ENGINEERING DESIGN CALCULATION - DENNIS KIRK
CENTRIFUGAL FAN PERFORMANCE CHARACTERISTICS V 1.000
[Typically up to 0.5 psi (3.5 kPa)]
CLIENT:
PROJECT:
TITLE:
Shaft Power
P [kW] = Q [m3/sec] x dP [kPa] / Effy
Vary Speed
Kapasitas bervariasi secara langsung dengan kecepatan
Tekanan bervariasi dengan kuadrat kecepatan
Kekuatan bervariasi dengan kecepatan kubus
Vary Temperature
Tekanan bervariasi berbanding terbalik dengan suhu absolut
Daya bervariasi berbanding terbalik dengan suhu absolut
Vary Density
Tekanan bervariasi dengan kepadatan
Kekuatan bervariasi dengan kepadatan
CALCULATIONS
Design Performance and Speed Alternate Speed
Flow Rate 52.5 m3/hr Flow Rate 160.714286 m3/hr
14.5833 l/sec 44.6428571 l/sec
Diff Pressure 5.60 kPa Diff Pressure 52.48 kPa
571 mm H2O 5349 mm H2O
22.5 inch H2O 210.6 inch H2O
Temperature 40.0 o
C Temperature 40.0 o
C
Density 1.1 kg/m3 Density 1.1 kg/m3
Shaft Power 0.08 kW Shaft Power 2.34 kW
Efficency 80.0% Efficency 30.0%
Motor Power 0.10 kW Motor Power 8 kW
Motor RPM 980 Motor RPM 1500
Motor Pulley 100 Motor Pulley 100
Fan Pulley 100 Fan Pulley 50
Drive Ratio 1.00 Drive Ratio 2.00
Fan RPM 980.0 Fan RPM 3000.0
Rotor Diam 2024 mm Rotor Diam 2024 mm
Tip Speed 103.86 m/sec Tip Speed 317.93 m/sec
Alternate Temperature Alternative Density
Flow Rate 52.5 m3/hr Flow Rate 52.5 m3/hr
14.5833 l/sec 14.5833333 l/sec
Diff Pressure 3.35 kPa Diff Pressure 51.38 kPa
342 mm H2O 5237 mm H2O
13.5 inch H2O 206.2 inch H2O
Temperature 250.0 o
C Temperature 40.0 o
C
Density 1.1 kg/m3 Density 10.0 kg/m3
Shaft Power 0.05 kW Shaft Power 0.75 kW
Efficency 30.0% Efficency 30.0%
Motor Power 0.16 kW Motor Power 2.50 kW
Motor RPM 980 Motor RPM 980
Motor Pulley 100 Motor Pulley 100
Fan Pulley 100 Fan Pulley 100
Drive Ratio 1.00 Drive Ratio 1.00
Fan RPM 980.0 Fan RPM 980.0
Rotor Diam 2024 mm Rotor Diam 2024 mm
Tip Speed 103.86 m/sec Tip Speed 103.86 m/sec
857341400.xlsx Fan Calculation 03/01/2025
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
DESIGN CALCULATION FOR THE HVAC SYSTEM 0 0 0 1 OF 1 0
PROJECT 0 LOCATION 0 JOB ORDER NO. 0 DWG. CONT. SHT. 0
DATA:
Toilet length 4.00 M
Toilet width 4.20 M
Toilet height 2.80 M
Air change per hour 10 AC/Hr.
Notes:
Number of Air changes required for the toilet is 6-10 as per the clause No.4.1.11 of SES-P-119-19 & clause No.10.11 of SES-K-100. Hence
10 air changes per hour is considered in calculation.
CALCULATION:
Volume of Toilet Room V= 4x4.2x2.8 M3
= 47.04 M3
= 1661.2 Ft3
Fan capacity in CFM = Room volume x No. Of Air changes/Hr
60
= 1661.2x10 / 60
Use fan capacity of = 277 CFM
= 471 CMH
Pressure loss through the exhaust duct = 0.225 in.W.G. (Ref. To comp. Cal
enclosed)
SAY = 0.225 IN W.G (56.5 Pa)
BROUGHT TO YOU BY: MEP WORK
* Hourly ventilating frequency according to kinds of rooms
: (Target values by Sanitation Laboratory Corp. Japan)
Frequenc
Kinds of rooms y / Air
Change RUMUS EXHAUST FAN
Dance-hall 8 = Panjang x Lebar x Tinggi x Air Change
Restaurant 5 mtr feet
Cooking room 15 PANJANG 3.28 1.75 5.74 panjang ruangan
Hotel Gallery 5 LEBAR 3.28 1.00 3.28 lebar ruangan
Toilet (W.C.) 10 TINGGI 3.28 3.00 9.84 tinggi ruangan
Engine/boiler room 20 AIR CHANGE / HOUR (ACH) 10 jenis ruangan
Washing room 15 LUASAN 2
Waiting room 10 REQUIRED
Consulting room 6 AIR FLOW 31 cfm
Patient's room 6 AIR FLOW 53 cmh
Bath room 10
Hospital
Office 6
Dining room 8 Notes :
Kitchen 15 Pengisian Data Pada Kolom Blok Warna Biru
Gallery 5
Public toilet service 20
Ship Cabins 6
Library Reading room 6
Dark room Photography dark room 10
General plant 5 ~ 15
Machining shop 10 ~ 20
Welding shop 15 ~ 25
Casting shop 20 ~ 60
Casting/rolling 30 ~ 80
Chemical plant 15 ~ 30
Plants / factories
Food-factory 10 ~ 30
Painting shop 30 ~ 100
Printing shop 5 ~ 15
Wooden crafts 15 ~ 25
Dyeing shop 15 ~ 30
Spinning factory 5 ~ 15
Incoming room (power) 20 ~ 30
Compressor room 15 ~ 30
Subsidiary Boiler house 20 ~ 30
equipment Change room 4 ~ 15
Dining room 5 ~ 10
Kitchen 10 ~ 30
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
DESIGN CALCULATION FOR THE HVAC SYSTEM 0 0 0 1 OF 1 0
PROJECT PIK2 Kitchen & Mess LOCATION Jakarta JOB ORDER NO. 0 DWG. CONT. SHT. 0
DATA:
Toilet length 1.75 M
Toilet width 1.00 M
Toilet height 3.00 M
Air change per hour 10 AC/Hr.
Notes:
Number of Air changes required for the toilet is 6-10 as per the clause No.4.1.11 of SES-P-119-19 & clause No.10.11 of SES-K-100.
Hence 10 air changes per hour is considered in calculation.
CALCULATION:
Volume of Toilet Room V= 1.75x1x3 M3
= 5.25 M3
= 185.4 Ft3
Fan capacity in CFM = Room volume x No. Of Air changes/Hr
60
= 185.4x10 / 60
Use fan capacity of = 31 CFM
= 53 CMH
Kapasitas
Jumlah
CFM TOTAL
Toilet Cewek 3 31 93
Pressure loss through the exhaust duct = 0.225 in.W.G. (Ref. To comp. Cal
enclosed)
SAY = 0.225 IN W.G (56.5 Pa)
BROUGHT TO YOU BY : ALPHALINE CIPTA ENGINEERING