NA8G Air Circuit Breaker Overview

The NA8G Air Circuit Breaker is designed for distribution networks with a rated current range of 200A to 6300A and service voltage of AC 415V or 690V. It features various wiring configurations, installation modes, and operational types, along with intelligent protection functions for enhanced reliability. The product adheres to IEC/EN 60947-2 standards and is suitable for use in power stations, factories, and modern buildings, including renewable energy projects.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views38 pages

NA8G Air Circuit Breaker Overview

The NA8G Air Circuit Breaker is designed for distribution networks with a rated current range of 200A to 6300A and service voltage of AC 415V or 690V. It features various wiring configurations, installation modes, and operational types, along with intelligent protection functions for enhanced reliability. The product adheres to IEC/EN 60947-2 standards and is suitable for use in power stations, factories, and modern buildings, including renewable energy projects.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

P-001 Air Circuit Breaker NA8G

2.6 Type designation

NA8 G - □-□□ / □-□-□-□-□

Voltage of secondary circuit


AC230V, AC400V
DC220V, DC110V

Wiring of main circuit:


H:Horizontal wiring of main circuit
V:Vertical wiring of main circuit

Mode of installation:
F:Fixed type
D:Draweout type

Mode of operation:
M:Manual
P: Power-driven

No. of poles:
3:3-pole
4:4-pole

Intelligent controller:
NA8G Air Circuit Breaker M: Standard type
H: Multifunctional type
1. General
Rated current:
1.1 Application scope

With rated current from 200A to 6300A, and rated service


voltage of AC 415V or 690V, NA8G series air circuit breaker is
Frame size
mainly used in the distribution network with the circuit of AC rated current Rated current

50HZ/60HZ to distribute electric energy and protect circuits


400A
and electric equipment against over-load, under-voltage, 630A
short- circuit, single-phase earthing fault. 800A
1600A
1000A
Having art-oriented appearance, high breaking capacity, zero 1250A
arcover and varities of intellectualized protection functions, the 1600A
1600A
breaker can be used for selective protection with accurate 2000A
3200A
action, no unnecessary power cut, and better power supply 2500A
reliability. 3200A
2500A
That breaker can be widely used for power stations, factories, 4000A 3200A
4000A
mines and modern tall buildings, especially the distribution
4000A
system in the intelligent building, and also widely used in 5000A
6300A
green projects such as wind and solar power generation. 6300A

1.2 Standard : IEC/EN 60947-2.

2. Operating conditions Frame size rated current:


1600A, 3200A, 6300A, 4000A
2.1 Temperature condition:
Improved product code
-5℃~40℃; the average value within 24h shall not exceed
+35℃ (special situation excluded); Design sequence number

2.2 Altitude:≤2000m; ACB


2.3 Pollution grade: Grade 3; Company code
2.4 Air conditions:

At mounting site, relative humidity not exceed 50% at the max


temperature of +40℃, higher relative humidity is allowable
under lower temperature, RH could be 90% at +20℃, special
measures should be taken to occurrence of dews;

2.5 Note: Without the intelligent controller,


the breaker functions as a switch-disconnector.
NA8G Air Circuit Breaker P-002

3. Product structure
Body structure

Secondary connecting part

Shunt release

Closing electromagnet

Under voltage release Energy storage handle


C
Breaking button Making button

Breaking/making indicator Energy storage & release indicator

Operating mechanism

Motor-driven energy storage mechanism

Intelligent controller

Zero arcover hood

Secondary connecting part

Energy storage handle

Fault-breaking indicator reset button Making button

Breaking button
Name plate
Breaking/Making indicator

Intelligent controller Energy storage & release indicator


P-003 Air Circuit Breaker NA8G

Breaker off and energy storage over Breaker off and no energy storage Breaker on and energy storage over Breaker on and no energy storage

Press Press Press Press


Press Press Press Press

Energy Energy
storage release Energy Energy
storage release

Drawout structure

Secondary connecting part

Side panel Safety separator

Baffle push rod

Rocking handle work hole


Guide rail

Locking device

Extraction draw plate

Rocking handle deposit hole

Position indicator
NA8G Air Circuit Breaker P-004

Connected Connected

Test Test

Disconnected Disconnected

Connected: both main circuit and secondary circuit are connected Test: the main circuit is disconnected,
the safety separator works well,
and the secondary circuit is connected.

Connected
C
Test

Disconnected

Disconnected: neither main circuit nor secondary circuit is connected

(1)Draw-out socket placed horizontally (2)Pull out the guide rail

(3)Place the breaker body on the guide rail (4)Move the breaker body onto the guide rail with a snap

(5)Push the breaker body in, and turn the break body to the connected position
P-005 Air Circuit Breaker NA8G

4. Main technical parameters


4.1 Main technical parameters

Shell grade rated current Inm (A) 1600 3200 4000 6300

400,630,800, 1600,2000,
Rated current In (A) 2500,3200,4000 4000,5000 6300
1000,1250,1600 2500,3200

Nominal insulation voltage Ui (V) 690 1000 1000 1000


Rated operational voltage Ue (V) 415 690 415 690 415 690 415
Rated ultimate short circuit breaking capacity Icu (kA) 50 25 100 65 100 65 120
Rated service short circuit breaking capacity Ics (kA) 40 20 80 65 100 65 100
Rated short time withstand current Icw, 1s (kA) 40 20 80 65 85 65 100
Number of poles 3P 4P 3P 4P 3P 4P 3P 4P 3P
Frequency of operation (number of times/hour) 20 10 10 10
Mechanical life 3000 3000 3000 2000
Number of operations
Electrical Life 1000 1000 1000 500
Flashover distance mm 0 0 0 0

Wire to enter from the Wire to enter from the Wire to enter from the Wire to enter from the
Wire incoming pattern
upper or lower port upper or lower port upper or lower port upper or lower port

fixed type (kg) 22/26.5 52.5/66.5 58/75 -


Net weight (3 poles/4 poles)
draw-out type (kg) 42.5/55 98/121 110/145 210/233 233

Size(3 poles/4 poles) fixed type 320×(254/324)×258 406×(422/537)×329 402×(432.5/547.5)×330 -


Height × width × depth draw-out type 351×(282/352)×352 439.5×(435/550)×445 439.5×(435/550)×445 439×(813/928)×501 439×928×501

4.2 Capacity-reducing usage

4.2.1 Capacity-reducing at different temperatures

The following table shows the continual current-loading capacity of the circuit breakers and buses in each wiring mode at the
corresponding ambient environment temperatures and under the conditions of the satisfaction of conventional heating with a
similarity in capacity reducing between the breaker connected in a mixed way and the breaker connected horizontally.

Style wiring Draw-out type


mode ambient Front/rear horizontal wiring mode Rear vertical wiring mode
temperature℃
-5~40 45 50 55 60 -5~40 45 50 55 60
400 400 400 400 400 400 400 400 400 400
630 630 630 630 550 630 630 630 630 580
800 800 800 800 700 800 800 800 800 700
1600
1000 1000 1000 950 900 1000 1000 1000 950 900
1250 1250 1250 1150 1050 1250 1250 1250 1200 1100
1600 1550 1500 1450 1350 1600 1600 1550 1500 1450
1600 1600 1600 1600 1600 1600 1600 1600 1600 1600
2000 2000 2000 2000 1900 2000 2000 2000 2000 1950
3200
2500 2500 2500 2450 2350 2500 2500 2500 2500 2400
3200 3200 3100 3000 2900 3200 3200 3200 3050 2900
2500 2500 2500 2450 2350 2500 2500 2500 2500 2400
4000 3200 3200 3100 3000 2900 3200 3200 3200 3050 2900
4000 3800 3600 3400 3200 4000 3800 3600 3400 3200
4000 4000 4000 3900 3800 4000 4000 4000 3900 3800
6300 5000 5000 4700 4600 4400 5000 5000 4800 4650 4500
6300 6100 6000 5500 5200 6300 6100 6000 5500 5200
NA8G Air Circuit Breaker P-006

4.2.2 Capacity-reducing at different altitudes


When the altitude is higher than 2000m, there will appear changes in insulation property, cooling performance, pressure,and the
performance can be modified in reference to the following table.

Altitude(m) 2000 3000 4000 5000


Insulation withstand voltage(V) 3500 3000 2500 2000
Insulation voltage(V) 1000 800 700 600
Rated operational voltage(V) 690 580 500 400
Rated operational current(A) 1×In 0.96×In 0.92×In - 0.87×In

4.3 Power loss


Power loss is the loss at each pole which is measured when the breaker is charged with the rated current.

Power loss
Breaker type Rated current Draw-out type Fixed type C
400 140 80
630 161 100
800 215 110
NA8G-1600
1000 230 120
1250 250 130
1600 460 220
1600 390 170
2000 470 250
NA8G-3200
2500 600 260
3200 670 420
2500 600 260
NA8G-4000 3200 670 420
4000 1047 656
4000 550 -

NA8G-6300 5000 590 -

6300 950 -

Note: The data and parameters in the above technical documentation results from tests and theoretical calculation,
and can only be used as a general type selection guide.They cannot replace industrial practical experience or proof test.

