Signature Not Verified: Digitally Signed by Kushal Dev Pandey Date: 2025.01.25 21:12:09 IST Reason: Sign IC Location

The document is an inspection certificate issued by Bureau Veritas India for a cable product supplied by M/s Veena Enterprises. The inspection confirmed that 1154 meters of the offered 1164 meters of cable passed the required tests, with satisfactory results noted for various quality checks. The certificate is valid for 30 days from the issue date and outlines specific details regarding the inspection process and vendor obligations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views2 pages

Signature Not Verified: Digitally Signed by Kushal Dev Pandey Date: 2025.01.25 21:12:09 IST Reason: Sign IC Location

The document is an inspection certificate issued by Bureau Veritas India for a cable product supplied by M/s Veena Enterprises. The inspection confirmed that 1154 meters of the offered 1164 meters of cable passed the required tests, with satisfactory results noted for various quality checks. The certificate is valid for 30 days from the issue date and outlines specific details regarding the inspection process and vendor obligations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Signature Not BUREAU VERITAS INDIA PRIVATE LIMITED-MUMBAI

Verified
(North)
Digitally signed by
KUSHAL DEV िनरी ण माण प
PANDEY
Date: 2025.01.25 INSPECTION CERTIFICATE
[Link] IST
Reason: Sign IC
Location:
Certificate No.: 5739209 Dated: 26/01/2025

Call Details: Call ID No.: 4090592903 dated 05/01/2025 IC Count No.: 2 (For PO Sl. No. 002)
PO Number: 41241509106747 Dated: 13/12/2024
Consignee: PUNE PO Serial Number: 002
Product - Final Product
PO Placed by: Central Railway Stage:
Inspection
Item Code / PL No- 40077603
Description of Final CABLE 16 SQ. MM, SIZE 126/0.4 MM UPTO INCLUDING 1100 VOLTS, COPPER CONDUCTOR, FLEXIBLE SINGLE CORE,
Product: PVC INSULATED, UNSHEATHED, CONFORMING TO RDSO SPECIFICATION No. RDSO/SPEC/PE/TL/0027-2002 [REV-0]
AMND. 1, COLOUR - BLACK. MAKE / BRAND : VEDANTA

Firm’s Name: M/s VEENA ENTERPRISES-EAST DELHI


Firm’s Regd.
A-6/B & A-6/C, SECOND FLOOR JHILMIL INDUSTRIAL AREA, EAST DELHI, Delhi - 110095
Address:
Second Floor of A-6B AND Secound Floor oF A-6/C ,JHILMIL INDUSTRIAL AREA ,DELHI-110095, DELHI, Delhi - 110095
Place of Inspection:
(India)
Inspection carried
Final Product as per the Product description mentioned above
out for:

Inspecting Engineer KUSHAL DEV PANDEY GM/QA ARUN KUMAR CHOUDHARY


Scheduled Date of Inspection 11/01/2025 to 22/01/2025 Delivery Date 14/03/2025

Actual Visit Details


Actual Visit Date 11/01/2025 No. of Visits 3

Inspection Quantity Details

Order Qty
Qty Offered Qty not due Qty Passed Qty Rejected Qty Consumed in Testing
(as per call)
1164 MTR 1164 MTR 0 MTR 1154 MTR 0 MTR 10 MTR
* Quantity Passed does not include the quantity consumed in testing

General Remarks
Inspection Date: - 11 To 12/01/2025 And 22/01/[Link] Documents PO, RDSO Spec. No. RDSO/PE/SPEC/TL/0027 - 2002 (Rev -0),
Amndt No. 1 . Following Acceptance Test Carried Out On Selected Sample Of 5 Coils Of Cable 16 Sq. Mm, Size 126/0.4 Mm Upto Includin
g 1100 Volts, Copper Conductor, Flexible Single Core, Pvc Insulated, Unsheathed, Bearing Coil No.: 5, 29, 44, 51 And 54 Out Of Offered 5
6 Coils. Cable 16 Sq. Mm, Size 126/0.4 Mm Upto Including 1100 Volts, Copper Conductor, Flexible Single Core, Pvc Insulated, Unsheathe
d, Considers As A Single Lot For The Inspection Further Distributed Two Inspection Certificates (4440 Meter And 1154 Meter = Total 559
4 Meter) As Per Applicable Spec And IS As Follow:-Visual Examination, Dimension Check, Conductor Resistance Test, Thickness Of Insula
tion, TS & Elongation, Marking, Thermal Stability, Water Immersion Test, Cable Identification, IR/VR Test, HV Test, Flammability Test. Inte
rnal , RMTC, BIS License & Calibration Certificate Reviewed And Found In Order. Results Of Inspection Found Satisfactory.

Remarks for destructive testing

Quantity offered- 1164 Meter, Quantity consumed in testing-10 Meter, Quantity Passed- 1154 Meter.

Hologram / Identification Details of the goods inspected

Bureau Veritas Hologram having Hologram number In- Between Sr No :- 6582436 to 6582491 placed on Joint of tape wrapped around coi
l.

Uploaded Documents

# Document Category Description File Name


1 Others CALIBRATION [Link]
2 Others INTERNAL TEST INTERNAL TEST [Link]
3 Others offer and packing list warranty offer packing list [Link]
4 Others MATERIAL INVOICE AND TC [Link]
5 Others PHOTO SHEET PHOTO SHEET [Link]
6 Inspection Plan INSPECTION SCHEME INSPECTION [Link]
7 Inspection Seal Image (PDF) SEAL PHOTO [Link]
8 Sample Test Report sample test report SAMPLE TEST [Link]

Created & Digitally Signed by:


KUSHAL DEV PANDEY
(Inspecting Engineer)
Page 1/2
(Inspecting Engineer)
For & on behalf of BUREAU VERITAS INDIA PRIVATE LIMITED-MUMBAI

Notes:
1. This Inspection certificate shall be valid for a period of 30 days from issue date.

Previous IC Details (for same PO Serial Number)

Stage Installment No IC No IC Date Qty Offered Qty Passed Qty Rejected Qty Consumed
Stage 1 Inspection 1 6698196 31/12/2024 1164 1164 0 10.0

Remarks for Vendors: The vendor will submit the despatch particulars for this consignment to the consignee through E-Despatch
functionality in Goods & Services module of IREPS.

Remarks for Accounts Department: The Inspection Charges payable against this certificate will be paid through online bill generated
through IREPS-TPI module only. No payment against inspection charges shall be made against this IC through manual or offline mode or
through the online bills received from RITES IBS system through backend integration with IMMS.