FL33818.
06-R5
GulfPBRTM
Gulf Coast Supply & Manufacturing 14229 SW 2nd Pl G30, Newberry FL 32669
Product Description: PBR exposed fastener panel with nominal 36” max coverage and nominal rib height
of 1-1/4”.
Product Material:
Material: 24ga (min) or 26ga (min) steel (corrosion resistant per FBC 1507.4.3 where required)
Fastener: #9 or #10 fastener Compliant with FBC 1506.6 where required.
Fastener:
Maximum Allowable Loads & Installation Requirements:
Allowable
System
Deck/Substrate Roof Panel Panel Attachment Pressure
No
(psf)
#9 fastener in 12”-12” pattern (1 per rib), fastener rows at
15/32” (min) plywood or 26ga (min)
GP-1 24” o.c. 1/4” lap fastener at 24” o.c and with continuous -60.5
¾” (min) wood plank PBR panel
bead of sealant or butyl tape in side lap.
#9 fastener in 7”-5”-7”-5” pattern (1 per rib), fastener rows
15/32” (min) plywood or 26ga (min)
GP-2 at 12” o.c. 1/4” lap fastener at 24” o.c and with continuous -154.75
54.75
¾” (min) wood plank PBR panel
bead of sealant or butyl tape in side lap.
#9 fastener in 12”-12” pattern (1 per rib), fastener rows at
1x4 SYP (nom, or better)
26ga (min) 24” o.c. 1/4” lap fastener at 24” o.c and with continuous
GP-3 on 15/32” (min) plywood -100.5
PBR panel bead of sealant or butyl tape in side lap. 1x4s attached to
or ¾” (min) wood plank
plywood with 8Dx2.5” ring shank nails at 4” o.c.
#9 fastener in 7”-5”-7”-5” pattern (1 per rib), fastener rows
1x4 SYP (nom, or better)
26ga (min) at 12” o.c. 1/4” lap fastener at 24” o.c and with continuous
GP-4 on 15/32” (min) plywood -151.75
PBR panel bead of sealant or butyl tape in side lap. 1x4s attached to
or ¾” (min) wood plank
plywood with 8Dx2.5” ring shank nails at 4” o.c.
A factor of safety of 2 has been applied. Digitally signed
by Locke D.
Bowden
Evaluated by: Date: 2024.05.16
13:23:37 -05'00'
David Eng, PE
Timberlake Cove, LLC
1317 Edgewater Dr, Ste 2339
Orlando FL
FL PE 81377 | FL CA 37675
www.TimberLakeCove.com
METAL ROOFING PRODUCTS
Digitally signed by
David E Eng
Date: 2024.05.01
21:32:59-04'00'
This item has been digitally signed and sealed by D.E. Eng, PE, on the date indicated. 1.888.393.0335
Printed copies of this document are not considered signed and sealed and the
signature must be verified on any electronic copies
www.GulfCoastSupply.com
GulfPBRTM FL33818.06-R5
Maximum Allowable Loads & Installation Requirements:
Allowable
System
Deck/Substrate Roof Panel Panel Attachment Pressure
No
(psf)
#12 fastener in 12”-12” pattern, purlins at 60” o.c. ¼” lap
16ga (min) steel
GP-5 26ga (min) PBR panel fastener at 20” o.c. and with continuous bead of sealant or -40
purlins at 60” o.c.
butyl tape in side lap.
#12 fastener in 12”-12” pattern, purlins at 60” o.c. ¼” lap
16ga (min) steel
GP-6 24ga (min) PBR panel fastener at 20” o.c. and with continuous bead of sealant or -60
purlins at 60” o.c.
butyl tape in side lap.
#12 fastener in 12”-12” pattern, purlins at 24” o.c. ¼” lap
16ga (min) steel
GP-7 24ga (min) PBR panel fastener at 20” o.c. and with continuous bead of sealant or -150
purlins at 24” o.c.
butyl tape in side lap.
A factor of safety of 2 has been applied.
Page 2 www.GulfCoastSupply.com
GulfPBRTM FL33818.06-R5
Underlayment: Comply with local building code or FBC 1507.1.1 where required.
Slope: Comply with local building code or FBC 1507.4.2 where required.
