ø15.88)
233 When drain socket
is installed
1 Drainage pipe connection(26mmI.D.) 246 (Drainage)
57

2 Drainage pipe connection(for the left arrangement)


3 Knockout hole for left drain-piping arrangement
680

4 Refrigerant-pipe connection(gas pipe side/flared connection)


5 Refrigerant-pipe connection(liquid pipe side/flared connection)
476

6 Knockout hole for upper drain pipe arrangement NOTES.


254

7 Knockout hole for fresh air intake ø100 [Link] M10 or W3/8 screw for anchor bolt.
8 Knockout hole for wiring arrangement 2-ø22 [Link] be sure when installing the
9 Knockout hole for wiring arrangement 2-ø26 182 85 drain pump (option parts),
Air intake
Accessory···Drain socket (I.D. 26) 1518 refrigerant pipe will be only upward.
Unit: mm
Unit: mm
WIRED REMOTE CONTROLLER (Option)

120 19

PAR-32MAA

120
46

83.5

OCH659 22
7 WIRING DIAGRAM

PCA-M35KA PCA-M50KA PCA-M60KA PCA-M71KA


PCA-M100KA PCA-M125KA PCA-M140KA

OCH659 23
8 REFRIGERANT SYSTEM DIAGRAM

PCA-M35KA PCA-M50KA PCA-M60KA PCA-M71KA


PCA-M100KA PCA-M125KA PCA-M140KA

Strainer
#50
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Condenser/evaporator
temperature thermistor
(TH5)
Refrigerant flow in cooling
Refrigerant flow in heating

Refrigerant LIQUID pipe connection


(Flare)
Pipe temperature
Room temperature thermistor/liquid
thermistor (TH1) (TH2)
Strainer
Distributor #50
with strainer 1/2
#50/#50

OCH659 24
9 TROUBLESHOOTING

9-1. TROUBLESHOOTING
<Check code displayed by self-diagnosis and actions to be taken for service (summary)>
Present and past check codes are logged, and they can be displayed on the wired remote controller or controller board of out-
door unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summa-
rized in the table below. Check the contents below before investigating details.

Unit conditions at service Check code Actions to be taken for service (summary)

Judge what is wrong and take a corrective action


Displayed
according to “9-3. SELF-DIAGNOIS ACTION TABLE”.
The trouble is reoccurring.
Conduct troubleshooting and ascertain the cause of the
Not displayed trouble according to “9-4. TROUBLESHOOTING
OF PROBLEMS”.

1Consider the temporary defects such as the work of


protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise, etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring, etc.
Logged
2Reset check code logs and restart the unit after finishing
service.
3There is no abnormality in electrical component,
controller board,remote controller, etc.
The trouble is not reoccurring.
1Re-check the abnormal symptom.
2Conduct troubleshooting and ascertain the cause of the
trouble according to “9-4. TROUBLESHOOTING
OF PROBLEMS”.
Not logged 3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality concerning of parts such as
electrical component, controller board, remote
controller, etc.

OCH659 25
9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
■ Wireless remote controller (Option)
[Procedure]
1. Press the CHECK button twice. • " CHECK" lights, and refrigerant address
Refrigerant "00" flashes.
address
display • Check that the remote controller's
CHECK
CHECK display has stopped before continuing.
display
2. Press the TEMP buttons. •S
 elect the refrigerant address of the
Temperature indoor unit for the self-diagnosis.
button
ON/OFF TEMP Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
ON/OFF (For more information, see the
button
outdoor unit installation manual.)
FAN AUTO STOP
3. P
 oint the remote controller at
MODE VANE AUTO START the sensor on the indoor unit • If an air conditioner error occurs, the
HOUR indoor unit's sensor emits an intermittent
button and press the HOUR button.
CHECK LOUVER h buzzer sound, the operation light flashes,
and the check code is output.
CHECK TEST RUN min
button (It takes 3 seconds at most for check
SET RESET CLOCK code to appear.)

4. P
 oint the remote controller at • The check mode is cancelled.
the sensor on the indoor unit
and press the ON/OFF button.

OCH659 26
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds Beep Beep Beep Beep Beep Beep Beep
OPERATION 1st 2 nd 3 rd nth 1st 2 nd · · ·Repeated
INDICATOR
lamp flash Off On On On On Off On On
pattern
Self-check Approx. 2.5 s 0.5 s 0.5 s 0.5 s 0.5 s Approx. 2.5 s 0.5 s 0.5 s
starts
(Start signal
received) Number of flashes/beeps in pattern indicates the check Number of flashes/beeps in pattern indicates
code in the following table (i.e., n=5 for “P5”) the check code in the following table

[Output pattern B]
Beeper sounds Beep Beep Beep Beep Beep Beep Beep

OPERATION 1st 2nd 3 rd nth 1st 2 nd · · · Repeated


INDICATOR
lamp flash Off On On On On On Off On On On
pattern
Self-check Approx. 2.5 s Approx. 3 s 0.5 s 0.5 s 0.5 s 0.5 s Approx. 2.5 s Approx. 3 s 0.5 s 0.5 s
starts
(Start signal
received) Number of flashes/beeps in pattern indicates the check Number of flashes/beeps in pattern indicates
code in the following table (i.e., n=5 for “U2”) the check code in the following table

[Output pattern A] Errors detected by indoor unit


Wireless remote controller Wired remote controller
Beeper sounds/OPERATION
Symptom Remarks
INDICATOR lamp flashes Check code
(Number of times)
1 P1 Intake sensor error
P2 Pipe (TH2) sensor error
2
P9 Pipe (TH5) sensor error
3 E6,E7 Indoor/outdoor unit communication error
4 P4 Drain sensor error/Float switch connector (CN4F) open
P5 Drain pump error
5
PA Forced compressor stop(due to water leakage abnormality)
6 P6 Freezing/Overheating protection operation
7 EE Combination error between indoor and outdoor units
8 P8 Pipe temperature error
9 E4, E5 Remote controller signal receiving error
10 – –
11 Pb Indoor unit fan motor error
12 Fb (FB)* Indoor unit control system error (memory error, etc.)
14 PL Refrigerant circuit abnormal
– E0, E3 Remote controller transmission error
– E1, E2 Remote controller control board error
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller Wired remote controller
Beeper sounds/OPERATION
Symptom Remarks
INDICATOR lamp flashes Check code
(Number of times)
Indoor/outdoor unit communication error
1 E9 (Transmitting error) (Outdoor unit)
2 UP Compressor overcurrent interruption
3 U3,U4 Open/short of outdoor unit thermistors
For details, check
4 UF Compressor overcurrent interruption (When compressor locked)
the LED display
Abnormal high discharging temperature/49C operated/ of the outdoor
5 U2 insufficient refrigerant
controller board.
Abnormal high pressure (63H operated)/Overheating As for outdoor
6 U1,Ud (UD)* protection operation
unit, refer to
7 U5 Abnormal temperature of heat sink outdoor unit's
8 U8 Outdoor unit fan protection stop service manual.
9 U6 Compressor overcurrent interruption/Abnormal of power module
10 U7 Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
11 U9,UH abnormal synchronous signal to main circuit/Current sensor error
12 – –
13 – –
14 Others Other errors (Refer to the technical manual for the outdoor unit.)
Notes:
1. If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on, there are no error records.
2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 seconds)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.
* The check code in the parenthesis indicates PAR-32MAA model.
OCH659 27
● If the unit cannot be operated properly after test run, refer to the following table to find the cause.
Symptom
Cause
Wired remote controller LED 1, 2 (PCB in outdoor unit)
For about 2 After LED 1, 2 are lit, LED 2 is •For about 2 minutes following power-on,op-
PLEASE WAIT minutes after turned off, then only LED 1 is lit. eration of the remote controller is not possible
power-on (Correct operation) due to system startup. (Correct operation)
•Connector for the outdoor unit’s protection
Only LED 1 is lit. → device is not connected.
PLEASE WAIT → Check code
Subsequent to LED 1, 2 blink. •Reverse or open phase wiring for the outdoor
about 2 minutes unit’s power terminal block (L1, L2, L3)
Display messages do not after power-on Only LED 1 is lit. → •Incorrect wiring between indoor and outdoor
appear even when operation LED 1 blinks twice, units (incorrect polarity of S1, S2, S3)
switch is turned ON (operation LED 2 blinks once. •Remote controller wire short
lamp does not light up).