5.4 Recommended bus for the breaker and recommendation for users to install the buses

Inm(A) NA8G-1600 NA8G-3200 NA8G-4000 NA8G-6300


In(A) 400 630 800 1000 1250 1600 1600 2000 2500 3200 250 3200 4000 4000 5000 6300
Thickness(mm) 5 5 5 5 8 10 6 6 5 10 6 10 10 10 10 10
Busbar Width(mm) 50 40 50 60 60 60 100 100 100 100 80 100 100 100 100 100
Number of buses 1 2 2 2 2 2 2 3 4 4 4 4 5 5 7 8
P-007 Air Circuit Breaker NA8G

5. Dimensions and connection


NA8G-1600 (In=400A ~1250A) Draw-out type
(Only horizontal connection is provided by the factory, vertical one has to be made by users themselves).

210 36
a

275
149

310
7
351

78.5

95 76

345(Connected position)
391(Disconnected position)

282(3P) Horizontal connection


Phases barrier
352(4P) (to be ordered
separately)

2-Φ6.5
95

149(3P)
155(4P)

2-Φ6.5×10
7
35

75.5(4P)
78.5(3P)

145(3P) 63
95 76
215(4P)
4P Central line
345(Connected position)
3P Central line 391(Disconnected position)
12×Φ11(3P) 60 Vertical connection
16×Φ11(4P)
15

25
N Pole
In(A) a(mm) Note: If users intend to change the
35

200, 400, 630 5 horizontal connection into vertical


connection, they need to replace the
76 76 76 800, 1000 10
upper and lower busbars on both sides
1250 15
with the same one as the central busbar.

NA8G-1600 (In=1600A) Draw-out type


(Only horizontal connection is provided by the factory, vertical one has to be made by users themselves).

210 36 Phases barrier


(to be ordered separately)
15

275
310
179

7
351

63.5

95 76

442(Connected position)

282(3P) 488(Disconnected position)


352(4P)
Horizontal connection
Phases barries
2-Φ6.5
(to be ordered separately)
95

2-Φ6.5×10
35

149(3P)
155(4P)

145(3P) 63 7
215(4P)
78.5(3P)
75.5(4P)

4P Central line
3P Central line 95 76
24×Φ11(3P) 85
15

32×Φ11(4P) 35
N pole 442(Connected position)
488(Disconnected position)
35

80.5

Vertical connection Note: If users intend to change the


horizontal connection into vertical
connection, they need to replace the
101 101 101 upper and lower busbars on both sides
with the same one as the central busbar.
NA8G Air Circuit Breaker P-008

NA8G-1600 (400A~1250A) Fixed type


(Only horizontal connection is provided by the factory, vertical one to has be made by users themselves).

210 22 C
Phases barrier
(to be ordered
separately)

a
320

149
281
275

48.5 7

237(3P)
307(4P)
254(3P)
100
251
92
C
Horizontal connection
324(4P)

Phases barrier
(to be ordered
separately)
4-Φ7
100

149(3P)
155(4P)

237(3P)
307(4P)
48.5(3P)
45.5(4P)

C 100 92
4P Central line
251
12×Φ11(3P) 3P Central line
16×Φ11(4P) 60 Vertical connection
N Pole 25
15

Note: If users intend to change the


35

horizontal connection into vertical


In(A) a(mm) connection, they need to replace the
76 76 76
200, 400, 630 5 upper and lower busbars on both sides
800, 1000 10 with the same one as the central busbar.
1250 15

NA8G-1600 (In=1600A) Fixed type


(Only horizontal connection is provided by the factory, vertical one has to be made by users themselves).

210 22

Separator between phases


(to be ordered separately)
320

149(3P)

155(4P)
275
281

48.5(3P)
45.5(4P)

237(3P) 100 92
307(4P) 341
254(3P)
324(4P) Vertical connection

4-Φ7
100

C
Phases barrier
(to be ordered
separately)
237(3P)
307(4P)
15

C 4P Central line
3P Central line
179

24-Φ11(3P)
85
32-Φ11(4P)
15

N Pole 35
7
35

80.5

33.5

100 92
Note: If users intend to change the
341
horizontal connection into vertical
101 101 101
connection, they need to replace the
Horizontal connection upper and lower busbars on both sides
with the same one as the central busbar.
P-009 Air Circuit Breaker NA8G

NA8G-1600 Draw-out type NA8G-1600 Fixed type


Size of the hole to be drilled on the panel Size of the hole to be drilled on the panel

220 220
10-Φ5 8-Φ5
118
120

322

285
320

Breaker mounting panel Breaker mounting panel


118

78
2

118.5
From the center of the mounting hole on the right side of the breaker From the center of the mounting hole on the right side of the breaker
258 258

NA8G-3200 Draw-out type


Size of the hole to be drilled on the panel

217.5(3P) 217.5
332.5(4P) 52 386 7
385
240

Datum line 2

258
199.5

Datum line 1

308

371
328
155

11×17
175

Datum line 2
268
376

Φ14
18
145

21.5
97

Installation panel
10

47

162.5(3P) 162.5 10×Φ6


277.5(4P) Datum line 1
Datum line
Size of the hole to be drilled on the panel
NA8G Air Circuit Breaker P-010

NA8G-3200(In=1600A~2500A) Draw-out type


(Only horizontal connection is provided by the factory).

C 7

52
C

78 50 Φ11
25

14

29
133

115 115 115

C
Datum line

C
84

445(Connected position)
492(Disconnceted position)

Note: If users want to change the horizontal connection into vertical connection, they only have to turn the busbar by 90°

NA8G-3200(In=1600A~2500A) Draw-out type


(Vertical connection has to be made by users themselves).

C 7

C
52
25
14
Φ11
78
55

115 115 115

Datum line
25
57.5

445(Connected position)
492(Disconnected position)

Note: If users want to change the vertical connection into horizontal connection, they only have to turn the busbar by 90°

NA8G-3200 Draw-out type; Front connection

C C
C 86 25 12-Φ13
15
29

115 115 115


301

Datum line

In(A) C

1600, 2000, 2500 20

3200 30
16.5
29
P-011 Air Circuit Breaker NA8G

NA8G-3200(In= 3200A) Draw-out type (Only horizontal connection is provided by the factory)

C
7

52
C
25

100 25
Φ11

29
14
112

126 126 126

Datum line
90

445(Connected position)
492(Disconnected position)

NA8G-3200(In= 3200A) Draw-out type (Vertical connection has to be made by users themselves)

C 7
52

14
Φ11 C
25
100
57

115 115 115

Datum line
25

35.5

445(Connected position)
492(Disconnected position)

Note: If users want to change the horizontal connection into vertical connection,
it is necessary to replace the upper and lower busbars for the N and B phases with the same one as the A and C phases.

NA8G-3200 Fixed type

308

N
402
258
Datum line 2
163.5
13

11 200(3P ) 200 11 246 44 7


315(4P )
Datum line 1
NA8G Air Circuit Breaker P-012

NA8G-3200 Fixed type, size of the hole to be drilled on the panel

4×Φ12 371
328
150

311
268
72.5

29.5
21.5
C
200(3P) 200
8×Φ6
315(4P) Installation
panel
Datum line Datum line

NA8G-3200 Fixed type (Only horizontal connection is provided by the factory)

Ferrous material

C
32

C
a

86 50 12-Φ13
18.5
112

In(A) a(mm)
115 115 115 1600~2500 20
Datum line 3200 30
55

Note: If users want to change the horizontal connection into vertical connection, they only have to additionally install vertical busbars.

NA8G-3200 Fixed type (Vertical connection has to be made by users themselves)

Ferrous material

C
32
29
a C
14
Φ11
100
57

In(A) a(mm)
115 115 115
1600~2500 20
25
55

Datum line
3200 30
45

Note: If users want to change the horizontal connection into vertical connection, they only have to additionally install vertical busbars.
P-013 Air Circuit Breaker NA8G

NA8G-4000 Draw-out type, size of the hole to be drilled on the panel

217.5(3P) 217.5
332.5(4P)
42 385 18
232

258
datum line 2
199.5

datu m li ne 1

308

371
328
155

11×17
φ11
175

268

datum line 2
376

φ14
18
145

φ14
11×17

21.5
97

47
10

10×Φ6
162.5(3P) 162.5
datu m li ne 1
277.5(4P) datu m li ne 1
Size of the hole to be drilled on the panel

NA8G-4000(In=2500A) Draw-out type (only horizontal connection is provided by the factory)

42

C
78 50 Φ11
25

14

29
133

115 115 115

datu m li ne 1
84

445(Connected position)
492(Disconnected position)

Note: If users want to change the horizontal connection into vertical connection,they only have to rotate the busbars by 90°

NA8G-4000(In=2500A) Draw-out type (vertical connection has to be made by users themselves)

42
25
14
C
Φ11
78
55

115 115 115

datu m li ne 1
25
57.5

445(Connected position)
492(Disconnected position)

Note: If users want to change the horizontal connection into vertical connection,they only have to rotate the busbars by 90°
NA8G Air Circuit Breaker P-014

NA8G-4000 Draw-out type, size of the hole to be drilled on the panel

C
C
C 78 25 Φ11

15
29

115 115 115


301

datu m li ne 1

In(A)

2500
C

25
C
3200~4000 30
16.5
29

NA8G-4000(In=3200A~4000A) Draw-out type (only horizontal connection is provided by the factory)

