VLT2800 Handbuch E
VLT2800 Handbuch E
■ Contents
Installation ........................................................................................................... 5
Mechanical dimensions ............................................................................................ 5
Mechanical installation .............................................................................................. 9
General information about electrical installation ...................................................... 10
EMC-correct electrical installation ........................................................................... 11
Grounding of shielded/armoured control cables ..................................................... 12
Diagram ................................................................................................................. 13
Electrical installation ............................................................................................... 14
Safety clamp .......................................................................................................... 16
Input fuses ............................................................................................................. 16
AC line connection ................................................................................................. 16
Motor connection ................................................................................................... 16
Direction of motor rotation ...................................................................................... 16
Motor thermal protection ........................................................................................ 16
Parallel connection of motors ................................................................................. 17
Motor cables .......................................................................................................... 17
Brake connection ................................................................................................... 17
Ground connection ................................................................................................ 17
Load sharing .......................................................................................................... 18
Tightening Torque, Power Terminals ....................................................................... 18
Calculation of brake resistance ............................................................................... 18
Access to control terminals .................................................................................... 18
Electrical installation, control circuitry ...................................................................... 18
Tightening torques, control cables .......................................................................... 20
Electrical installation, control terminals .................................................................... 20
Relay connection .................................................................................................... 20
VLT Software Dialog ............................................................................................... 21
Connection examples ............................................................................................. 22
Control unit ............................................................................................................ 24
Manual initialization ................................................................................................. 24
Programming the adjustable frequency drive .......................................................... 25
Display readout ...................................................................................................... 27
Hand / Auto mode operation .................................................................................. 27
Warnings/alarms .................................................................................................... 28
Special conditions .................................................................................................. 29
Temperature-related switching frequency ............................................................... 29
Derating for long motor cables .............................................................................. 29
VLT 2800 start-up .................................................................................................. 29
Programming .................................................................................................... 31
195NA009.17
Introduction to VLT
VLT 2800 Series
2800
Instruction Manual
Software version: 2.7x
This Instruction Manual can be used for all VLT 2800 Series
adjustable frequency drives (AFD) with software version 2.7x.
The software version number can be seen from parameter
640 Software Version.
NOTE
Indicates something to be noted by the reader.
Warning:
It can be extremely dangerous to touch the electrical parts
even when the mains supply has been disconnected.
Also ensure that other voltage inputs are disconnected
from load sharing through the DC bus.
Wait at least 4 minutes after the input power has been
removed before servicing the drive.
195NA139.10
■ Mechanical dimensions
The drawings below give the mechanical dimensions. The drawing below gives the mechanical dimensions of
All dimensions are in mm. VLT 2840 (5 HP) 200-240 Volt and VLT 2855-2875 (7 -
10HP) 380-480 Volt. All dimensions are in inches.
VLT 2803-2815 200-240 Volt
VLT 2805-2815 380-480 Volt VLT 2840 200-240 Volt
VLT 2855-2875 380-480 Volt
Installation
The drawing below gives the mechanical dimensions of
VLT 2822 (3 HP) 200-240 Volts and VLT 2822-2840 (3
- 5 HP) 380-480 Volts. All dimensions are in inches.
■ IP 21 solution
Dimensions
Installation
■ EMC filter for long motor cables
192H4719
192H4720
192H4893
Installation
■ Enclosures
In the USA and some other countries, a NEMA 1
terminal cover enclosing terminal connectors is required
if the drive is not installed within another enclosure.
NOTE
It is the responsibility of the user or installer
to ensure correct grounding and protection in
accordance with national and local standards.
■ Grounding
Comply with the following at installation:
Installation
1. Correct grounding
Control cables and cables for serial
communication must be attached with cable
clamps at both ends to ensure maximum
possible electrical contact.
2. Incorrect grounding
Do not use twisted shield ends that are
plaited together (pigtails), as these increase shield
impedance at higher frequencies.
3. Protection with respect to ground
potential between PLC and VLT
f the ground potential between the VLT
variable frequency drive and the PLC (etc.)
is different, electric noise may occur that will
disturb the whole system. This problem can
be solved by fitting an equalising cable, to be
placed next to the control cable. Minimum cable
cross-section: 6 AWG (16 mm2).
4. n the event of a 50/60 Hz ground loop
If very long control cables are used, 50/60 Hz
ground loops can arise, and these can interfere
with the whole system. This problem is resolved
by attaching one end of the shield to the ground
via a 100 nF capacitor (short pin length).
■ Diagram
Installation
* Integrated 1A RFI filter and brake is an option.
** VLT 2803-2815 200-240 V is not supplied
with intermediate circuit coils.
■ Electrical installation
Installation
VLT 2840 200-240 V, 2855-2875 380-480 V
Installation
these spoil the shielding effect at high frequencies. If
it is necessary to break the shield to install a motor
The adjustable frequency drive is able to control isolator or motor relay, the shield must be continued
several motors connected in parallel. The combined at the lowest possible HF impedance.
total current consumption of the motors is not to
exceed the maximum rated output current (IINV) for
the adjustable frequency drive. If the motors are to
have different rpm values, use motors with different ■ Brake connection
rated rpm values. Motor frequency is changed
NOTE
simultaneously, which means that the ratio between
Voltages up to 850 VDC occur on the terminals.
the rated rpm values is maintained.
even further, a Recidual Current Device (RCD) can be This requires that the installation is extended using
fitted to ensure that the adjustable frequency drive extra fuses and AC coils (see drawing below).
cuts out when the leakage currents get too high. Also For load sharing parameter 400 Brake function
see RCD Application note [Link].02. must be set to Load sharing [5].
Use 6.3 mm Faston Plugs for DC (Load Sharing).
Contact Danfoss or see instructions no. [Link].02
for further information.
■ Load sharing
Load sharing provides the facility to connect several No. 88 89 Loadsharing
frequency converters’ DC intermediate circuits. - +
Note that voltage levels of up to 850 V DC motor current exceeds the preset value in parameter
may occur between terminals 88 and 89. 140. When stopping the brake is engaged when the
output frequency is less than the brake engaging
frequency, which is set in par. 139.
If the variable frequency drive is placed at alarm
■ Tightening Torque, Power Terminals status or in an overvoltage situation the mechanical
Power and ground terminals must be tightened brake is cut in immediately.
with the following torques:
NOTE
VLT Terminals Torque [Nm] This application is only for lifting/lowering
2803- Power line brake 0.5-0.6 without a counterbalance.
{new- Ground 2-3
line/}2875
2880- Power line brake 1.2-1.5 ■ Access to control terminals
{new- Ground 2-3
All control terminals are located underneath the
line/}2882 protective plate on the front of the adjustable
frequency drive. Remove the protective plate by
sliding it downwards (see drawing).
■ Electrical installation, control circuitry Control wires must be shielded/armored. Connect the
shield to the drive chassis with a clamp. Normally,
NOTE the shield must also be connected to the chassis of
Using unshielded/unarmored cable may not the controlling device. (See the instructions for the
comply with some EMI/RFI requirements. specific device.) In analog signals or connections using
very long wires, 50/60 Hz ground loops may occur
because of noise transmitted from the AC line. It may
be necessary to break the shield and insert a 100 µF
capacitor between the shield and the chassis.
Installation
No. Function
01-03 Relay outputs 01-03 can be used for
indicating status and alarms/warnings.
12 24 VDC voltage supply.
18-33 Digital inputs.
20, 55 Common frame for input
and output terminals.
42 Analog output for displaying frequency, ■ Profibus DIP switches setting
reference, current or torque.
461 Digital output for displaying status,
warnings or alarms, as well as
frequency output. The dip switch is only on the control card with Profibus
50 +10 VDC supply DP communication. The switch position shown is the
voltage for potentiometer or thermistor. factory setting. Switches 1 and 2 are used as cable
53 Analog voltage input 0 - 10 V DC.
termination for the RS-485 interface. If the adjustable
60 Analog current input 0/4 - 20 mA.
frequency drive is located as the first or last (or only)
671 + 5 VDC supply voltage
unit in the bus system, switches 1 and 2 must be ON.
to Profibus.
On the remaining adjustable frequency drives, switches
68, RS-485, Serial communication.
1 and 2 must be OFF. Switches 3 and 4 are not applied.
691
701 Frame for terminals 67, 68 and 69.
Normally this terminal is not to be used.
■ Sub D plug
Installation
plug on the control card. Ordering number: 175N0131.
LCP control units with ordering number 175Z0401
are not to be connected.
■ Connection examples
■ Speed up/slow down
■ Start/stop Speed up/slow down using terminals 29/33.
Start/stop using terminal 18 and coasting
stop using terminal 27.
For Precise start/stop the following settings are made: ■ Potentiometer reference
Par. 302 Digital input = Precise start/stop [27] Voltage reference via a potentiometer.
Par. 304 Digital input = Coasting stop inverted [2]
■ Pulse start/stop
Pulse start using terminal 18 and pulse stop
using terminal 19. In addition, the jog frequency
is activated via terminal 29.
Installation
■ Control unit The [CHANGE DATA] key is also used for confirming
On the front of the variable frequency drive a change of parameter settings.
there is a control panel.
[+] / [-] are used for selecting parameters and
for changing parameter values.
These keys are also used in Display mode for selecting
the display of an operating value.
NOTE
If the [STOP/RESET] key is set at Not active
[0] in parameter 014 Local stop/reset,and
there is no stop command via the digital
inputs or serial communication, the motor can
The control panel is divided into five functional groups: only be stopped by disconnecting the electrical
1. Status LED voltage to the variable frequency drive.
2. Keys for changing parameters and shifting
display function. [START] is used for starting the variable frequency
3. LEDs. drive. It is always active, but the [START] key
4. Keys for local operation. cannot override a stop command.
■ Control keys
[QUICK MENU] allows access to the parameters
used for the Quick menu.
The[QUICK MENU] key is also used if a change to a
parameter value is not to be implemented.
See also [QUICK MENU] + [+].
■ Data readout:
Display mode
In normal operation, one item of operating data can The display shows that in parameter 128 Motor thermal
be displayed continuously at the operator’s own protection the selection made is Thermistor trip [2].
choice. By means of the [+/-] keys the following
Quick menu
options can be selected in Display mode:
- Output frequency[Hz]
- Output current [A]
- Output voltage [V]
- Intermediate circuit voltage [V] Using the [QUICK MENU] key, it is possible to access
- Output power [kW] the 12 most important parameters of the variable
- Scaled output frequency fout x p008 frequency drive. After programming, the variable
frequency drive is in most cases ready for operation.
Menu mode
When the [QUICK MENU] key is activated in Display
Installation
mode, the Quick menu starts. Scroll through the quick
menu using the [+/-] keys and change the data values
by first pressing [CHANGE DATA] and then changing
the parameter value with the [+/-] keys.
The Quick menu parameters are:
In order to enter the Menu mode [QUICK MENU] + • Par. 102 Motor power PM,N
[+] must be activated at the same time. • Par. 103 Motor voltage UM,N
In Menu mode, most of the variable frequency drive • Par. 104 Motor frequency fM,N
parameters can be changed. Scroll through the • Par. 105 Motor current IM,N
parameters using the [+/-] keys. While scrolling in the • Par. 106 Rated motor speed nM,N
Menu mode proceeds, the parameter number will flash. • Par. 107 Automatic motor adaption
• Par. 204 Minimum reference RefMIN
• Par. 205 Maximum reference RefMAX
• Par. 207 Ramp-up time
• Par. 208 Ramp-down time
• Par. 002 Local/remote operation
• Par. 003 Local reference
The display shows that the setting in parameter
102 Motor power PM,N is 0.75. In order to change Parameter 102 - 106 can be read out from
the value of 0.75, [CHANGE DATA] must first the motor’s nameplate.
be activated; the parameter value can then be
changed using the [+/-] keys.
Programming the adjustable frequency drive
NOTE
The motor must be stopped to change
parameter data.
If for a given parameter the display shows three Program the drive in accordance with the
dots at the right, it means that the parameter following procedure:
value has more than three digits. In order to see 1. Press the [QUICK MENU] key to enter
the value, activate [CHANGE DATA]. the Quick menu.
2. Scroll through the Quick menu using the 7. "107" will then continue to flash with the data
[+] and [-] keys. value [0]. Press [QUICK MENU] to exit Menu
3. Change the data values by first pressing mode and enter Display mode.
[CHANGE DATA] key
4. and then change the parameter value with
the [+] and [-] keys.
5. Press [CHANGE DATA] again to accept the change
or [QUICK MENU] to cancel the change. Press
[QUICK MENU] once more to exit Quick menu
mode and enter Display mode. (The drive will
default from Quick menu mode to Display mode
in 2 minutes if no activity has taken place.)
NOTE
Enter parameters 102 through 106 data, at
minimum, to ready the drive for operation.
Data for parameters 102 through 106 can
be read from the motor nameplate.
■ Display readout
Fr
■ Hand / Auto mode operation
The variable frequency drive shows the present
During Auto mode operation, the adjustable frequency
output frequency in Hertz [Hz].
drive receives an external reference through the control
Io terminals as analog or digital signals. In Auto mode, use
The variable frequency drive shows the present the [+] and [-] keys to scroll through the display of drive
output current in Amps [A]. status messages. In Hand mode, it is possible to control
the speed of the drive locally through the keypad.
Uo
The variable frequency drive shows the present On the control terminals, the following control signals
output voltage in Volt [V]. will remain active when Hand mode is activated:
• Hand Start (LCP2)
Ud • Off Stop (LCP2)
The variable frequency drive shows the intermediate • Auto Start (LCP2)
circuit voltage in Volt [V]. • Reset
• Coasting Stop Inverse
Po
• Reset and Coasting Stop Inverse
The variable frequency drive shows the calculated
• Quick Stop Inverse
output in kilowatt [kW].
Installation
• Stop Inverse
notrun • Reversing
This message is shown if an attempt is made to change • DC Braking Inverse
a parameter value while the motor is running. Stop • Setup Select LSB
the motor to change the parameter value. • Setup Select MSB
• Thermistor
LCP • Precise Stop Inverse
This message is shown if an LCP 2 control unit is • Precise Stop/Start
fitted and the [QUICK MENU] or [CHANGE DATA] • Jog
key is activated. If an LCP 2 control unit is fitted • Stop Command Via Serial Comm.
you can only change parameters with that.
Switching between Auto and Hand mode:
Ha To switch between operational modes, press
The variable frequency drive shows the present Hand the [Change Data] key. The display will indicate
mode reference frequency in Herz (Hz). the current mode of operation.
