VD (Electrical)

The document provides detailed calculations for current ratings and voltage drops for both three-phase and single-phase loads, including various cable sizes and their respective voltage drops. It also outlines the minimum allowable load and circuit breaker capacities for different cable sizes under normal conditions. Additionally, it specifies the minimum acceptable clearances for main distribution boards and panels based on their ratings.

Uploaded by

shyamalm94
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views7 pages

VD (Electrical)

The document provides detailed calculations for current ratings and voltage drops for both three-phase and single-phase loads, including various cable sizes and their respective voltage drops. It also outlines the minimum allowable load and circuit breaker capacities for different cable sizes under normal conditions. Additionally, it specifies the minimum acceptable clearances for main distribution boards and panels based on their ratings.

Uploaded by

shyamalm94
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

CURRENT RATINGS & VOLTAGE DROP CALCULATIONS FOR THREE PHASE LOADS

mV Drop
[Link]. Sqmm LOAD (KW) AMPERE Cable length from Voltage drop [Link] Voltage Drop
table

1 1.5 20 40 20 25 20.07 1 20.07


2 2.5 0 15 0.00 1 0.00
3 4 3 5 35 9.5 1.73 1 1.73
4 6 5 9 20.0 6.4 1.11 1 1.11
5 10 24.8 43 6 3.8 0.98 1 0.98
6 16 12.1 21 15 2.4 0.75 1 0.75
7 25 34.5 60 7 1.6 0.67 2 0.33
8 35 9 16 49 0.88 0.67 2 0.34
9 50 55 95 20.00 0.865 1.65 2 0.82
10 70 65 112 185.00 0.607 12.63 2 6.31
11 95 121.55 210 76.00 0.446 7.13 2 3.56
12 120 115.25 199 98.00 0.366 7.15 2 3.58
13 150 115 199 90 0.303 5.43 2 2.71
181 185 318 550 237 0.255 33.25 2 16.62
15 240 318 550 276 0.211 32.04 2 16.02
16 300 204.32 353 10 0.185 0.65 4 0.16
CURRENT RATINGS & VOLTAGE DROP CALCULATIONS FOR SINGLE PHASE
LOADS

[Link]. Sqmm LOAD (KW) AMPERE mV drop Cable length Voltage Drop [Link] Voltage Drop

1 1.5 2 12.1 29 0 0
2 2.5 2 12.1 18 0 0
3 4 2 12.1 11.0 23 3.0555555556
4 6 2 10.2 6.8 30 2.08896
5 10 5 25.6 4.7 172 20.69504
6 16 5 25.6 2.9 110 8.1664
7 25 5 25.6 1.9 128 6.22592
8 35 2 12.1 1.3 0 0
9 50 2 12.1 1 0 0
10 70 2 12.1 0.70 0 0
11 95 2 12.1 0.5 0 0
12 120 2 12.1 0.4 0 0
13 150 2 12.1 0.40 0 0
14 185 2 12.1 0.3 0 0
15 240 0 0.2 0 0
16 300 0 0.2 0 0
FOR (XLPE/SWA/PVC/Normal Condition)
Cable Size sqmm 4C Minimum allowable load in Circuit Breaker
[Link] [Link]
XLPE / SWA / PVC KW Capacity (A) TP
1 10 16 KW(17) 40 1
2 16 36 KW(18-32) 60-80 2
3 25 52 KW(33-52) 100 3
4 35 62 KW(53-62) 125 4
5 50 76KW(62-76) 150 5
6 70 100 KW(76-100) 200 6
7 95 125KW(110) 225 7
8 120 140 250 8
9 150 150 300 9
10 185 175 350 10
11 240 200 400 11
12 300 250 500 12
13 2x150 300KW 600 13
14 2x240 350KW 800 14
15 2x300 470KW 1000 15
16 3x240 550 KW 1250 16
17 4x240 1500 17
18 4x300 2000 18

FOR SINGLE CORE (NORMAL CONDITION)


Cable Size sqmm 4C Minimum allowable load in Circuit Breaker
[Link]
XLPE / SWA / PVC KW Capacity (A)
1 1.5 0.9 10
2 2.5 1.8 16
3 4.0 2.9 20
4 6.0 4.0 32
5 10.0 5.5 40
6 16.0 9.0 63
7 4x10+1x6 (Up to16)TP 40
8 4x16+1x10 (17 to 24) 63
9 4x25+1x16 (25 to 34) 63 to 80
10 4x35+1x25 (35 to 50) 100
11 4x50+1x35 (51 to 60) 125
XLPE/SWA/PVC
Cable Size sqmm 4C XLPE Maxiimum allowable load Circuit Breaker Capacity
/ SWA / PVC in KW (A)
10 (10 Earth) UP to (17 KW) 40
16 (10) (18-36 KW) 60-80
25 (16) (37-52 KW) 100
35 (25) (53-62 KW) 125
50 (35) (63-80 KW) 160
70 (50) (81-100 KW) 200
95 (70) (101-128 KW) 225-250
120 (95) UP TO 130 250
150 (120) 131-150 300
185 (150) 151-175 350
240 (185) 176-200 400
300 (240) 201-250 500
2x150 (2x1c 120) 251-300 600
2x240 (2x1c 185) 301-400 800
2x300 (2x1c 240) 401-500 1000
3x240 (3x1c 185) 501-600 1250
4x240 (4x1c 185) 601-800 1500
4x300 (4x1c 240) 801-1000 2000
Minimum acceptable Clearance
Back
Main D.B / PANEL Size of Main Electric room Type of Front Clearance Side Clearance
[Link]. Clearance in Remarks
Rating(Amp) (in Cms) Mounting in Cms in Cms
Cms
1 40
2 60
3 100
4 150 200x200
5 200
WALL Not Less Than
6 250
MOUNTED 150 Cms
7 315
8 400 60 Cms
9 630
250x250
10 800
11 1000
12 630
13 800
14 1000
15 630 250x250
16 800 For form 2
FLOOR
150 Cms 70 Cms 60 Cms construction
17 1000 MOUNTED
Panel
18 1250
19 1600 300x300
20 2000 300x300
21 2500 450x300