NA8G Air Circuit Breaker Overview
NA8G Air Circuit Breaker Overview
Mode of installation:
F:Fixed type
D:Draweout type
Mode of operation:
M:Manual
P: Power-driven
No. of poles:
3:3-pole
4:4-pole
Intelligent controller:
NA8G Air Circuit Breaker M: Standard type
H: Multifunctional type
1. General
Rated current:
1.1 Application scope
3. Product structure
Body structure
Shunt release
Closing electromagnet
Operating mechanism
Intelligent controller
Breaking button
Name plate
Breaking/Making indicator
Breaker off and energy storage over Breaker off and no energy storage Breaker on and energy storage over Breaker on and no energy storage
Energy Energy
storage release Energy Energy
storage release
Drawout structure
Locking device
Position indicator
NA8G Air Circuit Breaker P-004
Connected Connected
Test Test
Disconnected Disconnected
Connected: both main circuit and secondary circuit are connected Test: the main circuit is disconnected,
the safety separator works well,
and the secondary circuit is connected.
Connected
C
Test
Disconnected
(3)Place the breaker body on the guide rail (4)Move the breaker body onto the guide rail with a snap
(5)Push the breaker body in, and turn the break body to the connected position
P-005 Air Circuit Breaker NA8G
Shell grade rated current Inm (A) 1600 3200 4000 6300
400,630,800, 1600,2000,
Rated current In (A) 2500,3200,4000 4000,5000 6300
1000,1250,1600 2500,3200
Wire to enter from the Wire to enter from the Wire to enter from the Wire to enter from the
Wire incoming pattern
upper or lower port upper or lower port upper or lower port upper or lower port
The following table shows the continual current-loading capacity of the circuit breakers and buses in each wiring mode at the
corresponding ambient environment temperatures and under the conditions of the satisfaction of conventional heating with a
similarity in capacity reducing between the breaker connected in a mixed way and the breaker connected horizontally.
Power loss
Breaker type Rated current Draw-out type Fixed type C
400 140 80
630 161 100
800 215 110
NA8G-1600
1000 230 120
1250 250 130
1600 460 220
1600 390 170
2000 470 250
NA8G-3200
2500 600 260
3200 670 420
2500 600 260
NA8G-4000 3200 670 420
4000 1047 656
4000 550 -
6300 950 -
Note: The data and parameters in the above technical documentation results from tests and theoretical calculation,
and can only be used as a general type selection guide.They cannot replace industrial practical experience or proof test.
5.4 Recommended bus for the breaker and recommendation for users to install the buses
210 36
a
275
149
310
7
351
78.5
95 76
345(Connected position)
391(Disconnected position)
2-Φ6.5
95
149(3P)
155(4P)
2-Φ6.5×10
7
35
75.5(4P)
78.5(3P)
145(3P) 63
95 76
215(4P)
4P Central line
345(Connected position)
3P Central line 391(Disconnected position)
12×Φ11(3P) 60 Vertical connection
16×Φ11(4P)
15
25
N Pole
In(A) a(mm) Note: If users intend to change the
35
275
310
179
7
351
63.5
95 76
442(Connected position)
2-Φ6.5×10
35
149(3P)
155(4P)
145(3P) 63 7
215(4P)
78.5(3P)
75.5(4P)
4P Central line
3P Central line 95 76
24×Φ11(3P) 85
15
32×Φ11(4P) 35
N pole 442(Connected position)
488(Disconnected position)
35
80.5
210 22 C
Phases barrier
(to be ordered
separately)
a
320
149
281
275
48.5 7
237(3P)
307(4P)
254(3P)
100
251
92
C
Horizontal connection
324(4P)
Phases barrier
(to be ordered
separately)
4-Φ7
100
149(3P)
155(4P)
237(3P)
307(4P)
48.5(3P)
45.5(4P)
C 100 92
4P Central line
251
12×Φ11(3P) 3P Central line
16×Φ11(4P) 60 Vertical connection
N Pole 25
15
210 22
149(3P)
155(4P)
275
281
48.5(3P)
45.5(4P)
237(3P) 100 92
307(4P) 341
254(3P)
324(4P) Vertical connection
4-Φ7
100
C
Phases barrier
(to be ordered
separately)
237(3P)
307(4P)
15
C 4P Central line
3P Central line
179
24-Φ11(3P)
85
32-Φ11(4P)
15
N Pole 35
7
35
80.5
33.5
100 92
Note: If users intend to change the
341
horizontal connection into vertical
101 101 101
connection, they need to replace the
Horizontal connection upper and lower busbars on both sides
with the same one as the central busbar.