SC
The variable frequency drive shows scaled
output frequency (the present output frequency
x parameter 008). Use the [+] and [-] keys to toggle between Hand
and Auto mode. Press the [Change Data] key
again to activate the selected mode, otherwise
the mode displayed will take effect automatically
in about three seconds.
In Hand mode, the [+] and [-] keys are also used to
toggle through status messages. Press and hold the
[Change Data] key for approximately 3 seconds. When
the display begins to flash, use the [+] and [-] keys
to change the drive status display. The displays are
temporary and will default back to output frequency.
NOTE
Parameter 020 can be used to disable
Hand mode operation.
■ Warnings/alarms
Warnings or alarms appear in the LED display as a
numerical code [Err. xx]. A warning is displayed until
the fault has been corrected, while an alarm will flash
until the [STOP/RESET] key is pressed. The table in
Warnings/alarms messages in this manual explains
the various warnings and alarms, and whether a fault
locks the adjustable frequency drive. After a Trip
locked fault, cut off the AC line supply and correct the
fault. Then reconnect the AC line supply and press
the [STOP/RESET] key. The adjustable frequency
drive is now reset and ready. See Warnings/alarms
messages in this manual for more detail.
Installation
• Power line
• Motor
Installation checks
1. Input fusing in power supply for all drives Operational tests - AUTO
must be provided. 1. Ensure that drive follows run/stop and safety
2. Environmental concerns - for standard interlock commands from system.
NEMA 1 drive: 2. Ensure drive follows speed reference, or
• Clean air supply feedback, from system.
• Dry air (5% to 85% relative humidity,
non-condensing)
• 32°F (0°C) to 104°F (40°C) ambient temperature
operating range, or as rated
• 1000m (3,300 ft) maximum elevation
with no derating
• Keep any construction dirt out of drive.
3. Wiring
• Wire drive in accordance with instructions
and diagrams received with drive.
• Separate conduits must be provided to drive for
input power, output power, and control wiring.
• Protect signal wires from noise.
• Ground each drive individually.
• Double check input and output power
wiring for correct location.
Programming
Local operation (LOCAL) [1] parameter 203 Reference/feedback range to [0]:
RefMIN - RefMAX (par. 204-205) ✭ 000,000.000
Function:
There is a choice of two different modes of operation
of the variable frequency drive. Remote operation [0]
Par. 013 Local control must be set to [3] or [4] and
or Local operation [1]. See also parameter 013 Local
parameter 203 Reference/feedback range to [1]:
control if Local operation [1] is selected.
- RefMAX - + RefMAX (par. 204-205) ✭ 000,000.000
Description of choice:
Function:
If Remote operation [0] is selected, the variable In this parameter, the local reference can be set
frequency drive is controlled via: manually. The unit of the local reference depends on the
1. the control terminals or via serial communication. configuration selected in parameter 100 Configuration.
2. the [START] key. This cannot, however, override
stop commands transmitted via the digital inputs Description of choice:
or via serial communication. In order to protect the local reference, parameter
3. the [STOP/RESET] and [JOG] keys, on the 002 Local/remote operation must be set to
condition that these are active. Local operation [1]. Local reference cannot be
set via serial communication.
If Local operation [1], is selected, the variable
frequency drive is controlled via:
1. the [START] key. This cannot, however, override
stop commands via the digital inputs (see
parameter 013 Local control).
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 31
VLT® 2800 Series
NOTE
005 Programming Setup Copying is only possible in Stop (motor stopped
in connection with a stop command).
(EDIT SETUP)
Value:
Description of choice:
Factory Setup (FACTORY SETUP) [0]
Copying begins when the required copying function
Setup 1 (SETUP 1) [1]
has been selected and the [OK]/[CHANGE DATA]
Setup 2 (SETUP 2) [2]
key has been pushed. The display indicates
Setup 3 (SETUP 3) [3]
when copying is in progress.
Setup 4 (SETUP 4) [4]
✭Active Setup (ACTIVE SETUP) [5]
setups from one variable frequency drive to another Motor current [A] (MOTOR CURRENT [A]) [6]
by moving the LCP 2 control panel. Torque [%] (TORQUE [%]) [7]
Power[kW] (POWER[KW]) [8]
Description of choice:
Power [HP] (POWER [HP][US]) [9]
Select Upload all parameters [1] if you want all Motor voltage [V]
parameter values to be transferred to the control panel. (MOTOR VOLTAGE [V]) [11]
Select Download all parameters [2] if all parameter DC link voltage [V]
values transferred are to be copied to the frequency (DC LINK VOLTAGE [V]) [12]
converter to which the control panel is attached. Select Thermal load motor [%]
Download size-independent par. [3] if you only want (MOTOR THERMAL [%]) [13]
to downloade the size-independent parameters. This Thermal load [%]
is used when downloading to a variable frequency (FC. THERMAL[%]) [14]
drive with a different rated power size than that from Running hours [Hours]
which the parameter setup originates. (RUNNING HOURS]) [15]
NOTE Digital input [Bin]
Upload/download can only be performed (DIGITAL INPUT[BIN]) [16]
in stop mode. Download can only be analog input 53 [V]
performed to a frequency converter with (ANALOG INPUT 53 [V]) [17]
the same software version number, see parameter Analog input 60 [mA]
626 Database identification no. (ANALOG INPUT 60 [MA]) [19]
Pulse reference [Hz]
(PULSE REF. [HZ]) [20]
008 Display scaling of output frequency External reference [%]
(FREQUENCY SCALE) (EXTERNAL REF. [%]) [21]
Value: Status word [Hex] (STATUS WORD [HEX]) [22]
Heatsink temperature [°C]
0.01 - 100.00 ✭ 1.00
Programming
(HEATSINK TEMP [°C]) [25]
Function: Alarm word [Hex] (ALARM WORD [HEX]) [26]
In this parameter, the factor is selected by which the Control word [Hex] (CONTROL WORD [HEX]) [27]
output frequency is to be multiplied. The value is shown Warning word [Hex]
in the display, provided parameters 009-012 Display (WARNING WORD [HEX]) [28]
readout have been set to Output frequency x scaling [5]. Extended status word [Hex]
(EXT. STATUS [HEX]) [29]
Description of choice: Communication option card warning
Set the required scaling factor. (COMM OPT WARN [HEX]) [30]
Pulse count
(PULSE COUNTER) [31]
009 Large display readout
Function:
(DISPLAY LINE 2)
In this parameter you can select the data value that
Value: you wish to display in the LCP control unit display
No readout (NONE) [0] line 2 when the variable frequency drive is switched
Resulting reference [%] on. The display will also be included in the scrollbar
(REFERENCE %) [1] in display mode. In parameters 010-012 Display
Resulting reference [unit] readout you can select a further three data values,
(REFERENCE [UNIT]) [2] which are displayed in display line 1.
Feedback [unit] (FEEDBACK [UNIT]) [3]
✭Frequency [Hz] (FREQUENCY [HZ]) [4] Description of choice:
Output frequency x scaling No readout can only be selected in parameters
(FREQUENCY X SCALE) [5] 010-012 Small display readout.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 33
VLT® 2800 Series
Resulting reference [%] gives, as a percentage, Analog input 60 [mA] gives the present value
the resulting reference in the range from Minimum of terminal 60.
reference, RefMIN to Maximum reference, RefMAX.
Pulse reference [Hz] gives the reference in Hz
Reference [unit] gives the resulting reference with unit connected to terminal 33.
Hz in Open loop. In Closed loop the reference unit
is selected in parameter 416 Process units. External reference [%] gives the sum of external
references as a percentage (sum of analog/pulse/serial
Feedback [unit] gives the resulting signal value communication) in the range from Minimum reference,
using the unit/scaling selected in parameter 414 RefMIN to Maximum reference, RefMAX.
Minimum feedback, FBLOW, 415 Maximum feedback,
FBHIGH and 416 Process units. Status word [Hex] gives one or several status
conditions in a Hex code. See Serial communication
Frequency [Hz] gives the output frequency of in the Design Guide for further information.
the variable frequency drive.
Heatsink temp.[°C] gives the present heatsink
Output frequency x scaling [-] equals the present output temperature of the variable frequency drive. The
frequency fM multiplied by the factor set in parameter cut-out limit is 195-212 °F (90-100°C), while cutting
008 Display scaling of output frequency . back in occurs at 160 ± 5% (70 ± 5°C).
Motor current [A] gives the phase current of the Alarm word [Hex] gives one or several alarms
motor measured as an effective value. in hex code. See Serial communication in the
Design Guide for further information.
Torque [%] denotes the motor’s present load in
relation to the motor’s rated torque. Control word [Hex] gives the control word for the
variable frequency drive. See Serial communication
Power [kW] gives the present power that the in the Design Guide for further information.
motor is absorbing in kW.
Warning word [Hex] gives one or several warnings
Power [HP] gives the present power that the in hex code. See Serial communication in the
motor is absorbing in HP. Design Guide for further information.
Motor voltage[V] gives the voltage supplied to the motor. Extended status word [Hex] gives one or several status
DC link voltage [V] gives the intermediate circuit modes in Hex code. See Serial communication in
voltage of the variable frequency drive. the Design Guide for further information.
Thermal load motor [%] gives the calculated/estimated Communication option card warning [Hex] gives a
load on the motor. 100% is the cut-out limit. warning word if there is a fault in the communication
bus. Only active if communication options are installed.
Thermal load [%] gives the calculated/estimated If there are no communication options 0
thermal load on the variable frequency drive. Hex is displayed.
100% is the cut-out limit.
Pulse count gives the number of pulses that
Running hours [Hours] gives the number of hours that the unit has registered.
the motor has tun since the last reset in parameter
619 Reset of running hours counter.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Description of choice:
If Local not active [0] is selected, it is not possible to
011 Small display readout 1.2
set a reference via parameter 003 Local reference.
(DISPLAY LINE 1.2) In order to enable a shift to Local not active [0],
Value: parameter 002 Local/remote operation must be
See parameter 009 Large display readout set to Remote operation [0].
✭ Motor current [A][6]
Local control and open loop [1] is used if the motor
Function: speed is to be set via parameter 003 Local reference.
Programming
See the functional description given under parameter When this choice is made, parameter 100 Configuration
010 Small display readout. automatically shifts to Speed regulation, open loop [0].
012 Small display readout 1.3 Local control as parameter 100 [3] is used when the
(DISPLAY LINE 1.3) motor speed is to be set via parameter 003 Local
Value: reference, but without parameter 100 Configuration
See parameter 009 Large display readout automatically shifting to Speed regulation, open loop [0].
✭ Power [kW][8]
Remote-operated control as parameter 100 [4]
Function: works the same way as Local control as parameter
See the functional description given under parameter 100 [3]; however, the variable frequency drive can
010 Small display readout. also be controlled via the digital inputs.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 35
VLT® 2800 Series
Description of choice:
Shifting from Local operation to Remote operation
in parameter 002 Local/remote control, while If Not active [0] is selected in this parameter,
this parameter has been set to Remote-operated the [JOG]-key will be inactive.
control and open loop [1]: The configuration
selected in parameter 100 Configuration will be
active. The shift will be smooth. 016 Local reverse
(LOCAL REVERSE)
Shifting from Remote control to Local control in
Value:
parameter 002 Local/remote operation, while this
✭Not active (DISABLE) [0]
parameter has been set to Remote-operated control
Active (ENABLE) [1]
as parameter 100 [4]: the present reference will
be maintained. If the reference signal is negative, Function:
the local reference will be set to 0.
In this parameter you can select/deselect the reverse
Shifting from Local operation to Remote operation function on the LCP control panel. The key can only
in parameter 002 Local/remote operation, while be used if parameter 002 Local/remote operation
this parameter has been set to Remote operation: is set to Local operation [1] and parameter 013
The local reference will be replaced by the Localcontrol to Local control, open loop [1] or
remote-operated reference signal. Local control as parameter 100 [3].
Description of choice:
If Disable [0] is selected in this parameter, the
014 Local stop [FWD/REV] key will be disabled. See also parameter
(LOCAL STOP) 200 Output frequency range.
Value:
Not active (DISABLE) [0]
✭Active (ENABLE) [1] 017 Local reset of trip
(LOCAL RESET)
Function:
In this parameter, the local [STOP]-key can be Value:
engaged or disengaged on the control panel Not active (DISABLE) [0]
and on the LCP control panel. ✭Active (ENABLE) [1]
NOTE
Select Not active [0], only if an external reset
015 Local jog
signal has been connected via the digital inputs.
(LOCAL JOGGING)
Value:
✭Not active (DISABLE) [0] 018 Lock for data changes
Active (ENABLE) [1] (DATA CHANGE LOCK)
Function: Value:
In this parameter, the jog function on the LCP control ✭Not locked (NOT LOCKED) [0]
panel can be engaged/disengaged. Locked (LOCKED) [1]
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Function:
In this parameter, it is possible to ’lock’ the controls NOTE
to disable data changes via the control keys. In remote operation (parameter 002
Local/remote operation) the start/stop state at
Description of choice: the time of electrical connection will depend
If Locked [1] is selected, data changes in the on the external control signals. If Pulse start [8] is
parameters cannot be made; however, it will selected in parameter 302 Digital input, the motor will
still be possible to make data changes via serial remain stopped after electrical connection.
communication. Parameter 009-012 Display readout
can be changed via the control panel.
020 Hand operation
(HAND OPERATION)
Value:
019 Operating mode at power-up, local
✭Not active (DISABLE) [0]
operation
Active (ENABLE) [1]
(POWER UP ACTION)
Value: Function:
Auto restart, use saved reference In this parameter you can select whether it should be
(AUTO RESTART) [0] possible or not to switch between Auto- and Hand
✭Forced stop, use saved reference mode. In Auto mode the variable frequency drive is
(LOCAL=STOP) [1] controlled by external signals whereas the variable
Forced stop, set ref. to 0 frequency drive in Hand mode is controlled via a local
(LOCAL=STOP, REF=0) [2] reference directly from the control unit.
Programming
be active if Local operation [1] has been selected in you can switch between Auto- and Hand mode. For
parameter 002 Local/remote operation. further information, see the Control Unit section.