42

C
25

100 25
Φ11
29
14
133

126 126 126

datu m li ne 1
84

445(Connected position)
492(Disconnected position)

Note: If users want to change the horizontal connection into vertical connection,they only have to change the busbar of N、B phases to A、C phases

NA8G-4000(In=3200A~4000A) Draw-out type (vertical connection has to be made by users themselves)

42

14
Φ11 C
25
100
57

115 115 115

datu m li ne 1
25
35.5

445(Connected position)
492(Disconnected position)

Note: If users want to change the horizontal connection into vertical connection,they only have to change the busbar of N、B phases to A、C phases
P-015 Air Circuit Breaker NA8G

NA8G-4000 Fixed type , outline dimension


238.5

25
datum line 2

133
163.5

10.5

25
13

11 200(3P) 200 11 246 44 7


315(4P) datum line 1 330

NA8G-4000 Fixed type ,size of the hole to be drilled on the panel

371
328
150
330

311
268

4×Φ14
78

29.5
21.5

400(3P)
515(4P) 8×Φ6
432.5(3P)
547.5(4P)
datum line 1

NA8G-4000(In=2500A) Fixed type (only horizontal connection is provided by the factory)

33 C

78 50 φ11
14

29

C
25

115 115 115


133

datum line 1
25
47.5

Note: If users want to change the horizontal connection into vertical connection,they only have to rotate the busbars by 90°

NA8G-4000(In=2500A) Fixed type (vertical connection has to be made by users themselves)

33 25 C

C
78
55

115 115 115

datum line 1
25
21

Note: If users want to change the horizontal connection into vertical connection,they only have to rotate the busbars by 90°
NA8G Air Circuit Breaker P-016

NA8G-4000 Fixed type , outline dimension(Front connection)

15 61
C
10
C 78 25 φ11
15

15
155
388

115 115 115

datum line 1
155

C
67.5
15

NA8G-4000(In=3200A~4000A) Fixed type (only horizontal connection is provided by the factory)

C
33
Φ11 100 25

29
C
14
25

126 126 126


133

datum line 1
25
47.5

Note: If users want to change the horizontal connection into vertical connection,they only have to change the busbar of N、B phases to A、C phases

NA8G-4000(In=3200A~4000A) Fixed type (vertical connection has to be made by users themselves)

C C
25

33
14
Φ11
100

115 115 115


57

datum line 1
25
49

Note: If users want to change the horizontal connection into vertical connection,they only have to change the busbar of N、B phases to A、C phases
P-017 Air Circuit Breaker NA8G

NA8G-6300 In=(4000A~5000A) Draw-out type


Size of the hole to be drilled on the panel

710.5(4P)

595.5(3P) 217.5 391


240

Datum line 2

258
199

7
Datum line 1

308

371
328

φ14
155
175

268
2×11×17
376

Datum line 2
145

18
97

Φ11

162.5

21.5
703(3P)
47

10×Φ6

Datum line 1
Datum line 1
818(4P)
Size of the hole to be drilled on the panel

NA8G-6300 In=(6300A) Draw-out type


Size of the hole to be drilled on the panel

710.5 217.5 391 7


240

Datum line 2

258
199

Datum line 1

308

371
328

φ14
155
175

268

2×11×17
Datum line 2
376
145

18
97

Φ11

162.5
21.5

818
47

10×Φ6

Datum line 1
Datum line 1

Size of the hole to be drilled on the panel


NA8G Air Circuit Breaker P-018

NA8G-6300(In=4000A~5000A) Draw-out type


(Vertical connection has to be made by users themselves)

29 C
C Datum line 1
115 N pole
Φ11 103 129.5 105 142 105 142 105
30
125

25
57

14
10.5

Note: If users want to change the horizontal connection into vertical connection,
they only have to additionally install vertical busbars. C
NA8G-6300(In=4000A~5000A) Draw-out type (Only horizontal connection is provided by the factory)

C
C
N pole
28×Φ15
100 155 210

20
40
103
30
112

55 52.5
182.5 246.5 194 164
92

Datum line 1

Note: If users want to change the horizontal connection into vertical connection,
they only have to additionally install vertical busbars.

NA8G-6300(In=6300A) Draw-out type (Vertical connection has to be made by users themselves)

14 C C
Datum line 1
115
Φ11 103 130 207 130 207 130
30
125

25
57

29
10.5

Note: If users want to change the horizontal connection into vertical connection,
they only have to additionally install vertical busbars.

NA8G-6300(In=6300A) Draw-out type (Only horizontal connection is provided by the factory)

C C
180 259.5
20
40
103
30

24×Φ15
112

80 65
316.5 258.5 140
92

Datum line 1

Note: If users want to change the horizontal connection into vertical connection,
they only have to additionally install vertical busbars.
P-019 Air Circuit Breaker NA8G

6. Secondary circuit wiring

Connection diagram for the secondary circuit of NA8G-1600 with standard type intelligent controller

Fault indicator
N A B C

HL2 HL3 HL4


HL1 SB2 SB1

XT 3 4 6 8 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55 FU

Breaker body

M L1
QF F DT Q/QY
Intelligent controller
SAL
AX Control power

SA L2(N)
TA

FU
XT 1 2 5 7 9 10 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56

+DC24V -
S

Power
Energy
-driven ON OFF
Main circuit Intelligent controller Open Close Under storage energy indication indication Auxiliary contact available for users AC auxiliary contact for standby application
voltage indication storage

FU—fuse
DT——closing electromagnet F——shunt release Q/QY—under voltage release
TA—current transformer
SA——travel switch M——energy storage motor AX—auxiliary contact
SB1~SB2——pushbutton HL1~HL4——indicator light XT—connection terminal
QF——breaker S——power module SAL—sensitive switch

# #
1 and 2: input (terminals) for intellectual controller auxiliary power supply
#
4, #5 and #6: faulty tripping contact output (#5 is the common terminal, AC250V 5A)

The auxiliary contact modes for customer use

Ⅰ Four switch contact Ⅱ Five switch contact Ⅲ Six switch contact Ⅳ Three open and
(acquiescence) three close contact

38 39 41 42 44 45 47 48 38 39 41 42 44 45 47 48 50 51 38 39 41 42 44 45 47 48 50 51 53 54 38 40 42 44 46 48

37 40 43 46 37 40 43 46 49 37 40 43 46 49 52 37 39 41 43 45 47

Notes: 1. Four switch contact is the normal auxiliary contact mode.When special order is made for alternating current, five switch contact,six switch contact,
Q three open and three close contact can be selectedadditionally. Four switch contact is the only mode in case of direct current.
2. All control voltage of frame 1600 has to be put to #1 and #2 after the power module inputs DC24V.
3. The wiring for the part indicated by dashed lines shall be made by users.
NA8G Air Circuit Breaker P-020

Connection diagram for the secondary circuit of NA8G-3200 to 6300 with standard type intelligent controller

Fault indicator
N A B C

HL2 HL3 HL4


HL1 SB2 SB1

XT

Breaker body
3 4 6 8 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
FU

C
M L1
QF F DT Q/QY
Intelligent controller
SAL
AX Control power
SA L2(N)
TA

FU
XT 1 2 5 7 9 10 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56

3200 and 6300 frame controller power supply: AC230V and AC400V
+DC24V -
S
Frame 3200, 6300 shell controller power supply: DC220V,DC110V;
Power
Under Energy -driven ON OFF
Main circuit Intelligent controller Open Close storage
voltage indication energy indication indication
Auxiliary contact available for users AC auxiliary contact for standby application
storage

DT——closing electromagnet F——shunt release Q/QY—under voltage release FU—fuse


SA——travel switch M——energy storage motor XT—connection terminal TA—current transformer
SB1~SB2——pushbutton HL1~HL4——indicator light AX—Auxiliary contact
QF——breaker S——power module SAL—sensitive switch

#
1 and #2: input (terminals) for intelligent controller auxiliary power supply
#
4, #5 and #6: faulty tripping contact output (#5 is the common terminal, AC250V 5A)

The auxiliary contact modes for customer use

Ⅰ Four switch contact Ⅱ Five switch contact Ⅲ Three open and Ⅳ Four open and
(acquiescence) three close contact four close contact

38 39 41 42 44 45 47 48 38 39 41 42 44 45 47 48 50 51 38 40 42 44 46 48 38 40 42 44 46 48 50 52

37 40 43 46 37 40 43 46 49 37 39 41 43 45 47 37 39 41 43 45 47 49 51

Notes: 1. Four switch contact is the normal auxiliary contact mode. When special order, five switch contact, three open and three close contact, four open
and four close contact can be selected additionally.
# #
2. When the controller voltage of frame 3200 and 6300 is AC230V/400V, it can be directly put to 1 and 2; if the voltage is DC220V/110V, it has to be
put to #1 and #2 after the power module outputs DC24V.
3. The wiring of the part indicated by dashed lines shall be made by users.
P-021 Air Circuit Breaker NA8G

Connection diagram for the secondary circuit of NA8G-1600 with multifunctional type intelligent controller

FU
L1
N
PE

L N PE
Device Net Profibus-DP
PSU-1 power module
- + - + - + - +
ST-DN ST-DP
module module
12 13 14 15 16 17 18 19

N A B C
1 2 3 4 5 6 7 8
+ + COM D11 D12 D13
DC24V RU-1 relay module
Fault indicator SB2 SB1