Re-
Re-Roofing:
Roofing This panel may be installed over a single layer of existing shingles as permitted by local building code or FBC
1511, provided the existing roof meets the conditions required by the applicable code.
Fire Barrier: Comply with FBC 1516.1 and 1516.2 where required. Optional where not required by code.
Insulation (optional): ISO board or other insulation is permitted between steel deck and panels. Increase fastener length
to penetrate ¼” beyond underside of substrate. Comply with FBC 1508 and 1519.11 where required.
Compliance Statement: This product as described has demonstrated compliance with Florida Building Code 2023,
1504.3.2 (non
non-
non-HVHZ),
HVHZ as required by FL Rule 61G20-3, method 1D.
This product as described has been tested and demonstrated compliance with:
• UL580 – Test for Uplift Resistance of Roof Assemblies
• UL 1897 – Uplift test for roof covering systems
Technical Documentation:
• Force Engineering (TST-5328), TAS 125/UL 580/ASTM E1592, reports 117-0062T-07G-I, 117-0331T-08C, 84-0320T-
06A-D
Design Process: Compare the maximum allowable loads to the ASD uplift pressures for the project to determine
sufficiency and installation requirements. Alternatively, as an option, the load tables in this report may be used to identify
the pressure required for roofs within the parameters described.
For roofs outside of the listed parameters, design wind loads shall be determined as required by FBC 1609, ASCE 7, or
other design code in force, using allowable stress. These load tables are based on ASCE 7-22. Use of these tables assumes
that the structure is: Enclosed, partially enclosed, or partially open and conforms to wind-borne debris provisions and is a
regular shaped building and is not subject to across-wind loading, vortex shedding, or instability; nor does it have a site
location for which channeling or buffeting warrant consideration
Engineering analysis may be completed by other licensed engineers for project specific approval by local authorities
having jurisdiction.
Certification of Independence: David Eng, PE and Timberlake Cove, LLC do not have, nor will acquire a financial interest in
any company manufacturing or distributing products under this evaluation. The same entities do not have, nor will
acquire, a financial interest in any other entity involved in the approval process of the product.
Exclusions and Limitations: Design of deck and roof structure (to include attachment of substrate) shall be completed by
others. Fire classification and shear diaphragm design are outside the scope of this evaluation. Accelerated
weathering/salt spray is outside the scope of this evaluation.