Description of choice:
Auto restart, use saved ref. [0] is selected if the variable
024 User-defined Quick Menu
frequency drive is to start using the local reference (set
(USER QUICK MENU)
in parameter 003 Local reference) and the start/stop
state given via the control keys immediately prior Value:
to the electrical voltage being cut out. ✭Not active (DISABLE) [0]
Forced stop, use saved ref. [1] is selected if the variable Active (ENABLE) [1]
frequency drive is to remain stopped when the electrical
Function:
voltage is engaged, until the [START]-key is activated.
In this parameter you can select the standard
After a start command the motor speed is ramped up to
setup of the Quick menu key on the control panel
the saved reference in parameter 003 Local reference.
and the LCP 2 control panel.
Forced stop, set ref. to 0 [2] is selected if the
Using this function, in parameter 025 Quick Menu
variable frequency drive is to remain stopped when
setup the user can select up to 20 parameters
the electrical voltage is cut back in. Parameter
for the Quick Menu key.
003 Local reference is to be zeroed.
Description of choice:
If not active [0] is selected, the standard setup
of the Quick Menu key is active.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 37
VLT® 2800 Series
Function:
In this parameter you define which parameters are
required in the Quick Menu when parameter 024
User-defined Quick Menu is set to Active [1].´
Up to 20 parameters can be selected for the
user-defined Quick Menu.
NOTE
Please note that this parameter can only be set
using an LCP 2 control panel. See Order form.
Description of choice:
The Quick Menu is set up as follows:
1. Select parameter 025 Quick Menu setup
and press [CHANGE DATA].
2. Index 1 indicates the first parameter in Quick
Menu. You can scroll between the index numbers
using the [+ / -] keys. Select Index 1.
3. Using [< >] you can scroll between the
three figures. Press the [<] key once ad
the last number in the parameter number
can be selected using the [+ / -] keys.
Set Index 1 to 100 for parameter 100 Configuration.
4. Press [OK] when Index 1 has been set to 100.
5. Repeat steps 2 - 4 until all parameters required
have been set to the Quick Menu key.
6. Press [OK] to complete the Quick Menu setup.
If parameter 100 Configuration is selected at Index
1, Quick Menu will start with this parameter every
time Quick Menu is activated.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Programming
the load. See par. 135 U/f ratio.
If Speed control, closed loop [1] is selected, better Description of choice:
speed accuracy is obtained. A feedback signal must
If Constant torque [1] is selected, a load-dependent U/f
be added, and the PID regulator must be set in
characteristic is obtained, in which output voltage and
parameter group 400 Special functions.
output frequency are increased at increasing loads in
If Process control, closed loop [3] is selected, the order to maintain constant magnetization of the motor.
internal process regulator is activated to enable precise
Select Variable torque low [2], Variable torque
control of a process in relation to a given process
medium [3] or Variable torque high [4], if the load
signal. The process signal can be set to the relevant
is square (centrifugal pumps, fans).
process unit or as a percentage. A feedback signal
Variable torque - low with CT start [5], - medium with
must be added from the process and the process
CT start [6] or high with CT start [7], are selected if
regulator must be set in parameter group 400 Special
you need a greater breakaway torque than can be
functions. Process closed loop is not active if a
achieved with the three first characteristics.
DeviceNet card is mounted and Instance 20/70 or
21/71 is chosen in parameter 904 Instance types. NOTE
Load and slip compensation are not active
if variable torque or special motor mode
have been selected.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 39
VLT® 2800 Series
North American HP to kW
Conversion Chart
HP kW
1/2 0.37
3/4 0.55
1 0.75
1 1/2 1.1
2 1.5
3 2.2
4 3.0
5 4
7 1/2 5.5
Select Special motor mode [8], if a special U/f setting 10 7.5
is needed that is to be adapted to the present
motor. The break points are set in parameters
423-428 Voltage/frequency .
103 Motor voltage UM,N
(MOTOR VOLTAGE)
NOTE Value:
If a value set in the name-plate parameters For 200 V units: 50 - 999 V ✭ 230 V
102-106 is changed, parameters 108 Stator
resistance and 109 Stator reactance change
automatically. Enter motor name plate data in For 400 V units: 50 - 999 V ✭ 400 V
sequence from parameter 102 to 106. The relationship
between values are interdependent. Function:
This is where to set the rated motor voltage.
102 Motor power PM,N
(MOTOR POWER) Description of choice:
Select a value that corresponds to the nameplate
Value:
data on the motor, regardless of the adjustable
0.25 - 22 kW ✭ Depends on unit
frequency drive’s AC line voltage.
Function:
Here you must set a power value [kW] PM,N,
corresponding to the motor’s rated power. 104 Motor frequency fM,N
Description of choice:
Select a value that corresponds to the nameplate
data on the motor.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
105 Motor current IM,N - For AMT to define the motor parameters
(MOTOR CURRENT) acccurately, the correct nameplate data for the
Value: motor connected to the adjustable frequency drive
0,01 - IMAX ✭ Depends on choice of motor must be keyed into parameters 102 to 106.
- Alarms will appear in the display if faults arise
Function: during tuning of the motor. See Warnings/alarms
The nominal, rated current of the motor IM,N forms part messages in this manual.
of the variable frequency drive calculation of features - As a rule, the AMT function can measure the RS
such as torque and motor thermal protection. values for motors that are 1-2 sizes larger or smaller
than the adjustable frequency drive’s nominal size.
Description of choice: - If you wish to interrupt automatic motor tuning,
Set a value that corresponds to the nameplate data press the [STOP/RESET] key.
on the motor. Set the motor current IM,N taking
into account whether the motor is star-connected
Y or delta-connected .
NOTE
AMT may not be performed on motors
connected in parallel, nor may setup changes
106 Rated motor speed be made while AMT is running.
(MOTOR NOM. SPEED)
See Automatic motor tuning in this manual
Value:
for the AMT procedure.
100 - fM,N x 60 (max. 60000 rpm)
✭ Depends on parameter 102 Motor power, PM,N Description of choice:
Select Optimization on [2] as part of the AMT
Function:
procedure if you want the adjustable frequency drive
This is where to set the value that corresponds
to perform automatic motor tuning.
to the rated motor speed nM,N that can be seen
Programming
from the nameplate data.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 41
VLT® 2800 Series
Function:
1. Use the factory settings of RS which the adjustable It is possible to optimize the resonance damping
frequency drive itself chooses on the basis in CT mode. The grade of the influence is
of the motor nameplate data. adjusted in this parameter.
2. The value is stated by the motor supplier. The value may be set between 0% (OFF) and 100%.
3. The value is obtained through manual 100% corresponds to 50% reduction of U/F ratio.
measurements: RS can be calculated by measuring Default value is OFF.
the resistance RPHASE-PHASE between two phase
terminals. Where RPHASE-PHASE is lower than 1-2 Internal settings (fixed):
Ohms (typical for motors > 7.5 HP, 400 V), a special The resonance filter is active from 10% of
Ohm-meter should be used (Thomson-bridge or nominal speed and above.
similar). RS = 0.5 x RPHASE-PHASE. In this case 5Hz and above.
4. RS is set automatically when AMT has been Speed to go from 0 to nominal flux level: 500ms
completed. See parameter 107 Auto motor tuning. Speed to go from nominal to 0 flux level: 500 ms
Description of functionality:
109 Stator reactance XS The filter monitors the active motor current and
(STATOR REACTANCE) changes the motor voltage according to the
Value: figure below. The filter reacts on levels referring
0.00 - X,XX to the nominal motor current.
✭ Depends on choice of motor
Function:
After setting of parameters 102-106 Nameplate data,
a number of adjustments of various parameters
are made automatically, including stator reactance
XS. The shaft performance can be improved by
fine-tuning RS and XS, see procedure below.
Description of choice:
XS can be set as follows:
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Description of choice:
119 High start torque
Select DC hold during start delay time [0] to energize
(HIGH START TORQ.) the motor with a DC hold voltage during the start delay
Value: time. Set voltage in parameter 137 DC hold voltage.
0.0 - 0.5 sec. ✭ 0.0 sec.
Choose DC brake during start delay time [1] to energize
Function: the motor with a DC brake voltage during the start delay
To ensure a high start torque approx. 1.8 x IINV. can be time. Set voltage in parameter 132 DC brake voltage.
permitted for max. 0.5 sec. The current is, however,
Choose Coasting during start delay time [2] and the
limited by the variable frequency drive’s (inverter’s)
motor will not be controlled by the variable frequency
safety limit. 0 sec. corresponds to no high start torque.
drive during the start delay time (inverter turned off).
Description of choice:
Choose Start frequency/voltage clockwise [3] to
Set the necessary time for which a high start
obtain the function described in parameter 130
torque is required.
Start frequency and 131 Voltage at start during start
delay time. Regardless of the value assumed by
the reference signal, the output frequency equals
120 Start delay the setting in parameter 130 Start frequency and
(START DELAY) the output voltage will correspond to the setting
Value: in parameter 131 Voltage at start .
0.0 - 10.0 sec. ✭ 0.0 sec. This functionality is typically used in hoist applications.
It is used in particular in applications in which a cone
Function: anchor motor is applied, where the direction of rotation
Programming
This parameter enables a delay of the start-up time is to start clockwise followed by the reference direction.
after the conditions for start have been fulfilled.
Select Start frequency/voltage in reference direction
When the time has passed, the output frequency
[4] to obtain the function described in parameter
will start by ramping up to the reference.
130 Start frequency and 131 Voltage at start
Description of choice: during the start delay time.
Set the necessary time before commencing The direction of rotation of the motor will always
to accelerate. follow in the reference direction. If the reference signal
equals zero, the output frequency will equal 0 Hz,
while the output voltage will correspond to the setting
in parameter 131 Voltage at start. If the reference
121 Start function
signal is different from zero, the output frequency will
(START FUNCTION)
equal parameter 130 Start frequency and the output
Value: voltage will equal parameter 131 Voltage at start. This
DC hold during start delay time functionality is used typically for hoist applications with
(DC HOLD/DELAY TIME) [0] counterweight. It is used in particular for applications
DC brake during start delay time in which a cone anchor motor is applied. The cone
(DC BRAKE/DELAY TIME) [1] anchor moto r can break away using parameter 130
✭Coasting during start delay time Start frequency and parameter 131 Voltage at start.
(COAST/DELAY TIME) [2]
Start frequency/voltage clockwise
(CLOCKWISE OPERATION) [3]
Start frequency/voltage in reference direction
(VERTICAL OPERATION) [4]
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 43
VLT® 2800 Series
Function:
128 Thermal motor protection
In this parameter, the output frequency is set at
([Link] PROTEC)
which the function selected in parameter 122
Function at stop is to be activated. Value:
✭No protection (NO PROTECTION) [0]
Description of choice: Thermistor warning
Set the required output frequency. (THERMISTOR WARN) [1]
Thermistor trip (THERMISTOR TRIP) [2]
NOTE ETR warning 1 (ETR WARNING 1) [3]
If parameter 123 is set higher than parameter ETR trip 1 (ETR TRIP 1) [4]
130, then the start delay function (parameter
ETR warning 2 (ETR WARNING 2) [5]
120 and 121) will be skipped.
ETR trip 2 (ETR TRIP 2) [6]
NOTE ETR warning 3 (ETR WARNING 3) [7]
If parameter 123 is set too high, and DC ETR trip 3 (ETR TRIP 3) [8]
hold has been chosen in parameter 122, ETR warning 4 (ETR WARNING 4) [9]
the output frequency will jump to the value ETR trip 4 (ETR TRIP 4) [10]
in parameter 123 without ramping up. This may
Function:
cause an overcurrent warning / alarm.
The adjustable frequency drive can monitor the
motor temperature in two different ways:
(+10V) and one of the digital input terminals 18, 19, You can also program the adjustable frequency drive
27 or 29. See parameter 300 Digital inputs. to give a warning signal via one of the digital outputs.
- Thermal load calculation (ETR - Electronic Select ETR Trip 1-4 if you want a trip when the motor
Thermal Relay), based on present load and is overloaded according to the calculations.
time. This is compared with the rated motor
current IM,N and rated motor frequency f M,N. NOTE
The calculations take into account the need for This function cannot protect the individual
lower loading at low speeds due to the motor’s motors in the case of motors linked in parallel.
internal ventilation being reduced.
Function:
The start frequency is active for the time set in
parameter 120 Start delay, after a start command.
The output frequency will ’jump’ to the next preset
frequency. Certain motors, such as conical anchor
motors, need an extra voltage/start frequency
(boost) at start to disengage the mechanical brake.
To achieve this parameters 130 Start frequency
ETR functions 1-4 do not begin to calculate the load and 131 Initial voltage are used.
until you switch to the Setup in which they have been Description of choice:
selected. This means that you can use the ETR function
Set the required start frequency. It is a precondition
even when changing between two or more motors.
Programming
that parameter 121 Start function, is set to
NOTE Start frequency/voltage clockwise [3] or Start
The electronic thermal relay (ETR) in UL frequency voltage in reference direction [4] and
listed VLTs provides Class 20 motor overload that in parameter 120 Start delay a time is set
protection in accordance with the NEC in and a reference signal is present.
single motor applications when parameter 128
NOTE
is set for "ETR TRIP" and parameter 105 Motor
If parameter 123 is set higher than parameter
current is set for rated motor current.
130, the start delay function (parameter
Description of choice: 120 and 121) will be skipped.
Select No protection [0] if you do not want a warning
or trip when a motor is overloaded. 131 Initial voltage
Select Thermistor warning [1] if you want a warning
(INITIAL VOLTAGE)
when the connected thermistor becomes too warm.
Select Thermistor trip [2] if you want a trip when the Value:
connected thermistor becomes too warm. 0.0 - 200.0 V ✭ 0.0 V
Select ETR WARNING if you want a warning when the
Function:
motor is overloaded according to the calculations.
Initial voltage is active for the time set in parameter
You can also program the adjustable frequency drive
120 Start delay , after a start command. This
to give a warning signal via the digital output.
parameter can be used for example for lifting/dropping
Select ETR Trip if you want a trip when the motor is
applications (conical anchor motors).
overloaded according to the calculations.
Select ETR warning 1-4 if you want a warning when
the motor is overloaded according to the calculations.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 45
VLT® 2800 Series
Description of choice:
135 U/f-ratio
(U/F RATIO)
Value:
0.00 - 20.00 at Hz ✭ Depends on unit
Function:
This parameter enables a linear shift in the ratio
between output voltage (V) and output frequency
(f) to ensure correct energizing of the motor and
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
thus optimum dynamics, accuracy and efficiency. 138 Brake cut out value
The V/f-ratio only affects the voltage characteristic if (BRAKE CUT OUT)
Constant torque [1] has been selected in parameter Value:
101 Torque characteristic . 0.5 - 132.0/1000.0 Hz ✭ 3.0 Hz
Description of choice: Function:
Change the V/f-ratio only if it is not possible to set Select the frequency at which the external brake is
the correct motor data in parameters 102-109. released, via the output defined in parameter 323 Relay
The value programmed in the factory settings output 1-3 or 341 Digital output, terminal 46.
is based on idle operation.
