Outdoor Units
3. Dimensions
A B C Liquid(Φ) Vapor(Φ)
MOV-30 636/25 554/21-7/8 554/21-7/8 9.53(3/8) 15.9(5/8)
MOV-36 840/33-1/8 554/21-7/8 554/21-7/8 12.7(1/2) 19(3/4)
MOV-48 852/33-1/2 740/29-1/8 740/29-1/8 12.7(1/2) 19(3/4)
MOV-60 852/33-1/2 740/29-1/8 740/29-1/8 12.7(1/2) 19(3/4)
4. Service Space
Note: 1 inch=25.4mm; 48 inch=1219mm; 12 inch=305mm; 24inch=610mm
MOV-30HRA
MOV-36HRS, MOV-48HRS, MOV-60HRS
6. Electric Characteristics
Outdoor Unit Power Supply Compressor OFM
Model
Hz Voltage Min. Max. MCA MFA TOCA MSC RLA kW FLA
MOV-30C(H)RA 50 220~240 198 264 15.2 20 17.3 61 11.1 0.08 0.62
MOV-36C(H)RS 50 380 342 415 7.9 20 9.5 49 6.7 0.08 0.62
MOV-48C(H)RS 50 380 342 415 13.6 20 14.8 58 10 0.165 1.2
MOV-60C(H)RS 50 380 342 415 13.6 20 14.0 67 10 0.165 1.2
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Load Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
kW: Rated Motor Output (KW)
7. Operation Limits
Temperature range for unit operation:
Item Cooling mode Heating mode
Model Outdoor Indoor Outdoor Indoor
All model 21℃~43℃ 17℃~30℃ -5℃~24℃ 17℃~30℃
Heating
30
Cooling
25
20
43
emp.(°C)
Range for continuous
Outdoor temperature(℃ WB)
35 STD 15
10
operation
21 5
Ambient
-5
17 27 30 -10
Indoor temp.(°C) 10 15 17 20 25 30 35
Indoor temperature(℃ DB)
8. Sound Levels
Outdoor unit Microphone
Heat pump
Cooling only
H
1.0 m
Note: H= (unit’s hight+1)/2 m
Model MOV- Noise level dB(A)
30CRA 61.7
36CRS 59.9
48CRS 65.8
60CRS 65
30HRA 62.8
36HRS 61.4
48HRS 67.1
60HRS 67