D01 D02 D03

HL1 12 13 14 15 16 17 HL2 HL3 HL4

Green Red

XT 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55

PE
QF M
D14 F DT Q/QY
Intelligent controller
SAL D13 D15 D16
AX
SA
TA
Breaker body

XT 1 2 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56

controller power suply:AC220V, AC380V


+DC24V-
S

controller power suply:DC220V, DC110V


Power
Under Energy -driven ON OFF
Main circuit Intelligent controller Open Close voltage
storage energy
indication indication
Auxiliary contact available for users AC auxiliary contact for standby application
indication storage

DT——closing electromagnet F——shunt release Q/QY—under voltage release FU—fuse


SA——travel switch M——energy storage motor XT—connection terminal TA—current transformer
SB1~SB2——pushbutton HL1~HL4——indicator light ST-DP —communication module RU-1—relay module (optional)
QF——breaker S——power module ST-DN—communication module
PSU-1——power module (optional) AX—Auxiliary contact SAL—sensitive switch

#
1 and #2: input (terminals) for intelligent controller auxiliary power supply
#
3:PE
# # # #
4, 5 and 6: faulty tripping contact output ( 5 is the common terminal, AC250V 5A)
#
7, #8 and #9: auxiliary contact output (#8 is the common terminal, AC250V 5A)
# # # #
10, 11 and 12: auxiliary contact output ( 11 is the common terminal, AC250V 5A)
# #
14 and 15:RS485 communication interfaces (in case of communication type)
#
16, #17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V, 5A)
# # # #
20, 21, 22, and 23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V)
# #
24 and 25: to be externally connected to the mutual inductor input

The auxiliary contact modes for customer use

Ⅰ Four switch contact Ⅱ Five switch contact Ⅲ Six switch contact Ⅳ Three open and
(acquiescence) three close contact

38 39 41 42 44 45 47 48 38 39 41 42 44 45 47 48 50 51 38 39 41 42 44 45 47 48 50 51 53 54 38 40 42 44 46 48

37 40 43 46 37 40 43 46 49 37 40 43 46 49 52 37 39 41 43 45 47

Notes: 1. Notes: 1. Four switch contact is the normal auxiliary contact mode. When special order is made for alternating current, five switch contact,six switch contact,
three open and three close contact can be selected additionally. Four switch contact is the only mode in case of direct current.
2. The wiring of the part indicated by dashed lines to be made by users.
NA8G Air Circuit Breaker P-022

Connection diagram for the secondary circuit of NA8G-3200 and 6300 with multifuctional type itelligent controller.

FU
L1
N
PE

L N PE
Device Net Profibus-DP
PSU-1 power module
- + - + - + - +
ST-DN ST-DP
module module
12 13 14 15 16 17 18 19

N A B C
1 2 3 4 5 6 7 8
+ + COM D11 D12 D13
DC24V RU-1 relay module
Fault indicator SB2 SB1

D01 D02 D03

HL1 12 13 14 15 16 17 HL2 HL3 HL4

XT 3 4 6 8 10 12
Green Red

14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
C
PE
QF M
D14 F DT Q/QY
Intelligent controller
SAL D13 D15 D16
AX
SA
TA
Breaker body

XT 1 2 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56

Frame 3200 and 6300 shell controller power supply: AC230V and AC400V
+DC24V-
S

Frame 3200, 6300 shell controller power supply: DC220V,DC110V;

Power
Under Energy
-driven ON OFF Auxiliary contact
Main circuit Intelligent controller Open Close voltage
storage energy
indication indication available for users
AC auxiliary contact for standby application
indication storage

DT——closing electromagnet F——shunt release Q/QY—under voltage release FU—fuse


SA——travel switch M——energy storage motor XT—connection terminal TA—current transformer
SB1~SB2——pushbutton HL1~HL4——indicator light ST-DP —communication module RU-1—relay module (optional)
QF——breaker S——power module ST-DN—communication module
PSU-1——power module (optional) AX—Auxiliary contact SAL—sensitive switch

#
1 and # 2: input (terminals) for intelligent controller auxiliar y power supply
#
3:PE
# # # #
4, 5 and 6: faulty tripping contact output ( 5 is the common terminal, AC250V 5A)
#
7, #8 and #9: auxiliar y contact output ( #8 is the common terminal, AC250V 5A)
# # # #
10, 11 and 12: auxiliar y contact output ( 11 is the common terminal, AC250V 5A)
# #
14 and 15:RS485 communication interfaces (in case of communication type)
#
16, #17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V, 5A)
#
20, #21, #22, and #23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V)
#
24 and #25: to be externally connected to the mutual inductor input

The auxiliar y contact modes for customer use

Ⅰ Four switch contact Ⅱ Five switch contact Ⅲ Three open and Ⅳ Four open and
(acquiescence) three close contact four close contact

38 39 41 42 44 45 47 48 38 39 41 42 44 45 47 48 50 51 38 40 42 44 46 48 38 40 42 44 46 48 50 52

37 40 43 46 37 40 43 46 49 37 39 41 43 45 47 37 39 41 43 45 47 49 51

Notes: 1 Four switch contact is the normal auxiliary contact mode. When special order, five switch contact, three open and three close contact, four open and four close
contact can be selected additionally.
# # #
2. When the controller voltage of the 3200 and 6300 shells is AC230V/400V, it can be directly put to 1 and 2;if the voltage is DC220V/110V, it has to be put to 1
#
and 2 after the power module inputs DC24V.
3. The wiring of the part indicated by the dashed lines shall be made by users.
P-023 Air Circuit Breaker NA8G

7. Intelligent controller and protective characteristics


7.1 User interface of the standard type controller

10

11

12

13

14

15

16

1 LED window LED window capable of showing the current for each phase, various setting parameters,
rated current, fault current, tripping time, and the like
2 “ Ig ” limp Single-phase earthing fault indicator

3 “ IR ” limp Long time-delay overcurrent fault indicator


4 “ Isd ” limp Short-circuit short time-delay overcurrent

5 “ Ii ” limp Short-circuit instantaneous overcurrent fault indication

6 “ MENU ” Pushbutton Successively access to submenus at various levels by pressing the MENU key
To inquire the current for each phase at present:
recurrently select the contents in the menus at various levels

7 “ “ Pushbutton Return to previous menu; the intelligent controller software is reset;

8 “ RESET ” Pushbutton RESET key must be pressed after the encoder switch position is adjusted;
the intellectual controller faulty tripping results in fault memory which
can be cleared only by pressing the RESET key;

9 “ IR ” Knob switch There are (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 0.98, 1.0)In,
nine settings altogether, for the current multiple setting of long time-delay overcurrent.

10 “ tR ” Knob switch There are (1, 2, 4, 8, 12, 16, 20, 24, 30)s, nine settings altogether,
for the time delay time setting of long time-delay overcurrent in case of 6IR.

11 “ Isd ” Knob switch There are (1.5, 2, 2.5, 3, 4, 5, 6, 8, 10)Ir, nine settings altogether,
for the current multiple setting of short-time short time-delay.

12 “ tsd ” Knob switch For the short-circuit short time-delay time setting, there are nine settings:
2
the inverse time limit, i.e., I t on(0.1, 0.2, 0.3, 0.4)s, the definite-time limit,
2
i.e., I t OFF (0.1 0.2 0.3 0.4)s and X, i.e., closing the short time-delay

13 “ Ig ” Knob switch There are (A, B, C, D, E, F G, H, J), nine settings altogether, for the current multiple setting
of single-phase earthing.

14 “ test ” Pushbutton Button for simulating instantaneous tripping test

15 “ tg ” Knob switch For the time setting of single-phase earthing, there are nine settings: the inverse time limit,
2 2
i.e., I t on(0.1, 0.2, 0.3, 0.4)s, and the definite-time limit, i.e., I t OFF(0.1 0.2 0.3 0.4)s, and X,
i.e., closing the single-phase earthing.

16 “ Ii ” Knob switch Short-circuit instantaneous current multiple setting.


NA8G Air Circuit Breaker P-024

7.2 Default interface and operation method for the standard type controller
The default interface for the standard type controller is described as follows: (The current for each phase to be selected
by pressing "→")
Press "MENU"key once to go to the status for parameter query as follows, and then press"→"to go to query
the setting parameter of quadruple overcurrent protection.

Default interface of the standard type controller Status for parameter query─setting current of long time-delay

Press "MENU" key twice to go to the status for fault query as follows,show the latest fault information:

Status for fault query─tripping current Status for fault query─tripping time

Press "TEST" key to go to the status for simulating tripping test in case of 6IR, and after tripping as follows:

Status of simulating tripping test─simulating current Status of simulating tripping test─simulating time

Press "RESET"key at any status to go back to default interface.


P-025 Air Circuit Breaker NA8G

7.3 User interface of the multifunctional controller

5
3
6

10

11

13 12

1 Brand "CHINT" Brand

2 LED window LCD window capable of showing the current for each phase, various setting parameters, rated current,
fault current, tripping time and the like

3 SET key Switch to the set default menu (left arrow key, when it is necessary to move leftwards or rightwards
for the set interface).

4 UP key Move the box select menu under the current menu to change the position of said box upwards,
and perform the setting of the parameter ADD in the parameter setup menu.