On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microprocessor) Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for remote controller) Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant addresses “0”.
LED3 (communication between indoor and Indicates state of communication between the indoor and outdoor units.
outdoor units) Make sure that this LED is always blinking.

OCH659 28
Note:
Errors to be detected in outdoor unit, such as codes starting with F, U
or E (excluding E0 to E7), are not covered in this document. Please
9-3. SELF-DIAGNOSIS ACTION TABLE refer to the outdoor unit's service manual for the details.
Check code Abnormal point and detection method Cause Countermeasure
Room temperature thermistor (TH1) Defective thermistor – Check resistance value of thermistor.
The unit is in 3-minute resume characteristics 0˚C...15.0 kΩ
prevention mode if short/open of Contact failure of connector 10˚C.... 9.6 kΩ
thermistor is detected. Abnormal if the (CN20) on the indoor controller 20˚C.... 6.3 kΩ
unit does not reset normally after 3 board (Insert failure) 30˚C.... 4.3 kΩ
minutes. (The unit returns to normal Breaking of wire or contact 40˚C.... 3.0 kΩ
operation, if it has been reset normally.) failure of thermistor wiring If you put force on (draw or bend) the lead wire
Constantly detected during cooling, Defective indoor controller with measuring resistance value of thermistor,
drying, and heating operation. board breaking of wire or contact failure can be
Short: −90˚C or more detected.
Open: −40˚C or less Check contact failure of connector (CN20)
P1 on the indoor controller board. Refer to "9-7.
TEST POINT DIAGRAM".
Turn the power on again and check restart
after inserting connector again.
Check room temperature display on remote
controller.
Replace indoor controller board if there
is abnormal difference with actual room
temperature.

Turn the power off, and on again to operate


after check.
Pipe temperature thermistor/Liquid (TH2) Defective thermistor – Check resistance value of thermistor.
The unit is in 3-minute resume characteristics For characteristics, refer to (P1) above.
prevention mode if short/open of Contact failure of connector Check contact failure of connector (CN44)
thermistor is detected. Abnormal if the (CN44) on the indoor controller on the indoor controller board. Refer to "9-7.
unit does not reset normally after 3 board (Insert failure) TEST POINT DIAGRAM".
minutes. (The unit returns to normal Breaking of wire or contact Turn the power on and check restart after
operation, if it has been reset normally.) failure of thermistor wiring inserting connector again.
Constantly detected during cooling, Defective refrigerant circuit is Check pipe <liquid> temperature with remote
drying, and heating (except defrosting) causing thermistor temperature controller in test run mode. If pipe <liquid>
P2 operation of 90˚C or more or −40˚C or temperature is extremely low (in cooling
Short: 90˚C or more less. mode) or high (in heating mode), refrigerant
Open:−40˚C or less Defective indoor controller circuit may have defective.
board Check pipe <liquid> temperature with
remote controller in test run mode. If there is
extremely difference with actual pipe <liquid>
temperature, replace indoor controller board.

Turn the power off, and on again to operate


after check.
Contact failure of drain float switch Contact failure of connector Check contact failure of float switch connector.
(CN4F) (Insert failure) Turn the power on again and check after
• Extract when the connector of drain float inserting connector again.
switch is disconnected. Operate with connector (CN4F) short-
P4
( and of connector CN4F is not Defective indoor controller circuited.
short-circuited.) board Replace indoor controller board if
• Constantly detected during operation abnormality reappears.

Drain over flow protection operation Malfunction of drain pump Check if drain pump operates.
Suspensive abnormality, if drain float Defective drain Check drain function.
switch is detected to be underwater for Clogged drain pump
1 minute and 30 seconds continuously Clogged drain pipe
with drain pump on. Defective drain float switch Remove drain float switch connector CN4F
Compressor and indoor fan will be Catch of drain float switch or and check if it is short (Switch On) with the
turned off. malfunction of moving parts moving part of float switch UP, or OPEN with
Drain pump is abnormal if the condition cause drain float switch to be the moving part of float switch down.
above is detected during suspensive detected under water (Switch Replace float switch if it is short with the
abnormality. On) moving part of float switch down.
P5 Constantly detected during drain pump Defective indoor-controller Replace indoor controller board if it is short-
operation board circuited between – of the drain float
switch connector CN4F and abnormality
reappears.

It is not abnormal if there is no problem about


the above-mentioned 1–4.
Turn the power off, and on again to operate
after check.

OCH659 29
Check code Abnormal point and detection method Cause Countermeasure
Freezing/overheating protection is (Cooling or drying mode) (Cooling or drying mode)
operating Clogged filter (reduced airflow) Check clogs of the filter.
Freezing protection (Cooling mode) Short cycle of air path Remove blockage.
The unit is in 6-minute resume Low-load (low temperature)
prevention mode if pipe <liquid or operation out of the tolerance
condenser/evaporator> temperature range
stays under −15˚C for 3 minutes, 3 Defective indoor fan motor Refer to "9-6. HOW TO CHECK THE
minutes after the compressor started. • Fan motor is defective. PARTS".
Abnormal if it stays under −15˚C for 3 • Indoor controller board is defec-
minutes again within 16 minutes after tive.
6-minute resume prevention mode.

Defective outdoor fan control


Overcharge of refrigerant Check outdoor fan motor.
Defective refrigerant circuit Check operating condition of refrigerant
(clogs) circuit.

(Heating mode)
Overheating protection (Heating mode) Clogged filter (reduced airflow) (Heating mode)
P6 The unit is in 6-minute resume Short cycle of air path Check clogs of the filter.
prevention mode if pipe <liquid or Over-load (high temperature) Remove blockage.
condenser/evaporator> temperature operation out of the tolerance
is detected as over 70˚C after the range
compressor started. Abnormal if the Defective indoor fan motor Refer to "9-6. HOW TO CHECK THE
temperature of over 70˚C is detected • Fan motor is defective. PARTS".
again within 30 minutes after 6-minute • Indoor controller board is defec-
resume prevention mode. tive.
Defective outdoor fan control
Overcharge of refrigerant Check outdoor fan motor.
Defective refrigerant circuit – Check operating condition of refrigerant
(clogs) circuit.
Bypass circuit of outdoor unit
is defective.