This report is limited to compliance with structural wind load requirements of FBC 1504.3.2, as required by Rule 61G20-3.
Neither Timberlake Cove nor the manufacturer shall be responsible for any conclusions, interpretations, or designs made
by others based on this evaluation report. This report is limited solely to documenting compliance with Rule 61G20-3, and
makes no express or implied warranty regarding performance of this product. Installation shall be subject to the local
building code and authority having jurisdiction; this report shall not be construed to supersede local codes in force.
Page 3 www.GulfCoastSupply.com
GulfPBRTM FL33818.06-R5
Allowable Design Pressures required for Gable and Hip Roofs in Exposure B with roof slope between 2:12 and 12:12
Mean Roof Ultimate Windspeed (mph)
Building Type Zone
Height (ft) 120 130 140 150 160 170 180 190 200
20 -25.4 -29.8 -34.6 -39.7 -45.2 -51.0 -57.2 -63.7 -70.6
25 -27.1 -31.7 -36.8 -42.3 -48.1 -54.3 -60.9 -67.8 -75.1
30 -28.7 -33.7 -39.0 -44.8 -51.0 -57.6 -64.6 -71.9 -79.7
1
40 -30.3 -35.6 -41.3 -47.4 -53.9 -60.9 -68.2 -76.0 -84.2
50 -32.4 -38.0 -44.1 -50.6 -57.6 -65.0 -72.9 -81.2 -89.9
60 -34.0 -39.9 -46.3 -53.2 -60.5 -68.3 -76.5 -85.3 -94.5
20 -33.6 -39.4 -45.7 -52.5 -59.7 -67.4 -75.5 -84.2 -93.3
25 -35.7 -41.9 -48.6 -55.8 -63.5 -71.7 -80.4 -89.6 -99.3
Enclosed or 30 -37.9 -44.5 -51.6 -59.2 -67.4 -76.1 -85.3 -95.0 -105.3
2
Partially Open 40 -40.1 -47.0 -54.5 -62.6 -71.2 -80.4 -90.2 -100.4 -111.3
50 -42.8 -50.2 -58.2 -66.8 -76.0 -85.8 -96.2 -107.2 -118.8
60 -44.9 -52.7 -61.2 -70.2 -79.9 -90.2 -101.1 -112.7 -124.8
20 -44.1 -51.7 -60.0 -68.8 -78.3 -88.4 -99.1 -110.5 -122.4
25 -46.9 -55.0 -63.8 -73.3 -83.4 -94.1 -105.5 -117.6 -130.3
30 -49.7 -58.4 -67.7 -77.7 -88.4 -99.8 -111.9 -124.7 -138.2
3
40 -52.6 -61.7 -71.6 -82.2 -93.5 -105.5 -118.3 -131.8 -146.1
50 -56.1 -65.9 -76.4 -87.7 -99.8 -112.7 -126.3 -140.7 -156.0
60 -59.0 -69.2 -80.3 -92.2 -104.9 -118.4 -132.7 -147.9 -163.8
20 -29.7 -34.9 -40.5 -46.4 -52.8 -59.7 -66.9 -74.5 -82.6
25 -31.6 -37.1 -43.1 -49.4 -56.3 -63.5 -71.2 -79.3 -87.9
30 -33.6 -39.4 -45.7 -52.4 -59.7 -67.4 -75.5 -84.1 -93.2
1
40 -35.5 -41.6 -48.3 -55.4 -63.1 -71.2 -79.8 -88.9 -98.5
50 -37.9 -44.4 -51.6 -59.2 -67.3 -76.0 -85.2 -94.9 -105.2
60 -39.8 -46.7 -54.2 -62.2 -70.7 -79.9 -89.5 -99.8 -110.5
20 -37.9 -44.5 -51.6 -59.2 -67.3 -76.0 -85.2 -95.0 -105.2
25 -40.3 -47.3 -54.9 -63.0 -71.7 -80.9 -90.7 -101.1 -112.0
Partially 30 -42.8 -50.2 -58.2 -66.8 -76.0 -85.8 -96.2 -107.2 -118.8
2
Enclosed 40 -45.2 -53.1 -61.5 -70.6 -80.4 -90.7 -101.7 -113.4 -125.6
50 -48.3 -56.7 -65.7 -75.4 -85.8 -96.9 -108.6 -121.0 -134.1
60 -50.7 -59.5 -69.0 -79.2 -90.2 -101.8 -114.1 -127.1 -140.9
20 -48.4 -56.8 -65.8 -75.6 -86.0 -97.1 -108.8 -121.3 -134.4
25 -51.5 -60.4 -70.1 -80.5 -91.5 -103.3 -115.9 -129.1 -143.0
