E5CC/E5CC-U Digital Temp Controller
E5CC/E5CC-U Digital Temp Controller
Control Output 1
Indication Accuracy
• Relay output
• Thermocouple input:
• Voltage output (for driving SSR)
±0.3% of PV
• Linear current output
• Pt input: ±0.2% of PV
• Analog input:
±0.2% of FS Control Output 2
<E5CC> <E5CC-U>
• None • None
Sampling Period • Voltage output
• 50 ms (for driving SSR)
Serial Communications
<E5CC> <E5CC-U>
• None • None
• RS-485
16
E5CC/E5CC-U
Model Number Legend and Standard Models
Model Number Legend
●Models with Screw Terminals
E5CC-@@ 3 @ 5 M -@@@ (Example: E5CC-RX3A5M-000)
−− − − − − −−−
A B C D E F
A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5CC 48 × 48 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*1 *3 CX Linear current output *2 None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
CQ Linear current output *2
(for driving SSR)
3 3 (one common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminals (with cover)
M Universal input
HB alarm and Event Remote Transfer
Communications
HS alarm inputs SP Input output
000 --- --- --- --- ---
*1 001 1 --- 2 --- ---
2
*1 003 (for 3-phase RS-485 --- --- ---
heaters)
*3 004 --- RS-485 2 --- ---
005 --- --- 4 --- ---
006 --- --- 2 Provided.
007 --- --- 2 Provided. ---
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The control output cannot be used as a transfer output.
*3. Option 004 can be selected only when "CX" is selected for the control outputs.
17
E5CC/E5CC-U
A B C D E F
Model Control No. of Power Meaning
Terminal Input
outputs auxiliary supply Options
type type
1 and 2 outputs voltage
E5CC 48 × 48 mm
Control output 1 Control output 2
RW Relay output (SPDT) None
QX Voltage output (for driving SSR) None
CX Linear current output* None
0 None
1 1
2 2 (one common)
A 100 to 240 VAC
D 24 VAC/DC
U Plug-in model
M Universal input
HB alarm and HS Communi- Remote SP Transfer out-
Event inputs
alarm cations Input put
000 --- --- --- --- ---
* The control output can be used as a simple transfer output for the Digital Temperature Controllers manufactured in May 2014 or later.
List of Models
Options Model Model
No. of auxiliary Power supply voltage Power supply voltage
Control output HB alarm and No. of event
outputs Communications
HS alarm inputs
100 to 240 VAC 24 VAC/DC
18
E5CC/E5CC-U
Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.
Waterproof Cover
Model
Y92A-48N
Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
19
E5CC/E5CC-U
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Models with option selection of 000: 5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or
Power consumption 1.6 W max. at 24 VDC
All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Sensor input
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to the
E5CC-U only for those manufactured in May 2014 or later.)
Current input: 150 Ω max., Voltage input: 1 MΩ min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
E5CC: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum ap-
plicable load: 5 V, 10 mA (reference value)
Relay output
E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applica-
Control ble load: 5 V, 10 mA (reference value)
output
Voltage output
Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
E5CC: 3
Number of outputs
E5CC-U: 1 or 2 (depends on model)
Auxiliary
output SPST-NO relay outputs, 250 VAC, Models with 1 or 2 outputs: 3 A (resistive load), or Models with 3
Output specifications outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at
5 V (reference value)
Number of inputs 2 or 4 (depends on model)
Event Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
input* External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output* Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000
Setting method Digital setting using front panel keys
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)
Remote SP input*
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)
11-segment digital display and individual indicators
Indication method
Character height: PV: 15.2 mm, SV: 7.1 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations,
Multi SP*
or serial communications.
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
Other functions filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, logic operations, temperature status display, simple programming, moving
average of input value, and display brightness setting
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting
Ambient operating temperature
(with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page 18.
20
E5CC/E5CC-U
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor
10 to 60 to 115 to 140 to
specifica- Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
tion
2300
2300
1800
1800
1700 1700
1700
1600
1500
Temperature range (°C)
1400
1300 1300 1300
1300
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.
●Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V 0 to 50 mV*
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29 30
* The range applies to the E5CC-U only for those manufactured in May 2014 or later.
