Illuminance and Luminaire Data Analysis

The document outlines the illumination calculations for the fuel supply system at Noi Bai International Airport, Terminal 2, prepared by the Taisei – Vinaconex Joint Venture. It includes details on luminaire specifications, luminous emittance, and various lighting metrics such as average illuminance and glare evaluation. The document also provides a luminaire parts list and photometric results for the lighting design.

Uploaded by

Vu Vovan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views94 pages

Illuminance and Luminaire Data Analysis

The document outlines the illumination calculations for the fuel supply system at Noi Bai International Airport, Terminal 2, prepared by the Taisei – Vinaconex Joint Venture. It includes details on luminaire specifications, luminous emittance, and various lighting metrics such as average illuminance and glare evaluation. The document also provides a luminaire parts list and photometric results for the lighting design.

Uploaded by

Vu Vovan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Taisei – Vinaconex Joint Venture

Noi Bai International Airport, Terminal 2, Package No 10a

Section 70000 - Utility Works

Division 72000 – Fuel Supply System

Illumination Calculation

TVJV Signature

Approved by : Yutaka Hodono Date:

odono
Authorized by : Yutaka Hodono Date:

APPROVED BY Y.OT. Matsumura JOB NO. JS-1108

CHECKED BY H.S DATE OF PREP. DATE OF ISSUE

PREPARED BY A.H>A / H. Tamura 26th Dec, 2012 28th Dec, 2012

DOC. NO.

SECTION Electrical Design Department 330-CS-R-0011 Rev.C

TOTAL SHEETS (W/COVER) 1


330-CS-R-0011
SCHEDULE OF REVISIONS
REV. C

REV. DESCRIPTION DATE PREP’D - CHK’D APP’D

A Issued for Approval 31th /Oct /'12 A.H H.S Y.O

B Issued for Approval 03rd /Dec /'12 A.H H.S Y.O

C Issued for Approval 28th /Dec /'12 A.H H.S Y.O

2
Admin Office 1 FL
23.11.2012

Operator
Telephone
Fax
e-Mail

Philips TBH318 3xTL-D36W HFE M5 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

80
60° 60°

120

45° 160 45°

200

240

30° 15° 0° 15° 30°

cd/klm  48%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 63 96 100 100 48
Glare Evaluation According to UGR
Hygeia TBH318
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
Functional, fully closed recessed luminaire for 2 or 3 TL’D fluorescent lamps  Floor 20 20 20 20 20 20 20 20 20 20
for application in cleanrooms and dust-/ water-ingress protected areas. Room Size Viewing direction at right angles Viewing direction parallel
Double parabolic mirror is integrated in the luminaire with clear PMMA cover. X Y to lamp axis to lamp axis

2H 2H 15.4 16.5 15.7 16.7 16.9 14.5 15.6 14.8 15.8 16.0
3H 15.4 16.4 15.7 16.6 16.9 14.5 15.4 14.8 15.7 15.9
4H 15.4 16.3 15.7 16.5 16.8 14.4 15.3 14.7 15.6 15.9
6H 15.3 16.1 15.7 16.4 16.7 14.4 15.2 14.7 15.5 15.8
8H 15.3 16.1 15.6 16.4 16.7 14.3 15.1 14.7 15.4 15.7
12H 15.3 16.0 15.6 16.3 16.6 14.3 15.0 14.7 15.4 15.7
4H 2H 15.5 16.4 15.8 16.6 16.9 14.7 15.6 15.0 15.9 16.1
3H 15.5 16.3 15.9 16.6 16.9 14.7 15.4 15.1 15.8 16.1
4H 15.5 16.2 15.9 16.5 16.9 14.7 15.3 15.0 15.6 16.0
6H 15.5 16.0 15.9 16.4 16.8 14.6 15.2 15.0 15.5 15.9
8H 15.4 16.0 15.9 16.3 16.7 14.6 15.1 15.0 15.5 15.9
12H 15.4 15.9 15.9 16.3 16.7 14.5 15.0 15.0 15.4 15.8
8H 4H 15.4 15.9 15.8 16.3 16.7 14.6 15.1 15.0 15.5 15.9
6H 15.4 15.8 15.8 16.2 16.7 14.5 14.9 15.0 15.4 15.8
8H 15.4 15.7 15.8 16.2 16.6 14.5 14.8 15.0 15.3 15.8
12H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7
12H 4H 15.4 15.8 15.8 16.2 16.7 14.5 15.0 15.0 15.4 15.8
6H 15.3 15.7 15.8 16.1 16.6 14.5 14.8 14.9 15.3 15.8
8H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7

Variation of the observer position for the luminaire distances S

S = 1.0H +0.8 / -1.2 +0.7 / -1.1


S = 1.5H +2.0 / -5.0 +1.8 / -4.4
S = 2.0H +3.7 / -6.8 +2.7 / -8.0

Standard table BK01 BK01


Correction
-5.0 -5.8
Summand
Corrected Glare Indices referring to 10050lm Total Luminous Flux

Page 1
Admin Office 1 FL
23.11.2012

Operator
Telephone
Fax
e-Mail

Admin Office 1 FL / Summary

280 12.00 m
350
420 420
420
350 420 420
350
420 420
420
490 490
350 420
420 420
350
420 420
420
420 490 490

420 420 350

420 420
350
420 350
350
0.00
0.00 6.00 m

Height of Room: 3.800 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:155
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 383 168 503 0.437
Floor 10 345 183 437 0.530
Ceiling 70 42 33 48 0.800
Walls (4) 50 111 33 246 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 15 15
Grid: 32 x 64 Points Lower Wall 15 15
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.254, Ceiling / Working Plane: 0.109.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 8 Philips TBH318 3xTL-D36W HFE M5 (1.000) 10050 0.0
Total: 80400 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 72.00 m²)

Page 2
Admin Office 1 FL
23.11.2012

Operator
Telephone
Fax
e-Mail

Admin Office 1 FL / Luminaire parts list

8 Pieces Philips TBH318 3xTL-D36W HFE M5


Article No.:
Luminaire Luminous Flux: 10050 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 100
CIE flux code: 63 96 100 100 48
Fitting: 3 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Admin Office 1 FL
23.11.2012

Operator
Telephone
Fax
e-Mail

Admin Office 1 FL / Photometric Results

Total Luminous Flux: 80400 lm


Total Load: 0.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 343 40 383 / /
Floor 296 49 345 10 11
Ceiling 0.00 42 42 70 9.29
Wall 1 63 41 104 50 17
Wall 2 73 43 116 50 18
Wall 3 62 41 103 50 16
Wall 4 73 41 114 50 18

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.437 (1:2) Left Wall 15 15
Emin / Emax: 0.333 (1:3) Lower Wall 15 15
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.254, Ceiling / Working Plane: 0.109.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 72.00 m²)

Page 4
Control Room 2 FL
05.12.2012

Operator
Telephone
Fax
e-Mail

Philips TBH318 3xTL-D36W HFE M5 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

80
60° 60°

120

45° 160 45°

200

240

30° 15° 0° 15° 30°

cd/klm  48%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 63 96 100 100 48
Glare Evaluation According to UGR
Hygeia TBH318
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
Functional, fully closed recessed luminaire for 2 or 3 TL’D fluorescent lamps  Floor 20 20 20 20 20 20 20 20 20 20
for application in cleanrooms and dust-/ water-ingress protected areas. Room Size Viewing direction at right angles Viewing direction parallel
Double parabolic mirror is integrated in the luminaire with clear PMMA cover. X Y to lamp axis to lamp axis

2H 2H 15.4 16.5 15.7 16.7 16.9 14.5 15.6 14.8 15.8 16.0
3H 15.4 16.4 15.7 16.6 16.9 14.5 15.4 14.8 15.7 15.9
4H 15.4 16.3 15.7 16.5 16.8 14.4 15.3 14.7 15.6 15.9
6H 15.3 16.1 15.7 16.4 16.7 14.4 15.2 14.7 15.5 15.8
8H 15.3 16.1 15.6 16.4 16.7 14.3 15.1 14.7 15.4 15.7
12H 15.3 16.0 15.6 16.3 16.6 14.3 15.0 14.7 15.4 15.7
4H 2H 15.5 16.4 15.8 16.6 16.9 14.7 15.6 15.0 15.9 16.1
3H 15.5 16.3 15.9 16.6 16.9 14.7 15.4 15.1 15.8 16.1
4H 15.5 16.2 15.9 16.5 16.9 14.7 15.3 15.0 15.6 16.0
6H 15.5 16.0 15.9 16.4 16.8 14.6 15.2 15.0 15.5 15.9
8H 15.4 16.0 15.9 16.3 16.7 14.6 15.1 15.0 15.5 15.9
12H 15.4 15.9 15.9 16.3 16.7 14.5 15.0 15.0 15.4 15.8
8H 4H 15.4 15.9 15.8 16.3 16.7 14.6 15.1 15.0 15.5 15.9
6H 15.4 15.8 15.8 16.2 16.7 14.5 14.9 15.0 15.4 15.8
8H 15.4 15.7 15.8 16.2 16.6 14.5 14.8 15.0 15.3 15.8
12H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7
12H 4H 15.4 15.8 15.8 16.2 16.7 14.5 15.0 15.0 15.4 15.8
6H 15.3 15.7 15.8 16.1 16.6 14.5 14.8 14.9 15.3 15.8
8H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7

Variation of the observer position for the luminaire distances S

S = 1.0H +0.8 / -1.2 +0.7 / -1.1


S = 1.5H +2.0 / -5.0 +1.8 / -4.4
S = 2.0H +3.7 / -6.8 +2.7 / -8.0

Standard table BK01 BK01


Correction
-5.0 -5.8
Summand
Corrected Glare Indices referring to 10050lm Total Luminous Flux

Page 1
Control Room 2 FL
05.12.2012

Operator
Telephone
Fax
e-Mail

Control Room 2 FL / Summary

280 280 6.00 m


350 280
350
420 420 420
420 420
350
420

350
420 420 420 420
350

420 420 420


420 420 350

350 420
420 420 420 420
350 350
280
280 280
0.00
0.00 6.00 m

Height of Room: 3.800 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:78
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 372 183 488 0.492
Floor 20 324 193 407 0.596
Ceiling 70 55 42 66 0.752
Walls (4) 50 121 42 256 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 16 15
Grid: 32 x 32 Points Lower Wall 16 15
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.291, Ceiling / Working Plane: 0.149.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 4 Philips TBH318 3xTL-D36W HFE M5 (1.000) 10050 0.0
Total: 40200 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 36.00 m²)

Page 2
Control Room 2 FL
05.12.2012

Operator
Telephone
Fax
e-Mail

Control Room 2 FL / Luminaire parts list

4 Pieces Philips TBH318 3xTL-D36W HFE M5


Article No.:
Luminaire Luminous Flux: 10050 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 100
CIE flux code: 63 96 100 100 48
Fitting: 3 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Control Room 2 FL
05.12.2012

Operator
Telephone
Fax
e-Mail

Control Room 2 FL / Photometric Results

Total Luminous Flux: 40200 lm


Total Load: 0.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 321 51 372 / /
Floor 264 60 324 20 21
Ceiling 0.00 55 55 70 12
Wall 1 62 57 118 50 19
Wall 2 68 56 124 50 20
Wall 3 62 56 118 50 19
Wall 4 68 56 124 50 20

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.492 (1:2) Left Wall 16 15
Emin / Emax: 0.376 (1:3) Lower Wall 16 15
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.291, Ceiling / Working Plane: 0.149.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 36.00 m²)

Page 4
Corridor 1FL-1
14.12.2012

Operator
Telephone
Fax
e-Mail

Corridor 1FL-1 / Summary

13.92 m
120

140
160
160

140

160

140

140

0.00
1.25 m

Height of Room: 3.800 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:179
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 146 90 169 0.612
Floor 10 147 89 167 0.605
Ceiling 70 20 16 23 0.779
Walls (4) 50 67 15 439 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 20 18
Grid: 128 x 32 Points Lower Wall 20 18
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.461, Ceiling / Working Plane: 0.140.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 4 Mazda FBS120 2xPL-C/2P26W GL (1.000) 3600 65.6
Total: 14400 262.4

Specific connected load: 15.08 W/m² = 10.31 W/m²/100 lx (Ground area: 17.40 m²)

Page 1
Corridor 1FL-1
14.12.2012

Operator
Telephone
Fax
e-Mail

Corridor 1FL-1 / Luminaire parts list

4 Pieces Mazda FBS120 2xPL-C/2P26W GL


Article No.:
Luminaire Luminous Flux: 3600 lm
Luminaire Wattage: 65.6 W
Luminaire classification according to CIE: 100
CIE flux code: 80 99 100 100 55
Fitting: 2 x PL-C/2P26W/840 (Correction Factor
1.000).

Page 2
Corridor 1FL-1
14.12.2012

Operator
Telephone
Fax
e-Mail

Corridor 1FL-1 / Photometric Results

Total Luminous Flux: 14400 lm


Total Load: 262.4 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 113 34 146 / /
Floor 113 34 147 10 4.67
Ceiling 0.00 20 20 70 4.56
Wall 1 14 25 39 50 6.18
Wall 2 40 30 70 50 11
Wall 3 14 24 38 50 6.12
Wall 4 40 30 70 50 11

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.612 (1:2) Left Wall 20 18
Emin / Emax: 0.528 (1:2) Lower Wall 20 18
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.461, Ceiling / Working Plane: 0.140.