Description of choice:
Set the required frequency.
136 Slip compensation
(SLIP COMP.)
Value: 139 Brake cut in frequency
-500 - +500% of rated slip compensation (BRAKE CUT IN)
✭ 100% Value:
0.5 - 132.0/1000.0 Hz ✭ 3.0 Hz
Function:
Slip compensation is calculated automatically, on Function:
the basis of such data as the rated motor speed Select the frequency at which the external brake
nM,N. In this parameter, the slip compensation can be is activated; this takes place via the output
fine-tuned, thereby compensating for tolerances on defined in parameter 323 Relay output 1-3 or
the value for nM,N. Slip compensation is only active if 341 Digital output terminal 46.
a selection has been made of Speedregulation, open
loop [0] in parameter 100 Configuration and Constant Description of choice:
Set the required frequency.
Programming
torque [1] in parameter 101 Torque characteristic.
Description of choice:
Key in a % value.
140 Current, minimum value
(CURRENT MIN VAL)
Value:
137 DC hold voltage 0 % of Inom - 100 % of Inom ✭ 0 %
(DC HOLD VOLTAGE)
Value: Function:
0 - 100% of max. DC hold voltage ✭ 0% This is where the user selects the minimum motor
current running for the mechanical brake to be
Function: released. Current monitoring is only active from stop
This parameter is used to keep the motor until the point when the brake is released.
(holding torque) at start/stop.
Description of choice:
Description of choice: This is an extra safety precaution, aimed at
This parameter can only be used if a selection has guaranteeing that the load is not lost during start
been made of DC hold in parameter 121 Start of a lifting/lowering operation.
function or 122 Function at stop . To be set as
a percentage value of the max. DC hold voltage,
which depends on the choice of motor.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 47
VLT® 2800 Series
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Programming
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 49
VLT® 2800 Series
Description of choice:
A value can be selected from fMIN to the value chosen
in parameter 200 Output frequency range.
Function:
In this parameter you select whether the reference
signal must be positive or whether it can be both
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
positive and negative. The minimum limit may be a 205 Maximum reference, RefMAX
negative value, unless in parameter 100 Configuration ([Link])
a selection has been made of Speed regulation, Value:
closed loop. You should select Min ref. - Max. ref. Par. 100 Config. = Open loop [0].
[0], if Process regulation, closed loop [3] has been Par. 204 RefMIN - 1000.000 Hz ✭ 50.000 Hz
selected in parameter 100 Configuration.
Description of choice:
Par. 100 Config. = Closed loop [1]/[3].
Select the required range.
Par. 204 RefMIN - Par. 415 Max. feedback
✭ 50.000 rpm/par 416
Programming
[3] is selected, the minimum reference is limited by
parameter 414 Minimum feedback. Minimum reference Description of choice:
is ignored if the local reference is active. Maximum reference is set, if the speed of the
motor is to be max. the set value, regardless
The reference unit can be defined from the
of the whether the resulting reference is greater
following table:
than the maximum reference.
Par. 100 Configuration Unit
Open loop [0] Hz
Speed reg, closed loop [1] rpm
206 Ramp type
Process reg, closed loop [3] Par. 416
(RAMP TYPE)
Description of choice:
Select the required ramp type depending on
requirementsfor the acceleration/deceleration process.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 51
VLT® 2800 Series
Function:
The ramp-down time is the deceleration time
from the rated motor frequency fM,N (parameter
104 Motor frequency, f M,N) to 0 Hz, provided
no overvoltage arises in the inverter because of
generating operation of the motor.
Description of choice:
Set the required ramp-down time.
207 Ramp-up time 1
(RAMP-UP TIME 1)
Value: 209 2 Ramp-up time
0.02 - 3600.00 sec ✭ 3.00 sec (VLT 2803-2875) (2 RAMP-UP TIME)
10.00 sec (VLT 2880-2882) Value:
0.02 - 3600.00 sec. ✭ 3.00 sec (VLT 2803-2875)
Function:
10.00 sec (VLT 2880-2882)
The ramp-up time is the acceleration time from 0
Hz to the rated motor frequency fM,N (parameter Function:
104 Motor frequency, fM,N). It is assumed that the See description of parameter 207 Ramp-up time 1.
output current will not reach the current limit (set
in parameter 221 Current limit ILIM). Description of choice:
Set the required ramp-up time. Shift from ramp 1 to
ramp 2 by activating Ramp 2 via a digital input.
Function:
Description of choice: See description of parameter 208 Ramp-down time 1.
Set the required ramp-up time.
Description of choice:
Set the required ramp-down time. Shift from ramp 1 to
ramp 2 by activating Ramp 2 via a digital input.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Function: Function:
The jog ramp time is the acceleration/deceleration Jog frequency fJOG means a fixed output frequency
time from 0 Hz to the rated motor frequency fM,N that the variable frequency drive supplies to the motor
(parameter 104 Motor frequency, fM,N). It is assumed when the Jog function is activated. Jog can be
that the output current will not reach the current limit activated via the digital inputs, serial communication
(set in parameter 221 Current limit ILIM). or via the LCP control panel, on the condition that
this is active in parameter 015 Local jog.
Description of choice:
Set the required frequency.
Programming
It is possible to define how preset references are to
Description of choice: be added to the other references; for this purpose,
Set the required ramp time. use Sum or Relative. It is also possible by using the
External/preset to select whether a shift between
external references and preset references is required.
External reference is the sum of the analog
212 Quick stop ramp-down time references, pulse references and any references
(Q STOP RAMP TIME) from serial communication.
Value:
Description of choice:
0.02 - 3600.00 sec. ✭ 3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882) If Sum [0] is selected, one of the adjusted
preset references (parameters 215-218 Preset
Function: reference) is summarized as a percentage of
The quick-stop ramp-down time is the deceleration the reference range (RefMIN - RefMAX), added to
time from the rated motor frequency to 0 Hz, provided the other external references.
no overvoltage arises in the inverter because of If Relative [1] is selected, one of the added preset
generating operation of the motor, or if the generated references (parameters 215-218 Preset reference)
current exceeds the current limit in parameter 221 is summarized as a percentage of the sum of
Current limit ILIM. Quick stop is activated via one of present external references.
the digital inputs or the serial communication. If External/preset [2] is selected, it is possible via
a digital input to shift between external references
Description of choice: or preset references. Preset references will be a
Set the required ramp-down time. percentage value of the reference range.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 53
VLT® 2800 Series
Description of choice:
NOTE
If Sum or Relative is selected, one of the If Catch up is active via a digital input, the percentage
preset references will always be active. If the value in parameter 219 Catch up/Slow down reference
preset references are to be without influence, will be added to the remote-controlled reference.
they must be set to 0% (factory setting). If Slow down is active via a digital input, the percentage
value in parameter 219 Catch up/Slow down reference
will be deducted from the remote-controlled reference.
215 Preset reference 1 (PRESET REF. 1)
216 Preset reference 2 (PRESET REF. 2)
217 Preset reference 3 (PRESET REF. 3) 221 Current limit, ILIM
218 Preset reference 4 (PRESET REF. 4) (CURRENT LIMIT)
Value: Value:
-100.00% - +100.00% ✭ 0.00% 0 - XXX.X % of par. 105 ✭ 160 %
of the reference range/external reference
Function:
Function: In this parameter, the maximum output current ILIM is
Four different preset references can be programmed set. The factory-set value corresponds to the maximum
in parameters 215-218 Preset reference. output current IMAX. If the current limit is to be used
The preset reference is stated as a percentage of the as motor protection, set the rated motor current. f
reference range (RefMIN - RefMAX) or as a percentage the current limit is set above 100% (the rated output
of the other external references, depending on the current of the variable frequency drive, IINV.), the variable
choice made in parameter 214 Reference function. frequency drive can only handle a load intermittently,
The choice between preset references can be made i.e. for short periods at a time. After the load has been
via the digital inputs or via serial communication. higher than IINV., it must be ensured that for a period the
load is lower than IINV. Please note that if the current
Preset ref., msb Preset ref. lsb
0 0 Preset ref. 1 limit is set at a lower value than IINV., the acceleration
0 1 Preset ref. 2 torque will be reduced to the same extent.
1 0 Preset ref. 3
Description of choice:
1 1 Preset ref. 4
Set the required maximum output current ILIM.
Description of choice:
Set the preset reference(s) that is/are to be the options.
223 Warning: Low current, ILOW
(WARN. CURRENT LO)
Value:
219 Catch up/ Slow down reference
0.0 - par. 224 Warning: High current, IHIGH ✭ 0.0 A
(CATCH UP/SLW DWN)
Value: Function:
0.00 - 100% of the given reference ✭ 0.00% If the output current falls below the preset limit
ILOW a warning is given.
Function: Parameters 223-228 Warning functions are out of
In this parameter, the percentage value can be set function during ramp-up after a start command and
which will either be added to or deducted from after a stop command or during stop. The warning
the remote-controlled references. functions are activated when the output frequency
The remote-controlled reference is the sum of preset reaches the resulting reference. The signal outputs
references, analog references, pulse reference and can be programmed to give a warning signal via
any references from serial communication. terminal 46 and via the relay output.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Function:
If the output frequency falls below the preset
limit fLOW, a warning is given.
Parameters 223-228 Warning functions are out of
function during ramp-up after a start command and
after stop command or during stop. The warning
functions are activated when the output frequency
has reached the resulting reference. The signal
outputs can be programmed to give a warning signal
via terminal 46 and via the relay output.
Description of choice:
The lower signal limit of the output frequency fLOW
must be programmed within the normal operating
224 Warning: High current, IHIGH
range of the variable frequency drive. See drawing
(WARN. CURRENT HI) at parameter 223 Warning: Low current, ILOW.
Value:
0 - IMAX ✭ IMAX
Programming
IHIGH a warning is given. Value:
Parameters 223-228 Warning functions do not Par. 200 Frequency range = 0-132 Hz [0]/[1].
work during ramp-up after a start command and par. 225 fLOW - 132 Hz ✭ 132.0 Hz
after stop command or during stop. The warning
functions are activated when the output frequency
has reached the resulting reference. The signal Par. 200 Frequency range = 0-1000 Hz [2]/[3].
outputs can be programmed to give a warning signal par. 225 fLOW - 1000 Hz ✭ 132.0 Hz
via terminal 46 and via the relay output.
Function:
Description of choice: If the output frequency exceeds the preset limit
The output current’s upper signal limit IHIGH must be fHIGH a warning is given.
programmed within the variable frequency drive’s Parameters 223-228 Warning functions do not
normal operating range. See drawing at parameter work during ramp-up after a start command and
223 Warning: Low current, ILOW. after stop command or during stop. The warning
functions are activated when the output frequency
has reached the resulting reference. The signal
outputs can be programmed to give a warning signal
via terminal 46 and via the relay output.
Description of choice:
The output frequency’s upper signal limit fHIGH must
be programmed within the variable frequency drive’s
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 55
VLT® 2800 Series
normal operating range. See drawing at parameter 229 Frequence bypass, bandwidth
223 Warning: Low current, ILOW. (FREQ BYPASS B.W.)
Value:
0 (OFF) - 100 Hz ✭ 0 Hz
227 Warning: Low feedback, FBLOW
Function:
([Link]. LOW)
Some systems call for some output frequencies
Value:
to be avoided because of mechanical resonance
-100,000.000 - par. 228 Warn.: FBHIGH✭ -4000.000
problems in the system. In parameters 230-231
Frequency bypass these output frequencies can be
Function:
programmed. In this parameter a bandwidth can be
If the feedback signal falls below the preset limit
defined on either side of these frequencies.
FBLOW, a warning is given.
Parameters 223-228 Warning functions are out of Description of choice:
function during ramp-up after a start command and
The frequency set in this parameter will be centered
after a stop command or during stop. The warning
around parameters 230 Frequency bypass 1
functions are activated when the output frequency has
and 231 Frequency bypass 2.
reached the resulting [Link] signal outputs can
be programmed to give a warning signal via terminal 46
and via the relay [Link] unit for feedback in Closed
loop is programmed in parameter 416 Process units. 230 Frequency bypass 1 (FREQ. BYPASS 1)
231 Frequency bypass 2 (FREQ. BYPASS 2)
Description of choice:
Value:
Set the required value within the feedback range 0 - 1000 Hz ✭ 0.0 Hz
(parameter 414 Minimum feedback, FBMIN and
415 Maximum feedback, FBMAX). Function:
Some systems call for some output frequencies
to be avoided because of mechanical resonance
228 Warning: High feedback, FBHIGH problems in the system.
Function:
If the feedback signal gets above the preset
limit FBHIGH, a warning is given.
Parameters 223-228 Warning functions are out of
function during ramp-up after a start command and
after a stop command or during stop. The warning
functions are activated when the output frequency has
reached the resulting reference. The signal outputs can
be programmed to give a warning signal via terminal 46
and via the relay output. The unit for feedback in Closed
loop is programmed in parameter 416 Process units.
Description of choice:
Set the required value within the feedback range
(parameter 414 Minimum feedback, FBMIN and
415 Maximum feedback, FBMAX).
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Programming
Preset ref, LSB (PRESET REF, LSB) [22] [22] [22] [22] [22]
Preset ref., msb Preset ref., msb [23] [23] [23] [23] [23]
Preset reference on (PRESET REFERENCE ON) [24] [24] [24] [24] [24]
Thermistor (THERMISTOR) [25] [25] [25] [25]
Precise stop, inverse (PRECISE STOP INV.) [26] [26]
Precise start/stop (PRECISE START/STOP) [27] [27]
Pulse reference (PULSE REFERENCE) [28]
Pulse feedback (PULSE FEEDBACK) [29]
Pulse input (PULSE INPUT) [30]
Selection of Setup, lsb Select Setup (lsb) [31] [31] [31] [31] [31]
Selection of Setup, msb (SETUP SELECT MSB) [32] [32] [32] [32] [32]
Reset and start (RESET AND START) [33] [33] [33] [33] [33]
Pulse counter start (PULSE COUNTER START) [34] [34]
1. All functions on terminal 18 and 19 are
controlled by an interrupter, which means that
the repetitive accuracy of the response time is
constant. Can be used for start/stop, setup switch
and especially for changing digital preset, i.e. to
obtain a reproduceable stop point when using
creep speed. For further information see VLT 2800
Precise Stop Instruction, [Link].02.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 57
VLT® 2800 Series
Function:
In these parameters 302-307 Digital inputs it is possible
to choose between the different enabled functions
related to the digital inputs (terminals 18-33).