Pipe temperature Slight temperature difference – Check pipe <liquid or condenser/evapo-


<Cooling mode> between indoor room rator> temperature with room tempera-
Detected as abnormal when the pipe temperature and pipe <liquid ture display on remote controller and
temperature is not in the cooling range or condenser/evaporator> outdoor controller circuit board.
3 minutes after compressor start and 6 temperature thermistor Pipe <liquid or condenser/evaporator>
minutes after the liquid or condenser/ • Shortage of refrigerant temperature display is indicated by set-
evaporator pipe is out of cooling range. • Disconnected holder of ting SW2 of outdoor controller circuit
Note 1: It takes at least 9 minutes to detect. pipe <liquid or condenser/ board as follows.
Note 2: Abnormality P8 is not detected in evaporator> thermistor

( )
drying mode. • Defective refrigerant circuit Conduct temperature check with outdoor
Cooling range : −3°C (TH−TH1) Converse connection of controller circuit board after connecting
TH: Lower temperature between liquid pipe extension pipe (on plural units ‘A-Control Service Tool(PAC-SK52ST)’.
temperature (TH2) and condenser/ connection)
evaporator temperature (TH5) Converse wiring of indoor/ Check converse connection of extension
TH1: Intake temperature outdoor unit connecting wire pipe or converse wiring of indoor/outdoor
(on plural units connection) unit connecting wire.
P8 <Heating mode> Defective detection of indoor
When 10 seconds have passed after the room temperature and pipe
compressor starts operation and the hot <condenser/evaporator>
adjustment mode has finished, the unit is temperature thermistor
detected as abnormal when condenser/ Stop valve is not opened
evaporator pipe temperature is not in completely.
heating range within 20 minutes.

Note 3: It takes at least 27 minutes to


detect abnormality.
Note 4: It excludes the period of defrosting.
(Detection restarts when defrosting
mode is over.)
Heating range: 3°C (TH5−TH1)

OCH659 30
Check code Abnormal point and detection method Cause Countermeasure
Pipe temperature thermistor/ Defective thermistor – Check resistance value of thermistor.
Condenser-Evaporator (TH5) characteristics For characteristics, refer to (P1) above.
The unit is in 3-minute resume protection Contact failure of connector Check contact failure of connector (CN44)
mode if short/open of thermistor is (CN44) on the indoor controller on the indoor controller board.
detected. Abnormal if the unit does not board (Insert failure) Refer to "9-7. TEST POINT DIAGRAM".
get back to normal within 3 minutes. (The Breaking of wire or contact Turn the power on and check restart after
unit returns to normal operation, if it has failure of thermistor wiring inserting connector again.
been reset normally.) Temperature of thermistor is Operate in test run mode and check pipe
Constantly detected during cooling, 90˚C or more or −40˚C or less <condenser/evaporator> temperature with
drying, and heating operation (except caused by defective refrigerant outdoor controller circuit board. If pipe
defrosting) circuit. <condenser/evaporator> temperature is
Short: 90˚C or more extremely low (in cooling mode) or high (in
Defective indoor controller
heating mode), refrigerant circuit may have
P9 Open: −40˚C or less board
defect.
Operate in test run mode and check pipe
<condenser/evaporator> temperature
with outdoor control circuit board. If there
is extreme difference with actual pipe
<condenser/evaporator> temperature,
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off and on again to operate.

( )
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
tool (PAC-SK52ST).
Remote controller transmission Contact failure at transmission Check disconnection or looseness of indoor
error(E0)/signal receiving error(E4) wire of remote controller unit or transmission wire of remote controller.
Abnormal if main or sub remote con- All remote controllers are set Set one of the remote controllers “main” if
troller cannot receive any transmission as “sub” remote controller. there is no problem with the action above.
normally from indoor unit of refrigerant Check wiring of remote controller.
In this case, E0 is displayed
• Total wiring length: maximum 500 m
address “0” for 3 minutes. on remote controller, and E4 (Do not use cable × 3 or more.)
(Check code: E0) is displayed at LED (LED1, • The number of connecting indoor units:
Abnormal if sub remote controller could LED2) on the outdoor controller maximum 16 units
not receive any signal for 2 minutes. circuit board. • The number of connecting remote control-
(Check code: E0) Miswiring of remote controller ler: maximum 2 units
Defective transmitting receiving
Abnormal if indoor controller board can circuit of remote controller If the cause of trouble is not any of – above,
E0 not receive any data normally from Defective transmitting receiving Diagnose remote controllers.
or remote controller board or from other circuit of indoor controller board a) When “RC OK” is displayed,
E4 indoor controller board for 3 minutes. of refrigerant addresses “0”. Remote controllers have no problem.
(Check code: E4) Noise has entered into the Turn the power off, and on again to check.
Indoor controller board cannot receive transmission wire of remote If abnormality generates again, replace
indoor controller board.
any signal from remote controller for 2 controller. b) When “RC NG” is displayed,
minutes. (Check code: E4) Replace remote controller.
c) When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
Note:
If the unit is not normal after replacing indoor
controller board in group control, indoor con-
troller board of address “0” may be abnormal.

Remote controller transmission 2 remote controllers are set as Set a remote controller to main, and the
error(E3)/signal receiving error(E5) “main.” other to sub.
Abnormal if remote controller could not (In case of 2 remote controllers)
find blank of transmission path for 6 sec- Remote controller is connected
onds and could not transmit. with 2 indoor units or more.
(Check code: E3) Repetition of refrigerant Remote controller is connected with only one
Remote controller receives transmitted address indoor unit.
data at the same time and compares the
received and transmitted data. Abnormal Defective transmitting receiving The address changes to a separate setting.
if these data are judged to be different circuit of remote controller
E3
30 continuous times. (Check code: E3) Defective transmitting receiving – Diagnose remote controller.
or
circuit of indoor controller board a) When “RC OK” is displayed, remote con-
E5 trollers have no problem.
Abnormal if indoor controller board could Noise has entered into transmis-
not find blank of transmission path. sion wire of remote controller. Turn the power off,and on again to check.
(Check code: E5) When becoming abnormal again, replace
Indoor controller board receives trans- indoor controller board.
mitted data at the same time and com- b) When “RC NG” is displayed, replace
pares the received and transmitted data. remote controller.
Abnormal if these data are judged to be c) When “RC E3” or “ERC 00-66” is dis-
different 30 continuous times. (Check played, noise may be causing abnormal-
code: E5) ity.