Specific connected load: 15.08 W/m² = 10.31 W/m²/100 lx (Ground area: 17.40 m²)

Page 3
Corridor 1FL-2
14.12.2012

Operator
Telephone
Fax
e-Mail

Corridor 1FL-2 / Summary

1.50 m
130

150 150 150 150 140 120


150 150
150
150 150

140 150
150
130 150 150
150 150 150
130 120
150 150 150 150
140

0.00
0.00 2.94 m

Height of Room: 3.800 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:22
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 138 108 155 0.780
Floor 10 138 106 155 0.766
Ceiling 70 16 14 18 0.867
Walls (4) 50 59 12 235 /

Workplane:
Height: 0.000 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.429, Ceiling / Working Plane: 0.116.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 1 Mazda FBS120 2xPL-C/2P26W GL (1.000) 3600 65.6
Total: 3600 65.6

Specific connected load: 14.83 W/m² = 10.74 W/m²/100 lx (Ground area: 4.42 m²)

Page 1
Corridor 1FL-2
14.12.2012

Operator
Telephone
Fax
e-Mail

Corridor 1FL-2 / Luminaire parts list

1 Pieces Mazda FBS120 2xPL-C/2P26W GL


Article No.:
Luminaire Luminous Flux: 3600 lm
Luminaire Wattage: 65.6 W
Luminaire classification according to CIE: 100
CIE flux code: 80 99 100 100 55
Fitting: 2 x PL-C/2P26W/840 (Correction Factor
1.000).

Page 2
Corridor 1FL-2
14.12.2012

Operator
Telephone
Fax
e-Mail

Corridor 1FL-2 / Photometric Results

Total Luminous Flux: 3600 lm


Total Load: 65.6 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 103 35 138 / /
Floor 103 35 138 10 4.40
Ceiling 0.00 16 16 70 3.57
Wall 1 37 26 63 50 10
Wall 2 25 25 50 50 8.03
Wall 3 37 26 63 50 10
Wall 4 25 25 50 50 8.03

Uniformity on the working plane


u0: 0.780 (1:1)
Emin / Emax: 0.696 (1:1)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.429, Ceiling / Working Plane: 0.116.

Specific connected load: 14.83 W/m² = 10.74 W/m²/100 lx (Ground area: 4.42 m²)

Page 3
Management Office 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Philips TBH318 3xTL-D36W HFE M5 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

80
60° 60°

120

45° 160 45°

200

240

30° 15° 0° 15° 30°

cd/klm  48%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 63 96 100 100 48
Glare Evaluation According to UGR
Hygeia TBH318
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
Functional, fully closed recessed luminaire for 2 or 3 TL’D fluorescent lamps  Floor 20 20 20 20 20 20 20 20 20 20
for application in cleanrooms and dust-/ water-ingress protected areas. Room Size Viewing direction at right angles Viewing direction parallel
Double parabolic mirror is integrated in the luminaire with clear PMMA cover. X Y to lamp axis to lamp axis

2H 2H 15.4 16.5 15.7 16.7 16.9 14.5 15.6 14.8 15.8 16.0
3H 15.4 16.4 15.7 16.6 16.9 14.5 15.4 14.8 15.7 15.9
4H 15.4 16.3 15.7 16.5 16.8 14.4 15.3 14.7 15.6 15.9
6H 15.3 16.1 15.7 16.4 16.7 14.4 15.2 14.7 15.5 15.8
8H 15.3 16.1 15.6 16.4 16.7 14.3 15.1 14.7 15.4 15.7
12H 15.3 16.0 15.6 16.3 16.6 14.3 15.0 14.7 15.4 15.7
4H 2H 15.5 16.4 15.8 16.6 16.9 14.7 15.6 15.0 15.9 16.1
3H 15.5 16.3 15.9 16.6 16.9 14.7 15.4 15.1 15.8 16.1
4H 15.5 16.2 15.9 16.5 16.9 14.7 15.3 15.0 15.6 16.0
6H 15.5 16.0 15.9 16.4 16.8 14.6 15.2 15.0 15.5 15.9
8H 15.4 16.0 15.9 16.3 16.7 14.6 15.1 15.0 15.5 15.9
12H 15.4 15.9 15.9 16.3 16.7 14.5 15.0 15.0 15.4 15.8
8H 4H 15.4 15.9 15.8 16.3 16.7 14.6 15.1 15.0 15.5 15.9
6H 15.4 15.8 15.8 16.2 16.7 14.5 14.9 15.0 15.4 15.8
8H 15.4 15.7 15.8 16.2 16.6 14.5 14.8 15.0 15.3 15.8
12H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7
12H 4H 15.4 15.8 15.8 16.2 16.7 14.5 15.0 15.0 15.4 15.8
6H 15.3 15.7 15.8 16.1 16.6 14.5 14.8 14.9 15.3 15.8
8H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7

Variation of the observer position for the luminaire distances S

S = 1.0H +0.8 / -1.2 +0.7 / -1.1


S = 1.5H +2.0 / -5.0 +1.8 / -4.4
S = 2.0H +3.7 / -6.8 +2.7 / -8.0

Standard table BK01 BK01


Correction
-5.0 -5.8
Summand
Corrected Glare Indices referring to 10050lm Total Luminous Flux

Page 1
Management Office 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Management Office 2 FL / Summary

280 6.00 m
280
350
420 350 420
420 350 420
420 420 420
280 490 490 420
420 420 420
420
420 420 490 420 490
420 420 420 420
420
420
420 420
420 420 280
420 420
420 490
420 490
420 420 420 420
280 490 420 490 420
420
420
420 420 420 420
420 420
350
350 350 350 210

0.00
0.00 12.00 m

Height of Room: 3.800 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:86
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 384 168 504 0.438
Floor 10 345 183 438 0.531
Ceiling 70 42 32 48 0.766
Walls (4) 50 111 33 244 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 15 15
Grid: 64 x 32 Points Lower Wall 15 15
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.254, Ceiling / Working Plane: 0.109.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 8 Philips TBH318 3xTL-D36W HFE M5 (1.000) 10050 0.0
Total: 80400 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 72.00 m²)

Page 2
Management Office 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Management Office 2 FL / Luminaire parts list

8 Pieces Philips TBH318 3xTL-D36W HFE M5


Article No.:
Luminaire Luminous Flux: 10050 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 100
CIE flux code: 63 96 100 100 48
Fitting: 3 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Management Office 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Management Office 2 FL / Photometric Results

Total Luminous Flux: 80400 lm


Total Load: 0.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 343 40 384 / /
Floor 296 49 345 10 11
Ceiling 0.00 42 42 70 9.32
Wall 1 73 41 114 50 18
Wall 2 62 41 103 50 16
Wall 3 73 42 115 50 18
Wall 4 62 42 105 50 17

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.438 (1:2) Left Wall 15 15
Emin / Emax: 0.333 (1:3) Lower Wall 15 15
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.254, Ceiling / Working Plane: 0.109.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 72.00 m²)

Page 4
Meeting Room 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Philips TBH318 3xTL-D36W HFE M5 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

80
60° 60°

120

45° 160 45°

200

240

30° 15° 0° 15° 30°

cd/klm  48%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 63 96 100 100 48
Glare Evaluation According to UGR
Hygeia TBH318
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
Functional, fully closed recessed luminaire for 2 or 3 TL’D fluorescent lamps  Floor 20 20 20 20 20 20 20 20 20 20
for application in cleanrooms and dust-/ water-ingress protected areas. Room Size Viewing direction at right angles Viewing direction parallel
Double parabolic mirror is integrated in the luminaire with clear PMMA cover. X Y to lamp axis to lamp axis

2H 2H 15.4 16.5 15.7 16.7 16.9 14.5 15.6 14.8 15.8 16.0
3H 15.4 16.4 15.7 16.6 16.9 14.5 15.4 14.8 15.7 15.9
4H 15.4 16.3 15.7 16.5 16.8 14.4 15.3 14.7 15.6 15.9
6H 15.3 16.1 15.7 16.4 16.7 14.4 15.2 14.7 15.5 15.8
8H 15.3 16.1 15.6 16.4 16.7 14.3 15.1 14.7 15.4 15.7
12H 15.3 16.0 15.6 16.3 16.6 14.3 15.0 14.7 15.4 15.7
4H 2H 15.5 16.4 15.8 16.6 16.9 14.7 15.6 15.0 15.9 16.1
3H 15.5 16.3 15.9 16.6 16.9 14.7 15.4 15.1 15.8 16.1
4H 15.5 16.2 15.9 16.5 16.9 14.7 15.3 15.0 15.6 16.0
6H 15.5 16.0 15.9 16.4 16.8 14.6 15.2 15.0 15.5 15.9
8H 15.4 16.0 15.9 16.3 16.7 14.6 15.1 15.0 15.5 15.9
12H 15.4 15.9 15.9 16.3 16.7 14.5 15.0 15.0 15.4 15.8
8H 4H 15.4 15.9 15.8 16.3 16.7 14.6 15.1 15.0 15.5 15.9
6H 15.4 15.8 15.8 16.2 16.7 14.5 14.9 15.0 15.4 15.8
8H 15.4 15.7 15.8 16.2 16.6 14.5 14.8 15.0 15.3 15.8
12H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7
12H 4H 15.4 15.8 15.8 16.2 16.7 14.5 15.0 15.0 15.4 15.8
6H 15.3 15.7 15.8 16.1 16.6 14.5 14.8 14.9 15.3 15.8
8H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7

Variation of the observer position for the luminaire distances S

S = 1.0H +0.8 / -1.2 +0.7 / -1.1


S = 1.5H +2.0 / -5.0 +1.8 / -4.4
S = 2.0H +3.7 / -6.8 +2.7 / -8.0

Standard table BK01 BK01


Correction
-5.0 -5.8
Summand
Corrected Glare Indices referring to 10050lm Total Luminous Flux

Page 1
Meeting Room 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Meeting Room 2 FL / Summary

280 12.00 m
350
420 420
420
350 420
420
350
420 420
490 420
420 490 490
420
350
420 420
490 420
420 490 490
420 350
420
420
420
350
420
350 280
0.00
0.00 6.00 m

Height of Room: 3.800 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:155
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 396 181 517 0.458
Floor 20 357 194 450 0.544
Ceiling 70 63 45 73 0.714
Walls (4) 50 129 46 266 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 15 15
Grid: 32 x 64 Points Lower Wall 15 15
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.290, Ceiling / Working Plane: 0.159.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 8 Philips TBH318 3xTL-D36W HFE M5 (1.000) 10050 0.0
Total: 80400 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 72.00 m²)

Page 2
Meeting Room 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Meeting Room 2 FL / Luminaire parts list

8 Pieces Philips TBH318 3xTL-D36W HFE M5


Article No.:
Luminaire Luminous Flux: 10050 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 100
CIE flux code: 63 96 100 100 48
Fitting: 3 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Meeting Room 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Meeting Room 2 FL / Photometric Results

Total Luminous Flux: 80400 lm


Total Load: 0.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 343 52 396 / /
Floor 296 61 357 20 23
Ceiling 0.00 63 63 70 14
Wall 1 63 59 122 50 19
Wall 2 73 61 134 50 21
Wall 3 62 59 121 50 19
Wall 4 73 60 132 50 21

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.458 (1:2) Left Wall 15 15
Emin / Emax: 0.351 (1:3) Lower Wall 15 15
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.290, Ceiling / Working Plane: 0.159.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 72.00 m²)

Page 4
Pantry room
14.12.2012

Operator
Telephone
Fax
e-Mail

Pantry room / Summary

1.75 m
80
80

90 90
90
90

80 90 90
90
80

0.00
0.00 1.59 m

Height of Room: 3.800 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:23
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 82 67 92 0.825
Floor 10 49 43 55 0.876
Ceiling 70 7.86 7.15 8.12 0.910
Walls (4) 50 31 5.80 118 /

Workplane:
Height: 0.800 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.389, Ceiling / Working Plane: 0.096.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 1 Mazda FBS120 1xPL-C/2P18W GL (1.000) 1200 25.3
Total: 1200 25.3

Specific connected load: 9.09 W/m² = 11.13 W/m²/100 lx (Ground area: 2.78 m²)

Page 1
Pantry room
14.12.2012

Operator
Telephone
Fax
e-Mail

Pantry room / Luminaire parts list

1 Pieces Mazda FBS120 1xPL-C/2P18W GL


Article No.:
Luminaire Luminous Flux: 1200 lm
Luminaire Wattage: 25.3 W
Luminaire classification according to CIE: 100
CIE flux code: 79 100 100 100 55
Fitting: 1 x PL-C/2P18W/840 (Correction Factor
1.000).

Page 2
Pantry room
14.12.2012

Operator
Telephone
Fax
e-Mail

Pantry room / Photometric Results

Total Luminous Flux: 1200 lm


Total Load: 25.3 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 61 21 82 / /
Floor 33 17 49 10 1.57
Ceiling 0.00 7.86 7.86 70 1.75
Wall 1 15 14 29 50 4.54
Wall 2 19 14 33 50 5.26
Wall 3 15 14 29 50 4.54
Wall 4 19 14 33 50 5.26

Uniformity on the working plane


u0: 0.825 (1:1)
Emin / Emax: 0.729 (1:1)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.389, Ceiling / Working Plane: 0.096.