Description of choice:
No operation is selected if the variable frequency drive
is not to react to signals transmitted to the terminal.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Freeze output freezes the present output frequency Preset reference, lsb and Preset reference, msb
(in Hz). The output frequency can now only be makes it possible to select one of the four preset
changed via Speed up and Slow down . references, see the table below:
NOTE
Preset ref. Preset ref. Function
If Freeze output is active the variable
msb lsb
0 0 Preset ref. 1
frequency drive can only be stopped if
0 1 Preset ref. 2
you select Motor coast, Quick stop or
1 0 Preset ref. 3
DC braking via a digital input.
1 1 Preset ref. 4
Speed up and Slow down are selected if digital
control of the speed up/slow down is required. This Preset reference on is used for shifting between
function is only active if Freeze reference or Freeze remote-controlled reference and preset reference.
output frequency has been selected. It is assumed that External/preset [2] has been
If Speed up is active the reference or output frequency selected in parameter 214 Reference function. Logic
will be increased, and if Speed down is active the ’0’ = remote-controlled references are active, logic
reference or output frequency will be reduced. The ’1’ = one of the four preset references is active,
output frequency is changed via the preset ramp as can be seen from the table above.
times in parameters 209-210 Ramp 2.
Thermistor is to be selected if a possibly integrated
One pulse (logic ’1’ minimum high for 14 ms
thermistor in the motor is to be able to stop the
and a minimum break time of 14 ms) will lead
variable frequency drive if the motor overheats.
to a speed change of 0.1 % (reference) or 0.1
The cut-out value is 3 k .
Hz (output frequency). Example:
Term. Term. Freeze ref/ Function
29 33 freeze outp.
0 0 1 No speed change
Programming
0 1 1 Speed up
1 0 1 Slow down
1 1 1 Slow down
Catch-up/Slow-down is selected if the reference If a motor features a Klixon thermal switch instead, this
value is to be increased or reduced by a can also be connected to the input. If motors operate
programmable percentage value set in parameter in parallel, the thermistors/thermal switches can be
219 Catch-up/Slow-down reference . connected in series (total resistance lower than 3 k ).
Parameter 128 Motor thermal protection must be
Slow-down Catch-up Function
programmed for Thermistor warning [1] or Thermistor
0 0 Unchanged speed
0 1 Increase by % value trip [2] and the thermistor is to be connected between
1 0 Reduce by % value a digital input and terminal 50 (+ 10 V supply).
1 1 Reduce by % value
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 59
VLT® 2800 Series
Function:
This parameter is used for setting the signal value
308 Terminal 53, analog input voltage that is to correspond to the maximum reference value
(AI [V]53FUNCT.) or maximum feedback, parameter 205 Maximum
Value: reference, RefMAX / 414 Maximum feedback, FBMAX.
No function (NO OPERATION) [0] Description of choice:
✭REFERENCE % (REFERENCE %) [1]
Set the required voltage value. For reasons of
Feedback (FEEDBACK) [2]
accuracy, compensation should be made for
Function: voltage losses in long signal cables.
In this parameter it is possible to select the function
required to be connected to terminal 53. Scaling of the
input signal is made in parameter 309 Terminal 53, min.
scaling and parameter 310 Terminal 53, max. scaling.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
314 Terminal 60, analog input current 316 Terminal 60 Max. scaling
(AI [MA] 60 FUNCT) (AI 60 SCALE HIGH)
Value: Value:
✭No function (NO OPERATION) [0] 0.0 - 20.0 mA ✭ 20.0 mA
REFERENCE % (REFERENCE %) [1]
Feedback (FEEDBACK) [2] Function:
This parameter is used for setting the signal value that
Function: is to correspond to the maximum reference value,
This parameter allows a choice between the parameter 205 Maximum reference value, RefMAX.
different functions available for the input, terminal 60.
Scaling of the input signal is effected in parameter Description of choice:
315 Terminal 60, min. scaling and parameter Set the required current value.
316 Terminal 60, max. scaling.
Description of choice:
317 Time out
No function [0]. Is selected if the variable frequency
(LIVE ZERO TIME O)
drive is not to react to signals connected to the terminal.
Value:
Reference [1]. If this function is selected, the reference
1 - 99 sec. ✭ 10 sec.
can be changed by means of an analog reference
signal. If reference signals are connected to more than Function:
one input, these reference signals must be added up.
If the signal value of the reference or feedback signal
If one current feedback signal is connected, select
connected to one of the input terminals 53 or 60 falls
Feedback [2] on terminal 60.
below 50 % of the minimum scaling for a period longer
than the time set, the function selected in parameter
318 Function after time out will be activated. This
315 Terminal 60 Min. scaling function is only active if in parameter 309 Terminal
Programming
(AI 60 SCALE LOW) 53, min. scaling a value higher than 1 Volt has been
selected, or if in parameter 315 Terminal 60, min.
Value:
scaling a value higher than 2 mA has been selected.
0.0 - 20.0 mA ✭ 0.0 mA
Description of choice:
Function:
In this parameter you can set the signal value that will Set the required time.
correspond to the minimum reference or minimum
feedback, parameter 204 Minimum reference, RefMIN
/ 414 Minimum feedback, FBMIN. 318 Function after time out
(LIVE ZERO FUNCT.)
Description of choice:
Value:
Set the required current value. If the Time out function is
✭No operation (NO OPERATION) [0]
to be used (parameter 317 Time out and 318 Function
Freeze output frequency
after time out ) the value set must be higher than 2 mA.
(FREEZE OUTPUT FREQ.) [1]
Stop (STOP) [2]
Jog (JOG) [3]
Max. speed (MAX SPEED) [4]
Stop and trip (STOP AND TRIP) [5]
Function:
This parameter allows a choice of the function to be
activated after the expiration of the Time out (parameter
317 Time out ). If a time-out function occurs at the
same time as a bus time-out function (parameter
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 61
VLT® 2800 Series
513 Bus time interval function ), the time-out function output the resulting resistance from the equipment
in parameter 318 will be activated. connected may not exceed 500 .
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
(RUN IN RANGE/ NO WARN) [6] The adjustable frequency drive is ready for operation,
Ready - AC line voltage within range but no start command has been given. No warning.
(RDY NO OVER/UNDERVOL) [7]
Running:
Alarm or warning
A start command has been given. Also active
(ALARM OR WARNING) [8]
during ramp down.
Current higher than current limit, par. 221
(CURRENT LIMIT) [9] Running in reference, no warning:
Alarm (ALARM) [10] The drive is running at reference speed. No warning.
Output frequency higher than fLOW par. 225
(ABOVE FREQUENCY LOW) [11] Running, no warning:
Output frequency lower than fHIGH par. 226 A start command has been given. No warning.
(BELOW FREQUENCY HIGH) [12]
Running in reference range:
Output current higher than ILOW par. 223
The drive is being controlled by a remote reference
(ABOVE CURRENT LOW) [13]
and is running within range.
Output current lower than IHIGH par. 224
(BELOW CURRENT HIGH) [14] Ready - AC line voltage within range:
Feedback higher than FBLOW par. 227 The adjustable frequency drive is ready for use; the
(ABOVE FEEDBACK LOW) [15] control card is receiving a supply voltage; and there
Feedback lower than FBHIGH par. 228 are no active control signals on the inputs. The AC
(UNDER FEEDBACK HIGH) [16] line voltage lies within the voltage limits.
Relay 123 (RELAY 123) [17]
Reversing (REVERSE) [18] Alarm or warning:
Thermal warning (THERMAL WARNING) [19] An alarm or a warning exists in the drive.
Local operation (LOCAL MODE) [20] Current limit:
Out of frequency range par. 225/226
The output current is higher than the value programmed
(OUT OF FREQ RANGE) [22] in parameter 221 Current limit ILIM.
Programming
Out of current range
(OUT OF CURRENT RANGE) [23] Alarm:
Out of feedback range The output is activated by an alarm.
(OUT OF FDBK. RANGE) [24]
Output frequency higher than fLOW:
Mechanical brake control
(MECH. BRAKE CONTROL) The output frequency is higher than the value set in
[25]
parameter 225 Warning: Low frequency, fLOW.
Control word bit 11
(CONTROL WORD BIT 11) [26] Output frequency higher than Flow:
The output frequency is higher than the value set in
Function:
parameter 225 Warning: Low frequency, fLOW.
The relay output can be used for giving the present
status or warning. The relay is a Form C with contacts Output current higher than ILOW:
1 and 3 normally closed. The output is activated The output current is higher than the value set in
when a given condition is fulfilled. parameter 223 Warning: Low current, ILOW.
Description of choice:
No function:
Is selected if the adjustable frequency drive
is not to react to signals.
Unit ready:
The drive’s control card receives a supply voltage
and the drive is ready for operation.
Enable, no warning:
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 63
VLT® 2800 Series
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Description of choice:
Pulse reference RefMIN - Ref MAX 343 Precise stop function
An output signal is obtained, which is proportional (PRECISE STOP)
to the resulting reference value in the interval Value:
Minimum reference, Ref MIN - Maximum reference, ✭Precise ramp stop (NORMAL) [0]
RefMAX (parameters 204/205). Counter stop with reset
(COUNT STOP RESET) [1]
Pulse feedback FBMIN-FBMAX .
Counter stop without reset
An output signal is obtained, which is proportional to the
(COUNT STOP NO RESET) [2]
feedback value in the interval Minimum feedback, FBMIN
Speed-compensated stop (SPD CMP STOP) [3]
- Maximum feedback, FBMAX (parameter 414/415).
Speed-compensated counter stop with reset
Output frequency 0-fMAX. (SPD CMP CSTOP W. RES) [4]
An output signal is obtained, which is proportional to Speed-compensated counter stop without reset
the output frequency in the interval 0 - fMAX (parameter (SPD CMP CSTOP NO RES) [5]
202 Output frequency, high limit, fMAX).
Function:
Pulse current 0 - IINV.. In this parameter you select which stop function is
An output signal is obtained, which is proportional performed in response to a stop command. All six
to the output current in the interval 0 - IINV. data selections contain a precise stop routine, thus
ensuring a high level of repeat accuracy.
Pulse power 0 - PM,N. The selections are a combination of the
An output signal is obtained, which is proportional to functions described below.
the present output power. Par. 342 corresponds to the
Programming
value set in parameter 102 Motor power, PM,N. NOTE
Pulse start [8] may not be used together
Pulse temperature 0 - [Link]. with the precise stop function.
An output signal is obtained, which is proportional to
the present heatsink temperature. 0 Hz corresponds Description of choice:
to a heatsink temperature of less than 68 °F (20° C),
Precise ramp stop [0] is selected to achieve high
and 20 mA corresponds to 212 °F (100° C).
repetitive precision at the stopping point.
NOTE Counter stop. Once it has received a pulse start signal
Output terminal 46 is not available on the variable frequency drive runs until the number of
DeviceNet. Minimum output frequency at pulses programmed by the user have been received at
frequency output = 16 Hz input terminal 33. In this way an internal stop signal will
activate the normal ramp down time (parameter 208).
The counter function is activated (starts timing)
342 Terminal 46, max. pulse scaling at the flank of the start signal (when it changes
(DO 46 MAX. PULS) from stop to start).
Value: Speed compensated stop. To stop at precisely
150 - 10000 Hz ✭ 5000 Hz the same point, regardless of the present speed,
a stop signal received is delayed internally when
Function: the present speed is lower than the maximum
This parameter is used for setting the pulse output speed (set in parameter 202).
signal’s maximum frequency.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 65
VLT® 2800 Series
Function:
In this parameter you can select the counter
value to be used in the integrated precise stop
function (parameter 343).
Description of choice:
The factory setting is 100000 pulses. The highest
frequency (max. resolution) that can be registered
at terminal 33 is 67.6 kHz.
Function:
In this parameter the user can set the system’s
delay time (Sensor, PLC, etc.). If you are running
speed-compensated stop, the delay time at
different frequencies has a major influence on
the way in which you stop.
Description of choice:
The factory setting is 10 ms. This means that it is
assumed that the total delay from the Sensor, PLC
and other hardware corresponds to this setting.
NOTE
Only active for speed-compensated stop.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Description of choice:
406 Automatic restart time
Select Resistor brake [1] if a brake resistor is connected.
(AUTORESTART TIME)
Select AC brake [4] if short-term generated loads occur.
See parameter 144 Gain AC brake to set the brake. Value:
Programming
0 - 10 sec. ✭ 5 sec.
Select Load sharing [5] if this is used.
Function:
NOTE This parameter allows setting of the time from
A change of selection will not become tripping until the automatic reset function begins. It
active until the AC line voltage has been is assumed that automatic reset has been selected
disconnected and reconnected. in parameter 405 Reset function.
Description of choice:
405 Reset function Set the required time.
(RESET MODE)
Value:
✭Manual reset (MANUAL RESET) [0]
409 Trip delay overcurrent, ILIM
Automatic reset x 1
(TRIP DELAY CUR.)
(AUTOMATIC X 1) [1]
Automatic reset x 3 Value:
(AUTOMATIC X 3) [3] 0 - 60 sec. (61=OFF) ✭ OFF
Automatic reset x 10
Function:
(AUTOMATIC X 10) [10]
When the variable frequency drive registers that
Reset at power-up
the output current has reached the current limit
(RESET AT POWER UP) [11]
ILIM (parameter 221 Current limit) and remains
there for the preset time, it is disconnected. Can
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 67
VLT® 2800 Series
NOTE
When the LC filter is selected, the switching
411 Switching frequency frequency is changed to 4.5 kHz.
(SWITCH FREQ.)
Value:
3000 - 14000 Hz (VLT 2803-75) ✭ 4500 Hz 413 Overmodulation function
3000 - 10000 Hz (VLT 2880-82) ✭ 4500 Hz (OVERMODULATION)
Value:
Function:
Off (OFF) [0]
The set value determines the switching frequency of the
✭On (ON) [1]
inverter. If the switching frequency is changed, this may
help to minimize possible acoustic noise from the motor. Function:
This parameter allows connection of the
NOTE
overmodulation function for the output voltage.
