Digital Temperature Controller

E5CC/E5CC-U (48 × 48 mm)

Large White PV Display That’s Easier to Read.


Easy to Use, from Model Selection to
Setup and Operation.
A Complete Range of I/O Capacities,
Functions, and Performance.
Handles More Applications.
• The white PV display with a height of 15.2 mm improves visibility.
• High-speed sampling at 50 ms. 48 × 48 mm 48 × 48 mm
E5CC E5CC-U
• Models are available with up to 3 auxiliary outputs, up to 4 event
inputs, a transfer output, and a remote SP input to cover a wide Refer to your OMRON website for the most recent information on
range of applications. applicable safety standards.

• E5CC: Short body with depth of only 60 mm.


• Set up the Controller without wiring the power supply by Refer to Safety Precautions on page 104.
connecting to the computer with a Communications Conversion
Cable (sold separately). Setup is easy with the CX-Thermo (sold
separately).
• Easy connections to a PLC with programless communications. Use component communications to link
Temperature Controllers to each other.

Main I/O Functions


Sensor Input E5CC/E5CC-U
Universal input
• Thermocouple
Dual displays: PV/SV 4-digit displays
• Pt
• Analog current/voltage

Control Output 1
Indication Accuracy
• Relay output
• Thermocouple input:
• Voltage output (for driving SSR)
±0.3% of PV
• Linear current output
• Pt input: ±0.2% of PV
• Analog input:
±0.2% of FS Control Output 2
<E5CC> <E5CC-U>
• None • None
Sampling Period • Voltage output
• 50 ms (for driving SSR)

Event Inputs Auxiliary Outputs


<E5CC> <E5CC-U> • PF (shift) Key <E5CC> <E5CC-U>
• None • None • Temperature status display •3 • None
•2 • Simple programming •1
•4 • Independent heating and •2
cooling PID control
Remote SP Input Transfer Output
• Changed parameter display
<E5CC> <E5CC-U> <E5CC> <E5CC-U>
• Display brightness setting
• None • None • None • None
•1 •1

Serial Communications
<E5CC> <E5CC-U>
• None • None
• RS-485

This datasheet is provided as a guideline for selecting products.


Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)
E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)

16
E5CC/E5CC-U
Model Number Legend and Standard Models
Model Number Legend
●Models with Screw Terminals
E5CC-@@ 3 @ 5 M -@@@ (Example: E5CC-RX3A5M-000)
−− − − − − −−−
A B C D E F

A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5CC 48 × 48 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*1 *3 CX Linear current output *2 None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
CQ Linear current output *2
(for driving SSR)
3 3 (one common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminals (with cover)
M Universal input
HB alarm and Event Remote Transfer
Communications
HS alarm inputs SP Input output
000 --- --- --- --- ---
*1 001 1 --- 2 --- ---
2
*1 003 (for 3-phase RS-485 --- --- ---
heaters)
*3 004 --- RS-485 2 --- ---
005 --- --- 4 --- ---
006 --- --- 2 Provided.
007 --- --- 2 Provided. ---
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The control output cannot be used as a transfer output.
*3. Option 004 can be selected only when "CX" is selected for the control outputs.

Heating and Cooling Control


● Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.

17
E5CC/E5CC-U

Model Number Legend


●Plug-in Models
E5CC-@@ @ @ U M -000 (Example: E5CC-RW0AUM-000)
A B C D E F

A B C D E F
Model Control No. of Power Meaning
Terminal Input
outputs auxiliary supply Options
type type
1 and 2 outputs voltage
E5CC 48 × 48 mm
Control output 1 Control output 2
RW Relay output (SPDT) None
QX Voltage output (for driving SSR) None
CX Linear current output* None
0 None
1 1
2 2 (one common)
A 100 to 240 VAC
D 24 VAC/DC
U Plug-in model
M Universal input
HB alarm and HS Communi- Remote SP Transfer out-
Event inputs
alarm cations Input put
000 --- --- --- --- ---
* The control output can be used as a simple transfer output for the Digital Temperature Controllers manufactured in May 2014 or later.