P-009 Air Circuit Breaker NA8G
220 220
10-Φ5 8-Φ5
118
120
322
285
320
78
2
118.5
From the center of the mounting hole on the right side of the breaker From the center of the mounting hole on the right side of the breaker
258 258
217.5(3P) 217.5
332.5(4P) 52 386 7
385
240
Datum line 2
258
199.5
Datum line 1
308
371
328
155
11×17
175
Datum line 2
268
376
Φ14
18
145
21.5
97
Installation panel
10
47
C 7
52
C
78 50 Φ11
25
14
29
133
C
Datum line
C
84
445(Connected position)
492(Disconnceted position)
Note: If users want to change the horizontal connection into vertical connection, they only have to turn the busbar by 90°
C 7
C
52
25
14
Φ11
78
55
Datum line
25
57.5
445(Connected position)
492(Disconnected position)
Note: If users want to change the vertical connection into horizontal connection, they only have to turn the busbar by 90°
C C
C 86 25 12-Φ13
15
29
Datum line
In(A) C
3200 30
16.5
29
P-011 Air Circuit Breaker NA8G
NA8G-3200(In= 3200A) Draw-out type (Only horizontal connection is provided by the factory)
C
7
52
C
25
100 25
Φ11
29
14
112
Datum line
90
445(Connected position)
492(Disconnected position)
NA8G-3200(In= 3200A) Draw-out type (Vertical connection has to be made by users themselves)
C 7
52
14
Φ11 C
25
100
57
Datum line
25
35.5
445(Connected position)
492(Disconnected position)
Note: If users want to change the horizontal connection into vertical connection,
it is necessary to replace the upper and lower busbars for the N and B phases with the same one as the A and C phases.
308
N
402
258
Datum line 2
163.5
13
4×Φ12 371
328
150
311
268
72.5
29.5
21.5
C
200(3P) 200
8×Φ6
315(4P) Installation
panel
Datum line Datum line
Ferrous material
C
32
C
a
86 50 12-Φ13
18.5
112
In(A) a(mm)
115 115 115 1600~2500 20
Datum line 3200 30
55
Note: If users want to change the horizontal connection into vertical connection, they only have to additionally install vertical busbars.
Ferrous material
C
32
29
a C
14
Φ11
100
57
In(A) a(mm)
115 115 115
1600~2500 20
25
55
Datum line
3200 30
45
Note: If users want to change the horizontal connection into vertical connection, they only have to additionally install vertical busbars.
P-013 Air Circuit Breaker NA8G
217.5(3P) 217.5
332.5(4P)
42 385 18
232
258
datum line 2
199.5
datu m li ne 1
308
371
328
155
11×17
φ11
175
268
datum line 2
376
φ14
18
145
φ14
11×17
21.5
97
47
10
10×Φ6
162.5(3P) 162.5
datu m li ne 1
277.5(4P) datu m li ne 1
Size of the hole to be drilled on the panel
42
C
78 50 Φ11
25
14
29
133
datu m li ne 1
84
445(Connected position)
492(Disconnected position)
Note: If users want to change the horizontal connection into vertical connection,they only have to rotate the busbars by 90°
42
25
14
C
Φ11
78
55
datu m li ne 1
25
57.5
445(Connected position)
492(Disconnected position)
Note: If users want to change the horizontal connection into vertical connection,they only have to rotate the busbars by 90°
NA8G Air Circuit Breaker P-014
C
C
C 78 25 Φ11
15
29
datu m li ne 1
In(A)
2500
C
25
C
3200~4000 30
16.5
29
42
C
25
100 25
Φ11
29
14
133
datu m li ne 1
84
445(Connected position)
492(Disconnected position)
Note: If users want to change the horizontal connection into vertical connection,they only have to change the busbar of N、B phases to A、C phases
42
14
Φ11 C
25
100
57
datu m li ne 1
25
35.5
445(Connected position)
492(Disconnected position)
Note: If users want to change the horizontal connection into vertical connection,they only have to change the busbar of N、B phases to A、C phases
P-015 Air Circuit Breaker NA8G
25
datum line 2
133
163.5
10.5
25
13
371
328
150
330
311
268
4×Φ14
78
29.5
21.5
400(3P)
515(4P) 8×Φ6
432.5(3P)
547.5(4P)
datum line 1
33 C
78 50 φ11
14
29
C
25
datum line 1
25
47.5
Note: If users want to change the horizontal connection into vertical connection,they only have to rotate the busbars by 90°
33 25 C
C
78
55
datum line 1
25
21
Note: If users want to change the horizontal connection into vertical connection,they only have to rotate the busbars by 90°
NA8G Air Circuit Breaker P-016
15 61
C
10
C 78 25 φ11
15
15
155
388
datum line 1
155
C
67.5
15
C
33
Φ11 100 25
29
C
14
25
datum line 1
25
47.5
Note: If users want to change the horizontal connection into vertical connection,they only have to change the busbar of N、B phases to A、C phases
C C
25
33
14
Φ11
100
datum line 1
25
49
Note: If users want to change the horizontal connection into vertical connection,they only have to change the busbar of N、B phases to A、C phases
P-017 Air Circuit Breaker NA8G
710.5(4P)
Datum line 2
258
199
7
Datum line 1
308
371
328
φ14
155
175
268
2×11×17
376
Datum line 2
145
18
97
Φ11
162.5
21.5
703(3P)
47
10×Φ6
Datum line 1
Datum line 1
818(4P)
Size of the hole to be drilled on the panel
Datum line 2
258
199
Datum line 1
308
371
328
φ14
155
175
268
2×11×17
Datum line 2
376
145
18
97
Φ11
162.5
21.5
818
47
10×Φ6
Datum line 1
Datum line 1
29 C
C Datum line 1
115 N pole
Φ11 103 129.5 105 142 105 142 105
30
125
25
57
14
10.5
Note: If users want to change the horizontal connection into vertical connection,
they only have to additionally install vertical busbars. C
NA8G-6300(In=4000A~5000A) Draw-out type (Only horizontal connection is provided by the factory)
C
C
N pole
28×Φ15
100 155 210
20
40
103
30
112
55 52.5
182.5 246.5 194 164
92
Datum line 1
Note: If users want to change the horizontal connection into vertical connection,
they only have to additionally install vertical busbars.