OCH659 31
Check code Abnormal point and detection method Cause Countermeasure
Indoor/outdoor unit communication Contact failure, short circuit or, Note:
error (Signal receiving error) miswiring (converse wiring) of Check LED display on the outdoor control
Abnormal if indoor controller board indoor/outdoor unit connecting circuit board. (Connect A-control service
cannot receive any signal normally for wire tool, PAC-SK52ST.) Refer to outdoor unit ser-
6 minutes after turning the power on. vice manual.
Defective transmitting receiving Check disconnection or looseness of indoor/
Abnormal if indoor controller board circuit of indoor controller board outdoor unit connecting wire of indoor unit or
cannot receive any signal normally for Defective transmitting receiving outdoor unit.
3 minutes. circuit of indoor controller board Check all the units in case of twin triple
E6
Consider the unit abnormal under Noise has entered into indoor/ indoor unit system.
the following condition: When 2 or outdoor unit connecting wire. – Turn the power off, and on again to
more indoor units are connected to an check. If abnormality generates again,
outdoor unit, indoor controller board replace indoor controller board or outdoor
cannot receive a signal for 3 minutes controller circuit board.
Note:
from outdoor controller circuit board, a
Other indoor controller board may have defect
signal which allows outdoor controller in the case of twin triple indoor unit system.
circuit board to transmit signals.
Indoor/outdoor unit communication Defective transmitting receiving – Turn the power off, and on again to
error (Transmitting error) circuit of indoor controller board check. If abnormality generates again,
Abnormal if “1” receiving is detected 30 Noise has entered into power replace indoor controller board.
E7 times continuously though indoor controller supply.
board has transmitted “0”. Noise has entered into outdoor
control wire.

Indoor controller board Defective indoor controller Replace indoor controller board.
Abnormal if data cannot be read normally board
Fb
from the nonvolatile memory of the indoor
(FB)*
controller board. * The check code in the parenthesis indicates
PAR-32MAA model.

Remote controller control board Defective remote controller Replace remote controller.
Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
E1 (Check code: E1)
or
E2 Abnormal if the clock function of remote
controller cannot be operated normally.
(Check code: E2)

Forced compressor stop Drain pump trouble Check the drain pump.
(due to water leakage abnormality)
The unit has a water leakage abnormality Drain defective Check whether water can be drained.
when the following conditions, a) and b), · Drain pump clogging
are satisfied while the above-mentioned · Drain pipe clogging
detection is performed.
a) The intake temperature subtracted Open circuit of float switch Check the resistance of the float switch.
with liquid pipe temperature detects
to be less than −10˚C for a total of Contact failure of float switch Check the connector contact failure.
30 minutes. (When the drain sensor connector
is detected to be NOT soaked in the
water, the detection record of a) and b) Dew condensation on float Check the float switch leadwire mounted.
will be cleared.) switch Check the filter clogging.
b) Drain float switch detects to be in the · Drain water descends along
water for more than 15 minutes. lead wire.
Note: · Drain water is waving due to
PA Once the water leakage abnormality is filter clogging.
detected, abnormality state will not be
released until the main power is reset. Extension piping connection Check the piping connection.
difference at twin, triple or
quadruple system

Miswiring of indoor/outdoor Check the indoor/outdoor connecting wires.


connecting at twin, triple or
quadruple system

Room temperature thermistor/ Check the room temperature display of


liquid pipe temperature remote controller.
thermistor detection is defective. Check the indoor liquid pipe temperature dis-
play of outdoor controller board.

OCH659 32
Check code Abnormal point and detection method Cause Countermeasure
Fan motor trouble 1 Defective fan motor 12 Refer to "9-6-2. DC Fan Motor (fan motor/
2 Defective indoor controller board indoor controller board)".
Pb

Abnormal refrigerant circuit Abnormal operation of 4-way When this error occurs, be sure to replace
During Cooling, Dry, or Auto Cooling valve the 4-way valve.
operation, the following conditions are Disconnection of or leakage in Check refrigerant pipes for disconnection or
regarded as failures when detected for 1 refrigerant pipes leakage.
second. Air into refrigerant piping After the recovery of refrigerant, vacuum dry
a)The compressor continues to run for 30 Abnormal operation (no rotation) the whole refrigerant circuit.
PL or more seconds. of indoor fan Refer to section "9-6-2. DC Fan motor (fan
b)The liquid pipe temperature or the · Defective fan motor. motor/indoor controller circuit board)".
condenser/evaporator temperature is · Defective indoor control board. Check refrigerant circuit for operation.
75°C or more. Defective refrigerant circuit To avoid entry of moisture or air into
These detected errors will not be (clogging) refrigerant circuit which could cause
cancelled until the power source is abnormal high pressure, purge air in
reset. refrigerant circuit or replace refrigerant.

OCH659 33
9-4. TROUBLESHOOTING OF PROBLEMS
Note: Refer to the outdoor unit's service manual for the detail of remote controller.
Phenomena Cause Countermeasure
(1) LED2 on indoor controller board • When LED1 on indoor controller board is also off.
is off. Power supply of rated voltage is not supplied to out- Check the voltage of outdoor power
door unit. supply terminal block (L, N) or (L3, N).
• When 220–240 V AC is not detected,
check the power wiring to outdoor unit
and the breaker.
• When 220–240 V AC is detected, check
(below).
Defective outdoor controller circuit board Check the voltage between outdoor
terminal block S1 and S2.
• When 220–240 V AC is not detected,
—check the fuse on outdoor controller
circuit board.
—check the wiring connection.
• When 220–240 V AC is detected, check
(below).
Power supply of 220–240 V is not supplied to indoor Check the voltage between indoor
unit. terminal block S1 and S2.
• When 220–240 V AC is not detected,
check indoor/outdoor unit connecting
wire for miswiring.
• When 220–240 V AC is detected, check
(below).
Defective indoor controller board Check the fuse on indoor controller board.
Check the wiring connection.
If no problem is found, indoor controller
board is defective.

(For the separate indoor/outdoor unit power sup-


ply system)
Power supply of 220–240 V AC is not supplied to Check the voltage of indoor power supply
indoor unit. terminal block (L,N).
• When 220–240 V AC is not detected,
check the power supply wiring.
• When 220–240 V AC is detected, check
(below).
The connectors of the optional replacement kit are Check that there is no problem in the
not used. method of connecting the connectors.
• When there are problems in the method
of connecting the connectors, connect
the connector correctly referring to
installation manual of an optional kit.
• When there is no problem in the method
of connecting the connectors, check
(below).
Check the fuse on indoor controller board.
Defective indoor controller board Check the wiring connection.
If no problem is found, indoor controller
board is defective.

• When LED1 on indoor controller board is lit.


Mis-setting of refrigerant address for outdoor unit Check again the setting of refrigerant
(There is no unit corresponding to refrigerant address address for outdoor unit.
“0”.) Set the refrigerant address to “0”.
(For grouping control system under which
2 or more outdoor units are connected,
set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.

OCH659 34
Note: Refer to the outdoor unit's service manual for the detail of remote controller.
Phenomena Cause Countermeasure
(2) L
 ED2 on indoor controller board • When LED1 on indoor controller board is also blinking. Check indoor/outdoor unit connecting wire
is blinking. Connection failure of indoor/outdoor unit connecting for connection failure.
wire

• When LED1 is lit. Check the connection of remote controller


Miswiring of remote controller wires wires in the case of twin triple indoor unit
Under twin triple indoor unit system, 2 or more indoor system. When 2 or more indoor units are
units are wired together. wired in one refrigerant system, connect
remote controller wires to one of those
units.
Refrigerant address for outdoor unit is wrong or not Check the setting of refrigerant address
set. in case of grouping control system.
Under grouping control system, there are some units If there are some units whose refrigerant
whose refrigerant addresses are 0. addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor
controller circuit board.
Short-circuit of remote controller wires Remove remote controller wires and
Defective remote controller check LED2 on indoor controller board.
• When LED2 is blinking, check the short-
circuit of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block, etc. has returned to normal.