Specific connected load: 9.09 W/m² = 11.13 W/m²/100 lx (Ground area: 2.78 m²)

Page 3
Staff Room 1 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Philips TBH318 2xTL-D36W HFE M5 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

80
60° 60°

120

45° 160 45°

200

240

30° 15° 0° 15° 30°

cd/klm  40%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 72 96 100 100 40
Glare Evaluation According to UGR
Hygeia TBH318
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
Functional, fully closed recessed luminaire for 2 or 3 TL’D fluorescent lamps  Floor 20 20 20 20 20 20 20 20 20 20
for application in cleanrooms and dust-/ water-ingress protected areas. Room Size Viewing direction at right angles Viewing direction parallel
Double parabolic mirror is integrated in the luminaire with clear PMMA cover. X Y to lamp axis to lamp axis

2H 2H 12.5 13.5 12.8 13.7 13.9 16.3 17.3 16.6 17.5 17.7
3H 12.5 13.4 12.8 13.6 13.9 16.4 17.3 16.7 17.5 17.8
4H 12.5 13.3 12.8 13.6 13.9 16.4 17.2 16.7 17.5 17.7
6H 12.5 13.2 12.8 13.5 13.8 16.3 17.1 16.7 17.4 17.7
8H 12.4 13.1 12.8 13.4 13.8 16.3 17.0 16.6 17.3 17.6
12H 12.4 13.1 12.8 13.4 13.7 16.3 16.9 16.6 17.2 17.6
4H 2H 12.7 13.5 13.0 13.8 14.0 16.2 17.0 16.5 17.3 17.6
3H 12.7 13.4 13.1 13.7 14.0 16.3 17.0 16.6 17.3 17.6
4H 12.7 13.3 13.1 13.6 14.0 16.3 16.9 16.7 17.2 17.6
6H 12.7 13.2 13.1 13.6 13.9 16.2 16.7 16.6 17.1 17.5
8H 12.7 13.1 13.1 13.5 13.9 16.2 16.7 16.6 17.0 17.5
12H 12.6 13.0 13.1 13.4 13.9 16.2 16.6 16.6 17.0 17.4
8H 4H 12.7 13.1 13.1 13.5 13.9 16.2 16.6 16.6 17.0 17.4
6H 12.6 13.0 13.1 13.4 13.9 16.1 16.5 16.6 16.9 17.4
8H 12.6 12.9 13.1 13.4 13.8 16.1 16.4 16.6 16.9 17.3
12H 12.6 12.8 13.1 13.3 13.8 16.1 16.3 16.5 16.8 17.3
12H 4H 12.6 13.0 13.1 13.4 13.9 16.1 16.5 16.6 16.9 17.4
6H 12.6 12.9 13.1 13.3 13.8 16.1 16.4 16.6 16.9 17.3
8H 12.6 12.8 13.0 13.3 13.8 16.1 16.3 16.5 16.8 17.3

Variation of the observer position for the luminaire distances S

S = 1.0H +2.1 / -3.6 +0.7 / -1.0


S = 1.5H +3.4 / -5.3 +1.7 / -3.7
S = 2.0H +5.0 / -6.6 +3.5 / -7.3

Standard table BK01 BK00


Correction
-8.4 -5.2
Summand
Corrected Glare Indices referring to 6700lm Total Luminous Flux

Page 1
Staff Room 1 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Staff Room 1 FL / Summary

12.18 m
160
160

240 240
240 200
200

240 200
200 240

240
160
160

240
200
240
160
120 160
0.00
0.00 4.34 m

Height of Room: 3.800 m, Mounting Height: 3.900 m, Light loss factor: Values in Lux, Scale 1:157
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 190 90 269 0.474
Floor 10 170 98 220 0.575
Ceiling 70 26 21 29 0.809
Walls (4) 50 68 22 147 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 13 16
Grid: 64 x 32 Points Lower Wall 13 16
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.357, Ceiling / Working Plane: 0.137.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 6 Philips TBH318 2xTL-D36W HFE M5 (1.000) 6700 0.0
Total: 40200 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 52.92 m²)

Page 2
Staff Room 1 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Staff Room 1 FL / Luminaire parts list

6 Pieces Philips TBH318 2xTL-D36W HFE M5


Article No.:
Luminaire Luminous Flux: 6700 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 100
CIE flux code: 72 96 100 100 40
Fitting: 2 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Staff Room 1 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Staff Room 1 FL / Photometric Results

Total Luminous Flux: 40200 lm


Total Load: 0.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 162 27 190 / /
Floor 140 30 170 10 5.40
Ceiling 0.00 26 26 70 5.80
Wall 1 41 26 67 50 11
Wall 2 44 25 69 50 11
Wall 3 41 25 66 50 10
Wall 4 44 25 69 50 11

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.474 (1:2) Left Wall 13 16
Emin / Emax: 0.334 (1:3) Lower Wall 13 16
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.357, Ceiling / Working Plane: 0.137.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 52.92 m²)

Page 4
Admin Office 1 FL
21.12.2012

Operator
Telephone
Fax
e-Mail

Admin Office 1 FL / Summary

3.39 m

90
100
100 90
100

100
100

100
100

100
100
100 100

90

0.00
0.00 2.61 m

Height of Room: 3.800 m, Mounting Height: 3.800 m, Light loss factor: Values in Lux, Scale 1:44
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 98 82 110 0.835
Floor 10 98 83 110 0.850
Ceiling 70 113 53 738 0.467
Walls (4) 50 115 45 259 /

Workplane:
Height: 0.000 m
Grid: 16 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.171, Ceiling / Working Plane: 1.161.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 1 Philips TCW097 2xTL-D36W EBS (1.000) 6700 0.0
Total: 6700 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 8.85 m²)

Page 1
Admin Office 1 FL
21.12.2012

Operator
Telephone
Fax
e-Mail

Admin Office 1 FL / Luminaire parts list

1 Pieces Philips TCW097 2xTL-D36W EBS


Article No.:
Luminaire Luminous Flux: 6700 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 88
CIE flux code: 37 66 87 85 69
Fitting: 2 x TL-D36W/840 (Correction Factor
1.000).

Page 2
Admin Office 1 FL
21.12.2012

Operator
Telephone
Fax
e-Mail

Admin Office 1 FL / Photometric Results

Total Luminous Flux: 6700 lm


Total Load: 0.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 48 50 98 / /
Floor 48 50 98 10 3.12
Ceiling 53 61 113 70 25
Wall 1 74 52 126 50 20
Wall 2 52 54 106 50 17
Wall 3 74 52 126 50 20
Wall 4 52 54 106 50 17

Uniformity on the working plane


u0: 0.835 (1:1)
Emin / Emax: 0.742 (1:1)

Illuminance Quotient (according to LG7): Walls / Working Plane: 1.171, Ceiling / Working Plane: 1.161.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 8.85 m²)

Page 3
Supervisor Office 1 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Philips TBH318 3xTL-D36W HFE M5 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

80
60° 60°

120

45° 160 45°

200

240

30° 15° 0° 15° 30°

cd/klm  48%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 63 96 100 100 48
Glare Evaluation According to UGR
Hygeia TBH318
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
Functional, fully closed recessed luminaire for 2 or 3 TL’D fluorescent lamps  Floor 20 20 20 20 20 20 20 20 20 20
for application in cleanrooms and dust-/ water-ingress protected areas. Room Size Viewing direction at right angles Viewing direction parallel
Double parabolic mirror is integrated in the luminaire with clear PMMA cover. X Y to lamp axis to lamp axis

2H 2H 15.4 16.5 15.7 16.7 16.9 14.5 15.6 14.8 15.8 16.0
3H 15.4 16.4 15.7 16.6 16.9 14.5 15.4 14.8 15.7 15.9
4H 15.4 16.3 15.7 16.5 16.8 14.4 15.3 14.7 15.6 15.9
6H 15.3 16.1 15.7 16.4 16.7 14.4 15.2 14.7 15.5 15.8
8H 15.3 16.1 15.6 16.4 16.7 14.3 15.1 14.7 15.4 15.7
12H 15.3 16.0 15.6 16.3 16.6 14.3 15.0 14.7 15.4 15.7
4H 2H 15.5 16.4 15.8 16.6 16.9 14.7 15.6 15.0 15.9 16.1
3H 15.5 16.3 15.9 16.6 16.9 14.7 15.4 15.1 15.8 16.1
4H 15.5 16.2 15.9 16.5 16.9 14.7 15.3 15.0 15.6 16.0
6H 15.5 16.0 15.9 16.4 16.8 14.6 15.2 15.0 15.5 15.9
8H 15.4 16.0 15.9 16.3 16.7 14.6 15.1 15.0 15.5 15.9
12H 15.4 15.9 15.9 16.3 16.7 14.5 15.0 15.0 15.4 15.8
8H 4H 15.4 15.9 15.8 16.3 16.7 14.6 15.1 15.0 15.5 15.9
6H 15.4 15.8 15.8 16.2 16.7 14.5 14.9 15.0 15.4 15.8
8H 15.4 15.7 15.8 16.2 16.6 14.5 14.8 15.0 15.3 15.8
12H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7
12H 4H 15.4 15.8 15.8 16.2 16.7 14.5 15.0 15.0 15.4 15.8
6H 15.3 15.7 15.8 16.1 16.6 14.5 14.8 14.9 15.3 15.8
8H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7

Variation of the observer position for the luminaire distances S

S = 1.0H +0.8 / -1.2 +0.7 / -1.1


S = 1.5H +2.0 / -5.0 +1.8 / -4.4
S = 2.0H +3.7 / -6.8 +2.7 / -8.0

Standard table BK01 BK01


Correction
-5.0 -5.8
Summand
Corrected Glare Indices referring to 10050lm Total Luminous Flux

Page 1
Supervisor Office 1 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Supervisor Office 1 FL / Summary

300 300 5.50 m

360 240
300 360
420 420 300
420 420

300 360
420 420 420 360 300
420
420
420

420 420
300
300
420
420
360 360
300 300 300
0.00
0.00 6.28 m

Height of Room: 3.800 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:71
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 375 183 481 0.488
Floor 10 323 193 408 0.598
Ceiling 70 41 30 48 0.752
Walls (4) 50 109 31 227 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 16 15
Grid: 32 x 32 Points Lower Wall 16 15
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.259, Ceiling / Working Plane: 0.108.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 4 Philips TBH318 3xTL-D36W HFE M5 (1.000) 10050 0.0
Total: 40200 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 34.54 m²)

Page 2
Supervisor Office 1 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Supervisor Office 1 FL / Luminaire parts list

4 Pieces Philips TBH318 3xTL-D36W HFE M5


Article No.:
Luminaire Luminous Flux: 10050 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 100
CIE flux code: 63 96 100 100 48
Fitting: 3 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Supervisor Office 1 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Supervisor Office 1 FL / Photometric Results

Total Luminous Flux: 40200 lm


Total Load: 0.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 331 44 375 / /
Floor 271 53 323 10 10
Ceiling 0.00 41 41 70 9.03
Wall 1 67 42 109 50 17
Wall 2 68 42 110 50 17
Wall 3 67 42 109 50 17
Wall 4 68 42 110 50 18

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.488 (1:2) Left Wall 16 15
Emin / Emax: 0.381 (1:3) Lower Wall 16 15
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.259, Ceiling / Working Plane: 0.108.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 34.54 m²)

Page 4
Supervisor Office 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Philips TBH318 3xTL-D36W HFE M5 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

80
60° 60°

120

45° 160 45°

200

240

30° 15° 0° 15° 30°

cd/klm  48%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 63 96 100 100 48
Glare Evaluation According to UGR
Hygeia TBH318
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
Functional, fully closed recessed luminaire for 2 or 3 TL’D fluorescent lamps  Floor 20 20 20 20 20 20 20 20 20 20
for application in cleanrooms and dust-/ water-ingress protected areas. Room Size Viewing direction at right angles Viewing direction parallel
Double parabolic mirror is integrated in the luminaire with clear PMMA cover. X Y to lamp axis to lamp axis

2H 2H 15.4 16.5 15.7 16.7 16.9 14.5 15.6 14.8 15.8 16.0
3H 15.4 16.4 15.7 16.6 16.9 14.5 15.4 14.8 15.7 15.9
4H 15.4 16.3 15.7 16.5 16.8 14.4 15.3 14.7 15.6 15.9
6H 15.3 16.1 15.7 16.4 16.7 14.4 15.2 14.7 15.5 15.8
8H 15.3 16.1 15.6 16.4 16.7 14.3 15.1 14.7 15.4 15.7
12H 15.3 16.0 15.6 16.3 16.6 14.3 15.0 14.7 15.4 15.7
4H 2H 15.5 16.4 15.8 16.6 16.9 14.7 15.6 15.0 15.9 16.1
3H 15.5 16.3 15.9 16.6 16.9 14.7 15.4 15.1 15.8 16.1
4H 15.5 16.2 15.9 16.5 16.9 14.7 15.3 15.0 15.6 16.0
6H 15.5 16.0 15.9 16.4 16.8 14.6 15.2 15.0 15.5 15.9
8H 15.4 16.0 15.9 16.3 16.7 14.6 15.1 15.0 15.5 15.9
12H 15.4 15.9 15.9 16.3 16.7 14.5 15.0 15.0 15.4 15.8
8H 4H 15.4 15.9 15.8 16.3 16.7 14.6 15.1 15.0 15.5 15.9
6H 15.4 15.8 15.8 16.2 16.7 14.5 14.9 15.0 15.4 15.8
8H 15.4 15.7 15.8 16.2 16.6 14.5 14.8 15.0 15.3 15.8
12H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7
12H 4H 15.4 15.8 15.8 16.2 16.7 14.5 15.0 15.0 15.4 15.8
6H 15.3 15.7 15.8 16.1 16.6 14.5 14.8 14.9 15.3 15.8
8H 15.3 15.6 15.8 16.1 16.6 14.4 14.8 14.9 15.2 15.7