14 C C
Datum line 1
115
Φ11 103 130 207 130 207 130
30
125
25
57
29
10.5
Note: If users want to change the horizontal connection into vertical connection,
they only have to additionally install vertical busbars.
C C
180 259.5
20
40
103
30
24×Φ15
112
80 65
316.5 258.5 140
92
Datum line 1
Note: If users want to change the horizontal connection into vertical connection,
they only have to additionally install vertical busbars.
P-019 Air Circuit Breaker NA8G
Connection diagram for the secondary circuit of NA8G-1600 with standard type intelligent controller
Fault indicator
N A B C
XT 3 4 6 8 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55 FU
Breaker body
M L1
QF F DT Q/QY
Intelligent controller
SAL
AX Control power
SA L2(N)
TA
FU
XT 1 2 5 7 9 10 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56
+DC24V -
S
Power
Energy
-driven ON OFF
Main circuit Intelligent controller Open Close Under storage energy indication indication Auxiliary contact available for users AC auxiliary contact for standby application
voltage indication storage
FU—fuse
DT——closing electromagnet F——shunt release Q/QY—under voltage release
TA—current transformer
SA——travel switch M——energy storage motor AX—auxiliary contact
SB1~SB2——pushbutton HL1~HL4——indicator light XT—connection terminal
QF——breaker S——power module SAL—sensitive switch
# #
1 and 2: input (terminals) for intellectual controller auxiliary power supply
#
4, #5 and #6: faulty tripping contact output (#5 is the common terminal, AC250V 5A)
Ⅰ Four switch contact Ⅱ Five switch contact Ⅲ Six switch contact Ⅳ Three open and
(acquiescence) three close contact
38 39 41 42 44 45 47 48 38 39 41 42 44 45 47 48 50 51 38 39 41 42 44 45 47 48 50 51 53 54 38 40 42 44 46 48
37 40 43 46 37 40 43 46 49 37 40 43 46 49 52 37 39 41 43 45 47
Notes: 1. Four switch contact is the normal auxiliary contact mode.When special order is made for alternating current, five switch contact,six switch contact,
Q three open and three close contact can be selectedadditionally. Four switch contact is the only mode in case of direct current.
2. All control voltage of frame 1600 has to be put to #1 and #2 after the power module inputs DC24V.
3. The wiring for the part indicated by dashed lines shall be made by users.
NA8G Air Circuit Breaker P-020
Connection diagram for the secondary circuit of NA8G-3200 to 6300 with standard type intelligent controller
Fault indicator
N A B C
XT
Breaker body
3 4 6 8 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
FU
C
M L1
QF F DT Q/QY
Intelligent controller
SAL
AX Control power
SA L2(N)
TA
FU
XT 1 2 5 7 9 10 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56
3200 and 6300 frame controller power supply: AC230V and AC400V
+DC24V -
S
Frame 3200, 6300 shell controller power supply: DC220V,DC110V;
Power
Under Energy -driven ON OFF
Main circuit Intelligent controller Open Close storage
voltage indication energy indication indication
Auxiliary contact available for users AC auxiliary contact for standby application
storage
#
1 and #2: input (terminals) for intelligent controller auxiliary power supply
#
4, #5 and #6: faulty tripping contact output (#5 is the common terminal, AC250V 5A)
Ⅰ Four switch contact Ⅱ Five switch contact Ⅲ Three open and Ⅳ Four open and
(acquiescence) three close contact four close contact
38 39 41 42 44 45 47 48 38 39 41 42 44 45 47 48 50 51 38 40 42 44 46 48 38 40 42 44 46 48 50 52
37 40 43 46 37 40 43 46 49 37 39 41 43 45 47 37 39 41 43 45 47 49 51
Notes: 1. Four switch contact is the normal auxiliary contact mode. When special order, five switch contact, three open and three close contact, four open
and four close contact can be selected additionally.