5 RETURN key Exit the current menu and go to the previous menu, or cancel the value of the current setup parameter.

6 ACK key Go to the next menu of the currently selected select box (go to the set state under the set interface, a
nd exit the set state by pressing the key again).

7 DOWN key Move the box select menu under the current menu to change the position of said box downwards,
and perform the setting of the parameter SUBTRACT in the parameter setup menu.

8 INQUIRY key Switch to the inquiry default menu (right arrow key, when it is necessary to move leftwards
or rightwards for the set interface).

9 “ IR “ limp Long time-delay overcurrent fault indicator

10 “ Isd “ limp Short-circuit short time-delay overcurrent fault indicator

11 “ test ” Button for simulating instantaneous tripping test

12 “ Ii “ limp Short-circuit instantaneous overcurrent fault indicator

13 “ Ig “ limp Single-phase earthing fault indicator


NA8G Air Circuit Breaker P-026

Default interface for the multifunctional controller


7.4 Default interface and menu structure for the multifunctional
controller
1002A
N A B C
The multifunctional controller provides 4 title menus 150

(measurement menu, parameter setup menu, protection 100


parameter setup menu, and history record and maintenance 50
menu) and 1 default menu.
0

7.4.1 Structure of the measurement menu

Primary menu Secondary menu Third menu Fourth menu Fifth menu
Ia= 1000A
Ia
Ib
Ic
Ib= 1001A
Ic= 998A
C
In In= 0A
Ig= 0A or I△n=0.00A
Ia= 1300A
Ib= 1400A
Instantaneous value
Maximum Ic= 1380A
In= 200A
Ig= 0A or I△n=0.00A
Ia= 3%
Magnitude of currentⅠ Unbalance rate Ib= 5%
Ic= 1%
Current thermal capacitance 100%
15min
Ia= 1000A
Real-time value
Ia,Ib, Ib= 1000A
Ic,In
Ic= 998A
In= 0A
Required value Ia= 1050A
Ib= 1040A
Maximum
Ic= 1010A
In= 0A
Uab= 380V
Ubc= 380V
Instantaneous value Uca= 380V
Uan= 220V
Voltage U Ubn= 220V
Ucn= 220V
Mean value Uav= 380V
Unbalance rate 0%
Phase sequence A,B,C
FrequencyF 50Hz
EP= 200kWh

Total electric energy EQ= 10kvarh


ES= 200kVAh
EP= 200kWh
Electric energy E Input electric energy
EQ= 200kvarh
EP= 0kWh
Output electric energy
EQ= 0kvarh
Electric energy reset Reset
P-027 Air Circuit Breaker NA8G

Primary menu Secondary menu Third menu Fourth menu Fifth menu
P= 660kW
P, Q, S Q= 0kvar
S= 660kVA
-1.00
Perceptual
Power factor PFa= 1.00
PFb= 1.00
PFc= 1.00
Instantaneous value Pa= 220kW
Pa, Qa, Sa Qa= 0kvar
Sa= 220kVA
Pb= 220kW
Power P
Pb, Qb, Sb Qb= 0kvar
Sb= 220kVA
Pc= 220kW
Pc, Qc, Sc Qc= 0kvar
Sc= 220kVA
P= 660kW
P, Q, S Q= 0kvar
S= 660kVA
Required value P= 661kW
Q= 2kvar
Maximum
S= 662kVA
Reset(+/-)
Ia

Ib
Ia,Ib
Ic,In
Ic

In
Waveform

Uan

Uan,Ubn Ubn
Ucn
Ucn

Ia= 1000A
I(A) Ib= 1000A
Ic= 1000A
In= 1000A
Uab= 380V
Base form
Ubc= 380V
U(V) Uca= 380V
Harmonic H Uan= 220V
Ubn= 220V
Ucn= 220V
Ia= 0.0%
Ib= 0.0%
I(%)
Ic= 0.0%
In= 0.0%
Uab= 0.0%
THD
Ubc= 0.0%
Uca= 0.0%
U(%)
Uan= 0.0%
Ubn= 0.0%
Ucn= 0.0%
Ia= 0.0%
Ib= 0.0%
thd I(%)
Ic= 0.0%
In= 0.0%
NA8G Air Circuit Breaker P-028

Primary menu Secondary menu Third menu Fourth menu Fifth menu
Uab= 0.0%
Ubc= 0.0%
Uca= 0.0%
thd U(%)
Uan= 0.0%
Ubn= 0.0%
Ucn= 0.0%

Ia FFT THD=0.0%
0.0%
Ia(3, 5, 7...31)
3 5 7 9 11...31)

Ib FFT THD=0.0%
0.0%
Ib(3, 5, 7...31)
I(3, 5, 7...31)

C
3 5 7 9 11...31)

Ic FFT THD=0.0%
0.0%
Ic(3, 5, 7...31)
3 5 7 9 11...31)

In FFT THD=0.0%
0.0%
In(3, 5, 7...31)
3 5 7 9 11...31)

FFT Uab FFT THD=0.0%


0.0%
Uab(3, 5, 7...31)
3 5 7 9 11...31)

Ubc FFT THD=0.0%


0.0%
Ubc(3, 5, 7...31)
3 5 7 9 11...31)
U(3, 5, 7...31)
Ubc FFT THD=0.0%
0.0%
Ubc(3, 5. 7...31)
3 5 7 9 11...31)

Uca FFT THD=0.0%


0.0%
Uca(3, 5, 7...31)
3 5 7 9 11...31)

7.4.2 Structure of the parameter setup menu

Primary menu Secondary menu Third menu Fourth menu Fifth menu

Setting of the System type =3Φ4W 4CT


measurement meter Line incoming pattern =Wire to enter from the upper port
Test type =three section protection
Test tripping Test parameter =I:9999A
Test initiation =start
Remote locking Remote locking =unlock
Test & lock
Parameter locking
Parameter locking
=locking
Parameter locking
(input) user password User password (change)
=0000 =0000

Address =3
Communication setting
Baud rate =9.6K

=DO1
Function setting
=regional interlocking

=DO1
Executive mode =N.O. pulse
I/O setting
=360s

I/O state
I/O state DO1 DO2 DO3 DI1
1 1 1 1

7.4.3 Structure of the protection parameter setup menu

Primary menu Secondary menu Third menu Fourth menu Fifth menu
Ir e.g.: =1000A=100%In
Current protection e.g.: =ON
Current protection Long time delay
Delay time e.g.: =C1,Is@6Ir
Cooling time e.g.: =3h
P-029 Air Circuit Breaker NA8G

Primary menu Secondary menu Third menu Fourth menu Fifth menu
e.g. =5000A=5.0Ir
Definite-time limit Operating current
e.g. =0.1s
Short-time delay
e.g. =2000A=2.0Ir
Inverse-time limit Delay time
e.g. =C1,0.Is@6Ir
Instantaneous Operating current e.g. =10000A=10.0In
Neutral phase protection Neutral phase protection e.g. =200%
Operating current e.g. =800A
Ground protection Delay time e.g. =0.4s
Coefficient of earthing e.g. =6.0
Current protection Starting current e.g. =600A
Starting time e.g. =0.1s
Grounding alarm
Return current e.g. =100A
Return time e.g. =0.1s
Operating current e.g. =8.0A
Leakage protection
Setup delay time e.g. =0.75s
Starting current e.g. =5.0A
Starting time e.g. =0.1s
Electric leakage alarm
Return current e.g. =4.0A
Return time e.g. =0.1s
Executive mode e.g. =I the first method
Unloading value 1 e.g. =800A
Load Monitoring Unloading time 1 e.g. =50%tr
Unloading value 2 e.g. =700A
Unloading time 2 e.g. =25%tr
Executive mode e.g. =Alarm
Startup value e.g. =200V
Under voltage Starting time e.g. =0.2s
Return value e.g. =320V
Return time e.g. =60.0s
Executive mode e.g. =Alarm
Startup value e.g. =480V
Voltage protection Over voltage Starting time e.g. =1s
Return value e.g. =400V
Return time e.g. =60.0s
Executive mode e.g. =Alarm
Startup value e.g. =10%
U unbalanced Starting time e.g. =1s
Return value e.g. =5%
Return time e.g. =60.0s

7.4.4 Structure of the history record and maintenance menu

Primary menu Secondary menu Third menu Fourth menu Fifth menu
Current alarm e.g. phase sequence alarm, Inverse power alarm, over frequency alarm...

Total number of times e.g.: 300


Number of operations
Number of operations e.g.: 219(ACK key, reset)

Total wear e.g.: 120


Contact wear
lContact wear e.g.: 20(ACK key, reset)

Product information Zhejiang CHINT electrics co., LTD


Under voltage tripping
T=0.20s
Umax=0V
11:24:59
e.g.: 6/17
Tripping record 1 Under voltage tripping
2004/06/17 F=0.00Hz
Uab= 0V
Ubc= 0V
Uca= 0V
...... ......
NA8G Air Circuit Breaker P-030

Primary menu Secondary menu Third menu Fourth menu Fifth menu
A phase short-circuit definite-time limit
T= 0.4s
I= 4300A
15:28:25
e.g.
Tripping record 8 (for) short-circuit definite-time limit 5/30
2004/05/30 Ia= 4300A
Ib= 4200A
Ic= 4000A
In= 150A
Di input alarm
e.g.
Di1
1 DI (for) DI input alarm
2004/07/16 2004/07/16

Alarm logging ......