(3) U
 pward/downward vane The vane is not downward during defrosting and Normal operation (The vane is set to
performance failure heat preparation and when the thermostat is OFF in horizontal regardless of remote control.)
HEAT mode. (Working of COOL protection function)
Vane motor does not rotate. Check (left).
• Defective vane motor • Check the vane motor. (Refer to “How
• Breaking of wire or connection failure of connector to check the parts”.)
• Check for breaking of wire or
connection failure of connector.
Upward/downward vane does not work. Normal operation (Each connector on
• The vane is set to fixed position. vane motor side is disconnected or
setting the fixed vanes by wired remote
controller.)

(4) R
 eceiver for wireless remote Weak batteries of wireless remote controller Replace batteries of wireless remote
controller controller.
Contact failure of connector (CNB) on wireless –
remote controller board Check contact failure of each connector.
(Insert failure) If no problems is found of connector,
Contact failure of connector (CN90) on indoor con- replace indoor controller board.
troller board (Insert failure) When the same trouble occurs even
Contact failure of connector between wireless remote if indoor controller board is replaced,
controller board and indoor controller board replace wireless remote controller
board.

OCH659 35
9-5. EMERGENCY OPERATION
9-5-1. When wireless remote controller fails or its battery is exhausted
When the remote controller cannot be used
When the batteries of the remote controller run out or the remote control-
ler malfunctions, the emergency operation can be done using the emer-
gency buttons on the grille.
DEFROST/STAND BY lamp
Operation lamp
Emergency operation switch (heating)
Emergency operation switch (cooling)
Receiver
Starting operation
• To operate the cooling mode, press the button for more than 2
seconds.
• To operate the heating mode, press the button for more than 2
seconds.
Note: Lighting of the Operation lamp means the start of operation.

Details of emergency mode are as shown below.


Operation mode COOL HEAT
Set temperature 24°C 24°C
Fan speed High High
Airflow direction Horizontal Downward 5
Stopping operation
• To stop operation, press the button or the button .

9-5-2. When wired remote controller or indoor unit microprocessor fails


[Link] the wired remote control or the indoor unit microprocessor has failed, but all other components work properly,
if you set the switch (SWE) on the indoor controller board ON, the indoor unit will begin emergency operation.
When emergency operation is activated, the indoor unit operates as follows:
(1) Indoor fan is running at high speed. (2) Drain pump is operating. (option)
Note on the wireless remote control: when the remote control does not function, it is possible to activate
emergency operation by using the indoor unit emergency operation switch (SW1, SW2 of the wireless signal
receiver board).
However, if the indoor unit microprocessor has failed, it is necessary to proceed with points (2) and (3) below as in the
case of the wired remote controller.

[Link] you activate emergency operation of the cooling or heating, you have to set the switch (SWE) on the indoor
controller board and activate emergency operation of the outdoor unit.
For details on how to activate emergency operation of the outdoor unit, refer to the outdoor unit wiring diagram.
Note: Emergency operation will not work unless outdoor unit is PU series.
[Link] you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• it has detected the malfunction of drain pump during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off.
ON/OFF on the remote control or temperature control etc. does not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation
of the heating is activated because it will start to blow cold air.
(4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(5) After emergency operation has been deactivated, set the switches etc. to their original positions.
(6) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them
manually to the appropriate position.

OCH659 36
9-6. HOW TO CHECK THE PARTS
PCA-M35KA PCA-M50KA PCA-M60KA PCA-M71KA
PCA-M100KA PCA-M125KA PCA-M140KA

Parts name Check points


Room temperature Disconnect the connector then measure the resistance with a tester.
thermistor (TH1) (At the ambient temperature of 10 to 30°C)
Pipe temperature
thermistor/liquid(TH2) Normal Abnormal
Condenser/evaporator Refer to “9-6-1. Thermistor”.
temperature thermistor (TH5) 4.3 to 9.6kΩ Open or short

Vane motor (MV) Measure the resistance between the terminals with a tester.
(At the ambient temperature of 20 to 30°C
White
Connector Normal Abnormal
MV Red - Yellow
Orange Red - Blue
300Ω Open or short
Red Red - Orange
Blue Yellow Red - White

Drain pump (DP) Measure the resistance between the terminals with a tester.
(Option) (Winding temperature 20°C)
1 Normal Abnormal
3 290Ω Open or short

Drain float switch (FS)


Measure the resistance between the terminals with a tester.
Moving part Switch
State of moving part Normal Abnormal Magnet
1
2 UP Short Other than short
3 DOWN Open Other than open
Moving part
(Option) 4

9-6-1. Thermistor
<Thermistor Characteristic Graph> < Thermistor for lower temperature >
50
Room temperature thermistor(TH1)
Thermistor for
lower temperature Pipe temperature thermistor/liquid(TH2)
Condenser/evaporator temperature 40
thermistor(TH5)
Resistance (k")

Thermistor R0=15kΩ ± 3% 30
Fixed number of B=3480 ± 2%

Rt=15exp { 3480( 1 1 )} 20
273+t 273
0˚C 15 kΩ
10˚C 9.6 kΩ 10
20˚C 6.3 kΩ
25˚C 5.4 kΩ
30˚C 4.3 kΩ 0
-20 -10 0 10 20 30 40 50
40˚C 3.0 kΩ Temperature (:)

OCH659 37
9-6-2. DC Fan motor (fan motor/indoor controller circuit board)

Check method of DC fan motor (fan motor/indoor controller circuit board)


1 Notes
· High voltage is applied to the connecter (CNMF) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on.
(It causes trouble of the indoor controller circuit board and fan motor.)
2 Self check
Symptom : The indoor fan cannot rotate.

Wiring contact check


Contact of fan motor connector (CNMF)

Is there contact failure? Yes Wiring recovery


No
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit board.
TEST POINT 1 : VDC (between 1 (+) and 4 (−) of the fan connector): VDC 310–340 V DC
TEST POINT 2 : VCC (between 5 (+) and 4 (−) of the fan connector): VCC 15 V DC

Is the voltage normal? No Indoor controller board fuse check

Yes
No
Is the fuse normal? Replace
the fuse.
Yes
Fail OK
Replace the indoor
Check the operation. END
controller board.

OK
Check the operation. END

Fail
Replace the fan motor.

Sensor signal check


Measure the voltage between CNMF 7 and 4 0 V DC
and 15 V DC in the indoor controller circuit board.

Does the voltage repeat No


Replace the fan motor.
0 V DC and 15 V DC?
Yes OK
Yes
Check the operation of fan. END
Replace the indoor
Fail
controller board.
Replace the indoor controller board.
OK
Check the operation. END
Fail
Replace the fan motor.