21
E5CC/E5CC-U
Alarm Types
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Absolute-value upper-lim- ON
X
ON
X The alarm will turn ON if the process value is larger than the
8
it OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
ON
X
ON
X The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
Absolute-value upper-lim- ON
X
ON
X A standby sequence is added to the absolute-value upper-
10
it with standby sequence OFF
0
PV OFF
0
PV limit alarm (8). *6
Absolute-value lower-limit ON
X
ON
X A standby sequence is added to the absolute-value lower-
11
with standby sequence OFF
0
PV OFF
0
PV limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
14
upper-limit alarm OFF
0
SP OFF
0
SP is higher than the alarm value (X).
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
15
lower-limit alarm OFF
0
SP OFF
0
SP is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
X
RSP absolute-value ON
X ON This alarm type turns ON the alarm when the remote SP
18 OFF RSP
upper-limit alarm *10 OFF
0
RSP
0 (RSP) is higher than the alarm value (X).
RSP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the remote SP
19
lower-limit alarm *10 OFF
0
RSP OFF
0
RSP (RSP) is lower than the alarm value (X).
22
E5CC/E5CC-U
*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4 Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as “L” and “H.” For Upper- and Lower-Limit Alarm Described Above *2
*2 Set value: 1, Upper- and lower-limit alarm
• Case 1 and 2
Case 1 Case 2 Case 3 (Always ON)
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
H<0, L<0
SP L H H SP L • Case 3: Always OFF
L H SP
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L| *6 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H>0, L<0
H174) for information on the operation of the standby sequence.
SP H L |H| ≤ |L|
*7 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat.
*3 Set value: 4, Upper- and lower-limit range No.H174) for information on the loop burnout alarm (LBA).
Case 1 Case 2 Case 3 (Always OFF) *8 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H<0, L<0 H174) for information on the PV change rate alarm.
L H SP SP L H H SP L *9 When heating/cooling control is performed, the MV absolute upper limit
H<0, L>0 H>0, L<0 H<0, L>0 alarm functions only for the heating operation and the MV absolute lower
|H| < |L| |H| > |L| H L SP |H| ≥ |L| limit alarm functions only for the cooling operation.
*10 This value is displayed only when a remote SP input is used. It functions in
H>0, L<0 both Local SP Mode and Remote SP Mode.
SP H L |H| ≤ |L| Remote SP input is supported only for the E5CC.
23
E5CC/E5CC-U
Characteristics
E5CC
Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
Indication accuracy
CT input: ±5% FS ±1 digit max.
(at the ambient temperature of 23°C)
E5CC-U
Thermocouple: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
Transfer output accuracy ±0.3% FS max.
Remote SP Input Type ±0.2% FS ±1 digit max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit
max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2 Analog input: ±1%FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Remote SP input: ±1% FS ±1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Influence of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
E5CC: Controller: Approx. 120 g, Adapter: Approx. 10 g
Weight
E5CC-U: Controller: Approx. 100 g, Adapter: Approx. 10 g
E5CC: Front panel: IP66, Rear case: IP20, Terminals: IP00
Degree of protection
E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool E5CC: CX-Thermo version 4.5 or higher
E5CC-U: CX-Thermo version 4.61 or higher
E5CC/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB
Setup Tool port
port on the computer. *5
Approved standards UL 61010-1*6, KOSHA certified (some models) *7, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II, Lloyd's standards *8
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and
S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C,
whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100°C max.: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6 The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11
is not certified for UL listing.
*7 Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html
*8 Refer to information on maritime standards in Shipping Standards on page 106 for compliance with Lloyd's Standards.
24
E5CC/E5CC-U
You can use the memory in the PLC to read and 300
write E5@C parameters, start and stop operation,
etc. The E5@C automatically performs communi-
cations with PLCs. No communications program- 100
ming is required.