The output frequency of the adjustable
frequency drive can never assume a value Description of choice:
higher than 1/10 of the switching frequency. Off [0] means that there is no overmodulation
of the output voltage, which means that torque
Description of choice:
ripple on the motor shaft is avoided. This can
When the motor is running, the switching frequency
be a good feature, e.g. on grinding machines.
is adjusted in parameter 411 Switching frequency
On [1] means that an output voltage can be obtained
until the frequency has been obtained at which the
which is greater than the AC line voltage (up to 5 %).
motor is as low-noise as possible.
NOTE
The switching frequency is reduced 414 Minimum feedback, FBMIN
automatically as a function of the load. (MIN. FEEDBACK)
See Temperature-Dependent Switching
Value:
Frequency under Special Conditions .
-100,000.000 - par. 415 FBMAX ✭ 0.000
When LC-filter connected is selected in parameter
412, the switching frequency is 4.5 kHz. Function:
Parameter 414 Minimum feedback, FBMIN and 415
Maximum feedback, FBMAX are used to scale the
412 Variable switching frequency
display text to make it show the feedback signal in a
(VAR CARRIER FREQ.) process unit proportionally to the signal on the input.
Value:
✭Without LC-filter (WITHOUT LC-FILTER) [2] Description of choice:
LC-filter connected Set the value to be shown on the display as the
(LC-FILTER CONNECTED) [3] minimum feedback signal value on the selected
feedback input (parameters 308/314 Analog inputs).
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Programming
Units/min. (UNITS/MI) [8]
parameter 100 Configuration the selection
Units/h (UNITS/H) [9]
made is Speed regulation, closed loop [1].
°C (°C) [10]
Pa (PA) [11] 417 Speed PID proportional gain
l/s (L/S) [12] (SPEED PROP GAIN)
m3/s (M3/S) [13]
Value:
l/min. (L/M) [14]
0.000 (OFF) - 1.000 ✭ 0.010
m3/min. (M3/MIN) [15]
l/h (L/H) [16] Function:
m3/h (M3/H) [17] Proportional gain indicates how many times the
Kg/s (KG/S) [18] fault (deviation between the feedback signal and
Kg/min. (KG/MIN) [19] the setpoint) is to be amplified.
Kg/hour (KG/H) [20]
Tons/min. (T/MIN) [21] Description of choice:
Tons/hour (T/H) [22] Quick regulation is obtained at high amplification,
Metres (M) [23] but if the amplification is too high, the process may
Nm (NM) [24] become unstable in the case of overshooting.
m/s (M/S) [25]
m/min. (M/MIN) [26]
°F (°F) [27]
In wg (IN WG) [28]
gal/s (GAL/S) [29]
Ft3/s (FT3/S) [30]
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 69
VLT® 2800 Series
418 Speed PID integral time frequencies, limiting the gain may be useful. This
(SPEED INT. TIME) enables obtaining a pure D-gain at low frequencies
Value: and a constant D-gain at higher frequencies.
20.00 - 999.99 ms (1000 = OFF) ✭ 100 ms Description of choice:
Function:
The differentiator does not react to a constant error.
It only makes a contribution when the error changes.
The quicker the error changes, the stronger the gain
from the differentiator will be. The contribution is
proportional to the speed at which errors change.
Description of choice:
Quick control is obtained by a long differential time.
However, if this time is too long, it can make the
process unstable. When the differential time is
Description of choice:
0 ms, the D-function is not active.
If a time constant (t) of 100 ms is programmed, the
cut-off frequency for the lowpass filter will be 1/0.1 =
10 RAD/sec., corresponding to (10 / 2 x π) = 1.6 Hz.
420 Speed PID D- gain limit
The PID regulator will then only regulate a feedback
(SPEED D-GAIN LIM) signal that varies with a frequency of less than 1.6 Hz.
Value: If the feedback signal varies by a higher frequency than
5.0 - 50.0 ✭ 5.0 1.6 Hz, it will be dampened by the lowpass filter.
Function:
It is possible to set a limit for the gain provided by the
differentiator. Since the D-gain increases at higher
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Function:
426 F2 frequency
Parameters 423-428 are used when in parameter
(F2 FREQUENCY)
101Torque characteristic a selection has been made
of Special motor characteristic [8]. It is possible to Value:
determine a U/f characteristic on the basis of four Par. 424 F1 frequency - par. 428 F3 frequency
definable voltages and three frequencies. The voltage ✭ Par. 104 Motor frequency
at 0 Hz is set in parameter 133 Start voltage.
Function:
See parameter 423 U1 voltage.
Description of choice:
Set the output frequency (F2) that is to match the
second output voltage (U2), parameter 425 U2 voltage .
427 U3 voltage
(U3 VOLTAGE)
Description of choice: Value:
Set the output voltage (U1) that is to match the first 0.0 - 999.0 V ✭ par. 103
output frequency (F1), parameter 424 F1 frequency.
Function:
See parameter 423 U1 voltage.
Programming
424 F1 frequency Description of choice:
(F1 FREQUENCY) Set the output voltage (U3) that is to match the third
Value: output frequency (F3), parameter 428 F3 frequency .
0.0 - par. 426 F2 frequency
✭ Par. 104 Motor frequency
428 F3 frequency
Function:
(F3 FREQUENCY)
See parameter 423 U1 voltage .
Value:
Description of choice: Par. 426 F2 frequency - 1000 Hz
Set the output frequency (F1) that is to match the first ✭ Par. 104 Motor frequency
output voltage (U1), parameter 423 U1 voltage .
Function:
See parameter 423 U1 voltage.
Function:
See parameter 423 U1 voltage.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 71
VLT® 2800 Series
NOTE
NOTE
Parameters 437-444 are only used
If Disable [0] is selected, it will mean that when
if in parameter 100 Configuration a
the deviation changes its sign, the integrator
selection has been made of Process
will first have to integrate down from the level
regulation, closed loop. [3].
obtained as a result of the former error, before any
437 Process PID normal/inverse control change in output frequency occurs.
(PROC NO/INV CTRL)
Value: 439 Process PID start frequency
✭Normal (NORMAL) [0]
(PROC START VALUE)
Inverse (INVERSE) [1]
Value:
Function: fMIN - fMAX (parameter 201/202)
It is possible to choose whether the process regulator ✭ Par. 201 Output frequency, low limit, fMIN
is to increase/reduce the output frequency if there
is a deviation between the reference/setpoint Function:
and the actual process mode. When the start signal comes, the variable frequency
drive will react in the form of Open loop and will not
Description of choice: change to Closed loop until the programmed start
If the variable frequency drive is to reduce frequency is reached. This makes it possible to set a
the output frequency in case the feed- frequency that corresponds to the speed at which the
back signal increases, select Normal [0]. process normally runs, which will enable the required
If the variable frequency drive is to increase the process conditions to be reached sooner.
output frequency in case the feedback signal
Description of choice:
increases, select Inverse [1].
Set the required start frequency.
NOTE
438 Proces PID anti windup If the variable frequency drive is running a the
(PROC ANTI WINDUP) current limit before the required start frequency
is obtained, the process regulator will not be
Value:
activated. For the regulator to be activated anyway, the
Not active (DISABLE) [0]
start frequency must be lower to the required output
✭Active (ENABLE) [1]
frequency. This can be done during operation.
Function:
It is possible to select whether the process regulator is
440 Proces PID proportioanl gain
to continue regulating on a deviation even if it is not
possible to increase/reduce the output frequency. (PROC. PROP. GAIN)
Value:
Description of choice: 0.0 - 10.00 ✭ 0.01
The factory setting is Enable [1], which means that
the integration link is initialized in relation to the Function:
actual output frequency if either the current limit, the The proportional gain indicates the number of
voltage limit or the max./min. frequency has been times the deviation between the setpoint and the
reached. The process regulator will not engage again feedback signal is to be applied.
until either the error is zero or its sign has changed.
Description of choice:
Select Disable [0] if the integrator is to continue
integrating on the deviation, even if it is not possible Quick regulation is obtained by a high gain, but
to remove the fault by such control. if the gain is too high, the process may become
unstable due to overshoot.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
441 Process PID integration time at slow changes and a constant differentiator gain
(PROC. INTEGR. T.) where quick changes to the deviation occur.
Value: Description of choice:
0.01 - 9999.99 (OFF) ✭ OFF
Select a differentiator gain limit as required.
Function:
The integrator provides an increasing gain at a constant
error between the reference/setpoint and the feedback 444 Process PID lowpass filter time
signal. The greater the error, the quicker the integrator (PROC FILTER TIME)
frequency contribution will [Link] integral time
Value:
is the time needed by the integrator to make the
0.02 - 10.00 ✭ 0.02
same change as the proportional gain.
Function:
Description of choice:
Noise in the feedback signal is dampened by a first
Quick regulation is obtained at a short integral time.
order lowpass filter to reduce the noise’s impact on
However, this time may become too short, which can
the process regulation. This can be an advantage
make the process unstable due to overswing. If the
e.g. if there is a lot of noise on the signal.
integral time is long, major deviations from the required
setpoint may occur, since the process regulator will Description of choice:
take a long time to regulate in relation to a given error. Select the required time constant (t). If a time constant
(t) of 0.1 s is programmed, the cut-off frequency
for the lowpass filter will be 1/0.1 = 10 RAD/sec.,
442 Process PID differentiation time corresponding to (10 / 2 x π) = 1.6 Hz. The process
(PROC. DIFF. TIME) regulator will thus only regulate a feedback signal
that varies by a frequency lower than 1.6 Hz. If the
Value:
feedback signal varies by a higher frequency than 1.6
0.00 (OFF) - 10.00 sec. ✭ 0.00 sec.
Hz, it will be dampened by the lowpass filter.
Programming
Function:
The differentiator does not react to a constant error.
It only makes a gain when an error changes. The 445 Flying start
quicker the deviation changes, the stronger the gain
(FLYING START)
from the differentiator. The gain is proportional to
Value:
the speed at which the deviation changes.
✭Off (DISABLE) [0]
Description of choice: OK - same direction
Quick regulation is obtained with a long differentiation (OK-SAME DIRECTION) [1]
time. However, this time may become too long, which OK - both directions
can make the process unstable due to overswing. (OK-BOTH DIRECTIONS) [2]
DC brake and start
(DC-BRAKE BEF. START) [3]
Function:
The user sets the voltage by which the level for
451 Speed PID feedforward factor resistor braking is reduced. It is only active when
(FEEDFORWARD FACT) resistor in parameter 400 is selected.
Value:
Description of choice:
0 - 500 % ✭ 100 %
The greater the reduction value, the faster the reaction
Function: to a generator overload. Should only be used if there are
This parameter is only active if in parameter 100 problems with overvoltage in the intermediate circuit.
Configuration the selection made is Speed regulation,
closed loop. The FF function sends a larger or smaller
part of the reference signal outside the PID controller
in such a way that the PID controller only has an
influence on part of the control signal. Any change
to the set point will thus have a direct effect on the
motor speed. The FF factor provides high dynamism
when changing the set point and less overswing.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Programming
600 Baud (600 BAUD) [1]
1200 Baud (1200 BAUD) [2] Digital input [0]
2400 Baud (2400 BAUD) [3] Dig. input Ser. port Function
4800 Baud (4800 BAUD) [4] 0 0 Coasting
✭9600 Baud (9600 BAUD) [5] 0 1 Coasting
1 0 Motor running
Function: 1 1 Motor running
This parameter is for programming the speed at which
data is transmitted via the serial port. Baud rate is Serial port [1]
defined as the number of bits transmitted per second. Dig. input Ser. port Function
0 0 Coasting
Description of choice: 0 1 Motor running
The variable frequency drive’s transmission speed 1 0 Coasting
must be set at a value corresponding to the 1 1 Motor running
transmission speed of the master.
Parameter 501 Baudrate cannot be selected via the Logic and [2]
serial port, but must be preset via the operating unit. Dig. input Ser. port Function
0 0 Coasting
0 1 Motor running
1 0 Motor running
1 1 Motor running
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 75
VLT® 2800 Series
Logic or [3]
Dig. input Ser. port Function
0 0 Coasting
0 1 Coasting
1 0 Coasting
1 1 Motor running
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Function: Function:
See function description for parameter 502 See function description for parameter 502
Coasting stop. Coasting stop.
NOTE NOTE
Note that Quick stop inverse and Bit 04 in the Note that DC braking inverse and Bit 02 in the
control word are active at logic ’0’. control word are active at logic ’0’.
Programming
Serial port [1] Serial port [1]
Dig. input Serial port Function Dig. input Ser. port Function
0 0 Quick stop 0 0 DC braking
0 1 Motor running 0 1 Motor running
1 0 Quick stop 1 0 DC braking
1 1 Motor running 1 1 Motor running
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 77
VLT® 2800 Series
Function: Function:
See function description for parameter 502 See function description for parameter 502
Coasting stop. Coasting stop.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Programming
0 1 Setup 2
1 0 Setup 3
1 1 Setup 4
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 79
VLT® 2800 Series
Function: Function:
See function description of parameter 502 In this parameter it is possible to preset the maximum
Coasting stop. time expected to elapse between receipt of two
consecutive telegrams. If this time is exceeded, the
Description of choice:
serial communication is assumed to have stopped
Preset references via serial communication are
and the desired reaction is preset in parameter
active when parameter 512 Telegram profile
514 Bus time interval function.
is set to FC protocol [1].
Description of choice:
Preset the required time.
509 Bus jog 1 (BUS JOG 1 FREQ.)
510 Bus jog 2 (BUS JOG 2 FREQ.)
Value: 514 Bus time interval function
0.0 - par. 202 Output frequency high limit (BUS TIMEOUT FUNC)
✭ 10,0 Hz Value:
✭Off (OFF) [0]
Function: Freeze output frequency (FREEZE OUTPUT) [1]
If parameter 512 Telegram Profile shows the selection
Stop (STOP) [2]
Profidrive [0], two fixed speeds (Jog 1 or Jog 2)
Jogging (JOGGING) [3]
can be selected via the serial port.
Max. speed (MAX SPEED) [4]
The function is the same as in parameter
Stop and trip (STOP AND TRIP) [5]
213 Jog frequency .
Function:
Description of choice:
In this parameter you can select the required reaction
Jog frequency fJOG can be selected between for the variable frequency drive when the preset
0 Hz and fMAX. time in parameter 513 Bus time interval has been
exceeded. If choices [1] to [5] are activated the
output relay will be deactivated.