OCH659 38
9-7. TEST POINT DIAGRAM
Indoor controller board
PCA-M35KA PCA-M50KA PCA-M60KA PCA-M71KA
PCA-M100KA PCA-M125KA PCA-M140KA

SWE CN2L
Emergency operation Connector (LOSSNAY)
LED3
Transmission
CNV
(Indoor/outdoor)
Vane motor output (MV)
CN90 12 V pulse output
Connect to the wireless remote
controller board (CNB) SW1
Model selection
CN105
SW2
LED2
Capacity setting
Power supply (R.B)

CN4F Jumper wire J41,J42


Drain float switch (FS) Pair No. setting for wireless
(option) remote controller
CN44 CN51
Pipe temperature Centrally control
thermistor 1-2 : Control signal
1-2 : Liquid (TH2) 13 V DC pulse input (1: +)
3-4 : Cond./Eva. (TH5) 3-4 : Operation indicator
13 V DC (3: +)
CN20 3-5 : Malfunction indicator
Room temperature 13 V DC (3: +)
thermistor (TH1) CN41
Connector (HA terminal-A)
LED1
Power supply (I.B) CN22
Connect to the terminal
block (TB5)
(Remote controller con-
VFG : Voltage between
necting wire)
PC6722 and C955(-)
(10.4–14.6 V DC)
(Same as 7(+)–4(-) of CNMF)
CN3C
Transmission
VSP : Voltage between pins of (Indoor/outdoor)
C626 (0–24 V DC)
0 V DC (FAN stop)
1–6.5 V DC (FAN operation) VCC : Voltage between pins of
(Same as 6(+)–4(-) of CNMF) C955 15 V DC
(Same as 5(+)–4(-) of CNMF)
CNMF
Fan motor
1-4: 310–340 V DC
5-4: 15 V DC
CN01
6-4: 0–6.5 V DC
Connect to the Terminal Block
7-4: Stop 0 or 15 V DC
(TB4)
Operation 7.5 V DC
(Indoor/outdoor connecting line)
(0–15 V pulse)
Between 3 and 5
220–240 V AC

CNP
Drain-pump output (DP)
FUSE
(220–240 V AC) (option)
6.3 A /250 V

OCH659 39
9-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the DIP switch and the jumper wire on the indoor controller board.
SW1 and SW2 are equipped only for service parts.
Model setting and capacity setting are preset in the nonvolatile memory of the controller board of the unit.

(Marks in the table below) Jumper wire ( : Short : Open)


The black square (■) indicates a switch position.

Jumper wire Functions Setting by the DIP switch and jumper wire Remarks

MODEL Service board


SW1 Model 1 2 3 4 5
settings PCA-M•KA ON
OFF

MODEL Service board


1 2 3 4 5
PCA-M35KA ON
OFF
1 2 3 4 5
PCA-M50KA ON
OFF
1 2 3 4 5
PCA-M60KA ON
SW2 Capacity OFF
settings
1 2 3 4 5
PCA-M71KA ON
OFF
1 2 3 4 5
PCA-M100KA ON
OFF
1 2 3 4 5
PCA-M125KA ON
OFF
1 2 3 4 5
PCA-M140KA ON
OFF

<Initial setting>
Wireless remote controller: 0
Wireless remote Control PCB setting Control PCB: (for both J41 and J42)
Pair number controller setting J41 J42
setting with 4 pair number settings are supported.
J41 0
wireless The pair number settings of the wireless remote
J42 1
remote controller and indoor control PCB (J41/J42) are
2
controller given in the table on the left.
3–9
(' ' in the table indicates the jumper line is disco-
nnected.)

Indoor
Indoor controller board type JP3
controller
JP3 For product
board type
Service parts
setting

OCH659 40
10 FUNCTION SETTING

10-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER


Each function can be set as necessary using the remote controller. The setting of function for each unit can only be
done by the remote controller.
(1) Functions available when setting the unit number to 00
Refer to the service manual that comes with each outdoor unit.
(2) Functions available when setting the unit number to 01–03 or AL (07 in case of wireless remote controller)
Setting
Function Settings Mode No. Initial setting Setting
No.
Filter sign 100 Hr 1
2500 Hr 07 2 ○
No filter sign indicator 3
Fan speed Silent (low ceiling) 1
Standard 08 2 ○
High ceiling 3
Installed options (high efficiency filter) Not supported
10
1 ○
Supported 2
Up/down vane setting No vanes 1
Equipped with vanes (vanes angle setup 1) 11 2 ○
Equipped with vanes (vanes angle setup 2) 3
Fan speed during the cooling thermostat Setting fan speed 1
is OFF Stop 27 2
Extra low 3 ○

OCH659 41
11 SPECIAL FUNCTION

11-1. ROTATION FUNCTION (AND BACK-UP FUNCTION, 2ND STAGE CUT-IN FUNCTION)
Note that this function is not available for SUZ model.

11-1-1. Operation
(1) Rotation function (and Back-up function)
• Outline of functions
· Main and sub unit operate alternately according to the interval of rotation setting.
Main and sub unit should be set by refrigerant address. (Outdoor DIP switch setting)
Refrigerant address "00" Main unit
Refrigerant address "01" Sub unit
· When an error occurs to one unit, another unit will start operation. (Back-up function)
• System constraint
· This function is available only by the grouping control system (INDOOR UNIT : OUTDOOR UNIT=1:1) of 2 refrigerant
groups. (Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line (TB5) for main and sub unit
should also be connected. (Refer to Fig. 1)
(This function cannot be set by wireless remote controller.)
· Set refrigerant address of each unit. (DIP switch on the outdoor unit ··· Refrigerant address 00/01)

Operation pattern Fig. 1 Refrigerant address Refrigerant address


"00" "01"
1 [Back-up function only]··· Request code number "312"
Error occurs on main unit.
Start operation Main Sub OC-1 OC-2
Main
unit Abnormal condition Main Sub
Run 3(2)
IC-1 unit 3(2) unit

Sub IC-1 IC-2


unit Stop Run
IC-2
2 2
2 [Rotation function] & [Back-up function]··· Request code number "313–318"
RC
Error occurs on main unit.
Start operation Main Sub Main Sub Main Sub OC : Outdoor unit
Main IC : Indoor unit
Abnormal condition RC : Wired remote controller
unit
Run Stop Run
IC-1

Sub
unit Stop Run Stop Run
IC-2
1–28 days 1–28 days
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)

Note:
· When the unit is restarted to operate after turning off the power or OFF operation, the unit which was operating will start
operation.
· To operate the main unit, refer to "11-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)" and set
the request code No. which is not the same as the current one, then set again the former request code No.

(2) 2nd stage cut-in function


• Outline of functions
· When the 1st unit can NOT supply with sufficient capacity for exceptionally high-demand conditions and the actual room
temperature reaches set point (*), the 2nd unit starts operation in conjunction with the 1st unit.
· Once the actual room temperature goes down to 4˚C below set point(*), the 2nd unit stops operation automatically.
(* set point = set temperature by R/C (remote controller) + 4, 6, 8˚C (selectable) )
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts. (2 units operation)
· When room temperature falls below set point −4˚C, standby unit stops. (1 unit operation)

OCH659 42
• System constraint
· This function is available only in cooling mode.