30 -54.6 -64.1 -74.3 -85.3 -97.1 -109.6 -122.9 -136.9 -151.7
3
40 -57.7 -67.8 -78.6 -90.2 -102.6 -115.9 -129.9 -144.7 -160.4
50 -61.6 -72.3 -83.9 -96.3 -109.6 -123.7 -138.7 -154.5 -171.2
60 -64.8 -76.0 -88.1 -101.2 -115.1 -130.0 -145.7 -162.3 -179.9
Page 4 www.GulfCoastSupply.com
GulfPBRTM FL33818.06-R5
Allowable Design Pressures required for Gable and Hip Roofs in Exposure C with roof slope between 2:12 and 12:12
Mean Roof Ultimate Windspeed (mph)
Building Type Zone
Height (ft) 120 130 140 150 160 170 180 190 200
20 -36.9 -43.3 -50.2 -57.6 -65.6 -74.0 -83.0 -92.5 -102.5
25 -38.5 -45.2 -52.4 -60.2 -68.5 -77.3 -86.7 -96.6 -107.0
30 -40.2 -47.1 -54.7 -62.8 -71.4 -80.6 -90.4 -100.7 -111.6
1
40 -42.6 -50.0 -58.0 -66.6 -75.8 -85.5 -95.9 -106.9 -118.4
50 -44.7 -52.4 -60.8 -69.8 -79.4 -89.7 -100.5 -112.0 -124.1
60 -46.3 -54.4 -63.0 -72.4 -82.3 -92.9 -104.2 -116.1 -128.6
20 -48.7 -57.2 -66.3 -76.1 -86.6 -97.8 -109.6 -122.2 -135.4
25 -50.9 -59.7 -69.3 -79.5 -90.5 -102.1 -114.5 -127.6 -141.4
Enclosed or 30 -53.1 -62.3 -72.2 -82.9 -94.3 -106.5 -119.4 -133.0 -147.4
2
Partially Open 40 -56.3 -66.1 -76.6 -88.0 -100.1 -113.0 -126.7 -141.2 -156.4
50 -59.0 -69.3 -80.3 -92.2 -104.9 -118.4 -132.8 -148.0 -163.9
60 -61.2 -71.8 -83.3 -95.6 -108.8 -122.8 -137.7 -153.4 -170.0
20 -64.0 -75.1 -87.1 -99.9 -113.7 -128.4 -143.9 -160.3 -177.7
25 -66.8 -78.4 -90.9 -104.4 -118.8 -134.1 -150.3 -167.5 -185.6
30 -69.6 -81.7 -94.8 -108.8 -123.8 -139.8 -156.7 -174.6 -193.5
3
40 -73.9 -86.7 -100.6 -115.5 -131.4 -148.3 -166.3 -185.3 -205.3
50 -77.5 -90.9 -105.4 -121.0 -137.7 -155.5 -174.3 -194.2 -215.2
60 -80.3 -94.2 -109.3 -125.5 -142.8 -161.2 -180.7 -201.3 -223.1
20 -43.1 -50.6 -58.7 -67.4 -76.7 -86.6 -97.1 -108.2 -119.9
25 -45.1 -52.9 -61.3 -70.4 -80.1 -90.4 -101.4 -113.0 -125.2
30 -47.0 -55.1 -63.9 -73.4 -83.5 -94.3 -105.7 -117.8 -130.5
1
40 -49.9 -58.5 -67.9 -77.9 -88.6 -100.1 -112.2 -125.0 -138.5
50 -52.3 -61.3 -71.1 -81.7 -92.9 -104.9 -117.6 -131.0 -145.2
60 -54.2 -63.6 -73.7 -84.6 -96.3 -108.7 -121.9 -135.8 -150.5
20 -55.0 -64.5 -74.9 -85.9 -97.8 -110.4 -123.7 -137.9 -152.8
25 -57.4 -67.4 -78.2 -89.7 -102.1 -115.3 -129.2 -144.0 -159.5
Partially 30 -59.9 -70.3 -81.5 -93.6 -106.5 -120.2 -134.7 -150.1 -166.3
2
Enclosed 40 -63.5 -74.6 -86.5 -99.3 -113.0 -127.5 -143.0 -159.3 -176.5
50 -66.6 -78.2 -90.7 -104.1 -118.4 -133.7 -149.9 -167.0 -185.0
60 -69.0 -81.0 -94.0 -107.9 -122.7 -138.6 -155.4 -173.1 -191.8
20 -70.2 -82.4 -95.6 -109.7 -124.8 -140.9 -158.0 -176.0 -195.1
25 -73.3 -86.1 -99.8 -114.6 -130.4 -147.2 -165.0 -183.9 -203.7
30 -76.5 -89.7 -104.1 -119.5 -135.9 -153.5 -172.0 -191.7 -212.4
3
40 -81.1 -95.2 -110.4 -126.8 -144.3 -162.9 -182.6 -203.4 -225.4