# #
2. When the controller voltage of frame 3200 and 6300 is AC230V/400V, it can be directly put to 1 and 2; if the voltage is DC220V/110V, it has to be
put to #1 and #2 after the power module outputs DC24V.
3. The wiring of the part indicated by dashed lines shall be made by users.
P-021 Air Circuit Breaker NA8G
Connection diagram for the secondary circuit of NA8G-1600 with multifunctional type intelligent controller
FU
L1
N
PE
L N PE
Device Net Profibus-DP
PSU-1 power module
- + - + - + - +
ST-DN ST-DP
module module
12 13 14 15 16 17 18 19
N A B C
1 2 3 4 5 6 7 8
+ + COM D11 D12 D13
DC24V RU-1 relay module
Fault indicator SB2 SB1
Green Red
XT 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
PE
QF M
D14 F DT Q/QY
Intelligent controller
SAL D13 D15 D16
AX
SA
TA
Breaker body
XT 1 2 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56
#
1 and #2: input (terminals) for intelligent controller auxiliary power supply
#
3:PE
# # # #
4, 5 and 6: faulty tripping contact output ( 5 is the common terminal, AC250V 5A)
#
7, #8 and #9: auxiliary contact output (#8 is the common terminal, AC250V 5A)
# # # #
10, 11 and 12: auxiliary contact output ( 11 is the common terminal, AC250V 5A)
# #
14 and 15:RS485 communication interfaces (in case of communication type)
#
16, #17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V, 5A)
# # # #
20, 21, 22, and 23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V)
# #
24 and 25: to be externally connected to the mutual inductor input
Ⅰ Four switch contact Ⅱ Five switch contact Ⅲ Six switch contact Ⅳ Three open and
(acquiescence) three close contact
38 39 41 42 44 45 47 48 38 39 41 42 44 45 47 48 50 51 38 39 41 42 44 45 47 48 50 51 53 54 38 40 42 44 46 48
37 40 43 46 37 40 43 46 49 37 40 43 46 49 52 37 39 41 43 45 47
Notes: 1. Notes: 1. Four switch contact is the normal auxiliary contact mode. When special order is made for alternating current, five switch contact,six switch contact,
three open and three close contact can be selected additionally. Four switch contact is the only mode in case of direct current.
2. The wiring of the part indicated by dashed lines to be made by users.
NA8G Air Circuit Breaker P-022
Connection diagram for the secondary circuit of NA8G-3200 and 6300 with multifuctional type itelligent controller.
FU
L1
N
PE
L N PE
Device Net Profibus-DP
PSU-1 power module
- + - + - + - +
ST-DN ST-DP
module module
12 13 14 15 16 17 18 19
N A B C
1 2 3 4 5 6 7 8
+ + COM D11 D12 D13
DC24V RU-1 relay module
Fault indicator SB2 SB1
XT 3 4 6 8 10 12
Green Red
14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
C
PE
QF M
D14 F DT Q/QY
Intelligent controller
SAL D13 D15 D16
AX
SA
TA
Breaker body
XT 1 2 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56
Frame 3200 and 6300 shell controller power supply: AC230V and AC400V
+DC24V-
S
Power
Under Energy
-driven ON OFF Auxiliary contact
Main circuit Intelligent controller Open Close voltage
storage energy
indication indication available for users
AC auxiliary contact for standby application
indication storage
#
1 and # 2: input (terminals) for intelligent controller auxiliar y power supply
#
3:PE
# # # #
4, 5 and 6: faulty tripping contact output ( 5 is the common terminal, AC250V 5A)
#
7, #8 and #9: auxiliar y contact output ( #8 is the common terminal, AC250V 5A)
# # # #
10, 11 and 12: auxiliar y contact output ( 11 is the common terminal, AC250V 5A)
# #
14 and 15:RS485 communication interfaces (in case of communication type)
#
16, #17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V, 5A)
#
20, #21, #22, and #23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V)
#
24 and #25: to be externally connected to the mutual inductor input
Ⅰ Four switch contact Ⅱ Five switch contact Ⅲ Three open and Ⅳ Four open and
(acquiescence) three close contact four close contact
38 39 41 42 44 45 47 48 38 39 41 42 44 45 47 48 50 51 38 40 42 44 46 48 38 40 42 44 46 48 50 52
37 40 43 46 37 40 43 46 49 37 39 41 43 45 47 37 39 41 43 45 47 49 51
Notes: 1 Four switch contact is the normal auxiliary contact mode. When special order, five switch contact, three open and three close contact, four open and four close
contact can be selected additionally.
# # #
2. When the controller voltage of the 3200 and 6300 shells is AC230V/400V, it can be directly put to 1 and 2;if the voltage is DC220V/110V, it has to be put to 1
#
and 2 after the power module inputs DC24V.