Variation of the observer position for the luminaire distances S

S = 1.0H +0.8 / -1.2 +0.7 / -1.1


S = 1.5H +2.0 / -5.0 +1.8 / -4.4
S = 2.0H +3.7 / -6.8 +2.7 / -8.0

Standard table BK01 BK01


Correction
-5.0 -5.8
Summand
Corrected Glare Indices referring to 10050lm Total Luminous Flux

Page 1
Supervisor Office 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Supervisor office 2 FL / Summary

6.00 m
440

440 550
330
330
220 550 550 220
440
550 550
330
330
440
220 440 220

550 550 330


330
440
550 550
220 220
330
330 440

0.00
0.00 4.50 m

Height of Room: 3.800 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:78
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 362 122 642 0.337
Floor 10 308 160 459 0.520
Ceiling 80 37 29 43 0.776
Walls (4) 50 97 30 423 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 16 15
Grid: 32 x 32 Points Lower Wall 15 14
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.232, Ceiling / Working Plane: 0.102.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 3 Philips TBH318 3xTL-D36W HFE M5 (1.000) 10050 0.0
Total: 30150 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 27.00 m²)

Page 2
Supervisor Office 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Supervisor office 2 FL / Luminaire parts list

3 Pieces Philips TBH318 3xTL-D36W HFE M5


Article No.:
Luminaire Luminous Flux: 10050 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 100
CIE flux code: 63 96 100 100 48
Fitting: 3 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Supervisor Office 2 FL
17.10.2012

Operator
Telephone
Fax
e-Mail

Supervisor office 2 FL / Photometric Results

Total Luminous Flux: 30150 lm


Total Load: 0.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 321 42 362 / /
Floor 258 50 308 10 9.80
Ceiling 0.00 37 37 80 9.37
Wall 1 76 38 114 50 18
Wall 2 44 40 84 50 13
Wall 3 76 38 114 50 18
Wall 4 44 40 84 50 13

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.337 (1:3) Left Wall 16 15
Emin / Emax: 0.190 (1:5) Lower Wall 15 14
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.232, Ceiling / Working Plane: 0.102.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 27.00 m²)

Page 4
Toilet-1-1fl and 2fl
14.12.2012

Operator
Telephone
Fax
e-Mail

Toilet-1-1fl and 2fl / Summary

2.37 m
80
100 100 100

80
100
120 120
120
100
120 120

100 120
120
100
120
120 120 120

100 80
100

80 100 100
0.00
0.00 4.01 m

Height of Room: 3.800 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:31
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 101 66 135 0.652
Floor 10 101 68 135 0.670
Ceiling 70 8.56 7.38 9.51 0.862
Walls (4) 50 28 6.32 95 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 17 14
Grid: 64 x 64 Points Lower Wall 17 14
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.277, Ceiling / Working Plane: 0.085.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 3 Mazda FBS120 1xPL-C/2P18W GL (1.000) 1200 25.3
Total: 3600 75.9

Specific connected load: 7.99 W/m² = 7.91 W/m²/100 lx (Ground area: 9.50 m²)

Page 1
Toilet-1-1fl and 2fl
14.12.2012

Operator
Telephone
Fax
e-Mail

Toilet-1-1fl and 2fl / Luminaire parts list

3 Pieces Mazda FBS120 1xPL-C/2P18W GL


Article No.:
Luminaire Luminous Flux: 1200 lm
Luminaire Wattage: 25.3 W
Luminaire classification according to CIE: 100
CIE flux code: 79 100 100 100 55
Fitting: 1 x PL-C/2P18W/840 (Correction Factor
1.000).

Page 2
Toilet-1-1fl and 2fl
14.12.2012

Operator
Telephone
Fax
e-Mail

Toilet-1-1fl and 2fl / Photometric Results

Total Luminous Flux: 3600 lm


Total Load: 75.9 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 83 18 101 / /
Floor 83 18 101 10 3.22
Ceiling 0.00 8.56 8.56 70 1.91
Wall 1 16 12 28 50 4.51
Wall 2 16 12 28 50 4.38
Wall 3 16 12 28 50 4.51
Wall 4 16 12 28 50 4.39

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.652 (1:2) Left Wall 17 14
Emin / Emax: 0.488 (1:2) Lower Wall 17 14
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.277, Ceiling / Working Plane: 0.085.

Specific connected load: 7.99 W/m² = 7.91 W/m²/100 lx (Ground area: 9.50 m²)

Page 3
Toilet-2-1fl and 2fl
21.12.2012

Operator
Telephone
Fax
e-Mail

Toilet-2-1fl and 2fl / Summary

3.13 m

80
100 80
100 100
100 100
120
120
120
100 100

100 100

80 80

0.00
0.00 1.77 m

Height of Room: 3.800 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:41
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 90 68 125 0.752
Floor 10 90 66 125 0.737
Ceiling 70 8.08 7.07 8.85 0.875
Walls (4) 50 31 5.95 101 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 17 14
Grid: 32 x 32 Points Lower Wall 17 14
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.347, Ceiling / Working Plane: 0.090.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 2 Mazda FBS120 1xPL-C/2P18W GL (1.000) 1200 25.3
Total: 2400 50.6

Specific connected load: 9.13 W/m² = 10.15 W/m²/100 lx (Ground area: 5.54 m²)

Page 1
Toilet-2-1fl and 2fl
21.12.2012

Operator
Telephone
Fax
e-Mail

Toilet-2-1fl and 2fl / Luminaire parts list

2 Pieces Mazda FBS120 1xPL-C/2P18W GL


Article No.:
Luminaire Luminous Flux: 1200 lm
Luminaire Wattage: 25.3 W
Luminaire classification according to CIE: 100
CIE flux code: 79 100 100 100 55
Fitting: 1 x PL-C/2P18W/840 (Correction Factor
1.000).

Page 2
Toilet-2-1fl and 2fl
21.12.2012

Operator
Telephone
Fax
e-Mail

Toilet-2-1fl and 2fl / Photometric Results

Total Luminous Flux: 2400 lm


Total Load: 50.6 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 69 21 90 / /
Floor 69 21 90 10 2.87
Ceiling 0.00 8.08 8.08 70 1.80
Wall 1 15 14 29 50 4.55
Wall 2 20 13 33 50 5.24
Wall 3 15 13 29 50 4.55
Wall 4 20 14 33 50 5.26

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.752 (1:1) Left Wall 17 14
Emin / Emax: 0.542 (1:2) Lower Wall 17 14
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.347, Ceiling / Working Plane: 0.090.

Specific connected load: 9.13 W/m² = 10.15 W/m²/100 lx (Ground area: 5.54 m²)

Page 3
PAGE NO. 1
PAGE NO. 1

NOIBAI PROJECT

ROOM(M) MTG WORK ROOM LUMINAIRE


ROOM NO. DESCRIPTION HGT. PLANE INDEX ρC ρw U M E T5 N E' REMARKS
H W L (M) (M) (LX) LAMP DISTRI. LUMENS (LX)
101 1F LOCKER ROOM 3.8 3.3 9.1 3.0 0.80 1.10 0.7 0.5 0.63 0.80 150 36W T-BAR DUHAL 1X36 2600 4 176 LDA-140

102 1F STORAGE 3.8 2.3 1.6 3.0 0.00 0.32 0.7 0.5 0.63 0.80 100 36W T-BAR DUHAL 1X36 2600 1 350 LDA-140

103 VOID 6.8 3.0 4.4 3.7 0.00 0.48 0.7 0.3 0.58 0.80 200 2X36W TMX-204 6700 2 471 WALL MOUNTED

104 ENTRANCE CANOPY 3.4 3.4 4.9 3.4 0.00 0.59 0.5 0 0.63 0.80 200 22 JOKENS 650081 1700 4 203 SURFACE MOUNTED
ρC,ρ
ρW:REFLECTION FACTORS U:CONFFICIENT OF UTILIZATION E:RECOMMEND ILLUMINATION N:NUMBER OF LUMINAIRES E':MAINTANED ILLUMINATION
Electrical Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Philips TMX204 2xTL-D36W HFP +GMX430 R / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

100
60° 60°

150

45° 200 45°

300

30° 15° 0° 15° 30°

cd/klm  76%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 46 79 96 100 76
Glare Evaluation According to UGR
TMX204 LS – slender and versatile
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
TMX204 LS is a functional batten for TL-D and TL5 fluorescent lamps for  Floor 20 20 20 20 20 20 20 20 20 20
general lighting. A wide range of reflectors and attachments from the Room Size Viewing direction at right angles Viewing direction parallel
TTX400 series can be fitted to enhance system efficiency and versatility, X Y to lamp axis to lamp axis

making it suitable for a variety of applications. This batten can be suspended 2H 2H 19.2 20.5 19.5 20.7 21.0 19.2 20.5 19.5 20.7 21.0
or surface-mounted. Thanks to its slim design, it is also well suited for build- 3H 20.6 21.8 20.9 22.0 22.3 20.8 22.0 21.1 22.3 22.5
4H 20.8 22.0 21.2 22.3 22.5 21.5 22.6 21.8 22.9 23.2
in applications and coves. 6H 21.0 22.1 21.4 22.4 22.7 21.9 23.0 22.3 23.3 23.6
8H 21.1 22.1 21.4 22.4 22.7 22.0 23.0 22.4 23.4 23.7
12H 21.1 22.1 21.5 22.4 22.7 22.1 23.0 22.5 23.4 23.7
4H 2H 19.9 21.0 20.2 21.3 21.6 19.9 21.0 20.2 21.3 21.6
3H 21.5 22.4 21.8 22.8 23.1 21.7 22.7 22.1 23.0 23.4
4H 21.8 22.7 22.2 23.0 23.4 22.5 23.4 22.9 23.7 24.1
6H 22.0 22.8 22.5 23.2 23.6 23.1 23.8 23.5 24.2 24.6
8H 22.1 22.8 22.6 23.2 23.6 23.3 24.0 23.7 24.4 24.8
12H 22.2 22.8 22.7 23.2 23.7 23.4 24.0 23.8 24.4 24.8
8H 4H 22.1 22.8 22.5 23.2 23.6 22.8 23.4 23.2 23.8 24.2
6H 22.4 23.0 22.9 23.4 23.8 23.4 24.0 23.9 24.4 24.9
8H 22.5 23.0 23.0 23.5 24.0 23.7 24.2 24.2 24.6 25.1
12H 22.7 23.1 23.2 23.5 24.0 23.8 24.2 24.3 24.7 25.2
12H 4H 22.1 22.7 22.6 23.1 23.6 22.7 23.4 23.2 23.8 24.2
6H 22.4 22.9 22.9 23.4 23.9 23.4 23.9 23.9 24.4 24.9
8H 22.6 23.0 23.1 23.5 24.0 23.7 24.1 24.2 24.6 25.1

Variation of the observer position for the luminaire distances S

S = 1.0H +0.2 / -0.2 +0.1 / -0.1


S = 1.5H +0.3 / -0.4 +0.3 / -0.4
S = 2.0H +0.4 / -0.7 +0.4 / -0.8

Standard table BK04 BK06


Correction
3.9 5.6
Summand
Corrected Glare Indices referring to 6700lm Total Luminous Flux

Page 1
Electrical Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Electrical Room / Summary

10.00 m

300 300 300 300


240 360 240
240
240
300 300 300
300 300
300
360 360
300 300
300 300
300 360 300
360 360
360 360
300 240
240 300 300
360 360 300 360
360 300 360
360 360 300 300
300 240
240
180 300
300 300
180 180
0.00
0.00 15.00 m

Height of Room: 5.850 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:129
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 279 129 406 0.461
Floor 10 279 125 405 0.448
Ceiling 70 28 21 32 0.756
Walls (4) 50 68 21 285 /

Workplane:
Height: 0.000 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.244, Ceiling / Working Plane: 0.099.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 12 Philips TMX204 2xTL-D36W HFP +GMX430 R (1.000) 6700 72.0
Total: 80400 864.0

Specific connected load: 5.76 W/m² = 2.07 W/m²/100 lx (Ground area: 150.00 m²)

Page 2
Electrical Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Electrical Room / Luminaire parts list

12 Pieces Philips TMX204 2xTL-D36W HFP +GMX430 R


Article No.:
Luminaire Luminous Flux: 6700 lm
Luminaire Wattage: 72.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 79 96 100 76
Fitting: 2 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Electrical Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Electrical Room / Photometric Results

Total Luminous Flux: 80400 lm


Total Load: 864.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 246 33 279 / /
Floor 246 33 279 10 8.87
Ceiling 0.00 28 28 70 6.15
Wall 1 45 27 73 50 12
Wall 2 34 28 62 50 9.88
Wall 3 45 28 73 50 12
Wall 4 34 28 62 50 9.89

Uniformity on the working plane


u0: 0.461 (1:2)
Emin / Emax: 0.317 (1:3)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.244, Ceiling / Working Plane: 0.099.