List of Models
Options Model Model
No. of auxiliary Power supply voltage Power supply voltage
Control output HB alarm and No. of event
outputs Communications
HS alarm inputs
100 to 240 VAC 24 VAC/DC

--- E5CC-RW0AUM-000 E5CC-RW0DUM-000


Relay output 1 --- --- --- E5CC-RW1AUM-000 E5CC-RW1DUM-000
2 E5CC-RW2AUM-000 E5CC-RW2DUM-000
--- E5CC-QX0AUM-000 E5CC-QX0DUM-000
Voltage output
1 --- --- --- E5CC-QX1AUM-000 E5CC-QX1DUM-000
(for driving SSR)
2 E5CC-QX2AUM-000 E5CC-QX2DUM-000
--- E5CC-CX0AUM-000 E5CC-CX0DUM-000
Linear current
1 --- --- --- E5CC-CX1AUM-000 E5CC-CX1DUM-000
output
2 E5CC-CX2AUM-000 E5CC-CX2DUM-000

Heating and Cooling Control


●Using Heating and Cooling Control
A Control Output Assignment
An auxiliary output is used as the cooling control output.
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.

18
E5CC/E5CC-U

Optional Products (Order Separately)


USB-Serial Conversion Cable Front Covers
Model Type Model
E58-CIFQ2 Hard Front Cover Y92A-48H
Soft Front Cover Y92A-48D
Terminal Covers (for E5CC)
Model CX-Thermo Support Software
E53-COV17 Model
E53-COV23 (3pcs) EST2-2C-MV4
Note: The Terminal Covers E53-COV23 are provided only with E5CC Note: CX-Thermo version 4.5 or higher is required for the E5CC.
Controllers. The E53-COV10 cannot be used. CX-Thermo version 4.61 or higher is required for the E5CC-U.
Refer to page 28 for the mounted dimensions. For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
Waterproof Packing (www.ia.omron.com).
Model
Y92S-P8
Note: The Waterproof Packing is provided only with E5CC
Controllers.
The E5CC-U cannot be waterproofed even if the Waterproof
Packing is attached.

Current Transformers (CTs)


Hole diameter Model
5.8 mm E54-CT1
12.0 mm E54-CT3

Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.

Waterproof Cover
Model
Y92A-48N

Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.

DIN Track Mounting Adapter


Model
Y92F-52

Sockets (for E5CC-U)


Type Model
Front-connecting Socket P2CF-11
Front-connecting Socket with Finger Protection P2CF-11-E
Back-connecting Socket P3GA-11
Terminal Cover for Back-connecting socket
Y92A-48G
with Finger Protection

19
E5CC/E5CC-U
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Models with option selection of 000: 5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or
Power consumption 1.6 W max. at 24 VDC
All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Sensor input
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to the
E5CC-U only for those manufactured in May 2014 or later.)
Current input: 150 Ω max., Voltage input: 1 MΩ min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
E5CC: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum ap-
plicable load: 5 V, 10 mA (reference value)
Relay output
E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applica-
Control ble load: 5 V, 10 mA (reference value)
output
Voltage output
Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
E5CC: 3
Number of outputs
E5CC-U: 1 or 2 (depends on model)
Auxiliary
output SPST-NO relay outputs, 250 VAC, Models with 1 or 2 outputs: 3 A (resistive load), or Models with 3
Output specifications outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at
5 V (reference value)
Number of inputs 2 or 4 (depends on model)
Event Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
input* External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output* Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000
Setting method Digital setting using front panel keys
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)
Remote SP input*
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)
11-segment digital display and individual indicators
Indication method
Character height: PV: 15.2 mm, SV: 7.1 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations,
Multi SP*
or serial communications.
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
Other functions filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, logic operations, temperature status display, simple programming, moving
average of input value, and display brightness setting
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting
Ambient operating temperature
(with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page 18.

20
E5CC/E5CC-U

Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor
10 to 60 to 115 to 140 to
specifica- Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
tion
2300
2300
1800
1800
1700 1700
1700
1600
1500
Temperature range (°C)

1400
1300 1300 1300
1300
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.

The applicable standards for the input types are as follows:


K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 JPt100: JIS C 1604-1989, JIS C 1606-1989
L: Fe-CuNi, DIN 43710-1985 Pt100: JIS C 1604-1997, IEC 60751
U: Cu-CuNi, DIN 43710-1985 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
W: W5Re/W26Re, ASTM E988-1990

●Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V 0 to 50 mV*
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29 30
* The range applies to the E5CC-U only for those manufactured in May 2014 or later.

21
E5CC/E5CC-U

Alarm Types
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.