Number of connected Digital Temperature Con- 50
trollers: 32 max. (Up to 16 for the FX Series) 30
Applicable PLCs
Programless
OMRON PLCs
communications*1
CS Series, CJ Series, or 10
CP Series
Mitsubishi Electric PLCs 5
E5CC
MELSEC Q Series, L Series, or FX Series 3 250 VAC, 30 VDC
(compatible with the FX2 or FX3 (excluding (resistive load)
the FX1S)) cosφ = 1
KEYENCE PLCs 1
KEYENCE KV Series 0 1 2 3 4 5 6
Switching current (A)
25
E5CC/E5CC-U
External Connections
E5CC
Control output 1
Relay output
250 VAC, 3A
E5CC-@@ 3 @ 5 M - @ @ @
(resistive load) (1) (2) (3) (4) (5) (6)
Voltage output ↑
(for driving SSR) Auxiliary outputs 1, 2, 3 Terminal type
12 VDC, 21 mA Control output 2 Relay outputs
Linear current output Models with 3 auxiliary
0 to 20 mA DC Voltage output The E5CC is set for a K-type thermocouple (input type = 5) by
(for driving SSR) outputs: 250 VAC, 2 A default. An input error (s.err) will occur if the input type setting does
4 to 20 mA DC
Load: 500 Ω max. 12 VDC, 21 mA (resistive load) not agree with the temperature sensor. Check the input type.
1 13 7
2 14 8
3 15 9
(5) Sensor (Temperature/Analog) Input (3) Input Power Supply
4 16 10
TC Pt I V 100 to 240 VAC 24 VAC/DC
A + 4 5 17 11
4 4 4
B mA 6 18 12 11 11
- 5 5 5 - 5
B - V 12 12
+ 6 6 6
+
6
(no polarity)
(6) Options
001 003 004 005 006 007
Event Inputs 1 Communications Communications Event Inputs Event Inputs Event Inputs
and 2, and CT1 (RS-485), CT1, (RS-485), and 1 to 4 1 and 2, and 1 and 2, and
and CT2 Event Inputs 3 and 4 Transfer Output Remote SP Input
- B(+) B(+)
13 13 13 - 13 - 13 - 13
RS-485 RS-485
+
14 14 14 + 14 + 14 + 14
+ EV1 A(-) A(-) + EV1
+ EV1 + EV1
EV2 15 15 15 EV2
15 EV2
15 EV2
15
16 16 - 16 - 16 16 + + 16
CT1 CT1
+ + +V V +
17 COM 17 EV3
17 17 17 mA 17
CT2 + + EV3 I
18 18 EV4 18 EV4
18 18 - - 18
E5CC-U
Control output 1
Auxiliary output 1
I Auxiliary output 2:
Pt
+ A Control output (cooling side)
mA V TC
− − B
− V
+ + Input power supply
B
26
E5CC/E5CC-U
Relay output
Auxiliary outputs 1, 2, 3
: Reinforced insulation
: Functional isolation
• E5CC-U
Models with 2 Auxiliary Outputs
Sensor input
: Reinforced insulation
: Functional isolation
Nomenclature
E5CC Front panel
Temperature unit Top View of E5CC Top View of E5CC-U
E5CC-U
Operation indicators No. 1 display
PV or specified parameter
No. 2 display
27
E5CC/E5CC-U
Dimensions (Unit: mm)
Controllers
E5CC
73.1
4
60
48 × 48 1 48 × 48
Panel Cutout
Mounted Separately Group Mounted
(48 × number of units - 2.5)+1.0
0
E5CC-U 76.8
4 14.2
48 × 48 58.6 48 × 48
58
Mounting Adapter
(Accessory)
Panel Cutout
Mounted Separately Group Mounted
(48 × number of units - 2.5)+1.0
0
45+0.6
0
28
E5CC/E5CC-U
Accessories (Order Separately)
● USB-Serial Conversion Cable
E58-CIFQ2 (2110)
250 263 1510
LED (RD)
USB connector
(type A plug) Serial connector
LED (PWR)
LED (SD)
10
Terminal Cover
(E53-COV23)
22 44.8
9.1
34 Y92A-48G
UP 47.7×47.7 48×48
P C
16.5
24.6 27.6
47.4
Note: You can attach the P3GA-11 Back-connecting Socket for finger protection.
● Waterproof Packing The Waterproof Packing is provided only with the E5CC.
Y92S-P8 (for DIN 48 × 48) Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years as a rough standard.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.
29