Specific connected load: 5.76 W/m² = 2.07 W/m²/100 lx (Ground area: 150.00 m²)

Page 4
Generator Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Philips TMX204 2xTL-D36W HFP +GMX430 R / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

100
60° 60°

150

45° 200 45°

300

30° 15° 0° 15° 30°

cd/klm  76%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 46 79 96 100 76
Glare Evaluation According to UGR
TMX204 LS – slender and versatile
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
TMX204 LS is a functional batten for TL-D and TL5 fluorescent lamps for  Floor 20 20 20 20 20 20 20 20 20 20
general lighting. A wide range of reflectors and attachments from the Room Size Viewing direction at right angles Viewing direction parallel
TTX400 series can be fitted to enhance system efficiency and versatility, X Y to lamp axis to lamp axis

making it suitable for a variety of applications. This batten can be suspended 2H 2H 19.2 20.5 19.5 20.7 21.0 19.2 20.5 19.5 20.7 21.0
or surface-mounted. Thanks to its slim design, it is also well suited for build- 3H 20.6 21.8 20.9 22.0 22.3 20.8 22.0 21.1 22.3 22.5
4H 20.8 22.0 21.2 22.3 22.5 21.5 22.6 21.8 22.9 23.2
in applications and coves. 6H 21.0 22.1 21.4 22.4 22.7 21.9 23.0 22.3 23.3 23.6
8H 21.1 22.1 21.4 22.4 22.7 22.0 23.0 22.4 23.4 23.7
12H 21.1 22.1 21.5 22.4 22.7 22.1 23.0 22.5 23.4 23.7
4H 2H 19.9 21.0 20.2 21.3 21.6 19.9 21.0 20.2 21.3 21.6
3H 21.5 22.4 21.8 22.8 23.1 21.7 22.7 22.1 23.0 23.4
4H 21.8 22.7 22.2 23.0 23.4 22.5 23.4 22.9 23.7 24.1
6H 22.0 22.8 22.5 23.2 23.6 23.1 23.8 23.5 24.2 24.6
8H 22.1 22.8 22.6 23.2 23.6 23.3 24.0 23.7 24.4 24.8
12H 22.2 22.8 22.7 23.2 23.7 23.4 24.0 23.8 24.4 24.8
8H 4H 22.1 22.8 22.5 23.2 23.6 22.8 23.4 23.2 23.8 24.2
6H 22.4 23.0 22.9 23.4 23.8 23.4 24.0 23.9 24.4 24.9
8H 22.5 23.0 23.0 23.5 24.0 23.7 24.2 24.2 24.6 25.1
12H 22.7 23.1 23.2 23.5 24.0 23.8 24.2 24.3 24.7 25.2
12H 4H 22.1 22.7 22.6 23.1 23.6 22.7 23.4 23.2 23.8 24.2
6H 22.4 22.9 22.9 23.4 23.9 23.4 23.9 23.9 24.4 24.9
8H 22.6 23.0 23.1 23.5 24.0 23.7 24.1 24.2 24.6 25.1

Variation of the observer position for the luminaire distances S

S = 1.0H +0.2 / -0.2 +0.1 / -0.1


S = 1.5H +0.3 / -0.4 +0.3 / -0.4
S = 2.0H +0.4 / -0.7 +0.4 / -0.8

Standard table BK04 BK06


Correction
3.9 5.6
Summand
Corrected Glare Indices referring to 6700lm Total Luminous Flux

Page 1
Generator Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Generator Room / Summary

200 200 12.00 m


250 250
300 250
300
300 300 300
250 300
200
250 250
250
300
300 300 300
250 350
300
300 300 300
300
250
250 250
250 300
300
300 300 300
300 200
200 200
0.00
0.00 10.00 m

Height of Room: 5.850 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:155
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 256 131 358 0.513
Floor 10 256 129 357 0.505
Ceiling 70 25 19 30 0.756
Walls (4) 50 63 19 211 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 23 24
Grid: 64 x 64 Points Lower Wall 23 24
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.245, Ceiling / Working Plane: 0.098.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 9 Philips TMX204 2xTL-D36W HFP +GMX430 R (1.000) 6700 72.0
Total: 60300 648.0

Specific connected load: 5.40 W/m² = 2.11 W/m²/100 lx (Ground area: 120.00 m²)

Page 2
Generator Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Generator Room / Luminaire parts list

9 Pieces Philips TMX204 2xTL-D36W HFP +GMX430 R


Article No.:
Luminaire Luminous Flux: 6700 lm
Luminaire Wattage: 72.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 79 96 100 76
Fitting: 2 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Generator Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Generator Room / Photometric Results

Total Luminous Flux: 60300 lm


Total Load: 648.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 225 31 256 / /
Floor 225 31 256 10 8.14
Ceiling 0.00 25 25 70 5.61
Wall 1 34 26 60 50 9.48
Wall 2 40 25 65 50 10
Wall 3 34 26 60 50 9.57
Wall 4 41 25 66 50 10

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.513 (1:2) Left Wall 23 24
Emin / Emax: 0.366 (1:3) Lower Wall 23 24
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.245, Ceiling / Working Plane: 0.098.

Specific connected load: 5.40 W/m² = 2.11 W/m²/100 lx (Ground area: 120.00 m²)

Page 4
Instrument Panel Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Philips TMX204 2xTL-D36W HFP +GMX430 R / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

100
60° 60°

150

45° 200 45°

300

30° 15° 0° 15° 30°

cd/klm  76%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 46 79 96 100 76
Glare Evaluation According to UGR
TMX204 LS – slender and versatile
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
TMX204 LS is a functional batten for TL-D and TL5 fluorescent lamps for  Floor 20 20 20 20 20 20 20 20 20 20
general lighting. A wide range of reflectors and attachments from the Room Size Viewing direction at right angles Viewing direction parallel
TTX400 series can be fitted to enhance system efficiency and versatility, X Y to lamp axis to lamp axis

making it suitable for a variety of applications. This batten can be suspended 2H 2H 19.2 20.5 19.5 20.7 21.0 19.2 20.5 19.5 20.7 21.0
or surface-mounted. Thanks to its slim design, it is also well suited for build- 3H 20.6 21.8 20.9 22.0 22.3 20.8 22.0 21.1 22.3 22.5
4H 20.8 22.0 21.2 22.3 22.5 21.5 22.6 21.8 22.9 23.2
in applications and coves. 6H 21.0 22.1 21.4 22.4 22.7 21.9 23.0 22.3 23.3 23.6
8H 21.1 22.1 21.4 22.4 22.7 22.0 23.0 22.4 23.4 23.7
12H 21.1 22.1 21.5 22.4 22.7 22.1 23.0 22.5 23.4 23.7
4H 2H 19.9 21.0 20.2 21.3 21.6 19.9 21.0 20.2 21.3 21.6
3H 21.5 22.4 21.8 22.8 23.1 21.7 22.7 22.1 23.0 23.4
4H 21.8 22.7 22.2 23.0 23.4 22.5 23.4 22.9 23.7 24.1
6H 22.0 22.8 22.5 23.2 23.6 23.1 23.8 23.5 24.2 24.6
8H 22.1 22.8 22.6 23.2 23.6 23.3 24.0 23.7 24.4 24.8
12H 22.2 22.8 22.7 23.2 23.7 23.4 24.0 23.8 24.4 24.8
8H 4H 22.1 22.8 22.5 23.2 23.6 22.8 23.4 23.2 23.8 24.2
6H 22.4 23.0 22.9 23.4 23.8 23.4 24.0 23.9 24.4 24.9
8H 22.5 23.0 23.0 23.5 24.0 23.7 24.2 24.2 24.6 25.1
12H 22.7 23.1 23.2 23.5 24.0 23.8 24.2 24.3 24.7 25.2
12H 4H 22.1 22.7 22.6 23.1 23.6 22.7 23.4 23.2 23.8 24.2
6H 22.4 22.9 22.9 23.4 23.9 23.4 23.9 23.9 24.4 24.9
8H 22.6 23.0 23.1 23.5 24.0 23.7 24.1 24.2 24.6 25.1

Variation of the observer position for the luminaire distances S

S = 1.0H +0.2 / -0.2 +0.1 / -0.1


S = 1.5H +0.3 / -0.4 +0.3 / -0.4
S = 2.0H +0.4 / -0.7 +0.4 / -0.8

Standard table BK04 BK06


Correction
3.9 5.6
Summand
Corrected Glare Indices referring to 6700lm Total Luminous Flux

Page 1
Instrument Panel Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Instrument Panel Room / Summary

150 250 5.00 m


200 250 250
250 250 300
300 250 150
250
200 250 250
250 250
250 250
250 250
200 300
250 250
250
250
250 250
200 250
300 250 300
250 300 300 200
300
250
250 250 200
0.00
0.00 15.00 m

Height of Room: 5.850 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:108
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 241 120 353 0.498
Floor 10 241 119 353 0.494
Ceiling 70 23 18 26 0.799
Walls (4) 50 65 17 283 /

Workplane:
Height: 0.000 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.269, Ceiling / Working Plane: 0.096.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 6 Philips TMX204 2xTL-D36W HFP +GMX430 R (1.000) 6700 72.0
Total: 40200 432.0

Specific connected load: 5.76 W/m² = 2.39 W/m²/100 lx (Ground area: 75.00 m²)

Page 2
Instrument Panel Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Instrument Panel Room / Luminaire parts list

6 Pieces Philips TMX204 2xTL-D36W HFP +GMX430 R


Article No.:
Luminaire Luminous Flux: 6700 lm
Luminaire Wattage: 72.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 79 96 100 76
Fitting: 2 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Instrument Panel Room
04.12.2012

Operator
Telephone
Fax
e-Mail

Instrument Panel Room / Photometric Results

Total Luminous Flux: 40200 lm


Total Load: 432.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 204 37 241 / /
Floor 204 37 241 10 7.69
Ceiling 0.00 23 23 70 5.14
Wall 1 42 26 69 50 11
Wall 2 28 26 54 50 8.67
Wall 3 42 27 69 50 11
Wall 4 28 26 54 50 8.66

Uniformity on the working plane


u0: 0.498 (1:2)
Emin / Emax: 0.341 (1:3)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.269, Ceiling / Working Plane: 0.096.

Specific connected load: 5.76 W/m² = 2.39 W/m²/100 lx (Ground area: 75.00 m²)

Page 4
Fire Pump House
17.10.2012

Operator
Telephone
Fax
e-Mail

Philips TMX204 2xTL-D36W HFP +GMX440 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

100
60° 60°

150

45° 200 45°

300

30° 15° 0° 15° 30°

cd/klm  78%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 48 81 97 100 78
Glare Evaluation According to UGR
TMX204 LS – slender and versatile
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
TMX204 LS is a functional batten for TL-D and TL5 fluorescent lamps for  Floor 20 20 20 20 20 20 20 20 20 20
general lighting. A wide range of reflectors and attachments from the Room Size Viewing direction at right angles Viewing direction parallel
TTX400 series can be fitted to enhance system efficiency and versatility, X Y to lamp axis to lamp axis

making it suitable for a variety of applications. This batten can be suspended 2H 2H 19.3 20.6 19.6 20.8 21.0 19.4 20.7 19.7 20.9 21.1
or surface-mounted. Thanks to its slim design, it is also well suited for build- 3H 20.6 21.7 20.9 22.0 22.3 20.9 22.0 21.2 22.3 22.6
4H 20.8 21.9 21.2 22.2 22.5 21.4 22.5 21.8 22.8 23.1
in applications and coves. 6H 20.8 21.9 21.2 22.2 22.5 21.8 22.8 22.1 23.1 23.4
8H 20.8 21.8 21.1 22.1 22.4 21.9 22.9 22.2 23.2 23.5
12H 20.7 21.7 21.1 22.0 22.3 21.9 22.9 22.3 23.2 23.5
4H 2H 19.9 21.0 20.3 21.3 21.6 20.0 21.2 20.4 21.4 21.7
3H 21.4 22.4 21.8 22.7 23.0 21.7 22.7 22.1 23.0 23.3
4H 21.8 22.6 22.2 22.9 23.3 22.4 23.3 22.8 23.6 24.0
6H 21.8 22.5 22.2 22.9 23.3 22.9 23.6 23.3 24.0 24.4
8H 21.8 22.4 22.2 22.8 23.2 23.1 23.7 23.5 24.1 24.6
12H 21.7 22.3 22.2 22.7 23.2 23.2 23.8 23.6 24.2 24.6
8H 4H 22.0 22.7 22.4 23.1 23.5 22.6 23.3 23.1 23.7 24.1
6H 22.1 22.6 22.5 23.0 23.5 23.3 23.8 23.7 24.2 24.7
8H 22.0 22.5 22.5 22.9 23.4 23.5 24.0 24.0 24.4 24.9
12H 22.0 22.4 22.5 22.9 23.4 23.7 24.1 24.2 24.5 25.0
12H 4H 22.0 22.6 22.5 23.0 23.5 22.6 23.2 23.1 23.6 24.1
6H 22.1 22.6 22.6 23.0 23.5 23.2 23.7 23.7 24.2 24.6
8H 22.1 22.5 22.6 22.9 23.4 23.5 23.9 24.0 24.4 24.9