Alarm output operation


Set Alarm type Description of function
value When alarm value X When alarm value X
is positive is negative
0 Alarm function OFF Output OFF No alarm
Set the upward deviation in the set point for the alarm upper
ON
L H limit (H) and the lower deviation in the set point for the alarm
1 Upper- and lower-limit *1 *2
OFF
SP
PV lower limit (L). The alarm is ON when the PV is outside this
deviation range.
Set the upward deviation in the set point by setting the alarm
2 ON
X
ON
X
Upper-limit value (X). The alarm is ON when the PV is higher than the
(default) OFF
SP
PV OFF
SP
PV
SP by the deviation or more.
X X Set the downward deviation in the set point by setting the
ON ON
3 Lower-limit OFF PV OFF PV alarm value (X). The alarm is ON when the PV is lower than
SP SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
Upper- and lower-limit ON
L H limit (H) and the lower deviation in the set point for the alarm
4 *3
range *1 OFF
SP
PV lower limit (L). The alarm is ON when the PV is inside this de-
viation range.
Upper- and lower-limit ON
L H A standby sequence is added to the upper- and lower-limit
5 *4
with standby sequence *1 *5 OFF
SP
PV alarm (1). *6
Upper-limit with standby ON
X
ON
X
6 A standby sequence is added to the upper-limit alarm (2). *6
sequence OFF
SP
PV OFF
SP
PV

Lower-limit with standby ON


X
ON
X
7 A standby sequence is added to the lower-limit alarm (3). *6
sequence OFF
SP
PV OFF
SP
PV

Absolute-value upper-lim- ON
X
ON
X The alarm will turn ON if the process value is larger than the
8
it OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
ON
X
ON
X The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
Absolute-value upper-lim- ON
X
ON
X A standby sequence is added to the absolute-value upper-
10
it with standby sequence OFF
0
PV OFF
0
PV limit alarm (8). *6
Absolute-value lower-limit ON
X
ON
X A standby sequence is added to the absolute-value lower-
11
with standby sequence OFF
0
PV OFF
0
PV limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
14
upper-limit alarm OFF
0
SP OFF
0
SP is higher than the alarm value (X).
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
15
lower-limit alarm OFF
0
SP OFF
0
SP is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
X
RSP absolute-value ON
X ON This alarm type turns ON the alarm when the remote SP
18 OFF RSP
upper-limit alarm *10 OFF
0
RSP
0 (RSP) is higher than the alarm value (X).
RSP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the remote SP
19
lower-limit alarm *10 OFF
0
RSP OFF
0
RSP (RSP) is lower than the alarm value (X).

22
E5CC/E5CC-U

*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4 Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as “L” and “H.” For Upper- and Lower-Limit Alarm Described Above *2
*2 Set value: 1, Upper- and lower-limit alarm
• Case 1 and 2
Case 1 Case 2 Case 3 (Always ON)
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
H<0, L<0
SP L H H SP L • Case 3: Always OFF
L H SP
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L| *6 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H>0, L<0
H174) for information on the operation of the standby sequence.
SP H L |H| ≤ |L|
*7 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat.
*3 Set value: 4, Upper- and lower-limit range No.H174) for information on the loop burnout alarm (LBA).
Case 1 Case 2 Case 3 (Always OFF) *8 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H<0, L<0 H174) for information on the PV change rate alarm.
L H SP SP L H H SP L *9 When heating/cooling control is performed, the MV absolute upper limit
H<0, L>0 H>0, L<0 H<0, L>0 alarm functions only for the heating operation and the MV absolute lower
|H| < |L| |H| > |L| H L SP |H| ≥ |L| limit alarm functions only for the cooling operation.
*10 This value is displayed only when a remote SP input is used. It functions in
H>0, L<0 both Local SP Mode and Remote SP Mode.
SP H L |H| ≤ |L| Remote SP input is supported only for the E5CC.

23
E5CC/E5CC-U

Characteristics
E5CC
Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
Indication accuracy
CT input: ±5% FS ±1 digit max.
(at the ambient temperature of 23°C)
E5CC-U
Thermocouple: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
Transfer output accuracy ±0.3% FS max.
Remote SP Input Type ±0.2% FS ±1 digit max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit
max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2 Analog input: ±1%FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Remote SP input: ±1% FS ±1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Influence of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
E5CC: Controller: Approx. 120 g, Adapter: Approx. 10 g
Weight
E5CC-U: Controller: Approx. 100 g, Adapter: Approx. 10 g
E5CC: Front panel: IP66, Rear case: IP20, Terminals: IP00
Degree of protection
E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool E5CC: CX-Thermo version 4.5 or higher
E5CC-U: CX-Thermo version 4.61 or higher
E5CC/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB
Setup Tool port
port on the computer. *5
Approved standards UL 61010-1*6, KOSHA certified (some models) *7, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II, Lloyd's standards *8
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and
S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C,
whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100°C max.: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6 The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11
is not certified for UL listing.
*7 Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html
*8 Refer to information on maritime standards in Shipping Standards on page 106 for compliance with Lloyd's Standards.