20:38:45
......
Under voltage alarm
C
e.ge
8 Under voltage alarm Umax= 0V
2004/06/20 2004/06/20
Note: Up to 8 times of alarms can be recorded
22:29:40

e.g. local switch on


1 (for) local switch on 2002/06/18
2002/06/18
9:30:56
Position changing record ...... ......

e.g. Test tripping


8 (for) testing tripping
2002/06/15 2002/06/15
Note: Up to 8 times can be recorded 10:30:20

Notes: a. The actual menu will very depend on the function selected by the user.
b. The controller starts screensaver automatically 10min later.

7.5 List of the controller functions


Standard configuration

Standard type (M type) Multifunction type (H type)

1.Quadruple overcurrent protection (for long time-delay, 1.Quadruple over current protection (for long time-delay,short-circuit short
short-circuit short time-delay,instantaneous,earthing); time-delay,instantaneous,earthing); earthing corresponds to vector sum
earthing corresponds to vector sum (T type); (T type);
2.Parameter setup: fixed value setting position setting function 2.Parameter setup: fixed value keyboard setting function;
3.Current measurement 3.Current measurement function;
4.Test function; 4.Current unbalance rate measurement function;
5.Fault recording function; 5.Two test functions:
6.Self-diagnostic function; (1)Instantaneous tripping test simulated on the panel;
7.MCR make/break function; (2)Triple over current, grounding/leakage and operating time tests
8.Human-machine interface: 33×22 LED; simulated by software;
6.Fault recording function: 8 times of failures can be recorded;
7.Self-diagnostic function
8.MCR make/break function
9.Communication function: MODBUS protocol;
10.Alarm logging function;
11.Recording number of operations;
12.Contact wear
13.Position changing record
14.Human-machine interface: 28×43 LCD;
15.Heat capacity measurement
P-031 Air Circuit Breaker NA8G

Heat capacity measurement

Multifunction type (H type)


Standard type (M type)
P Function H Function

1.Voltage measurement; 1.Voltage measurement;


2.Voltage unbalance measurement; 2.Voltage unbalance measurement;
3.Frequency measurement; 3.Frequency measurement;
4.Phase sequence measurement; 4.Phase sequence measurement;
5.Electric energy measurement; 5.Electric energy measurement;
6.Power measurement; 6.Power measurement;
7.Power factor measurement; 7.Power factor measurement;
8.Earth-current grounding protection; 8.Earth-current grounding protection;
None
9.Leakage protection; 9.Leakage protection;
10.Load monitoring function; 10.Load monitoring function;
11.Quadruple D0 output function; 11.Quadruple DO output function;
12.DI input function; 12.DI input function;
13.Regional interlocking function; 13.Regional interlocking function;
14.Under and over voltage protection; 14.Under and over voltage protection;
15.Measurement of harmonic current;
16.Neutral phase protection

7.6 Characteristic parameters of the standard type intelligent controller

Overcurrent protection characteristics

10000

5000

IR=(0.4-1)In
1000

500

200
TR=(1~30)s
100

50

20
T(s) 10
2
I t ON
5
Isd=(1.5~10)IR
2
Isd=(1.5~10)IR
1
2
I t OFF
0.5

0.2
0.1
Ii=(2~15)In
0.05

0.02
0.01
0.2 0.3 0.5 0.6 0.8 1 2 3 4 5 8 10 20 30 40 50 60 80 1.5 2 3 4 5 6 8 10 20 30

X IR

Neutral line (earthing) fault protection characteristic

10000

5000

Ig=(0.2-1)In
1000 MAX 1200A
500 MIN 120A

200
100

50
20
T(s) 10
I2 ON
5

1
0.5

0.2
0.1
I2 t OFF
0.05
0.02
0.01
0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30

X In
NA8G Air Circuit Breaker P-032

7.6.1 Long time-delay overcurrent protection characteristic

Rated current range [IR] Error Current [I] Operating time [tR(s)] Time error
≤1.05I R No actuation within 2h
>1.30I R <1h and then actuate
(0.4~1)In ±10% 1.5IR 16 32 64 128 192 256 320 384 480
2.0IR 9 18 36 72 108 144 180 216 270 ±15%
6.0IR 1 2 4 8 12 16 20 24 30

Explanation for parameter setting


Current of long time-delay overcurrent protection: IR=(0.4-
0.5-0.6-0.7-0.8-0.9-0.95-0.98-1)×In, optional.

The long-time delay tripping time represents the inverse-


time limit characteristic, and nine optional settings are
readily available for tripping time in case of 6IR:TR=(1-2-4-8-
C
12-16-20-24-30)s.

For setting, insert a small slotted screwdriver to the knob


groove as shown in the right drawing, gently turn it to make
the arrow of the knob point at the current and time set as Example 1: If it is known that in condition of I=6IR,
required. As shown in the figure, the over current long time The tripping time setting value is 2s,
delay protection current setting value IR=0.6In, and the delay and now the circuit current I=1.5IR,
tripping time is 2s (in the condition of 6IR). then the actual tripping time TR can be worked out by:
(1.5IR)2×TR=(6IR)2×2. The answer is obtained as TR=32s
7.6.2 Short-circuit short time-delay overcurrent protection characteristic.

Rated current range [Isd] Error Current [I] Operating time [tsd(s)] Time error

<0.85Isd No action
>1.15Isd Time-delay action
I 2t OFF 0.1 0.2 0.3 0.4
(1.5~10)IR
±15% 2
I t ON ±15%
+OFF(Power off)
0.1 0.2 0.3 0.4
I>10IR
2
I t ON
2 2
anti-time-limit delay:I Tsd=(10I R) tsd
I≤10IR

Explanation for parameter setting


Current of short-circuit short time-delay overcurrent
protection : Isd=(1.5-2-2.5-3-4-5-6-8-10)×IR, optional.

There are nine settings for the short-circuit short time-delay


tripping time, wherein 4 settings represent the definite-time
limit characteristic (i.e., I2t OFF), 4 seetings the inverse-time
limit characteristic, and 1 setting the function of closing the
short- circuit short time-delay (X).

When the tripping time is set as definite-time limit operating


characteristic (i.e., the arrow points at the off area), the Example 2: If it is known that the short-time delay
tripping time can be selected as tsd=(0.1s-0.2s-0.3s-0.4s-x (i.e., setting current is Isd=3IR,
the function of closing the short-time delay).
then the tripping time is set as tsd=0.2s
When the tripping time is set as inverse-time limit operating in the setting position of inverse
characteristic(i.e., I2t ON), there are two cases: ①the case of time limit (12t ON). Now the current is 7IR
1>1.15Isd and 1>10IR represents the definite-time limit; ② in the line current, then the short-time delay tripping time
the case of 1>1.15Isd and I≤10IR represents the inverse-time can be worked out by calculation:
limit characteristic and the actual tripping time is calculated 1.5Isd=1.15×3IR=3.45IR
2 2
according to the formula I Tsd=(10IR) tsd, where in I is the line Then I=7IR>1.15Isd
current, Tsd the actual tripping time, and tsd the setting And because I=7IR<10IR
tripping time. The method for setting the current and time So accotding to I2×Tsd=(10I)2tsd
for the short-circuit short time-delay overcurrent protection (7IR)2×Tsd=(10IR)2×0.2
is similar to that for over long time-delay overcurrent Tsd=0.41s
protection. As shown in the figure, the current for the short-
circuit short time-delay overcurrent protection is 3IR, and the
tripping time is set as tsd=0.2s in the setting position of
inverse time limit (I2t ON).
P-033 Air Circuit Breaker NA8G

7.6.3 Short-circuit instantaneous overcurrent protection

Rated current range [Ii] Error Line current [I] Operating Characteristics

(2~15)In ≤0.85Ii no-action


+OFF(Power off) ±15% >1.15Ii action

Explanation for parameter setting

Current of short-circuit instantaneous over current protection:


Ii=[2-3-4-6-8-10-12-15-OFF]×In, optional. Ii
8
The method for setting the current of short-circuit 6 10
4 12
instantaneous
3 15
2 Off
overcurrent protection is similar to that for long time-delay
overcurrent protection setting. As shown in the figure, the
instantaneous overcurrent protection current setting value is
8In.

7.6.4 Single-phase earthing fault protection

Rated current range [Ig] Error Line current [I] Operating time [tg(s)] Time (delay) error

<0.9Ig no-action
>1.1Ig time-delay action
I2T OFF 0.1 0.2 0.3 0.4
(A~J)In
±10% I2T ON
+OFF(Power off)
0.1 0.2 0.3 0.4 ±15%
I>J
2
I T ON
anti-time-limit delay I2Tg=(J)2tg
I≤J

Meaning of Ig

Rated current In A B C D E F G H J Note


In≤400A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 ×In
400A<In≤1200A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 ×In
1200A<In 500A 640A 720A 800A 880A 960A 1040A 1120A 1200A

Explanation for parameter setting

Current of single-phase earthing protection : Ig=(A-B-C-D-E- Tg


Ig
F-G-H-J)×In, optional. E (s)
D F .4 .4 . 3
C G .3 .2
There are nine setting positions for the protective delay H
B .2 .1
tripping time, wherein 4 settings represent the definite-time A J X
.1
2 ON Off
limit characteristic (i.e., I t OFF), 4 settings the inverse-time ×I n I2t

limit characteristic (I2t ON), and 1 setting the function of


closing the single-phase earthing protection (X).