3. The wiring of the part indicated by the dashed lines shall be made by users.
P-023 Air Circuit Breaker NA8G
10
11
12
13
14
15
16
1 LED window LED window capable of showing the current for each phase, various setting parameters,
rated current, fault current, tripping time, and the like
2 “ Ig ” limp Single-phase earthing fault indicator
6 “ MENU ” Pushbutton Successively access to submenus at various levels by pressing the MENU key
To inquire the current for each phase at present:
recurrently select the contents in the menus at various levels
8 “ RESET ” Pushbutton RESET key must be pressed after the encoder switch position is adjusted;
the intellectual controller faulty tripping results in fault memory which
can be cleared only by pressing the RESET key;
9 “ IR ” Knob switch There are (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 0.98, 1.0)In,
nine settings altogether, for the current multiple setting of long time-delay overcurrent.
10 “ tR ” Knob switch There are (1, 2, 4, 8, 12, 16, 20, 24, 30)s, nine settings altogether,
for the time delay time setting of long time-delay overcurrent in case of 6IR.
11 “ Isd ” Knob switch There are (1.5, 2, 2.5, 3, 4, 5, 6, 8, 10)Ir, nine settings altogether,
for the current multiple setting of short-time short time-delay.
12 “ tsd ” Knob switch For the short-circuit short time-delay time setting, there are nine settings:
2
the inverse time limit, i.e., I t on(0.1, 0.2, 0.3, 0.4)s, the definite-time limit,
2
i.e., I t OFF (0.1 0.2 0.3 0.4)s and X, i.e., closing the short time-delay
13 “ Ig ” Knob switch There are (A, B, C, D, E, F G, H, J), nine settings altogether, for the current multiple setting
of single-phase earthing.
15 “ tg ” Knob switch For the time setting of single-phase earthing, there are nine settings: the inverse time limit,
2 2
i.e., I t on(0.1, 0.2, 0.3, 0.4)s, and the definite-time limit, i.e., I t OFF(0.1 0.2 0.3 0.4)s, and X,
i.e., closing the single-phase earthing.
7.2 Default interface and operation method for the standard type controller
The default interface for the standard type controller is described as follows: (The current for each phase to be selected
by pressing "→")
Press "MENU"key once to go to the status for parameter query as follows, and then press"→"to go to query
the setting parameter of quadruple overcurrent protection.
Default interface of the standard type controller Status for parameter query─setting current of long time-delay
Press "MENU" key twice to go to the status for fault query as follows,show the latest fault information:
Status for fault query─tripping current Status for fault query─tripping time
Press "TEST" key to go to the status for simulating tripping test in case of 6IR, and after tripping as follows:
Status of simulating tripping test─simulating current Status of simulating tripping test─simulating time
5
3
6
10
11
13 12
2 LED window LCD window capable of showing the current for each phase, various setting parameters, rated current,
fault current, tripping time and the like
3 SET key Switch to the set default menu (left arrow key, when it is necessary to move leftwards or rightwards
for the set interface).
4 UP key Move the box select menu under the current menu to change the position of said box upwards,
and perform the setting of the parameter ADD in the parameter setup menu.
5 RETURN key Exit the current menu and go to the previous menu, or cancel the value of the current setup parameter.
6 ACK key Go to the next menu of the currently selected select box (go to the set state under the set interface, a
nd exit the set state by pressing the key again).
7 DOWN key Move the box select menu under the current menu to change the position of said box downwards,
and perform the setting of the parameter SUBTRACT in the parameter setup menu.
8 INQUIRY key Switch to the inquiry default menu (right arrow key, when it is necessary to move leftwards
or rightwards for the set interface).