Variation of the observer position for the luminaire distances S

S = 1.0H +0.2 / -0.2 +0.1 / -0.2


S = 1.5H +0.7 / -0.9 +0.5 / -0.6
S = 2.0H +0.9 / -1.1 +0.7 / -1.1

Standard table BK03 BK05


Correction
3.3 5.1
Summand
Corrected Glare Indices referring to 6700lm Total Luminous Flux

Page 1
Fire Pump House
17.10.2012

Operator
Telephone
Fax
e-Mail

Fire Pump House / Summary

10.00 m
120 120 120
120 120
120 120
120 240 240 120 240
120 120
240 120 240 120
120 240 180 240 120
120 240
240 120 180 300
120 240 240 180 300 240 120
120
180 120 180 120 180
120 120 180 120 120
120 120 120 120

120 120 120 120


120 120
180 180
120 180 120
120
240 180 120 120 120 180
120 300 240 120 180 300 240 120 300 120
180 240
240 300
120 240 120 120 240 120 120 120
240 180 240 240 240
120 120 120 120 120 120
120 120 120 60

0.00
0.00 15.00 m

Height of Room: 4.300 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:129
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 146 47 328 0.320
Floor 20 138 58 230 0.419
Ceiling 70 23 16 27 0.707
Walls (4) 50 41 16 99 /

Workplane:
Height: 0.500 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.244, Ceiling / Working Plane: 0.159.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 6 Philips TMX204 2xTL-D36W HFP +GMX440 (1.000) 6700 72.0
Total: 40200 432.0

Specific connected load: 2.88 W/m² = 1.98 W/m²/100 lx (Ground area: 150.00 m²)

Page 2
Fire Pump House
17.10.2012

Operator
Telephone
Fax
e-Mail

Fire Pump House / Luminaire parts list

6 Pieces Philips TMX204 2xTL-D36W HFP +GMX440


Article No.:
Luminaire Luminous Flux: 6700 lm
Luminaire Wattage: 72.0 W
Luminaire classification according to CIE: 100
CIE flux code: 48 81 97 100 78
Fitting: 2 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Fire Pump House
17.10.2012

Operator
Telephone
Fax
e-Mail

Fire Pump House / Photometric Results

Total Luminous Flux: 40200 lm


Total Load: 432.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 128 18 146 / /
Floor 118 20 138 20 8.78
Ceiling 0.00 23 23 70 5.16
Wall 1 19 21 40 50 6.35
Wall 2 21 21 42 50 6.67
Wall 3 19 21 40 50 6.37
Wall 4 21 21 42 50 6.65

Uniformity on the working plane


u0: 0.320 (1:3)
Emin / Emax: 0.142 (1:7)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.244, Ceiling / Working Plane: 0.159.

Specific connected load: 2.88 W/m² = 1.98 W/m²/100 lx (Ground area: 150.00 m²)

Page 4
Guard House
17.10.2012

Operator
Telephone
Fax
e-Mail

Philips TBH318 2xTL-D36W HFE M5 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

80
60° 60°

120

45° 160 45°

200

240

30° 15° 0° 15° 30°

cd/klm  40%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 72 96 100 100 40
Glare Evaluation According to UGR
Hygeia TBH318
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
Functional, fully closed recessed luminaire for 2 or 3 TL’D fluorescent lamps  Floor 20 20 20 20 20 20 20 20 20 20
for application in cleanrooms and dust-/ water-ingress protected areas. Room Size Viewing direction at right angles Viewing direction parallel
Double parabolic mirror is integrated in the luminaire with clear PMMA cover. X Y to lamp axis to lamp axis

2H 2H 12.5 13.5 12.8 13.7 13.9 16.3 17.3 16.6 17.5 17.7
3H 12.5 13.4 12.8 13.6 13.9 16.4 17.3 16.7 17.5 17.8
4H 12.5 13.3 12.8 13.6 13.9 16.4 17.2 16.7 17.5 17.7
6H 12.5 13.2 12.8 13.5 13.8 16.3 17.1 16.7 17.4 17.7
8H 12.4 13.1 12.8 13.4 13.8 16.3 17.0 16.6 17.3 17.6
12H 12.4 13.1 12.8 13.4 13.7 16.3 16.9 16.6 17.2 17.6
4H 2H 12.7 13.5 13.0 13.8 14.0 16.2 17.0 16.5 17.3 17.6
3H 12.7 13.4 13.1 13.7 14.0 16.3 17.0 16.6 17.3 17.6
4H 12.7 13.3 13.1 13.6 14.0 16.3 16.9 16.7 17.2 17.6
6H 12.7 13.2 13.1 13.6 13.9 16.2 16.7 16.6 17.1 17.5
8H 12.7 13.1 13.1 13.5 13.9 16.2 16.7 16.6 17.0 17.5
12H 12.6 13.0 13.1 13.4 13.9 16.2 16.6 16.6 17.0 17.4
8H 4H 12.7 13.1 13.1 13.5 13.9 16.2 16.6 16.6 17.0 17.4
6H 12.6 13.0 13.1 13.4 13.9 16.1 16.5 16.6 16.9 17.4
8H 12.6 12.9 13.1 13.4 13.8 16.1 16.4 16.6 16.9 17.3
12H 12.6 12.8 13.1 13.3 13.8 16.1 16.3 16.5 16.8 17.3
12H 4H 12.6 13.0 13.1 13.4 13.9 16.1 16.5 16.6 16.9 17.4
6H 12.6 12.9 13.1 13.3 13.8 16.1 16.4 16.6 16.9 17.3
8H 12.6 12.8 13.0 13.3 13.8 16.1 16.3 16.5 16.8 17.3

Variation of the observer position for the luminaire distances S

S = 1.0H +2.1 / -3.6 +0.7 / -1.0


S = 1.5H +3.4 / -5.3 +1.7 / -3.7
S = 2.0H +5.0 / -6.6 +3.5 / -7.3

Standard table BK01 BK00


Correction
-8.4 -5.2
Summand
Corrected Glare Indices referring to 6700lm Total Luminous Flux

Page 1
Guard House
17.10.2012

Operator
Telephone
Fax
e-Mail

Guard House / Summary

250 1.76 m
300
250
300
300
200 250 350
350 200
300 350
300 250
350
350
350
250 300 350 300
200 200
350 250
350
300 350 300
350
250
250
200 300 300 200

0.00
0.00 2.75 m

Height of Room: 2.600 m, Mounting Height: 2.600 m, Light loss factor: Values in Lux, Scale 1:23
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 261 141 381 0.542
Floor 10 173 131 210 0.755
Ceiling 70 34 24 39 0.711
Walls (4) 50 91 25 192 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.334, Ceiling / Working Plane: 0.129.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 1 Philips TBH318 2xTL-D36W HFE M5 (1.000) 6700 0.0
Total: 6700 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 4.84 m²)

Page 2
Guard House
17.10.2012

Operator
Telephone
Fax
e-Mail

Guard House / Luminaire parts list

1 Pieces Philips TBH318 2xTL-D36W HFE M5


Article No.:
Luminaire Luminous Flux: 6700 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 100
CIE flux code: 72 96 100 100 40
Fitting: 2 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Guard House
17.10.2012

Operator
Telephone
Fax
e-Mail

Guard House / Photometric Results

Total Luminous Flux: 6700 lm


Total Load: 0.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 216 45 261 / /
Floor 127 46 173 10 5.52
Ceiling 0.00 34 34 70 7.47
Wall 1 54 37 91 50 14
Wall 2 54 36 90 50 14
Wall 3 54 37 91 50 14
Wall 4 54 36 90 50 14

Uniformity on the working plane


u0: 0.542 (1:2)
Emin / Emax: 0.371 (1:3)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.334, Ceiling / Working Plane: 0.129.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 4.84 m²)

Page 4
Hydran Pump Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

ZUMTOBEL 40932137 (STD - Standard) KXA-2 2/58W DV5x2,5 / Luminaire Data


Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the 135° 150° 165° 180° 165° 150° 135°

luminaire. 160

120
120° 120°

80

105° 105°

90° 90°

75° 75°

60° 60°

45° 30° 15° 0° 15° 30° 45°

cd/klm  76%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 89 Luminous emittance 1:


CIE flux code: 37 67 88 89 76
Glare Evaluation According to UGR
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
 Floor 20 20 20 20 20 20 20 20 20 20
Room Size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 18.8 20.1 19.2 20.5 21.0 16.5 17.9 17.0 18.3 18.8
3H 21.2 22.4 21.7 22.8 23.4 17.8 19.0 18.3 19.4 20.0
4H 22.3 23.4 22.8 23.9 24.4 18.2 19.3 18.7 19.8 20.3
6H 23.2 24.2 23.7 24.7 25.3 18.4 19.5 18.9 20.0 20.5
8H 23.6 24.6 24.1 25.1 25.7 18.4 19.5 19.0 20.0 20.5
12H 24.0 25.0 24.5 25.5 26.1 18.5 19.4 19.0 20.0 20.5
4H 2H 19.4 20.5 19.9 21.0 21.5 17.7 18.9 18.2 19.3 19.9
3H 22.0 23.0 22.5 23.5 24.1 19.2 20.2 19.8 20.7 21.3
4H 23.3 24.1 23.8 24.7 25.3 19.8 20.7 20.4 21.2 21.8
6H 24.3 25.1 24.9 25.7 26.3 20.1 20.9 20.7 21.5 22.1
8H 24.8 25.5 25.4 26.1 26.8 20.2 20.9 20.8 21.5 22.2
12H 25.3 26.0 25.9 26.6 27.3 20.2 20.9 20.9 21.5 22.2
8H 4H 23.5 24.3 24.1 24.8 25.5 20.7 21.4 21.3 22.0 22.6
6H 24.8 25.4 25.4 26.0 26.7 21.3 21.9 21.9 22.5 23.2
8H 25.4 26.0 26.1 26.6 27.3 21.5 22.0 22.1 22.7 23.4
12H 26.1 26.6 26.8 27.3 28.0 21.6 22.1 22.3 22.7 23.5
12H 4H 23.5 24.2 24.1 24.8 25.5 20.8 21.5 21.5 22.1 22.8
6H 24.9 25.4 25.5 26.0 26.7 21.6 22.1 22.2 22.8 23.5
8H 25.6 26.0 26.2 26.7 27.4 21.9 22.4 22.6 23.0 23.8

Variation of the observer position for the luminaire distances S

S = 1.0H +0.1 / -0.1 +0.1 / -0.1


S = 1.5H +0.2 / -0.2 +0.2 / -0.3
S = 2.0H +0.2 / -0.3 +0.4 / -0.7

Standard table BK09 BK14


Correction
8.5 4.4
Summand
Corrected Glare Indices referring to 10400lm Total Luminous Flux

Page 1
Hydran Pump Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Hydran Pump Shed / Summary

21.00 m
120
120
90 90

150 120
150 150

120
120

120 150
150
120

150 150

120 120
120

0.00
0.00 13.00 m

Height of Room: 5.000 m, Mounting Height: 5.000 m, Light loss factor: Values in Lux, Scale 1:270
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 132 55 175 0.418
Floor 10 124 54 162 0.435
Ceiling 30 34 4.13 1117 0.122
Walls (4) 0 87 26 276 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.500 m Left Wall 23 21
Grid: 64 x 64 Points Lower Wall 26 21
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.673, Ceiling / Working Plane: 0.256.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 12 ZUMTOBEL 40932137 (STD - Standard) KXA-2 2/58W DV5x2,5 (1.000) 10400 100.0
Total: 124800 1200.0

Specific connected load: 4.40 W/m² = 3.33 W/m²/100 lx (Ground area: 273.00 m²)

Page 2
Hydran Pump Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Hydran Pump Shed / Luminaire parts list

12 Pieces ZUMTOBEL 40932137 (STD - Standard) KXA-2 See our luminaire


2/58W DV5x2,5 catalog for an image of
Article No.: 40932137 (STD - Standard) the luminaire.
Luminaire Luminous Flux: 10400 lm
Luminaire Wattage: 100.0 W
Luminaire classification according to CIE: 89
CIE flux code: 37 67 88 89 76
Fitting: 2 x T26 58W (Correction Factor 1.000).

Page 3
Hydran Pump Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Hydran Pump Shed / Photometric Results

Total Luminous Flux: 124800 lm


Total Load: 1200.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 126 6.33 132 / /
Floor 118 5.98 124 10 3.95
Ceiling 27 7.12 34 30 3.22
Wall 1 101 7.13 109 0 0.00
Wall 2 66 7.80 74 0 0.00
Wall 3 101 7.89 109 0 0.00
Wall 4 66 7.31 73 0 0.00

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.418 (1:2) Left Wall 23 21
Emin / Emax: 0.315 (1:3) Lower Wall 26 21
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.673, Ceiling / Working Plane: 0.256.