50 -85.0 -99.8 -115.8 -132.9 -151.2 -170.7 -191.4 -213.2 -236.2
60 -88.2 -103.5 -120.0 -137.8 -156.7 -176.9 -198.4 -221.0 -244.9
Page 5 www.GulfCoastSupply.com
GulfPBRTM FL33818.06-R5
Allowable Design Pressures required for Gable and Hip Roofs in Exposure D with roof slope between 2:12 and 12:12
Mean Roof Ultimate Windspeed (mph)
Building Type Zone
Height (ft) 120 130 140 150 160 170 180 190 200
20 -44.3 -51.9 -60.2 -69.2 -78.7 -88.8 -99.6 -111.0 -123.0
25 -45.9 -53.9 -62.5 -71.7 -81.6 -92.1 -103.3 -115.1 -127.5
30 -47.5 -55.8 -64.7 -74.3 -84.5 -95.4 -107.0 -119.2 -132.1
1
40 -50.0 -58.7 -68.1 -78.1 -88.9 -100.4 -112.5 -125.4 -138.9
50 -52.1 -61.1 -70.8 -81.3 -92.5 -104.5 -117.1 -130.5 -144.6
60 -53.7 -63.0 -73.1 -83.9 -95.5 -107.8 -120.8 -134.6 -149.1
20 -58.5 -68.6 -79.6 -91.4 -104.0 -117.4 -131.6 -146.6 -162.4
25 -60.6 -71.2 -82.5 -94.8 -107.8 -121.7 -136.4 -152.0 -168.5
Enclosed or 30 -62.8 -73.7 -85.5 -98.1 -111.7 -126.1 -141.3 -157.5 -174.5
2
Partially Open 40 -66.1 -77.5 -89.9 -103.2 -117.4 -132.6 -148.6 -165.6 -183.5
50 -68.8 -80.7 -93.6 -107.4 -122.2 -138.0 -154.7 -172.4 -191.0
60 -70.9 -83.2 -96.5 -110.8 -126.1 -142.4 -159.6 -177.8 -197.0
20 -76.8 -90.1 -104.5 -119.9 -136.4 -154.0 -172.7 -192.4 -213.2
25 -79.6 -93.4 -108.3 -124.4 -141.5 -159.7 -179.1 -199.5 -221.1
30 -82.4 -96.7 -112.2 -128.8 -146.6 -165.4 -185.5 -206.7 -229.0
3
40 -86.7 -101.8 -118.0 -135.5 -154.1 -174.0 -195.1 -217.4 -240.8
50 -90.3 -105.9 -122.8 -141.0 -160.5 -181.1 -203.1 -226.3 -250.7
60 -93.1 -109.3 -126.7 -145.5 -165.5 -186.8 -209.5 -233.4 -258.6
20 -51.8 -60.8 -70.5 -80.9 -92.0 -103.9 -116.5 -129.8 -143.8
25 -53.7 -63.0 -73.1 -83.9 -95.5 -107.8 -120.8 -134.6 -149.2
30 -55.6 -65.3 -75.7 -86.9 -98.9 -111.6 -125.1 -139.4 -154.5
1
40 -58.5 -68.6 -79.6 -91.4 -104.0 -117.4 -131.6 -146.6 -162.5
50 -60.9 -71.5 -82.9 -95.1 -108.2 -122.2 -137.0 -152.6 -169.1
60 -62.8 -73.7 -85.5 -98.1 -111.7 -126.0 -141.3 -157.4 -174.5
20 -66.0 -77.4 -89.8 -103.1 -117.3 -132.4 -148.5 -165.4 -183.3
25 -68.4 -80.3 -93.1 -106.9 -121.7 -137.3 -154.0 -171.6 -190.1
Partially 30 -70.9 -83.2 -96.5 -110.7 -126.0 -142.2 -159.5 -177.7 -196.9
2
Enclosed 40 -74.5 -87.5 -101.5 -116.5 -132.5 -149.6 -167.7 -186.9 -207.1
50 -77.6 -91.1 -105.6 -121.2 -138.0 -155.7 -174.6 -194.5 -215.6
60 -80.0 -93.9 -108.9 -125.1 -142.3 -160.6 -180.1 -200.7 -222.3
20 -84.3 -98.9 -114.7 -131.7 -149.8 -169.1 -189.6 -211.2 -234.1
25 -87.4 -102.6 -118.9 -136.5 -155.4 -175.4 -196.6 -219.1 -242.7
30 -90.5 -106.2 -123.2 -141.4 -160.9 -181.6 -203.6 -226.9 -251.4
3
40 -95.2 -111.7 -129.6 -148.7 -169.2 -191.0 -214.2 -238.6 -264.4
50 -99.1 -116.3 -134.9 -154.8 -176.2 -198.9 -222.9 -248.4 -275.2
60 -102.2 -120.0 -139.1 -159.7 -181.7 -205.1 -230.0 -256.2 -283.9
Page 6 www.GulfCoastSupply.com