When the tripping time is set as definite-time limit operating


Example 3: If it is known that the single-phase earthing
characteristic (i.e., the arrow points at the OFF area), the
protection setting current for the intelligent controller with
tripping time can be selected as tg=0.1s-0.2s—0.3s-0.4s-x
rated current of In=800A is as the setting position of C, the
(i.e., the function of closing the single-phase earthing
tripping time is set as the inverse time limit 0.4s.
protection).
Now there is a failure in the circuit, the circuit current I=400A,
When the tripping time is set as inverse-time limit operating then the actual tripping time can be worked out; it can be seen
2
characteristic (i.e., I t ON), there are two cases: from the table that the result is
① in the case of I>1.1Ig and I>J, the result of the automatic C=0.4
changeover process is the definite-time limit operating Ig=C×In=0.4×800=320A
So I=400A>1.1Ig
characteristic, tg=0.1s-0.2s-0.3s-0.4s; 2 2
According to the formula I Tg=(J) tg
② The case of the current meeting the condition of 1.1Ig<I≤J 2 2
(400) ×Tg=(1.0×800) ×0.4
represents the inverse-time limit characteristic and the actual
Tg=1.6s
tripping time is calculated according to the formula
2 2
I Tg=(J) tg.
Note: For the intelligent controller, the current settings for the
In the formula, I is the circuit current, Tg is the actual
long time-delay and the short-circuit short time-delay and the
operating time, J is the setting current, and tg is the setting
intantaueous overcurrent protection should not come across
tripping time.The method for setting the parameter is similar each other, and the condition of IR<Isd<Ii must be ensured.
to that for long time-delay current protection. As shown in
the figure, the single-phase earthing protection current is
C×In,and the tripping time setting is tg=0.4s in the setting
position of inverse time limit (I2t ON).
NA8G Air Circuit Breaker P-034

7.7 Explanation for auxiliary functions The controller still has the function of fault memory after reset
a. Explanation for test functions or de-energized to keep a latest historical event for post
When onsite adjustment, periodical inspection or overhaul is analysis. Only when there is a new fault again, the original
made with the controller supported by the breaker, breaking information is cleared with the current latest faulty data saved.
several times is necessary by using the test functions of the For the inquiry method, refer to the above explanation about
controller to check the cooperation of the controller and the fault display
breaker. With the breaker on, press the test key, and the
7.8 Explanation for display function
intelligent controller will trip instantaneously to cut off the
When the rated current is greater than or equal to 400A, the
breaker.
primary current shall not be lower than 0.4In for single phase,
Note: ① This function can be used only when onsite and 0.2In for three phases for normal operation of the
adjustment or overhaul for the breaker is made, and shall not breaker.
be used during the normal operation.

C
When the rated current is less than 400A, the primary current
② Each time before the controller is switched on, it is
shall not be lower than 0.8In for single phase,and 0.4In for
necessary to press the reset button in the upper position of
three phases for normal operation of the breaker.
the controller panel so that the breaker can be switched on
again for operation. Note: When the AC220V ST power module is energized, and
b. Explanation for fault memory the voltage falls to AC120V, there will be no display on the
controller

8. Accessories When the AC380V ST power module is energized, and the


voltage falls to AC200V, there will be no display on the
8.1 Under voltage release
controller
When the under voltage release is not energized, neither
power-driven nor manual operation can make the breaker on. a. Current display Error range for current display: ±5%
For the under voltage release, there are two varieties: b. Voltage display Error range for voltage display: ±1.5%
instantaneous and time-delay operations.The time for the
under voltage time-delay release is Inm=1600A, the time can
be selected from but not adjusted in the range of 0 – 7s;
Inm=3200A or 6300A, the time can be selected from but not
adjusted among 0.5s, 1s, 3s, and 5s. When, within 1/2 delay
time, the power voltage returns to 85%Ue or above, the
breaker will not get disconnected.

Operating characteristic:

Rated operational voltage Ue(V) AC230 AC400


Operating voltage(V) (0.35~0.7)Ue
Reliable switching voltage(V) (0.85~1.1)Ue
Reliable not-switching voltage(V) ≤0.35Ue
Under-voltage release Under-voltage release
Power dissipation(W) 20VA (Inm=1600A) (Inm=3200A, 6300A)

8.2 Shunt release


After the shunt release is energized, the breaker is switched off
instantaneously to allow remote operation.

Operating characteristic:

Rated control supply voltage Us(V) AC230 AC400 DC220 DC110

Operating voltage (V) (0.7~1.1)Us

Power consumption (W) 200VA 200W

Breaking time 50±10ms Shunt release Shunt release


(Inm=1600A) (Inm=3200A, 6300A)

8.3 Closing electromagnet


After the motor-driven energy storage is ended, energizing the
closing electromagnet will make the energy storage spring force of
the operating mechanism to be released instantaneously to rapidly
switch the breaker on.

Operating characteristic:

Rated control supply voltage Us(V) AC230 AC400 DC220 DC110

Operating voltage (V) (0.85~1.1)Us


Closing electromagnet Closing electromagne
Power dissipation (W) 200VA 200W
(Inm=1600A) (Inm=3200A, 6300A)
Closing time 50±10ms
P-035 Air Circuit Breaker NA8G

8.4 Motor-driven energy storage mechanism


The functions of motor-driven energy storage and automatic energy
re-storage after the breaker comes on are available to ensure that
the breaker can come on immediately after it gets

disconnected.Operating characteristic:

Rated control supply voltage Us(V) AC230 AC400 DC220 DC110


Operating voltage (V) (0.85~1.1)Us
(Inm=1600A) (Inm=3200A, 6300A )
Power dissipation (W) 75/150VA 75/150W
Energy storage time <4s
Frequency of operation At most 3 times in a minute

8.5 Auxiliary contact


Standard type:4 switch contact
Special type:5 switch contact
6 switch contact (Only for Inm=1600A, and not available for DC)
3 N.O. and 3 N.C.
(Inm=1600A) (Inm=3200A, 6300A )
4 N.O. and 4 N.C.(Inm=3200A and 6300A provided)

Technical parameters:

Rated voltage(V) Rated thermal current Ith(A) Rated control capacity


230
AC 6 300VA
400
DC 220 6 60W

8.6 Phases barrier


Phases barrier is installed between the phases of the line bank to improve the
insulating ability between the phases of the breaker

8.7 Key lock


The OFF pushbutton of the breaker can be locked in the position of depress,
and at this time, the breaker cannot be closed for operation; When the user
selects the option, the factory provides locks and keys; One breaker is provided
with one lock and one key for the lock; Two breakers are two provided with
locks and one key for the locks; Three breakers are provided with three same
locks and two same keys for the locks.
Note:
For the air circuit breaker with key lock, when the key has to be pulled out, it is
necessary to first press the OFF key, turn the key anticlockwise, and then pull
out the key.

8.8 Button locking device


It is used to lock the button for opening and closing the breaker with the
padlock used for such a purpose. (Padlock is provided by users themselves)

8.9 Doorcase
They are installed on the door of the distribution cabinet room to seal it with a
protection level of up to IP40.

8.10 “Disconnected” pation locking device for the draw-out.


For the “separation” position of the open frame (draw-out) circuit breaker, a
lock rod can be pulled out to lock the matter, and the breaker locked will be
unable to be turned towards the TEST or CONNECTION position. Padlocks have
to be provided by users themselves.

8.11 Three-position locking device for the draw-out.


After the breaker body is locked automatically in any working position, it is
necessary to turn the key to unlock the matter so that the break body can be
moved to the next working position by turning the handle. (this function
available for 3200 to 6300).

8.12 Door interlock


Door interlock for the breaker status
When the breaker is closed, the cabinet door must not be opened; when the
breaker is switched off, the cabinet door is allowed to be opened. Door
interlock for the breaker position When the breaker is in the position of
connection and test, the cabinet door must not be opened; when the breaker is
the separation position, the cabinet door is allowed to be opened.

8.13 Mechanical interlock


It can realize the interlock of two horizontal or vertical-installed,three poles or
four poles,drawout or fixed breakers.
NA8G Air Circuit Breaker P-036

9. Installation
9.1 Following items to be checked before installation Check the Listed below are the problems which users may encounter
label plate on the breaker panel to see if it is conform to the during installation, adjustment, and operation of the breaker,
specifications of the ordered goods. and the possible reasons and elimination methods.

a.Rated current 9.4 Installation of the fixed type breaker


b.Under voltage release voltage and delay time Place the breaker into the distribution cabinet, and fasten it
c.Shunt release voltage by using 4 pieces of M6(In=1600A) or M10(In=3200A or
d.Closing electromagnet voltage more) bolts and washers. The breaker shall be installed stably
e.Motor voltage with no additional mechanical stress to avoid damage of the
breaker or bad contact of the main bus bar.
9.2 Before installation, operation, maintenance and inspection,
you shall read this manual, and consult the manufacturer for 9.5 Installation of the open frame (draw-out) circuit breaker Take
questions, if any.