Specific connected load: 4.40 W/m² = 3.33 W/m²/100 lx (Ground area: 273.00 m²)

Page 4
Loading Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

ZUMTOBEL 40932137 (STD - Standard) KXA-2 2/58W DV5x2,5 / Luminaire Data


Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the 135° 150° 165° 180° 165° 150° 135°

luminaire. 160

120
120° 120°

80

105° 105°

90° 90°

75° 75°

60° 60°

45° 30° 15° 0° 15° 30° 45°

cd/klm  76%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 89 Luminous emittance 1:


CIE flux code: 37 67 88 89 76
Glare Evaluation According to UGR
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
 Floor 20 20 20 20 20 20 20 20 20 20
Room Size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 18.8 20.1 19.2 20.5 21.0 16.5 17.9 17.0 18.3 18.8
3H 21.2 22.4 21.7 22.8 23.4 17.8 19.0 18.3 19.4 20.0
4H 22.3 23.4 22.8 23.9 24.4 18.2 19.3 18.7 19.8 20.3
6H 23.2 24.2 23.7 24.7 25.3 18.4 19.5 18.9 20.0 20.5
8H 23.6 24.6 24.1 25.1 25.7 18.4 19.5 19.0 20.0 20.5
12H 24.0 25.0 24.5 25.5 26.1 18.5 19.4 19.0 20.0 20.5
4H 2H 19.4 20.5 19.9 21.0 21.5 17.7 18.9 18.2 19.3 19.9
3H 22.0 23.0 22.5 23.5 24.1 19.2 20.2 19.8 20.7 21.3
4H 23.3 24.1 23.8 24.7 25.3 19.8 20.7 20.4 21.2 21.8
6H 24.3 25.1 24.9 25.7 26.3 20.1 20.9 20.7 21.5 22.1
8H 24.8 25.5 25.4 26.1 26.8 20.2 20.9 20.8 21.5 22.2
12H 25.3 26.0 25.9 26.6 27.3 20.2 20.9 20.9 21.5 22.2
8H 4H 23.5 24.3 24.1 24.8 25.5 20.7 21.4 21.3 22.0 22.6
6H 24.8 25.4 25.4 26.0 26.7 21.3 21.9 21.9 22.5 23.2
8H 25.4 26.0 26.1 26.6 27.3 21.5 22.0 22.1 22.7 23.4
12H 26.1 26.6 26.8 27.3 28.0 21.6 22.1 22.3 22.7 23.5
12H 4H 23.5 24.2 24.1 24.8 25.5 20.8 21.5 21.5 22.1 22.8
6H 24.9 25.4 25.5 26.0 26.7 21.6 22.1 22.2 22.8 23.5
8H 25.6 26.0 26.2 26.7 27.4 21.9 22.4 22.6 23.0 23.8

Variation of the observer position for the luminaire distances S

S = 1.0H +0.1 / -0.1 +0.1 / -0.1


S = 1.5H +0.2 / -0.2 +0.2 / -0.3
S = 2.0H +0.2 / -0.3 +0.4 / -0.7

Standard table BK09 BK14


Correction
8.5 4.4
Summand
Corrected Glare Indices referring to 10400lm Total Luminous Flux

Page 1
Loading Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Loading Shed / Summary

80 80 15.70 m
100
100 100
120
120 120 80
120
80 100 140 100
140
140
120 140
140
140 120
140
100 140 100
120 140
140
140 120
120 120
100 120 100 80

80 100 100
60
80
0.00
0.00 20.60 m

Height of Room: 5.500 m, Mounting Height: 5.500 m, Light loss factor: Values in Lux, Scale 1:202
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 109 48 147 0.442
Floor 10 103 46 138 0.453
Ceiling 30 26 3.60 851 0.137
Walls (4) 0 75 25 132 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.500 m Left Wall 25 21
Grid: 64 x 64 Points Lower Wall 25 21
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.711, Ceiling / Working Plane: 0.262.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 12 ZUMTOBEL 40932137 (STD - Standard) KXA-2 2/58W DV5x2,5 (1.000) 10400 100.0
Total: 124800 1200.0

Specific connected load: 3.71 W/m² = 3.42 W/m²/100 lx (Ground area: 323.42 m²)

Page 2
Loading Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Loading Shed / Luminaire parts list

12 Pieces ZUMTOBEL 40932137 (STD - Standard) KXA-2 See our luminaire


2/58W DV5x2,5 catalog for an image of
Article No.: 40932137 (STD - Standard) the luminaire.
Luminaire Luminous Flux: 10400 lm
Luminaire Wattage: 100.0 W
Luminaire classification according to CIE: 89
CIE flux code: 37 67 88 89 76
Fitting: 2 x T26 58W (Correction Factor 1.000).

Page 3
Loading Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Loading Shed / Photometric Results

Total Luminous Flux: 124800 lm


Total Load: 1200.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 103 5.28 109 / /
Floor 98 5.01 103 10 3.27
Ceiling 20 5.93 26 30 2.50
Wall 1 62 6.17 68 0 0.00
Wall 2 79 5.69 85 0 0.00
Wall 3 62 6.25 68 0 0.00
Wall 4 79 5.79 85 0 0.00

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.442 (1:2) Left Wall 25 21
Emin / Emax: 0.327 (1:3) Lower Wall 25 21
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.711, Ceiling / Working Plane: 0.262.

Specific connected load: 3.71 W/m² = 3.42 W/m²/100 lx (Ground area: 323.42 m²)

Page 4
Motorcylce Parking
04.12.2012

Operator
Telephone
Fax
e-Mail

Philips TCW097 2xTL-D36W EBS / Luminaire Data Sheet

Luminous emittance 1:

135° 150° 165° 180° 165° 150° 135°

160

120
120° 120°

80

105° 105°

90° 90°

75° 75°

60° 60°

45° 30° 15° 0° 15° 30° 45°

cd/klm  69%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 88 Luminous emittance 1:


CIE flux code: 37 66 87 85 69
Glare Evaluation According to UGR
TWC097 Pacific II
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
Functional impact-, dust- and jetproof luminaire for single and twin TLD and  Floor 20 20 20 20 20 20 20 20 20 20
TL5 fluorescent lamps for indoor applications and semioutdoor applications. Room Size Viewing direction at right angles Viewing direction parallel
Housing and cover of TCW097 are made of high quality poly-carbonate X Y to lamp axis to lamp axis

which has an excellent impact resistant property. The cover has anti-UV 2H 2H 14.0 15.3 14.5 15.8 16.3 18.6 19.8 19.1 20.3 20.9
additives which bring additional performance levels to UV protection. 3H 14.8 16.0 15.3 16.5 17.1 21.1 22.3 21.6 22.8 23.4
4H 15.0 16.1 15.5 16.6 17.2 22.6 23.6 23.1 24.2 24.8
Available with conventional or high-frequency (HF) electronic control gears. 6H 15.0 16.1 15.6 16.6 17.2 24.0 25.0 24.5 25.5 26.2
Can be ceiling mounted or suspended. Equipped with mounting brackets, 8H 15.0 16.0 15.6 16.6 17.2 24.6 25.6 25.2 26.2 26.8
12H 15.0 15.9 15.6 16.5 17.2 25.3 26.3 25.9 26.8 27.5
mounting is made easy via screws without drilling into the luminaire housing.
4H 2H 15.5 16.6 16.1 17.2 17.8 18.9 19.9 19.4 20.5 21.1
Gear tray and metal toggles are re-installed; cable gland and mounting 3H 16.6 17.6 17.2 18.2 18.8 21.6 22.6 22.2 23.1 23.8
brackets are delivered with the luminaire. 4H 17.0 17.8 17.6 18.4 19.1 23.2 24.1 23.9 24.7 25.4
6H 17.1 17.9 17.8 18.5 19.2 24.8 25.6 25.5 26.2 26.9
8H 17.2 17.9 17.8 18.5 19.2 25.6 26.3 26.3 26.9 27.7
12H 17.2 17.8 17.8 18.4 19.2 26.4 27.0 27.1 27.7 28.4
8H 4H 18.2 18.9 18.9 19.5 20.3 23.4 24.1 24.0 24.7 25.4
6H 18.6 19.2 19.3 19.9 20.6 25.1 25.7 25.8 26.4 27.1
8H 18.7 19.3 19.4 19.9 20.7 26.0 26.5 26.7 27.2 28.0
12H 18.8 19.2 19.5 19.9 20.7 27.0 27.4 27.7 28.1 28.9
12H 4H 18.5 19.2 19.2 19.8 20.6 23.3 24.0 24.0 24.6 25.4
6H 19.1 19.6 19.8 20.3 21.1 25.1 25.6 25.8 26.3 27.1
8H 19.3 19.8 20.0 20.5 21.3 26.1 26.5 26.8 27.2 28.0

Variation of the observer position for the luminaire distances S

S = 1.0H +0.1 / -0.1 +0.1 / -0.1


S = 1.5H +0.3 / -0.5 +0.2 / -0.2
S = 2.0H +0.7 / -1.0 +0.4 / -0.4

Standard table BK13 ---


Correction
2.0 ---
Summand
Corrected Glare Indices referring to 6700lm Total Luminous Flux

Page 1
Motorcylce Parking
04.12.2012

Operator
Telephone
Fax
e-Mail

Motorcylce Parking / Summary

17.40 m
160 160
160

200 200
160
200 200 160

200 200

200 200 200


160 200
200 160
200 200
200
200 200
200 200
160
200 160
160 160
0.00
0.00 13.00 m

Height of Room: 3.000 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:224
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 180 65 240 0.358
Floor 10 180 64 240 0.354
Ceiling 30 43 13 80 0.294
Walls (4) 0 116 34 232 /

Workplane:
Height: 0.000 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.639, Ceiling / Working Plane: 0.236.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 20 Philips TCW097 2xTL-D36W EBS (1.000) 6700 0.0
Total: 134000 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 226.20 m²)

Page 2
Motorcylce Parking
04.12.2012

Operator
Telephone
Fax
e-Mail

Motorcylce Parking / Luminaire parts list

20 Pieces Philips TCW097 2xTL-D36W EBS


Article No.:
Luminaire Luminous Flux: 6700 lm
Luminaire Wattage: 0.0 W
Luminaire classification according to CIE: 88
CIE flux code: 37 66 87 85 69
Fitting: 2 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Motorcylce Parking
04.12.2012

Operator
Telephone
Fax
e-Mail

Motorcylce Parking / Photometric Results

Total Luminous Flux: 134000 lm


Total Load: 0.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 171 9.02 180 / /
Floor 171 9.03 180 10 5.74
Ceiling 30 13 43 30 4.07
Wall 1 133 11 143 0 0.00
Wall 2 82 12 94 0 0.00
Wall 3 136 11 147 0 0.00
Wall 4 82 11 94 0 0.00

Uniformity on the working plane


u0: 0.358 (1:3)
Emin / Emax: 0.269 (1:4)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.639, Ceiling / Working Plane: 0.236.

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 226.20 m²)

Page 4
Unloading Pump Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

ZUMTOBEL 40932137 (STD - Standard) KXA-2 2/58W DV5x2,5 / Luminaire Data


Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the 135° 150° 165° 180° 165° 150° 135°

luminaire. 160

120
120° 120°

80

105° 105°

90° 90°

75° 75°

60° 60°

45° 30° 15° 0° 15° 30° 45°

cd/klm  76%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 89 Luminous emittance 1:


CIE flux code: 37 67 88 89 76
Glare Evaluation According to UGR
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
 Floor 20 20 20 20 20 20 20 20 20 20
Room Size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 18.8 20.1 19.2 20.5 21.0 16.5 17.9 17.0 18.3 18.8
3H 21.2 22.4 21.7 22.8 23.4 17.8 19.0 18.3 19.4 20.0
4H 22.3 23.4 22.8 23.9 24.4 18.2 19.3 18.7 19.8 20.3
6H 23.2 24.2 23.7 24.7 25.3 18.4 19.5 18.9 20.0 20.5
8H 23.6 24.6 24.1 25.1 25.7 18.4 19.5 19.0 20.0 20.5
12H 24.0 25.0 24.5 25.5 26.1 18.5 19.4 19.0 20.0 20.5
4H 2H 19.4 20.5 19.9 21.0 21.5 17.7 18.9 18.2 19.3 19.9
3H 22.0 23.0 22.5 23.5 24.1 19.2 20.2 19.8 20.7 21.3
4H 23.3 24.1 23.8 24.7 25.3 19.8 20.7 20.4 21.2 21.8
6H 24.3 25.1 24.9 25.7 26.3 20.1 20.9 20.7 21.5 22.1
8H 24.8 25.5 25.4 26.1 26.8 20.2 20.9 20.8 21.5 22.2
12H 25.3 26.0 25.9 26.6 27.3 20.2 20.9 20.9 21.5 22.2
8H 4H 23.5 24.3 24.1 24.8 25.5 20.7 21.4 21.3 22.0 22.6
6H 24.8 25.4 25.4 26.0 26.7 21.3 21.9 21.9 22.5 23.2
8H 25.4 26.0 26.1 26.6 27.3 21.5 22.0 22.1 22.7 23.4
12H 26.1 26.6 26.8 27.3 28.0 21.6 22.1 22.3 22.7 23.5
12H 4H 23.5 24.2 24.1 24.8 25.5 20.8 21.5 21.5 22.1 22.8
6H 24.9 25.4 25.5 26.0 26.7 21.6 22.1 22.2 22.8 23.5
8H 25.6 26.0 26.2 26.7 27.4 21.9 22.4 22.6 23.0 23.8

Variation of the observer position for the luminaire distances S

S = 1.0H +0.1 / -0.1 +0.1 / -0.1


S = 1.5H +0.2 / -0.2 +0.2 / -0.3
S = 2.0H +0.2 / -0.3 +0.4 / -0.7

Standard table BK09 BK14


Correction
8.5 4.4
Summand
Corrected Glare Indices referring to 10400lm Total Luminous Flux

Page 1
Unloading Pump Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Unloading Pump Shed / Summary

80 15.00 m
80 100
100 100
80
120 120
120
100
100
120

100
100

120
120
100 120 120
100

100 100
80
80
0.00
0.00 9.00 m

Height of Room: 5.200 m, Mounting Height: 5.200 m, Light loss factor: Values in Lux, Scale 1:193
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 103 51 136 0.492
Floor 10 95 49 125 0.514
Ceiling 30 29 3.22 860 0.112
Walls (4) 0 75 21 149 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.500 m Left Wall 21 19
Grid: 64 x 64 Points Lower Wall 24 20
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.751, Ceiling / Working Plane: 0.302.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 6 ZUMTOBEL 40932137 (STD - Standard) KXA-2 2/58W DV5x2,5 (1.000) 10400 100.0
Total: 62400 600.0

Specific connected load: 4.44 W/m² = 4.30 W/m²/100 lx (Ground area: 135.00 m²)

Page 2
Unloading Pump Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Unloading Pump Shed / Luminaire parts list

6 Pieces ZUMTOBEL 40932137 (STD - Standard) KXA-2 See our luminaire


2/58W DV5x2,5 catalog for an image of
Article No.: 40932137 (STD - Standard) the luminaire.
Luminaire Luminous Flux: 10400 lm
Luminaire Wattage: 100.0 W
Luminaire classification according to CIE: 89
CIE flux code: 37 67 88 89 76
Fitting: 2 x T26 58W (Correction Factor 1.000).