24
E5CC/E5CC-U

USB-Serial Conversion Cable When Digital Temperature Controllers are con-


nected, set points and RUN/STOP commands
Applicable OS Windows XP/Vista/7/8 can be sent from the Digital Temperature Control-
Component ler that is set as the master to the Digital Temper-
CX-Thermo version 4.5 or higher (Version 4.61 or Communications*1 ature Controllers that are set as slaves.
Applicable software
higher is required for the E5CC-U.) Slope and offsets can be set for the set point.
Applicable models E5@C-T Series, E5@C Series, and E5CB Series Number of connected Digital Temperature Con-
trollers: 32 max. (including master)
USB interface standard Conforms to USB Specification 2.0.
When Digital Temperature Controllers are con-
DTE speed 38400 bps nected, the parameters can be copied from the
Computer: USB (type A plug) Copying*2 Digital Temperature Controller that is set as the
Connector master to the Digital Temperature Controllers that
Digital Temperature Controller:
specifications are set as slaves.
Special serial connector
Power supply Bus power (Supplied from USB host controller.)* MELSEC is a registered trademark of Mitsubishi Electric Corporation.
Power supply voltage 5 VDC KEYENCE is a registered trademark of Keyence Corporation.
Current consumption 450 mA max. *1 A Temperature Controller with version 1.1 or higher is required.
4.7±0.2 VDC
A Temperature Controller with version 2.1 or higher is required for
Output voltage (Supplied from USB-Serial Conversion Cable to the FX Series or the KV Series.
the Digital Temperature Controller.) *2 Both the programless communications and the component
communications support the copying.
250 mA max.
Output current (Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.) Current Transformer (Order Separately)
Ambient operating
temperature
0 to 55°C (with no condensation or icing) Ratings
Ambient operating
10% to 80%
Dielectric strength 1,000 VAC for 1 min
humidity
Vibration resistance 50 Hz, 98 m/s2
Storage temperature -20 to 60°C (with no condensation or icing)
E54-CT1: Approx. 11.5 g,
Storage humidity 10% to 80% Weight
E54-CT3: Approx. 50 g
Altitude 2,000 m max.
Accessories Armatures (2)
Weight Approx. 120 g (E54-CT3 only) Plugs (2)
Windows is a registered trademark of Microsoft Corporation in the
United States and or other countries.
* Use a high-power port for the USB port.
Heater Burnout Alarms and SSR Failure
Note: A driver must be installed on the computer. Refer to the Alarms
Instruction Manual included with the Cable for the installation Models with detection for single-phase
procedure. CT input (for heater heaters: One input
current detection) Models with detection for singlephase or
Communications Specifications three-phase heaters: Two inputs
Transmission line Maximum heater
connection method
RS-485: Multidrop 50 A AC
current
Communications RS-485 (two-wire, half duplex) Input current
±5% FS ±1 digit max.
Synchronization
Start-stop synchronization indication accuracy
method
Heater burnout
Protocol CompoWay/F, or Modbus 0.1 to 49.9 A (in units of 0.1 A)
alarm setting range
Baud rate* 9600, 19200, 38400, or 57600 bps Minimum detection ON time: 100 ms *3
*1
Transmission code ASCII SSR failure alarm 0.1 to 49.9 A (in units of 0.1 A)
Data bit length* 7 or 8 bits setting range *2 Minimum detection OFF time: 100 ms *4
Stop bit length* 1 or 2 bits
*1 For heater burnout alarms, the heater current will be measured
Vertical parity (none, even, odd) when the control output is ON, and the output will turn ON if the
Error detection Block check character (BCC) with
CompoWay/F or CRC-16 Modbus heater current is lower than the set value (i.e., heater burnout
Flow control None
detection current value).
*2 For SSR failure alarms, the heater current will be measured when
Interface RS-485 the control output is OFF, and the output will turn ON if the heater
Retry function None current is higher than the set value (i.e., SSR failure detection
Communications buffer 217 bytes current value).
*3 The value is 30 ms for a control period of 0.1 s or 0.2 s.
Communications 0 to 99 ms *4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
response wait time Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
Electrical Life Expectancy Curve for
Relays (Reference Values)
Communications Functions 500
Life (× 104 operations)