Primary menu Secondary menu Third menu Fourth menu Fifth menu
Ia= 1000A
Ia
Ib
Ic
Ib= 1001A
Ic= 998A
C
In In= 0A
Ig= 0A or I△n=0.00A
Ia= 1300A
Ib= 1400A
Instantaneous value
Maximum Ic= 1380A
In= 200A
Ig= 0A or I△n=0.00A
Ia= 3%
Magnitude of currentⅠ Unbalance rate Ib= 5%
Ic= 1%
Current thermal capacitance 100%
15min
Ia= 1000A
Real-time value
Ia,Ib, Ib= 1000A
Ic,In
Ic= 998A
In= 0A
Required value Ia= 1050A
Ib= 1040A
Maximum
Ic= 1010A
In= 0A
Uab= 380V
Ubc= 380V
Instantaneous value Uca= 380V
Uan= 220V
Voltage U Ubn= 220V
Ucn= 220V
Mean value Uav= 380V
Unbalance rate 0%
Phase sequence A,B,C
FrequencyF 50Hz
EP= 200kWh
Primary menu Secondary menu Third menu Fourth menu Fifth menu
P= 660kW
P, Q, S Q= 0kvar
S= 660kVA
-1.00
Perceptual
Power factor PFa= 1.00
PFb= 1.00
PFc= 1.00
Instantaneous value Pa= 220kW
Pa, Qa, Sa Qa= 0kvar
Sa= 220kVA
Pb= 220kW
Power P
Pb, Qb, Sb Qb= 0kvar
Sb= 220kVA
Pc= 220kW
Pc, Qc, Sc Qc= 0kvar
Sc= 220kVA
P= 660kW
P, Q, S Q= 0kvar
S= 660kVA
Required value P= 661kW
Q= 2kvar
Maximum
S= 662kVA
Reset(+/-)
Ia
Ib
Ia,Ib
Ic,In
Ic
In
Waveform
Uan
Uan,Ubn Ubn
Ucn
Ucn
Ia= 1000A
I(A) Ib= 1000A
Ic= 1000A
In= 1000A
Uab= 380V
Base form
Ubc= 380V
U(V) Uca= 380V
Harmonic H Uan= 220V
Ubn= 220V
Ucn= 220V
Ia= 0.0%
Ib= 0.0%
I(%)
Ic= 0.0%
In= 0.0%
Uab= 0.0%
THD
Ubc= 0.0%
Uca= 0.0%
U(%)
Uan= 0.0%
Ubn= 0.0%
Ucn= 0.0%
Ia= 0.0%
Ib= 0.0%
thd I(%)
Ic= 0.0%
In= 0.0%
NA8G Air Circuit Breaker P-028
Primary menu Secondary menu Third menu Fourth menu Fifth menu
Uab= 0.0%
Ubc= 0.0%
Uca= 0.0%
thd U(%)
Uan= 0.0%
Ubn= 0.0%
Ucn= 0.0%
Ia FFT THD=0.0%
0.0%
Ia(3, 5, 7...31)
3 5 7 9 11...31)
Ib FFT THD=0.0%
0.0%
Ib(3, 5, 7...31)
I(3, 5, 7...31)
C
3 5 7 9 11...31)
Ic FFT THD=0.0%
0.0%
Ic(3, 5, 7...31)
3 5 7 9 11...31)
In FFT THD=0.0%
0.0%
In(3, 5, 7...31)
3 5 7 9 11...31)
Primary menu Secondary menu Third menu Fourth menu Fifth menu
Address =3
Communication setting
Baud rate =9.6K
=DO1
Function setting
=regional interlocking
=DO1
Executive mode =N.O. pulse
I/O setting
=360s
I/O state
I/O state DO1 DO2 DO3 DI1
1 1 1 1
Primary menu Secondary menu Third menu Fourth menu Fifth menu
Ir e.g.: =1000A=100%In
Current protection e.g.: =ON
Current protection Long time delay
Delay time e.g.: =C1,Is@6Ir
Cooling time e.g.: =3h
P-029 Air Circuit Breaker NA8G
Primary menu Secondary menu Third menu Fourth menu Fifth menu
e.g. =5000A=5.0Ir
Definite-time limit Operating current
e.g. =0.1s
Short-time delay
e.g. =2000A=2.0Ir
Inverse-time limit Delay time
e.g. =C1,0.Is@6Ir
Instantaneous Operating current e.g. =10000A=10.0In
Neutral phase protection Neutral phase protection e.g. =200%
Operating current e.g. =800A
Ground protection Delay time e.g. =0.4s
Coefficient of earthing e.g. =6.0
Current protection Starting current e.g. =600A
Starting time e.g. =0.1s
Grounding alarm
Return current e.g. =100A
Return time e.g. =0.1s
Operating current e.g. =8.0A
Leakage protection
Setup delay time e.g. =0.75s
Starting current e.g. =5.0A
Starting time e.g. =0.1s
Electric leakage alarm
Return current e.g. =4.0A
Return time e.g. =0.1s
Executive mode e.g. =I the first method
Unloading value 1 e.g. =800A
Load Monitoring Unloading time 1 e.g. =50%tr
Unloading value 2 e.g. =700A
Unloading time 2 e.g. =25%tr
Executive mode e.g. =Alarm
Startup value e.g. =200V
Under voltage Starting time e.g. =0.2s
Return value e.g. =320V
Return time e.g. =60.0s
Executive mode e.g. =Alarm
Startup value e.g. =480V
Voltage protection Over voltage Starting time e.g. =1s
Return value e.g. =400V
Return time e.g. =60.0s
Executive mode e.g. =Alarm
Startup value e.g. =10%
U unbalanced Starting time e.g. =1s
Return value e.g. =5%
Return time e.g. =60.0s
Primary menu Secondary menu Third menu Fourth menu Fifth menu
Current alarm e.g. phase sequence alarm, Inverse power alarm, over frequency alarm...
Primary menu Secondary menu Third menu Fourth menu Fifth menu
A phase short-circuit definite-time limit
T= 0.4s
I= 4300A
15:28:25
e.g.