Page 3
Unloading Pump Shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Unloading Pump Shed / Photometric Results

Total Luminous Flux: 62400 lm


Total Load: 600.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 99 4.65 103 / /
Floor 91 4.27 95 10 3.03
Ceiling 24 4.24 29 30 2.74
Wall 1 82 5.25 88 0 0.00
Wall 2 62 5.63 67 0 0.00
Wall 3 82 5.25 88 0 0.00
Wall 4 62 5.57 67 0 0.00

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.492 (1:2) Left Wall 21 19
Emin / Emax: 0.375 (1:3) Lower Wall 24 20
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.751, Ceiling / Working Plane: 0.302.

Specific connected load: 4.44 W/m² = 4.30 W/m²/100 lx (Ground area: 135.00 m²)

Page 4
Unloading shed
25.10.2012

Operator
Telephone
Fax
e-Mail

ZUMTOBEL 40932137 (STD - Standard) KXA-2 2/58W DV5x2,5 / Luminaire Data


Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the 135° 150° 165° 180° 165° 150° 135°

luminaire. 160

120
120° 120°

80

105° 105°

90° 90°

75° 75°

60° 60°

45° 30° 15° 0° 15° 30° 45°

cd/klm  76%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 89 Luminous emittance 1:


CIE flux code: 37 67 88 89 76
Glare Evaluation According to UGR
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
 Floor 20 20 20 20 20 20 20 20 20 20
Room Size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 18.8 20.1 19.2 20.5 21.0 16.5 17.9 17.0 18.3 18.8
3H 21.2 22.4 21.7 22.8 23.4 17.8 19.0 18.3 19.4 20.0
4H 22.3 23.4 22.8 23.9 24.4 18.2 19.3 18.7 19.8 20.3
6H 23.2 24.2 23.7 24.7 25.3 18.4 19.5 18.9 20.0 20.5
8H 23.6 24.6 24.1 25.1 25.7 18.4 19.5 19.0 20.0 20.5
12H 24.0 25.0 24.5 25.5 26.1 18.5 19.4 19.0 20.0 20.5
4H 2H 19.4 20.5 19.9 21.0 21.5 17.7 18.9 18.2 19.3 19.9
3H 22.0 23.0 22.5 23.5 24.1 19.2 20.2 19.8 20.7 21.3
4H 23.3 24.1 23.8 24.7 25.3 19.8 20.7 20.4 21.2 21.8
6H 24.3 25.1 24.9 25.7 26.3 20.1 20.9 20.7 21.5 22.1
8H 24.8 25.5 25.4 26.1 26.8 20.2 20.9 20.8 21.5 22.2
12H 25.3 26.0 25.9 26.6 27.3 20.2 20.9 20.9 21.5 22.2
8H 4H 23.5 24.3 24.1 24.8 25.5 20.7 21.4 21.3 22.0 22.6
6H 24.8 25.4 25.4 26.0 26.7 21.3 21.9 21.9 22.5 23.2
8H 25.4 26.0 26.1 26.6 27.3 21.5 22.0 22.1 22.7 23.4
12H 26.1 26.6 26.8 27.3 28.0 21.6 22.1 22.3 22.7 23.5
12H 4H 23.5 24.2 24.1 24.8 25.5 20.8 21.5 21.5 22.1 22.8
6H 24.9 25.4 25.5 26.0 26.7 21.6 22.1 22.2 22.8 23.5
8H 25.6 26.0 26.2 26.7 27.4 21.9 22.4 22.6 23.0 23.8

Variation of the observer position for the luminaire distances S

S = 1.0H +0.1 / -0.1 +0.1 / -0.1


S = 1.5H +0.2 / -0.2 +0.2 / -0.3
S = 2.0H +0.2 / -0.3 +0.4 / -0.7

Standard table BK09 BK14


Correction
8.5 4.4
Summand
Corrected Glare Indices referring to 10400lm Total Luminous Flux

Page 1
Unloading shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Unloading Shed / Summary

90 14.65 m
90
90
120 120
120
120
90
120

150 150
90 120

120
90

120
120 120 120
90
90
90
0.00
0.00 27.40 m

Height of Room: 5.500 m, Mounting Height: 5.500 m, Light loss factor: Values in Lux, Scale 1:196
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 114 50 152 0.435
Floor 10 108 47 144 0.438
Ceiling 30 27 3.72 870 0.138
Walls (4) 0 77 23 144 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.500 m Left Wall 26 21
Grid: 64 x 32 Points Lower Wall 25 22
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.697, Ceiling / Working Plane: 0.257.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 15 ZUMTOBEL 40932137 (STD - Standard) KXA-2 2/58W DV5x2,5 (1.000) 10400 100.0
Total: 156000 1500.0

Specific connected load: 3.74 W/m² = 3.28 W/m²/100 lx (Ground area: 401.41 m²)

Page 2
Unloading shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Unloading Shed / Luminaire parts list

15 Pieces ZUMTOBEL 40932137 (STD - Standard) KXA-2 See our luminaire


2/58W DV5x2,5 catalog for an image of
Article No.: 40932137 (STD - Standard) the luminaire.
Luminaire Luminous Flux: 10400 lm
Luminaire Wattage: 100.0 W
Luminaire classification according to CIE: 89
CIE flux code: 37 67 88 89 76
Fitting: 2 x T26 58W (Correction Factor 1.000).

Page 3
Unloading shed
25.10.2012

Operator
Telephone
Fax
e-Mail

Unloading Shed / Photometric Results

Total Luminous Flux: 156000 lm


Total Load: 1500.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 108 5.56 114 / /
Floor 103 5.30 108 10 3.44
Ceiling 20 6.47 27 30 2.57
Wall 1 63 6.70 70 0 0.00
Wall 2 84 5.93 90 0 0.00
Wall 3 63 6.78 70 0 0.00
Wall 4 84 5.89 90 0 0.00

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.435 (1:2) Left Wall 26 21
Emin / Emax: 0.327 (1:3) Lower Wall 25 22
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.697, Ceiling / Working Plane: 0.257.

Specific connected load: 3.74 W/m² = 3.28 W/m²/100 lx (Ground area: 401.41 m²)

Page 4
Work Shop
30.10.2012

Operator
Telephone
Fax
e-Mail

Philips TMX204 2xTL-D36W HFP +GMX440 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

100
60° 60°

150

45° 200 45°

300

30° 15° 0° 15° 30°

cd/klm  78%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 48 81 97 100 78
Glare Evaluation According to UGR
TMX204 LS – slender and versatile
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
TMX204 LS is a functional batten for TL-D and TL5 fluorescent lamps for  Floor 20 20 20 20 20 20 20 20 20 20
general lighting. A wide range of reflectors and attachments from the Room Size Viewing direction at right angles Viewing direction parallel
TTX400 series can be fitted to enhance system efficiency and versatility, X Y to lamp axis to lamp axis

making it suitable for a variety of applications. This batten can be suspended 2H 2H 19.3 20.6 19.6 20.8 21.0 19.4 20.7 19.7 20.9 21.1
or surface-mounted. Thanks to its slim design, it is also well suited for build- 3H 20.6 21.7 20.9 22.0 22.3 20.9 22.0 21.2 22.3 22.6
4H 20.8 21.9 21.2 22.2 22.5 21.4 22.5 21.8 22.8 23.1
in applications and coves. 6H 20.8 21.9 21.2 22.2 22.5 21.8 22.8 22.1 23.1 23.4
8H 20.8 21.8 21.1 22.1 22.4 21.9 22.9 22.2 23.2 23.5
12H 20.7 21.7 21.1 22.0 22.3 21.9 22.9 22.3 23.2 23.5
4H 2H 19.9 21.0 20.3 21.3 21.6 20.0 21.2 20.4 21.4 21.7
3H 21.4 22.4 21.8 22.7 23.0 21.7 22.7 22.1 23.0 23.3
4H 21.8 22.6 22.2 22.9 23.3 22.4 23.3 22.8 23.6 24.0
6H 21.8 22.5 22.2 22.9 23.3 22.9 23.6 23.3 24.0 24.4
8H 21.8 22.4 22.2 22.8 23.2 23.1 23.7 23.5 24.1 24.6
12H 21.7 22.3 22.2 22.7 23.2 23.2 23.8 23.6 24.2 24.6
8H 4H 22.0 22.7 22.4 23.1 23.5 22.6 23.3 23.1 23.7 24.1
6H 22.1 22.6 22.5 23.0 23.5 23.3 23.8 23.7 24.2 24.7
8H 22.0 22.5 22.5 22.9 23.4 23.5 24.0 24.0 24.4 24.9
12H 22.0 22.4 22.5 22.9 23.4 23.7 24.1 24.2 24.5 25.0
12H 4H 22.0 22.6 22.5 23.0 23.5 22.6 23.2 23.1 23.6 24.1
6H 22.1 22.6 22.6 23.0 23.5 23.2 23.7 23.7 24.2 24.6
8H 22.1 22.5 22.6 22.9 23.4 23.5 23.9 24.0 24.4 24.9

Variation of the observer position for the luminaire distances S

S = 1.0H +0.2 / -0.2 +0.1 / -0.2


S = 1.5H +0.7 / -0.9 +0.5 / -0.6
S = 2.0H +0.9 / -1.1 +0.7 / -1.1

Standard table BK03 BK05


Correction
3.3 5.1
Summand
Corrected Glare Indices referring to 6700lm Total Luminous Flux

Page 1
Work Shop
30.10.2012

Operator
Telephone
Fax
e-Mail

Work Shop / Summary

10.00 m
100 200 200 100 200 100 200
200 200 200 200 100
400 200 400 200 200
200 400 200 400 400 400 200
200 200
200 400 200
200 400 400 200 200 400 400
200 200
200 200
200 200
100 200 200 200 200
100 100 100
100 100
100 100
100 100 100 100
200 200 200 200 200
200 200 200
200 200
200 400 200 400 400 200
400 200 200 400
200 200 200
200 400 400 400 400 200 200 400
200 200 400
200
200
200
200 200 200 200 200 200
100 100 100
0.00
0.00 14.00 m

Height of Room: 3.700 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:129
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 183 43 503 0.234
Floor 20 169 71 271 0.420
Ceiling 70 30 22 35 0.730
Walls (4) 50 55 20 124 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 22 24
Grid: 128 x 128 Points Lower Wall 22 23
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.236, Ceiling / Working Plane: 0.163.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 6 Philips TMX204 2xTL-D36W HFP +GMX440 (1.000) 6700 72.0
Total: 40200 432.0

Specific connected load: 3.09 W/m² = 1.68 W/m²/100 lx (Ground area: 140.00 m²)

Page 2
Work Shop
30.10.2012

Operator
Telephone
Fax
e-Mail

Work Shop / Luminaire parts list

6 Pieces Philips TMX204 2xTL-D36W HFP +GMX440


Article No.:
Luminaire Luminous Flux: 6700 lm
Luminaire Wattage: 72.0 W
Luminaire classification according to CIE: 100
CIE flux code: 48 81 97 100 78
Fitting: 2 x TL-D36W/840 (Correction Factor
1.000).

Page 3
Work Shop
30.10.2012

Operator
Telephone
Fax
e-Mail

Work Shop / Photometric Results

Total Luminous Flux: 40200 lm


Total Load: 432.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 162 22 183 / /
Floor 143 25 169 20 11
Ceiling 0.00 30 30 70 6.66
Wall 1 26 26 53 50 8.37
Wall 2 31 26 57 50 9.12
Wall 3 26 26 53 50 8.37
Wall 4 31 26 58 50 9.18

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.234 (1:4) Left Wall 22 24
Emin / Emax: 0.085 (1:12) Lower Wall 22 23
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.236, Ceiling / Working Plane: 0.163.

Specific connected load: 3.09 W/m² = 1.68 W/m²/100 lx (Ground area: 140.00 m²)