You can use the memory in the PLC to read and 300
write E5@C parameters, start and stop operation,
etc. The E5@C automatically performs communi-
cations with PLCs. No communications program- 100
ming is required.
Number of connected Digital Temperature Con- 50
trollers: 32 max. (Up to 16 for the FX Series) 30
Applicable PLCs
Programless
OMRON PLCs
communications*1
CS Series, CJ Series, or 10
CP Series
Mitsubishi Electric PLCs 5
E5CC
MELSEC Q Series, L Series, or FX Series 3 250 VAC, 30 VDC
(compatible with the FX2 or FX3 (excluding (resistive load)
the FX1S)) cosφ = 1
KEYENCE PLCs 1
KEYENCE KV Series 0 1 2 3 4 5 6
Switching current (A)

25
E5CC/E5CC-U
External Connections
E5CC
Control output 1
Relay output
250 VAC, 3A
E5CC-@@ 3 @ 5 M - @ @ @
(resistive load) (1) (2) (3) (4) (5) (6)
Voltage output ↑
(for driving SSR) Auxiliary outputs 1, 2, 3 Terminal type
12 VDC, 21 mA Control output 2 Relay outputs
Linear current output Models with 3 auxiliary
0 to 20 mA DC Voltage output The E5CC is set for a K-type thermocouple (input type = 5) by
(for driving SSR) outputs: 250 VAC, 2 A default. An input error (s.err) will occur if the input type setting does
4 to 20 mA DC
Load: 500 Ω max. 12 VDC, 21 mA (resistive load) not agree with the temperature sensor. Check the input type.

(1) Control outputs 1, 2


RX QX CX QQ CQ
Models with Models with 1 Models with Models with 2 Models with 2 Outputs: Linear Current (2) Auxiliary Outputs
1 Relay Voltage Output 1 Linear Voltage Outputs Output and Voltage (for Driving SSR) Auxiliary outputs 1, 2, 3
Output (for Driving SSR) Current Output (for Driving SSR)
OUT1 1 OUT1 OUT1 1 OUT1 1 OUT1 7
1 + 1 + +Q +C Auxiliary output 3
R - Q - C 2 2 8
2 2 2 - Q - Q Auxiliary output 2
3 3 3 3 + OUT2 3 + OUT2 9
Auxiliary output 1
10 ● ●

1 13 7
2 14 8
3 15 9
(5) Sensor (Temperature/Analog) Input (3) Input Power Supply
4 16 10
TC Pt I V 100 to 240 VAC 24 VAC/DC
A + 4 5 17 11
4 4 4
B mA 6 18 12 11 11
- 5 5 5 - 5
B - V 12 12
+ 6 6 6
+
6
(no polarity)
(6) Options
001 003 004 005 006 007
Event Inputs 1 Communications Communications Event Inputs Event Inputs Event Inputs
and 2, and CT1 (RS-485), CT1, (RS-485), and 1 to 4 1 and 2, and 1 and 2, and
and CT2 Event Inputs 3 and 4 Transfer Output Remote SP Input
- B(+) B(+)
13 13 13 - 13 - 13 - 13
RS-485 RS-485
+
14 14 14 + 14 + 14 + 14
+ EV1 A(-) A(-) + EV1
+ EV1 + EV1
EV2 15 15 15 EV2
15 EV2
15 EV2
15
16 16 - 16 - 16 16 + + 16
CT1 CT1
+ + +V V +
17 COM 17 EV3
17 17 17 mA 17
CT2 + + EV3 I
18 18 EV4 18 EV4
18 18 - - 18

E5CC-U

The E5CC-U is set for a K-type thermocouple (input type =


E5CC-UM-000
5) by default. An input error (s.err) will occur if the input Control output 1
type setting does not agree with the temperature sensor.
Check the input type. Auxiliary outputs 1, 2
Relay output
250 VAC, 3 A (resistive load)

Control output 1
Auxiliary output 1
I Auxiliary output 2:
Pt
+ A Control output (cooling side)
mA V TC
− − B
− V
+ + Input power supply
B