Tripping record 8 (for) short-circuit definite-time limit 5/30
2004/05/30 Ia= 4300A
Ib= 4200A
Ic= 4000A
In= 150A
Di input alarm
e.g.
Di1
1 DI (for) DI input alarm
2004/07/16 2004/07/16
Notes: a. The actual menu will very depend on the function selected by the user.
b. The controller starts screensaver automatically 10min later.
1.Quadruple overcurrent protection (for long time-delay, 1.Quadruple over current protection (for long time-delay,short-circuit short
short-circuit short time-delay,instantaneous,earthing); time-delay,instantaneous,earthing); earthing corresponds to vector sum
earthing corresponds to vector sum (T type); (T type);
2.Parameter setup: fixed value setting position setting function 2.Parameter setup: fixed value keyboard setting function;
3.Current measurement 3.Current measurement function;
4.Test function; 4.Current unbalance rate measurement function;
5.Fault recording function; 5.Two test functions:
6.Self-diagnostic function; (1)Instantaneous tripping test simulated on the panel;
7.MCR make/break function; (2)Triple over current, grounding/leakage and operating time tests
8.Human-machine interface: 33×22 LED; simulated by software;
6.Fault recording function: 8 times of failures can be recorded;
7.Self-diagnostic function
8.MCR make/break function
9.Communication function: MODBUS protocol;
10.Alarm logging function;
11.Recording number of operations;
12.Contact wear
13.Position changing record
14.Human-machine interface: 28×43 LCD;
15.Heat capacity measurement
P-031 Air Circuit Breaker NA8G
10000
5000
IR=(0.4-1)In
1000
500
200
TR=(1~30)s
100
50
20
T(s) 10
2
I t ON
5
Isd=(1.5~10)IR
2
Isd=(1.5~10)IR
1
2
I t OFF
0.5
0.2
0.1
Ii=(2~15)In
0.05
0.02
0.01
0.2 0.3 0.5 0.6 0.8 1 2 3 4 5 8 10 20 30 40 50 60 80 1.5 2 3 4 5 6 8 10 20 30
X IR
10000
5000
Ig=(0.2-1)In
1000 MAX 1200A
500 MIN 120A
200
100
50
20
T(s) 10
I2 ON
5
1
0.5
0.2
0.1
I2 t OFF
0.05
0.02
0.01
0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30
X In
NA8G Air Circuit Breaker P-032
Rated current range [IR] Error Current [I] Operating time [tR(s)] Time error
≤1.05I R No actuation within 2h
>1.30I R <1h and then actuate
(0.4~1)In ±10% 1.5IR 16 32 64 128 192 256 320 384 480
2.0IR 9 18 36 72 108 144 180 216 270 ±15%
6.0IR 1 2 4 8 12 16 20 24 30
Rated current range [Isd] Error Current [I] Operating time [tsd(s)] Time error
<0.85Isd No action
>1.15Isd Time-delay action
I 2t OFF 0.1 0.2 0.3 0.4
(1.5~10)IR
±15% 2
I t ON ±15%
+OFF(Power off)
0.1 0.2 0.3 0.4
I>10IR
2
I t ON
2 2
anti-time-limit delay:I Tsd=(10I R) tsd
I≤10IR
Rated current range [Ii] Error Line current [I] Operating Characteristics
Rated current range [Ig] Error Line current [I] Operating time [tg(s)] Time (delay) error
<0.9Ig no-action
>1.1Ig time-delay action
I2T OFF 0.1 0.2 0.3 0.4
(A~J)In
±10% I2T ON
+OFF(Power off)
0.1 0.2 0.3 0.4 ±15%
I>J
2
I T ON
anti-time-limit delay I2Tg=(J)2tg
I≤J
Meaning of Ig
7.7 Explanation for auxiliary functions The controller still has the function of fault memory after reset
a. Explanation for test functions or de-energized to keep a latest historical event for post
When onsite adjustment, periodical inspection or overhaul is analysis. Only when there is a new fault again, the original
made with the controller supported by the breaker, breaking information is cleared with the current latest faulty data saved.
several times is necessary by using the test functions of the For the inquiry method, refer to the above explanation about
controller to check the cooperation of the controller and the fault display
breaker. With the breaker on, press the test key, and the
7.8 Explanation for display function
intelligent controller will trip instantaneously to cut off the
When the rated current is greater than or equal to 400A, the
breaker.
primary current shall not be lower than 0.4In for single phase,
Note: ① This function can be used only when onsite and 0.2In for three phases for normal operation of the
adjustment or overhaul for the breaker is made, and shall not breaker.
be used during the normal operation.