Ex.) Set temp. by R/C = 20˚C [2nd stage cut-in function]··· Request code number "322–324"
Set point = 26˚C
When request code number is “323”. Room temp. ] Set point Room temp. < Set point −4:
Start operation Sub unit start operation Sub unit stop
Main
26˚C 2nd unit Cut-in unit
Run
IC-1
4˚C
Sub
22˚C 2nd unit Cut-out unit Stop Run Stop
IC-2

20˚C

11-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller. (Maintenance monitor)

NOTICE
Both main and sub unit should be set in same setting.
Every time replacing indoor controller board for servicing, the function should be set again.

(1) Request Code List


Rotation setting
Setting No. Initial
Setting contents
(Request code) setting
No.1
Monitoring the request code of current setting
(310)
No.2
Rotation and Back-up OFF (Normal group control operation)
(311)
No.3
Back-up function only
(312)
No.4
Rotation ON (Alternating interval = 1day) and back-up function
(313)
No.5
Rotation ON (Alternating interval = 3days) and back-up function
(314)
No.6
Rotation ON (Alternating interval = 5days) and back-up function
(315)
No.7
Rotation ON (Alternating interval = 7days) and back-up function
(316)
No.8
Rotation ON (Alternating interval = 14days) and back-up function
(317)
No.9
Rotation ON (Alternating interval = 28days) and back-up function
(318)

2nd unit cut-in setting


Setting No. Initial
Setting contents
(Request code) setting
No.1
Monitoring the request code of current setting
(320)
No.2
Cut-in function OFF
(321)
No.3
Cut-in function ON (Set point = Set temp.+ 4: [7.2°F]
(322)
No.4
(323) Cut-in function ON (Set point = Set temp.+ 6: [10.8°F]
No.5
(324) Cut-in function ON (Set point = Set temp.+ 8: [14.4°F]

OCH659 43
(2) Setting method of each function by wired remote controller

■ PAR-3xMAA ("x" represents 0 or later)

S
 top operation ( ) Check menu
Error history
Refrigerant volume check
Refrigerant leak check
S
 elect "Service" from the Main menu, and press the button. Smooth maintenance
Request code
Service menu:
Cursor
Select "Check" with the F1 or F2 button, and press the button.

Select "Request code" with the F1 or F2 button, and press the button.

Set the Refrigerant address and Request code. Request code


[Link]
• Select the item to be changed with the F1 or F2 button. Request code

• Select the required setting with the F3 or F4 button.


Request:
Cursor
• Select the required code No. (311–318, 321–324) with the F3 or F4 button.

■<[Link]>setting [ 0 ] – [ 15 ]
■<Request code>setting

Press the button, Data will be collected and displayed.

Request code
[Link]
Request code

Request code: 311


Rotation and Back-up OFF: 0311
Request:
Cursor

OCH659 44
(3) Rotation and back up operation
■ PAR-3xMAA ("x" represents 0 or later)
Press the button.
Main Main menu 3/3
Maintenance
Select "Service" with the [Cursor] buttons ( F1 and F2 ) or the [Page] buttons ( F3 Initial setting
Service
and F4 ), and press the button.

Main display:
Cursor Page

Enter the current maintenance password (4 numerical digits). Service menu


• Move cursor to the digit you want to change with the F1 or F2 button.
Enter maintenance password
• Set each number (0 through 9) with the F3 or F4 button. 9999
(Note: The initial maintenance password is "9999".)

Select:
Then, press the button. Cursor

Select "Check" with the F1 or F2 button, and press the button. Service menu 1/2
Test run
Input maintenance info.
Function setting
Check
Self check
Main menu:
Cursor

Select "Request code" with the F1 or F2 button, and press the button. Check menu 1/1
Error history
Refrigerant volume check
Refrigerant leak check
Smooth maintenance
Request code
Service menu:
Cursor

Set the Refrigerant address and Request code. Request code


• Select the item to be changed with the F1 or F2 button. [Link] 0
Request code 004
• Select the required setting with the F3 or F4 button.
Press the F3 or F4 button to set the Refrigerant address "0".
Press the F3 or F4 button to set the desired request code No. Request:
• Rotation & Back up operation: Enter one request code from 311 to 318. Cursor
• 2nd stage cut-in operation: Enter one request code from 321 to 324.
Press the button. Data will be collected and displayed.
Press the F3 or F4 button to set the Refrigerant address "1".
Set above – .
To return to the Main menu, press the button.

OCH659 45
12 DISASSEMBLY PROCEDURE

PCA-M35KA PCA-M50KA PCA-M60KA PCA-M71KA


PCA-M100KA PCA-M125KA PCA-M140KA

Be careful when removing heavy parts. (Photo: PCA-M125KA)

OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS


1. Removing the air intake grille
(1) Slide the air intake grille holding knobs (at 2 or 3 loca-
tions) to the rear to open the air intake grille. (See Figure 1)
(2) While the air intake grille left open, push the stoppers Figure 1
on the rear hinges (at 2 or 3 locations) to pull out the air
intake grille. (See Figure 2)

Figure 2

hinges
Air intake grille slide

Air intake grille


Pull out the air intake grille holding knobs

2. Removing the indoor controller board and the electrical box Photo 1
(1) Remove the air intake grille. (See Figure 1, 2) Beam
Beam fixing screws
(2) Remove the beam by removing screws. (See Photo 1)
(3) Remove 2 screws from the electrical cover, and remove
the electrical cover.
(4) Remove 2 screws from the electrical box and pull the
electrical box downward.
Temporarily secure the electrical box using 2 hooks in
the back of electrical box.
(5) Disconnect the connectors on the indoor controller
board.
Beam
fixing screw
[Removing the electrical box] Electrical cover
Electrical cover (4 × 8 PT)
(6) Disconnect the wires from the terminal blocks and pull fixing screws
out the electrical box. (See Photo 2) Photo 2
[Removing the indoor controller board]
(6) Remove the 6 supports from the indoor controller board
and remove the indoor controller board. (See Photo 3)

Electrical box
Electrical box fixing screws

Photo 3
Indoor controller
Room temperature board (I.B.) Reactor (DCL)
thermistor (TH1)

Terminal blocks
(TB4),(TB5)

OCH659 46
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
3. Removing the room temperature thermistor (TH1) Photo 4
(1) Remove the air intake grille. (See Figure 1, 2) Casing
(2) Remove the beam by removing screws. (See Photo 1)
(3) Remove 2 screws from the electrical cover, and remove
the electrical cover.
(4) Remove 2 screws from the electrical box and pull the Room temperature
electrical box downward. thermistor (TH1)
Temporarily secure the electrical box using 2 hooks in
the back of electrical box.
Electrical box
(5) Disconnect the connector CN20 (red) from the indoor
controller board.
(6) Remove the sensor holder from the electrical box and
remove the thermistor from the holder.

