Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
77404WS Multi-Conductor - 600V Shielded, Continous Flexing Applications Up to 14 Million Flex Life Cycles
For more Information
please call
1-800-Belden1
General Description:
14 AWG stranded (266x38) bare copper conductors, PVC insulation, oil-resistant PVC inner jacket, tinned
copper braid shield, 85% coverage, oil-resistant overall PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material Dia. (mm)
3 14 266x38 BC - Bare Copper 2.032
Total Number of Conductors: 4
Ground Wire
Ground Wire (Y/N): Y
Ground Wire AWG: 14
Ground Wire Stranding: 266x38
Ground Wire Conductor Material: BC - Bare Copper
Ground Wire Insulation Material: PVC - Polyvinyl Chloride
Insulation
Insulation Material:
Insulation Material Wall Thickness (mm) Dia. (mm)
PVC - Polyvinyl Chloride 0.559 3.150
Insulation Color Code Chart:
Color Description
Black Individually Numbered
Yellow/Green Ground
Inner Jacket
Inner Jacket Material:
Inner Jacket Material Nom Wall (mm) Nom. Dia. (mm)
PVC - Polyvinyl Chloride 0.889 10.008
Outer Shield
Outer Shield Material:
Outer Shield Material Coverage (%)
TC - Tinned Copper 85.000
Outer Shield Separator Material: Tissue Tape, 25% Overlap, Min.
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 1.270
Overall Cable
Overall Nominal Diameter: 13.411 mm
Mechanical Characteristics (Overall)
Storage Temperature Range: -40°C To +90°C
Installation Temperature Range: Flexing: -5°C To +90°C
Operating Temperature Range: Flexing: -5°C To +90°C
Bulk Cable Weight: 550.634 Kg/Km
Max. Recommended Pulling Tension: 649.437 N
Min. Bend Radius/Minor Axis: 106.680 mm
Min. Bend/Installation: 106.680 mm
Min. Bend Radius (Continuous Flexing): 106.680 mm
Flex Cycle Rating: 14 Million Flexes
Page 1 of 2 10-02-2017
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
77404WS Multi-Conductor - 600V Shielded, Continous Flexing Applications Up to 14 Million Flex Life Cycles
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: THHN/THWN Singles
AWM Specification: UL Style 2587 (600 V 90°C)
CSA Specification: 600 V AWM I/II A/B
EU Directive 2011/65/EU (ROHS II): Yes
Other Specification: AWM/STYLE 10012, AWM/STYLE 2587, AWM I/II A/B, FT1, VDE 0472, Section 803 Oil Test, EU Low
Voltage Directive 2014/35/EC, EU Directive 2011/65/EU(RoHS2), REACH Regulation (EC 1907/2006),
California Proposition 65
Flame Test
CSA Flame Test: FT1
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/m)
0.558
Nom. Capacitance Cond. to Other Cond. & Ground:
Description Freq. (kHz) Capacitance (pF/m)
Nom. Cond. to Cond 1.000 180.455
Nom. Ground. 1.000 324.819
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
8.203
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
6.693
Put Ups and Colors:
Item # Putup Ship Weight Color Notes Item Desc
Revision Number: 0 Revision Date: 09-27-2017
© 2017 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Page 2 of 2 10-02-2017