512 Telegram Profile
Description of choice:
(TELEGRAM PROFILE)
The output frequency of the variable frequency drive
Value:
can be frozen at the present value, stop the motor,
Profidrive (PROFIDRIVE) [0]
be frozen at parameter 213 Jogging frequency, be
✭FC protocol (FC PROTOCOL) [1]
frozen at parameter 202 Output frequency, high
Function: limit fMAX or stop and activate a cut out.
It is possible to choose between two different
control word profiles.
Description of choice:
Select the desired control word profile.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Programming
541 Extended status word (STATUS WORD) Hex
544 Pulse count (PULSE COUNT)
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 81
VLT® 2800 Series
Gives the motor’s present power in kW which Gives the heatsink temperature on the adjustable
the motor absorbs. frequency drive. The trip limit is 194°F - 212°F (90°C
- 100°C), with reset at 158°F ± 9°F (70 ± 5 °C).
Parameter 523, Power [HP]:
Gives the motor’s present voltage in HP which Parameter 538, Alarm word:
the motor absorbs. Gives in Hex code which alarm is on the adjustable
frequency drive. See Warning word, extended
Parameter 524, Motor voltage: status word and alarm word.
Gives the voltage supplied to the motor.
Parameter 539, Control word:
Parameter 525, DC link voltage: Gives the present control word on the adjustable
Gives the intermediate circuit voltage in the frequency drive in Hex. See Serial communication
adjustable frequency drive. for the VLT 2800.
Parameter 526, Thermal load, motor [%]: Parameter 540, Warning word:
Gives the calculated/estimated thermal load on the Gives whether there is a warning on the adjustable
motor. 100% is the trip point. See also parameter frequency drive in Hex. See Warning word, extended
128 Thermal motor protection. status word and alarm word.
Parameter 527, Thermal load INV [%]: Parameter 541, Extended status word:
Gives the calculated/estimated thermal load on the Gives whether there is a warning on the adjustable
adjustable frequency drive. 100% is the cut-out limit. frequency drive in Hex code. See Warning word,
Parameter 528, Digital input: extended status word and alarm word.
Gives the signal status from the 5 digital inputs (18, 19, Parameter 544, Pulse count:
27, 29 and 33). Input 18 corresponds to the bit on the This parameter can be read out via the LCP display
extreme left. ’0’ = no signal, ’1’ = connected signal. (009-012). When you run with counter stop, this
Parameter 529, Terminal 53 analog input [V]: parameter enables you, either with or without reset, to
Gives the voltage value for the signal on terminal 53. read the number of pulses registered by the device.
The highest frequency is 67.6 kHz, while the lowest is 5
Parameter 531, Terminal 60 analog input [mA]: Hz. The counter is reset when counter stop is restarted.
Gives the current value for the signal on terminal 60.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
Description of choice:
Set the required time.
561 Protocol
(PROTOCOL)
Value:
✭FC protocol (FC PROTOKOL) [1]
Metasys N2 (METASYS N2) [2]
Function:
There is a choice of two different protocols.
Description of choice:
Select the required control word protocol.
Programming
580-582 Defined parameters
(DEFINED PNU’S)
Value:
Read only
Function:
The three parameters hold a list of all the parameters
that are defined in the VLT 2800. It is possible to read
single elements of the list by using the corresponding
subindex. The subindexes start at 1 and follow
the order of the parameter numbers.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 83
VLT® 2800 Series
■ Technical functions
Function: NOTE
These parameters can be read out via the serial Parameters 615-617 Fault log cannot be read
communication port and the LCP control unit. out via the integral control unit.
Description of choice:
Parameter 600, Operating hours: 615 Fault log: Error code
Gives the number of hours the adjustable frequency
([Link]: ERROR COD)
drive has been operating. The value is saved
Value:
every hour and when there is an AC line failure.
[Index 1 - 10] Error code: 0 - 99
This value cannot be reset.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
saved data value, and the highest log number Description of choice:
[10] contains the oldest data value. If Reset [1] is selected and you press the [OK] key,
the variable frequency drive’s parameter 601 is
Description of choice:
reset to zero Hours run. This parameter cannot
Read out as one value. be selected via serial communication.
NOTE
When the [OK] key is activated the
617 Fault log: Value
parameter is reset to zero.
([Link]: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999 620 Operation Mode
Function: (OPERATION MODE)
In this parameter it is possible to see at which value a Value:
trip occurred. The unit of the value depends on which ✭Normal operation (NORMAL OPERATION) [0]
alarm is active in parameter 615 Fault log: Fault code . Control card test (CONTROL CARD TEST) [2]
Initialize (INITIALIZE) [3]
Description of choice:
Read out as one value. Function:
In addition to its normal function, this parameter
can be used to test the control card.
There is also the opportunity to perform an
618 Reset of kWh counter
initialization at the factory setting for all parameters
(RESET KWH COUNT)
in all Setups, with the exception of parameters
Value: 500 Address, 501 Baudrate, 600-605 Operating
✭No reset (DO NOT RESET) [0] data and 615-617 Fault log.
Reset (RESET COUNTER) [1]
Programming
Description of choice:
Function: Normal function [0] is used for normal
Resetting parameter 602 kWh counter to zero. operation of the motor.
Description of choice: Control card test [2] is selected if you wish to check
If Reset [1]is selected and you press the [OK] the control card’s analog/digital inputs, analog/digital
key, the variable frequency drive’s kWh counter outputs, relay outputs and 10 V and 24 V voltages.
is reset to zero. This parameter cannot be The test is performed as follows:
selected via serial communication. 27 - 29 - 33 - 46 are connected.
50 - 53 are connected.
NOTE
42 - 60 are connected.
When the [OK] key is activated, the
12 - relay terminal 01 is connected.
counter is reset to zero.
18 - relay terminal 02 is connected.
19 - relay terminal 03 is connected.
619 RESET RUNNING HOURS COUNTER See also the DeviceNet manual [Link]
(RESET RUN. HOUR) for further details.
Value:
✭No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Resetting of parameter 601 Hours run to zero.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 85
VLT® 2800 Series
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
621-642 Nameplate
Value:
Par. Description Display text
no Nameplate
621 Unit type (DRIVE TYPE)
624 Software version (SOFTWARE VERSION)
625 LCP identification no. (LCP VERSION)
626 Database identification no. (DATABASE VER.)
627 Power parts version (POWER UNIT DB ID)
628 Application option type (APP. OPTION)
630 Communication option type (COM. OPTION)
632 BMC software identification (BMC-SOFTWARE ID)
634 Unit identification for communication (UNIT ID)
635 Software parts no. (SW. PART NO.)
640 Software version (SOFTWARE VERSION)
641 BMC-software identification (BMC2 SW)
642 Power card identification (POWER ID)
Description of choice:
Parameter 621 Nameplate: Unit type:
Gives unit size and AC line voltage.
Example: VLT 2811 380-480 V.
Programming
Parameter 624 Nameplate: Software version no.:
The unit’s present software version number
appears here.
Example: V 1.00
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A8.22 - VLT is a registered Danfoss trademark 87
VLT® 2800 Series
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
LED indication
Warning yellow
Alarm red
Trip locked yellow and red
WARNING/ALARM 2: Live zero fault DC bus can occur if the motor frequency is reduced
The voltage or current signal on terminal 53 or too quickly due to ramp-down time being too short.
60 is below 50% of the preset value in parameter
309 or 315 Terminal, min. scaling. WARNING/ALARM 8: Undervoltage
If the DC bus voltage is lower than the inverter’s
WARNING/ALARM 4: AC line phase fault Undervoltage limit, the inverter will switch off until the
Missing phase on AC line supply side. VDC once more goes above the undervoltage limit.
Check the supply voltage to the adjustable frequency Check whether the supply voltage fits the adjustable
drive. This fault is only active in 3-phase AC line. frequency drive. (See Technical data.) If the VDC
remains under the undervoltage limit, the inverter will
WARNING 5: Voltage warning high trip after a fixed period of time. The time depends on
If the DC bus voltage (VDC) is higher than the unit and is set at 1 - 3 sec. When the adjustable
Voltage warning high, the adjustable frequency frequency drive is switched off an alarm 8 (and warning
drive will give a warning and the motor will 6) is displayed briefly and a trip reset is generated.
continue to operate unchanged.
NOTE: Voltage warning low (warning 6) will thus
Check whether the supply voltage matches the rating also be able to generate an alarm 8.
of the adjustable frequency drive. (See Technical data.)
If the VDC remains above the voltage warning limit, the WARNING/ALARM 9: Inverter overload
inverter will trip after a fixed period of time. The time Electronic thermal inverter protection indicates that the
depends on the unit and is set at 5 - 10 sec. adjustable frequency drive is close to disconnecting due
to overloading (output current too high for too long). The
NOTE: The adjustable frequency drive will trip with counter for electronic thermal inverter protection gives
an alarm 7 (overvoltage). A voltage warning can also a warning at 98% and trips at 100% giving an alarm.
occur if the motor frequency is reduced too quickly
due to the ramp down time being too short. The adjustable frequency drive cannot be reset
until the counter is below 90%. Remove the
WARNING 6: Voltage warning low overload condition to the drive.
If the DC bus voltage (VDC) is lower than Voltage warn
low, the adjustable frequency drive will give a warning WARNING/ALARM 10: Motor overloaded
and the motor will continue to operate unchanged. According to the electronic thermal inverter protection
the motor is too hot. In parameter 128 the user can
Check whether the supply voltage matches the rating select whether the VLT adjustable frequency drive
of the adjustable frequency drive. (See Technical data.) should emit a warning or an alarm when the counter
NOTE: The adjustable frequency drive will trip with reaches 100%. This fault is due to the motor being
an alarm 5 (undervoltage). When the adjustable overloaded by more than 100% for too long.
frequency drive is switched off, a warning 6 (and Check that motor parameters 102-106 are set correctly.
warning 8) is displayed briefly.
WARNING/ALARM 11: Motor thermistor
WARNING/ALARM 7: Overvoltage The motor is too hot or the thermistor/thermistor
If the DC bus voltage (VDC) is higher than the inverter’s connection is cut off. Parameter 128 Motor thermal
Overvoltage limit, the inverter will switch off until the protection allows a choice of whether the adjustable
VDC once more falls below the overvoltage limit. If the frequency drive is to give a warning or an alarm.
VDC remains above the overvoltage limit, the inverter
will trip after a fixed period of time. The time depends Check that the PTC thermistor has been correctly
on the unit and is set at 5 - 10 sec. When the inverter connected between terminal 18, 19, 27 or 29 (digital
is switched off a trip reset is generated. input) and terminal 50 (+10 V supply).
ALARM: 14: Ground fault If the VLT adjustable frequency drive is in a mode other
There is a discharge from the output phases to ground, than Process regulation, closed loop (parameter 100)
either in the cable between the adjustable frequency the warning will be active in the display. If the VLT
drive and the motor, or in the motor. adjustable frequency drive is in a mode other than
Process regulation, closed loop bit 008000 Out of
Turn off the adjustable frequency drive and frequency range in the extended status word will be
remove the ground fault. active, but there will be no warning in the display.
ALARM: 15: Switch mode fault WARNING/ALARM: 34: HPFB communication fault
Fault in switch mode power supply (internal supply). Communication fault only occurs in Profibus versions.
Contact your Danfoss supplier. ALARM 35: Inrush fault
This alarm appears when the adjustable frequency
ALARM: 16: Short-circuit
drive has been connected to the AC line supply
There is a short-circuit on the motor terminals
too many times within 1 minute.
or in the motor.
WARNING/ALARM 36: Overtemperature
Disconnect the AC line supply to the adjustable
If the temperature of the heatsink moves above
frequency drive and remove the short-circuit.
167°F - 185°F (75° - 85°C), depending on the unit,
WARNING/ALARM 17: Serial commu- the adjustable frequency drive gives a warning,
nication timeout and the motor continues to operate unchanged.
All about VLT
There is no serial communication to the If the temperature continues to rise, the switching
2800
The warning will only be active when parameter 514 Bus See Temperature-dependent switching frequency .
time interval function has been set to a value other than If the temperature of the heatsink rises above 199°F
OFF. If parameter 514 Bus time interval function has - 212°F (92 - 100 °C), depending on the unit, the
been set to Stop and trip [5], it will first give a warning adjustable frequency drive will trip.
and then until it trips and issues an alarm. Parameter
The temperature fault cannot be reset until the
513 Bus time interval could possibly be increased.
temperature of the heatsink has dropped to below
158°F (70 °C). The tolerance is ±9°F (±5 °C). The
temperature can be caused by the following:
- Ambient temperature too high.
- Motor cable too long.
ALARM 41: Internal fault number 4 ALARM 52: AMT faulty motor phase
Data values error in EEPROM. The motor current in at least one of the motor
phases is too low.
ALARM 42: Internal fault number 5
Fault in motor parameter database. ALARM 55: AMT timeout
The calculations are taking too long, possibly
ALARM 43: Internal fault number 6 due to noise in the motor cables.
General power card fault.
ALARM 56: AMT warning during AMT
ALARM 44: Iinternal fault number 7 An adjustable frequency drive warning is given
Minimum software version of control card or BMC2. while AMT is being performed.
NOTE
When restarting after an alarm 38-45,
the VLT adjustable frequency drive will
display an alarm 37. In parameter 615 the
actual alarm code can be read.
Alarm/warning limits:
Without brake With brake Without brake With brake
VLT 2800 1 / 3 x 200 - 240 V 1 / 3 x 200 - 240 V 3 x 380 - 480 V 3 x 380 - 480 V
[VDC] [VDC] [VDC] [VDC]
Undervoltage 215 215 410 410
Voltage warning low 230 230 440 440
Voltage warning high 385 400 765 800
Overvoltage 410 410 820 820
The voltages stated are the intermediate circuit of ± 5 %. The corresponding line voltage is the
voltage of the frequency converter with a tolerance intermediate circuit voltage divided by 1.35.
■ Special conditions of aggressive gases in the air are black copper rails
and cable ends on existing electrical installations.