C
When the rated current is less than 400A, the primary current
② Each time before the controller is switched on, it is
shall not be lower than 0.8In for single phase,and 0.4In for
necessary to press the reset button in the upper position of
three phases for normal operation of the breaker.
the controller panel so that the breaker can be switched on
again for operation. Note: When the AC220V ST power module is energized, and
b. Explanation for fault memory the voltage falls to AC120V, there will be no display on the
controller
Operating characteristic:
Operating characteristic:
Operating characteristic:
disconnected.Operating characteristic:
Technical parameters:
8.9 Doorcase
They are installed on the door of the distribution cabinet room to seal it with a
protection level of up to IP40.
9. Installation
9.1 Following items to be checked before installation Check the Listed below are the problems which users may encounter
label plate on the breaker panel to see if it is conform to the during installation, adjustment, and operation of the breaker,
specifications of the ordered goods. and the possible reasons and elimination methods.
1 Check the breaking current and operating time on the intelligent controlle
Short-circuit fault tripping 2 Promptly find and shoot the trouble if overload is confirmed
Breaker tripping (short time-delay or 3 Check the setting value of the intelligentcontroller
1 (fault indicator on) instantaneous overcurrent 4 Check to see whether the breaker is in good condition, and determine whether
indicator on) it can be closed for operation
5 Press the reset button to close the breaker again
1 Check the breaking current and operating time on the intelligent controller
2 Promptly find and shoot the trouble if it is confirmed that there is a earthing fault
Earthing fault tripping 3 If no earthing fault is detected, please determine whether the earthing fault
(earthing fault indicator on) current setting is proper, and can be well matched with the actual protection;
if not, the setting shall be modified
4 Press the reset button to close the breaker again
Under voltage release 1 Check to see if the power voltage is lower than 70%Ue
Tripping 2 Check the under voltage release and control unit for fault
Mechanical interlock action Check the working condition of two breakers equipped with mechanical interlock.
1 Whether the under voltage release has been energized
Under voltage release 2 Whether the power voltage is lower than 85%Ue
No attracting 3 Whether the under voltage release or control unit malfunctions,
if so, the release shall be replaced.
Reset button fails to reset Press the reset button to close the breaker again.
Put the open frame (draw-out) circuit breaker to the right position
Breaker fails to pre-store energy
by rocking (with it locked in the connected position)
1 There may be short circuit current when the matter is switched on,
and in this case you shall find and shoot the trouble
2 Check to see if there is any overload current in the circuit,
Breaker trips Tripping immediately find and shoot the trouble
3
after closed Delay tripping 3 Check the setting value of the intelligent controller for reasonability,
and a re-setting process is necessary if not reasonable
4 Press the reset button to close the breaker again
Breaker fails to be pulled out when the Rock rod fails to be pulled out Pull out the rock rod
6 open frame (draw-out) circuit breaker is Breaker fails to completely reach the Put the breaker completely
in the SEPARATION position SEPERATION position to the “disconnected” position by rocking
Installation mode □draw-out type □Fixed type (no such products for over 4000A)
Connection mode □Horizontal connection □Vertical connection □Front connection □mixed connection (connection mode to be noted)
Number of poles □3P □4P
Factory' s setting values: IR=1In, tr=2s@6IR:; Isd=8IR, inverse-time protection,tsd= 0.4s; Ii=12In;OFF(If on, when In>1200A Ig=800A;
when In≤1200A Ig=0.5In) If the user has some requirements different from the defaulting, please write the numerical values on
the line below
Operating current setting______In (0.4,0.5,0.6,0.7,0.8,0.9,0.95,0.98,1)
C
Long-time delay protectionIR
Operating time setting______s (1,2,4,8,12,16,20,24,30)
Setting of the
protection Operating current setting______IR (1.5,2,2.5,3,4,5,6,8,10)
Short-circuit short-time delay protectionIsd
parameter Operating time setting □inverse time______s (0.1,0.2,0.3,0.4,OFF)
Optional function
(this function to □Over voltage protection □Under voltage protection □Over frequency protection □Under frequency protection
be added as □Voltage unbalance measurement □Phase sequence protection □Voltage measurement □Frequency measurement
required by the □Measurement of harmonic current □Power factor measurement □Power measurement □Phase sequence detection
user, and to be □Voltage unbalance rate measurement □Electric energy measurement □Contact equivalent □MCR make/break function
matched with the □Load monitoring function □Signal contact output function □Communication function □ZSI regional interlocking protection
controller type)
Under voltage □Instantaneous □Time delay______s (1-2-3-4-5-6-7s provided for frame 1600, optional but not adjustable;
Accessories for standard
release 0.5-1-3-5s for frame 3200 and 6300l, optional but not adjustable) □AC400V □AC230V
OFF locking □Two breakers is provided with two same locks and one key
device □Three breakers is provided with three same locks and two keys
configuration
Mechanical
Mechanical interlock □Steel cable interlock □Connecting-rod interlock
interlock
□Button locking device □Three-position locking device for the draw-out socket □Door interlock
□Phases barrier
Note: Extra costs are needed for the optional functions, optional accessories and the like for the breaker.