Sensor (temperature/analog) input • 100 to 240 VAC


• 24 VAC/DC (no polarity)
Control output 1
Voltage output (for driving SSR) Control output 1:
12 VDC, 21 mA QX CX RW
Linear current output Models with 1 Models with 1 Models with 1
4 to 20 mA DC Voltage Output Linear Current Relay Output
0 to 20 mA DC (for Driving SSR) Output
Load: 500 Ω max. − − Output 1
Relay output (three terminals used) Output 1 Output 1 R
SPDT, 250 VAC, 3 A Q C
(resistive load) + +

Note: 1. The application of the terminals depends on the model.


2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.
Connect M3.5 crimped terminals for the E5CC-U.

26
E5CC/E5CC-U

Isolation/Insulation Block Diagrams


• E5CC
Models with 3 Auxiliary Outputs

Sensor input, CT inputs, and remote SP input

Communications and event inputs

Power Voltage output (for driving SSR),


supply linear current output, and transfer output

Relay output

Auxiliary outputs 1, 2, 3

: Reinforced insulation

: Functional isolation

Note: Auxiliary outputs 1 to 3 are not insulated.

• E5CC-U
Models with 2 Auxiliary Outputs

Sensor input

Voltage output (for driving SSR) and linear current output


Power
supply
Relay output

Auxiliary outputs 1 and 2

: Reinforced insulation

: Functional isolation

Nomenclature
E5CC Front panel
Temperature unit Top View of E5CC Top View of E5CC-U
E5CC-U
Operation indicators No. 1 display

PV or specified parameter

No. 2 display

SP or specified parameter value

Use the U D Keys to set the


parameter.

Top-panel Setup Tool port


Press O Key once to go to Adjustment Level.
Use S Key to change the digit (default setting).
Press O Key for at least 3 seconds to go to Initial Setting Level.
Use the M Key to change to another parameter.

27
E5CC/E5CC-U
Dimensions (Unit: mm)

Controllers
E5CC
73.1
4
60
48 × 48 1 48 × 48

44.8 × 44.8 48.8 58

Waterproof Packing Mounting Adapter


(Accessory) (Accessory)
Terminal Cover
(E53-COV17)
(Sold separately)
The Setup Tool port is on the top of the Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

Panel Cutout
Mounted Separately Group Mounted
(48 × number of units - 2.5)+1.0
0

• Recommended panel thickness is 1 to 5 mm.


45+0.6
0 • Group mounting is not possible in the vertical direction. (Maintain
the specified mounting space between Controllers.)
60 min. • To mount the Controller so that it is waterproof, insert the
waterproof packing onto the Controller.
• When two or more Controllers are mounted, make sure that the
45+0.6
0
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
45+0.6
• Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a
0
USB-Serial Conversion Cable are used together.

E5CC-U 76.8
4 14.2
48 × 48 58.6 48 × 48

58

Mounting Adapter
(Accessory)

The Setup Tool port is on the top of the Temperature Controller.


It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

Panel Cutout
Mounted Separately Group Mounted
(48 × number of units - 2.5)+1.0
0

• Recommended panel thickness is 1 to 5 mm.


45+0.6
0 • Group mounting is not possible in the vertical direction. (Maintain
the specified mounting space between Controllers.)
60 min.
• When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
45+0.6
0 • Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a
USB-Serial Conversion Cable are used together.

45+0.6
0

28
E5CC/E5CC-U
Accessories (Order Separately)
● USB-Serial Conversion Cable
E58-CIFQ2 (2110)
250 263 1510

LED (RD)

USB connector
(type A plug) Serial connector
LED (PWR)

LED (SD)

● Terminal Covers 48 ● Terminal Covers


E53-COV17 E53-COV23 (Three Covers provided.)
2 3.8
48.8

10

Terminal Cover
(E53-COV23)
22 44.8

9.1

● Terminal Cover (for the P3GA-11 Back-connecting Socket)


Y92A-48G
Twelve, 6.4-dia.

34 Y92A-48G
UP 47.7×47.7 48×48

P C

16.5
24.6 27.6

47.4

Note: You can attach the P3GA-11 Back-connecting Socket for finger protection.

● Waterproof Packing The Waterproof Packing is provided only with the E5CC.
Y92S-P8 (for DIN 48 × 48) Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years as a rough standard.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.

29