9.3 Preparations before installation Before the breaker is installed,


the breaker body out of the draw-out socket, and install the
socket in the distribution cabinet, and fasten it by using 4 C
pieces of M6(In=1600A) or M10(In=3200A or more) bolts and
check the insulation resistance of the breaker by using a
washers; the breaker shall be installed stably with no
1000V megohmmeter according to regulations; when the
additional mechanical stress to avoid damage of the breaker
surrounding media temperature is 25℃±5℃ and the relative
or bad contact of the main bus bar. After the work is
humidity 50% - 70%, the insulation resistance shall not be
completed, mount the body into the draw-out socket.
less than 20 megohm.
9.6 The specifications of the wiring copper bars for the primary
The place with the insulation resistance to be tested includes:
circuit of the breaker shall meet the copper bar specifications
the place between various phases and between various
used under the conditions of conventional heating in IEC/EN
phases and the frame when the breaker is closed; the place
60947-2
between in- and out- lines of various phases.
9.7 The breaker shall be grounded substantially.
10. Common faults and troubleshooting

No. Technical problems Possible causes


Diagnosis and trouble shooting
1 Check the breaking current and operating time on the intelligent controller
2 Analyze the operation of the load and power network
Overload fault tripping 3 Promptly find and shoot the trouble if overload is confirmed
(long time delay indicator on) 4 For lack of match between the actual running current and the long time delay
operating current, please modify the long time-delay operating current setting
for a proper match and protection according to the actual running current
5 Press the reset button to close the breaker again

1 Check the breaking current and operating time on the intelligent controlle
Short-circuit fault tripping 2 Promptly find and shoot the trouble if overload is confirmed
Breaker tripping (short time-delay or 3 Check the setting value of the intelligentcontroller
1 (fault indicator on) instantaneous overcurrent 4 Check to see whether the breaker is in good condition, and determine whether
indicator on) it can be closed for operation
5 Press the reset button to close the breaker again

1 Check the breaking current and operating time on the intelligent controller
2 Promptly find and shoot the trouble if it is confirmed that there is a earthing fault
Earthing fault tripping 3 If no earthing fault is detected, please determine whether the earthing fault
(earthing fault indicator on) current setting is proper, and can be well matched with the actual protection;
if not, the setting shall be modified
4 Press the reset button to close the breaker again

Under voltage release 1 Check to see if the power voltage is lower than 70%Ue
Tripping 2 Check the under voltage release and control unit for fault

Mechanical interlock action Check the working condition of two breakers equipped with mechanical interlock.
1 Whether the under voltage release has been energized
Under voltage release 2 Whether the power voltage is lower than 85%Ue
No attracting 3 Whether the under voltage release or control unit malfunctions,
if so, the release shall be replaced.
Reset button fails to reset Press the reset button to close the breaker again.

Open frame (draw-out) circuit


Breaker fails Check the contract status of the secondary circuit,
2 breaker fails to be put to the righ
to close and shoot the trouble, if any
t position by rocking

1 Check the motor control power supply and see if it is well


Open frame (draw-out) circuit breaker
providing power, and the voltage must be ≥85%Us
Bad contact for the secondary circuit
2 Check the status of the motor energy storage mechanism.

Put the open frame (draw-out) circuit breaker to the right position
Breaker fails to pre-store energy
by rocking (with it locked in the connected position)

1 Check the power voltage of the closing electromagnet,


and it must be higher than or equal to 85%Us
Closing electromagnet trouble
2 If there is any trouble in the closing electromagnet to enable the attracting,
it shall be replaced.
P-037 Air Circuit Breaker NA8G

No. Technical problems Possible causes

1 There may be short circuit current when the matter is switched on,
and in this case you shall find and shoot the trouble
2 Check to see if there is any overload current in the circuit,
Breaker trips Tripping immediately find and shoot the trouble
3
after closed Delay tripping 3 Check the setting value of the intelligent controller for reasonability,
and a re-setting process is necessary if not reasonable
4 Press the reset button to close the breaker again

1 Check the shunt release circuit for reliable connection


The breaker fails to break in
Breaker fails and the shunt release for trouble, and the release shall
4 power-driven modeThe breaker
to open be replaced if the fault is confirmed
fails tobreak in manual mode
2 Check the operating mechanism for mechanical fault.

1 Check the motor-driven energy storage mechanism control


Energy failed to be stored power voltage, and the voltage shall be ≥85%Us;
in power-driven mode check the status of the circuit connection
5 Breaker fails to store energy 2 Check the motor

Energy failed to be stored in


Check the operating mechanism for mechanical fault
manual mode

Breaker fails to be pulled out when the Rock rod fails to be pulled out Pull out the rock rod
6 open frame (draw-out) circuit breaker is Breaker fails to completely reach the Put the breaker completely
in the SEPARATION position SEPERATION position to the “disconnected” position by rocking

The "drawer” has seized up for


Open frame (draw-out) circuit foreign matters fall in it; damage in Check it for foreign matters and for condition
7 breaker fails to be put to the the mechanism for putting in by of the rack and gear
CONNECTION position by rocking rocking or the gear thereof; Position Turn the key on the “drawer” to unlock the matter
locking device fails to be unlocked

Intelligent controller fails to be


energized by power supply:
1 Check to see if the intelligent controller
Improper input voltage for the
power supply is well be connected and works well
auxiliary power supplyImproper
No display on the 2 Cut off the intellectual controller control
8 secondary output voltage for the
intellectual controller screen power supply, and then connect the power supply;
transmitter Unreliable connection
If the fault is still present, there may be some
between the secondary output
troubles in the controller which has to be replaced
terminal of the transmitter and
the controller
NA8G Air Circuit Breaker P-038

11. Ordering specification


User Order amount Order date Tel
Type and size □NA8G-1600 □NA8G-3200 □NA8G-4000 □NA8G-6300

Rated current □400 □630 □800 □1600 □2000 □4000 □5000


□ 2500 □ 3200 □ 4000
(In)A □1000 □1250 □1600 □2500 □3200 □6300(don’t have 4P)

Installation mode □draw-out type □Fixed type (no such products for over 4000A)
Connection mode □Horizontal connection □Vertical connection □Front connection □mixed connection (connection mode to be noted)
Number of poles □3P □4P

Factory' s setting values: IR=1In, tr=2s@6IR:; Isd=8IR, inverse-time protection,tsd= 0.4s; Ii=12In;OFF(If on, when In>1200A Ig=800A;
when In≤1200A Ig=0.5In) If the user has some requirements different from the defaulting, please write the numerical values on
the line below
Operating current setting______In (0.4,0.5,0.6,0.7,0.8,0.9,0.95,0.98,1)

C
Long-time delay protectionIR
Operating time setting______s (1,2,4,8,12,16,20,24,30)
Setting of the
protection Operating current setting______IR (1.5,2,2.5,3,4,5,6,8,10)
Short-circuit short-time delay protectionIsd
parameter Operating time setting □inverse time______s (0.1,0.2,0.3,0.4,OFF)

Short-circuit instantaneous protectionIi Operating current setting______In (2,3,4,6,8,10,12,15,OFF)


Intelligent controller

Operating current setting______In


Ground protectionIg
Operating time setting □inverse time______s □Definite-time limit______s

Selecting the type □Standard type □Multifunctional type


Power input □AC400V □AC230V □DC220V □DC110V □DC24V
Three-section protection against over current Neutral line or grounding fault protection Voltage measurement
Basic function Test function Fault inquiry/memory function Self-diagnostic function

Optional function
(this function to □Over voltage protection □Under voltage protection □Over frequency protection □Under frequency protection
be added as □Voltage unbalance measurement □Phase sequence protection □Voltage measurement □Frequency measurement
required by the □Measurement of harmonic current □Power factor measurement □Power measurement □Phase sequence detection
user, and to be □Voltage unbalance rate measurement □Electric energy measurement □Contact equivalent □MCR make/break function
matched with the □Load monitoring function □Signal contact output function □Communication function □ZSI regional interlocking protection
controller type)

Note: when the product is a multifunctional controller as arranged by the user,


the communication function and the like are the basic function configuration

Under voltage □Instantaneous □Time delay______s (1-2-3-4-5-6-7s provided for frame 1600, optional but not adjustable;
Accessories for standard

release 0.5-1-3-5s for frame 3200 and 6300l, optional but not adjustable) □AC400V □AC230V

Shunt release □AC400V □AC230V □DC220V □DC110V


configuration

Closing electromagnet □AC400V □AC230V □DC220V □DC110V


□AC400V □AC230V □DC220V □DC110V
Energy storage motor □4 switch contact □5 swith contact □6 switch contact(Only for frame 1600,and not available for DC)
Auxiliary contact □3 N.O. and 3 N.C. □4 N.O. and 4 N.C.(Frame 3200 and 6300 provided)

□One breaker is provided with one lock and one key


Accessories for optional

OFF locking □Two breakers is provided with two same locks and one key
device □Three breakers is provided with three same locks and two keys
configuration

Mechanical
Mechanical interlock □Steel cable interlock □Connecting-rod interlock
interlock

□Button locking device □Three-position locking device for the draw-out socket □Door interlock
□Phases barrier

Note: Extra costs are needed for the optional functions, optional accessories and the like for the breaker.