■ Extreme environments
An adjustable frequency drive contains a number
of mechanical and electronic components which ■ Galvanic isolation (PELV)
are vulnerable to environmental impact. PELV (Protective Extra-Low Voltage) separation is
Do not install the adjustable frequency drive achieved with galvanic separators between control
circuits and circuits connected to the AC line potential.
in environments where liquids, particles
or gases in the air would damage the These separators meet the requirements for increased
electronics of the drive. Take all necessary measures isolation in standard EN 50 178. Installation must be in
accordance with local and national PELV regulations.
to protect the drive. There is a risk of fault trips
and reduced service life of the drive. All control terminals, terminals for serial communication
and relay terminals are safely separated from the
Liquids carried through the air can condense in the
AC line potential, i.e. they comply with the PELV
adjustable frequency drive. Liquids may facilitate
requirements. Circuits that are connected to control
galvanic corrosion of components and metal parts.
terminals 12, 18, 19, 20, 27, 29, 33, 42, 46, 50, 55,
Steam, oil and brine may also cause corrosion of
53 and 60 are galvanically connected to one another.
components and metal parts. In these areas, it
Serial communication connected to terminals 67 -
is recommended to install units in cabinets. As a
70 is galvanically isolated from the control terminals,
minimum, cabinets should meet NEMA 12.
although this is only a functional isolation.
Particles in the air, such as dust, may lead to The relay contacts in terminals 1 - 3 are separated
mechanical, electrical and thermal faults in the from the other control circuits with increased isolation,
adjustable frequency drive. A typical indicator i.e. these comply with PELV even if there is AC
of too many particles in the air is dust around line potential in the relay terminals.
the fan. In very dusty areas, mounting the drive
The circuit elements described below form the safe
in a cabinet is recommended. As a minimum,
electric separation. They fulfill the requirements
cabinets should meet NEMA 12.
for increased isolation and associated testing
Aggressive gases, such as sulfur, nitrogen and pursuant to EN 50 178.
chlorine compounds, together with high humidity and 1. Optical isolation between basic motor control
temperature, facilitate possible chemical processes and control card.
on the components of the adjustable frequency 2. Optical isolation between basic motor control
drive. These chemical processes quickly damage the and control card.
electronics. In these areas, mounting in a cabinet with 3. Isolation between the control card and
fresh-air circulation is recommended, thereby ensuring the power part.
that aggressive gases are kept away from the drive. 4. Relay contacts and terminals relating to other
circuits on the control card.
NOTE
Installation of adjustable frequency drives PELV isolation of the control card is guaranteed
in extreme environments increases the risk under the following conditions:
of down-time, and considerable reduction - TT network with maximum 300 Vrms between
of the service life of the drive. phase and ground.
- TN network with maximum 300 Vrms between
Before the adjustable frequency drive is installed, check phase and ground.
whether there are liquids, particles or gases in the air. - IT network with maximum 400 Vrms between
Examine existing installations in the same environment. phase and ground.
Typical indicators of harmful airborne liquids are water or At higher voltages only SELV is achieved.
oil on metal parts or corrosion. Too many dust particles
are typically observed on top of cabinets. Indication
■ UL Standard
This device is UL-approved.
Torque characteristics:
Starting torque (parameter 101 Torque characteristic = Continuous torque) .................................. 160% in 1 min.*
Starting torque (parameter 101 Torque characteristics = Variable torque) ...................................... 160% in 1 min.*
Starting torque (parameter 119 High starting torque ) ................................................................ 180% for 0.5 sec.*
Overload torque (parameter 101 Torque characteristic = Continuous torque) ............................................... 160%*
Overload torque (parameter 101 Torque characteristic = Variable torque) ..................................................... 160%*
*Percentage relates to adjustable frequency drive’s nominal current.
Relay outputs:
Number of programmable relay outputs ................................................................................................................ 1
Terminal number, control card ............................................................................................. 1-3 (break), 1-2 (make)
Max. terminal load (AC) on 1-3, 1-2, control card ........................................................................... 240 V AC, 2 A
Min. terminal load on 1-3, 1-2, control card ...................................................... 24 V DC 10 mA, 24 V AC 100 mA
The relay contact is separated from the rest of the circuit by strengthened isolation.
See section entitled Galvanic Isolation.
Max. cross section to control cables, cable with enclosed core .................................................. 0.5 mm2/20 AWG
When complying with EN 55011 1A and EN 55011 1B the motor cable must be reduced in certain instances.
Control characteristics:
Frequency range ............................................................................................................ 0.2 - 132 Hz, 1 - 1000 Hz
Resolution of output frequency ......................................................................................... 0.013 Hz, 0.2 - 1000 Hz
Repeat accuracy of Precise start/stop (terminals 18, 19) .................................................................... ≤ ± 0.5 msec
System response time (terminals 18, 19, 27, 29, 33) .......................................................................... ≤ 26.6 msec
Speed control range (open loop) .................................................................................. 1:15 of synchronous speed
Speed control range (closed loop) .............................................................................. 1:120 of synchronous speed
Speed accuracy (open loop) ....................................................................... 90 - 3600 rpm: Max. error of ±23 rpm
Speed accuracy (closed loop) .................................................................... 30 - 3600 rpm: Max. error of ±7.5 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Enclosure ....................................................................................................................................................... IP 20
Enclosure with options ............................................................................................................................... NEMA 1
Vibration test ............................................................................................................................................ 0.037 oz
Max. relative humidity .................................................................................................. 5% - 93% during operation
Ambient temperature .................................................. Max. 122 °F (45 °C) (24-hour average max. 113 °F (40 °C))
Derating for ambient temperature, see special conditions in the Design Guide
Min. ambient temperature during full-scale operation .......................................................................... 32 °F (0 °C)
Min. ambient temperature at reduced performance ......................................................................... 14 °F (-10 °C)
Temperature during storage/transport ............................................................ -13 - +150/160 °F (-25 - +65/70 °C)
Max. altitude above sea level ........................................................................................................ 3280 ft (1000 m)
Derating for air pressure, see special conditions in the Design Guide
EMC standards, Emission ............................................................................. EN 50081-2, EN 61800-3, EN 55011
EMC standards, Immunity .................................................................................................................................. EN
50082-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61800-3
See section on special conditions in the Design Guide
Safeguards:
According to international standards Type 2803 2805 2807 2811 2815 2822 2840
Output current IINV. [A] 2.2 3.2 4.2 6.0 6.8 9.6 16
(3 x 200-240V) IMAX (60s) [A] 3.5 5.1 6.7 9.6 10.8 15.3 25.6
Output power (230 V) SINV. [KVA] 0.9 1.3 1.7 2.4 2.7 3.8 6.4
Typical shaft output PM,N [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3.7
Typical shaft output PM,N [HP] 0.5 0.75 1.0 1.5 2.0 3.0 5.0
Max. cable cross [mm2/AWG] 1) 4/10 4/10 4/10 4/10 4/10 4/10 4/10
section, motor
According to international standards Type 2805 2807 2811 2815 2822 2830
Output current IINV. [A] 1.7 2.1 3.0 3.7 5.2 7.0
(3 x 380-480V) IMAX (60s) [A] 2.7 3.3 4.8 5.9 8.3 11.2
Output power (400 V) SINV. [KVA] 1.1 1.7 2.0 2.6 3.6 4.8
Typical shaft output PM,N [kW] 0.55 0.75 1.1 1.5 2.2 3.0
Typical shaft output PM,N [HP] 0.75 1.0 1.5 2.0 3.0 4.0
Max. cable cross [mm2/AWG] 1) 4/10 4/10 4/10 4/10 4/10 4/10
section, motor
Input current IL,N [A] 1.6 1.9 2.6 3.2 4.7 6.1
(3 x 380-480 V) IL,MAX(60s)[A] 2.6 3.0 4.2 5.1 7.5 9.8
Max. cable cross [mm2/AWG] 1) 4/10 4/10 4/10 4/10 4/10 4/10
section, power
Max. pre-fuses IEC/UL2) [A] 20/20 20/20 20/20 20/20 20/20 20/20
Efficiency3) [%] 96 96 96 96 96 96
Power loss at 100% [W] 28 38 55 75 110 150
load
Weight [lb]/[kg] 4.6/2.1 4.6/2.1 4.6/2.1 4.6/2.1 8.2/3.7 8.2/3.7
Enclosure4 type IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
According to international standards Type 2840 2855 2875 2880 2881 2882
Output current IINV. [A] 9.1 12 16 24 32.0 37.5
(3 x 380-480V) IMAX (60s) [A] 14.5 19.2 25.6 38.4 51.2 60.0
Output power (400 V) SINV. [KVA] 6.3 8.3 11.1 16.6 22.2 26.0
Typical shaft output PM,N [kW] 4.0 5.5 7.5 11.0 15.0 18.5
Typical shaft output PM,N [HP] 5.0 7.5 10.0 15.0 20.0 25.0
Max. cable cross [mm2/AWG] 1) 4/10 4/10 4/10 16/6 16/6 16/6
section, motor
Input current IL,N [A] 8.1 10.6 14.9 24.0 32.0 37.5
(3 x 380-480 V) IL,MAX(60s)[A] 13.0 17.0 23.8 38.4 51.2 60
Max. cable cross [mm2/AWG] 1) 4/10 4/10 4/10 16/6 16/6 16/6
section, power
Max. pre-fuses IEC/UL2) [A] 20/20 25/25 25/25 50/50 50/50 50/50
Efficiency3) [%] 96 96 96 97 97 97
Power loss at 100% [W] 200 275 372 412 562 693
All about VLT
load
Weight [lb]/[kg] 3.7/8.2 13.2/6.0 13.2/6.0 40.8/18.5 40.8/18.5 40.8/18.5
2800
■ Available literature
4-Setup:
’Yes’ means that the parameter can be programmed
Data type:
individually in each of the four Setups, i.e. one single
Data type shows the type and length of the telegram.
parameter can have four different data values. ’No’
means that the data value will be the same in all Setups. Data type Description
3 Integer 16
Conversion index: 4 Integer 32
This number refers to a conversion figure to be used 5 Unsigned 8
when writing or reading via serial communication 6 Unsigned 16
All about VLT
4-Setup:
’Yes’ means that the parameter can be programmed
Data type:
individually in each of the four Setups, i.e. one single
Data type shows the type and length of the telegram.
parameter can have four different data values. ’No’
means that the data value will be the same in all Setups. Data type Description
3 Integer 16
Conversion index: 4 Integer 32
This number refers to a conversion figure to be used 5 Unsigned 8
when writing or reading via serial communication 6 Unsigned 16
with a variable frequency drive. 7 Unsigned 32
See Data character in Serial communication 9 Text string
in the Design Guide.
4-Setup:
’Yes’ means that the parameter can be programmed
Data type:
individually in each of the four Setups, i.e. one single
Data type shows the type and length of the telegram.
parameter can have four different data values. No’
means that the data value will be the same in all Setups. Data type Description
3 Integer 16
Conversion index: 4 Integer 32
This number refers to a conversion figure to be used 5 Unsigned 8
when writing or reading via serial communication 6 Unsigned 16
with a variable frequency drive. 7 Unsigned 32
All about VLT
A E
AC brake .................................................................... 67 Electrical installation ...................................................... 14
AC line connection ........................................................ 16 Electrical installation, control circuitry ................................. 18
Active Setup ................................................................ 32 EMC-correct electrical installation ..................................... 11
Address ...................................................................... 75 ETR - Electronic Thermal Relay ........................................ 45
Analog input ............................................................... 60 Extreme environments ................................................... 94
Analog output .............................................................. 62
Automatic motor tuning .................................................. 41
F
Fan control .................................................................. 48
B Fault log ..................................................................... 84
Baudrate ..................................................................... 75 Feedback, ................................................................... 68
Brake connection .......................................................... 17 Flying start .................................................................. 73
Brake cut in frequency ................................................... 47 Four Setups................................................................. 32
Brake cut out value ....................................................... 47 Frequence bypass, bandwidth ......................................... 56
Brake function .............................................................. 67 Function at stop ........................................................... 44
Brake resistance ........................................................... 18
Brake Voltage Reduce ................................................... 74
Bus jog ....................................................................... 80 G
Bus time interval ........................................................... 80 Gain AC brake ............................................................. 48
Galvanic isolation (PELV) ................................................. 94
Ground connection ....................................................... 17
C Grounding ................................................................... 10
control panel ................................................................ 24 Grounding of shielded/armoured control cables ................... 12
Catch up .................................................................... 54
CHANGE DATA ............................................................ 24
Connection of a 2-wire transmitter .................................... 22 H
Constant torque ........................................................... 39 Hand / Auto mode operation ........................................... 27
Control keys ................................................................ 24 Hand mode ................................................................. 37
Control terminals .......................................................... 18 High voltage test ........................................................... 10
Control unit ................................................................. 24 High voltage warning .................................................. 4, 10
Control wires ............................................................... 19
Counter value .............................................................. 66
Current limit, ................................................................ 54
I
Initialize....................................................................... 85
Current, minimum value .................................................. 47
Input fuses .................................................................. 16
IP 21 solution ................................................................. 6
D
Data readout................................................................ 25
DC brake time .............................................................. 44
J
Jog frequency .............................................................. 53
DC brake voltage .......................................................... 46
Jog ramp time .............................................................. 53
DC hold voltage ............................................................ 47
Diagram ...................................................................... 13
Digital / pulse output ...................................................... 64
L
Digital inputs ................................................................ 58
Language.................................................................... 31
Dimensions ................................................................... 5
Large display readout .................................................... 33
Direction of motor rotation .............................................. 16
LCP copy .................................................................... 32
Display mode ............................................................... 25
Leakage reactance ........................................................ 48
Display readout ............................................................ 27
Literature ...................................................................102
Display scaling of output frequency ................................... 33
Start/stop ................................................................... 22
Programming Setup ...................................................... 32
Stator reactance ........................................................... 42
2800
Terminal 46 .................................................................. 64
Terminal 53 .................................................................. 60
Terminal 60 .................................................................. 61
Terminal cover ................................................................ 6
Terminals .................................................................... 22
Thermal motor protection ............................................... 44
Thermistor .............................................................. 45, 59
Tightening Torque, Power Terminals .................................. 18
Time out ..................................................................... 61
Torque characteristic ..................................................... 39
U
U/f-ratio ...................................................................... 46
UL Standard ................................................................ 94
V
Variable torque ............................................................. 39
VLT 2800 start-up ......................................................... 29
VLT Software Dialog ...................................................... 21
W
Warning functions ........................................................ 54
Warning words, extended status words and alarmwords ....... 93
Warnings/alarm messages and ....................................... 89
Warnings/alarms ........................................................... 28