4. Removing the fan motor and right side fan Photo 5


(1) Remove the air intake grille. (See Figure 1, 2) Set screws
Fan guard fixing screws
(2) Remove the beam by removing screws. (See Photo 1)
(3) Remove 2 screws from the electrical cover, and remove
the electrical cover.
(4) Remove 2 screws from the electrical box and pull the Fan motor
electrical box downward.
(5) Temporarily secure the electrical box using 2 hooks in
the back of electrical box.
(6) Remove 4 screws fixing fan guard of the fan motor. (2
screws : See Photo 5 / 2 screws : Upper the electrical
box)
(7) Remove 2 screws fixing fan guard of piping side and
remove the fan guard. (See Photo 6)
(8) Remove the lower casing while pressing the 4 catches of
the casing (right side of the fan motor). Connecting Motor piece
joint fixing screws
(9) Loosen the 2 set screws (2 hexagon set screws) of con-
necting joint and slide the fan motor to the left. (See Photo 6
Photo 5) Catch
Fan guard fixing screws
(10) Remove the motor piece (left and right, each 1 screw).
(See Photo 5) Fan guard
(11) Remove the fan motor and right side fan together.
(12) Loosen the set screw (hexagon set screw) of fan and
remove the fan from the shaft. (See Photo 7, 8)
Catch

Photo 8

Photo 7
Hole for driver
Hexagon set screw

OCH659 47
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
5. Removing the fan (3 connection) Photo 9 Beam Fan guard
(1) Remove the air intake grille. (See Figure 1, 2)
(2) Remove the beam by removing screws. (See Photo 1)
(3) Remove 2 screws from the electrical cover, and remove
the electrical cover.
(4) Remove 2 screws from the electrical box and pull the
electrical box downward.
Temporarily secure the electrical box using 2 hooks in
the back of electrical box.
(5) Remove 4 screws from the fan guard of the fan motor.
(See Photo 5)
(6) Remove 2 screws from the left side beam and remove
the beam. (See Photo 1)
(7) Remove the 3 screws from center fan guard and remove
the fan guard. (2 screws : See Photo 9 / 1 screw : Drain
pan side)
(8) Remove 2 screws from the left fan guard and remove Fan guard Electrical box
the fan guard. (See Photo 10) Photo 10 fixing screws
(9) Loosen 2 set screws (2 hexagon set screws) of connect- Fan guard
ing joint. (See Photo 5) fixing screws
(10) Remove 3 lower casings while pressing each 4 catches
of the casing.
(11) Remove the 4 screws from the bearing support. (See
Photo 11)
(12) Slide the connecting joint to the left and remove the fans
and shaft together. (See Photo 12)
(13) Remove the fan from the shaft. (See Photo 7, 8)

Photo 12

Bearing support
Fans (3 connection) Photo 11

Bearing sup- Shaft


port fixing
screws

Bearing support Shaft

6. Removing the side panel Figure 3


(1) Remove the air intake grille. (See Figure 1, 2)
(2) Remove the screws from the side panel, and remove
Side panel
the side panel by sliding the panel to the front. (Right)
(3) Unhook the side panel support hanger, and then slide
the side panel forward to remove it.
Sliding the panel
to the front
Figure 4
Side panel
(Left)

Screws

Hole for side panel


support hanger Side panel
support hanger

OCH659 48
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
7. Removing the vane motor Photo 13
(1) Remove the air intake. (See Figure 1, 2)
(2) Remove the right side panel. (See Figure 3, 4) Connector
Vane motor and cover
(3) Remove the connector of vane motor.
(4) Remove 2 screws of vane motor cover , then remove
vane motor.

Screws

8. Removing the under panel Photo 14


(1) Remove the air intake grille. (See Figure 1, 2)
(2) Remove the left and right side panels. (See Figure 3, 4)
(3) Remove the beam. (See Photo 1)
(4) Remove the electrical cover. (See Photo 1)
(5) Pull the electrical box downward. (See Photo 2)
(6) (Wireless remote controller receiver type only)
Disconnect the connector CNB from the PCB for wire-
less remote controller and remove the clamp and strap
for wires.
(7) Remove 8 screws from the under panel. Under panel fixing
(8) Move the under panel forward by about 10mm and screws
remove the under panel.

9. Removing the drain pan Photo 15


(1) Remove the air intake grille. (See Figure 1,2)
(2) Remove the side panel (right and left). (See Figure 3, 4) Pipe cover fixing screws
(3) Remove the under panel. (See Photo 14)
Remove the screws of the right and left side drain pan.
(See Photo 15)
(4) Remove 2 insulation in center of the drain pan, and after
removing 2 screws with washer, remove the drain pan.
(See Photo 16,17)
Drain pan fixing
Note: screws
(left and right
Please be aware that there might be some drainage left in each 1 screw)
Drain pan
the drain pan when you remove the drain pan.

Photo 16
Vane Insulations

Photo 17

Screw with
washer
(2 locations)

OCH659 49
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
10. Removing the pipe temperature thermistors/liquid (TH2) Photo 18
and condenser/evaporator temperature thermistor (TH5).
(1) Remove the air intake grille. (See Figure 1, 2)
(2) Remove the left and right side panels. (See Figure 3,4)
(3) Remove the under panel. (See Photo 14)
(4) Remove the drain pan. (See Photo 15, 16, 17)
(5) Disconnect the connector CN44 (white) from the indoor
Pipe cover fixing
controller board. screws Pipe cover fix-
(6) Remove 6 screws from the pipe cover and remove the ing screws
pipe cover. (See Photo 15, 18) (See Photo 15)
(7) Remove the fastener for wires and remove the thermistors
(TH2 and TH5) from each holder. (See Photo 19) Pipe cover

Photo 19

Condenser/evaporator
tepmerature thermistor
(TH5)
Fastener

Pipe tempera-
ture thermistor/
liquid (TH2)

11. Removing the guide vane Photo 20


(1) Remove the intake grille. (See Figure 1, 2)
(2) Remove the side panel (right and left). (See Figure 3, 4) Screw
(3) Remove the under panel. (See Photo 14)
(4) Remove the drain pan. (See Photo 15,16,17)
(5) Remove the screw from the guide vane, then remove
the guide vane. Drain pan

Guide vane

12. Removing the Auto vane Photo 21


(1) Remove the intake grille. (See Figure 1, 2)
(2) Remove the right side panel. (See Figure 3, 4) Vane sleeve Vane support Vane
(3) Remove the vane motor and cover. (See Photo 13) Vane motor side
(4) Slide the auto vane to the vane motor side.
(5) Remove 2 axes from each vane support pushing the
vane support to the vane sleeve side.

OCH659 50
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
13. Removing the heat exchanger Photo 22
(1) Remove the air intake grille. (See Figure 1, 2)
(2) Remove the beam. (See Photo 1)
(3) Remove the electrical cover. (See Photo 1)
(4) Pull the electrical box downward. (See Photo 2)
(5) Remove the left and right side panels. (See Figure 3)
(6) Remove the under panel. (See Photo 14)
(7) Remove the drain pan. (See Photo 15,16,17) Heat exchanger
(8) Remove the pipe cover. (See Photo 18)
(9) Remove the pipe thermistors (TH2 and TH5) from each
holder. (See Photo 19)
(10) Remove the pipe band fixing screw and remove the Pipe band
pipe band. (See Photo 22)
(11) Remove 2 screws from the heat exchanger and
remove the heat exchanger.
Pipe band fixing
screw

Photo 23

Heat exchanger
fixing screws

Heat exchanger Vane

OCH659 51
HEAD OFFICE : TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

Copyright 2017 MITSUBISHI ELECTRIC CORPORATION


Published: Mar. 2017 No.OCH659
Made in Japan Specifications are subject to change without notice.

You might also like