Basic Instruction Manual: Adjustable Frequency Crane Controls
Basic Instruction Manual: Adjustable Frequency Crane Controls
The recommendations in this manual do not take precedence over any of the following requirements relating to
cranes, hoist lifting devices or other material handling equipment which use or include Magnetek Products:
• Instructions, manuals, and safety warnings of the manufacturers of the equipment where the Magnetek
Products are used,
• Plant safety rules and procedures of the employers and the owners of facilities where the Magnetek
Products are being used,
• Regulations issued by the Occupational Health and Safety Administration (OSHA),
• Applicable local, state or federal codes, ordinances, standards and requirements, or
• Safety standards and practices for the industries in which Magnetek Products are used.
This manual does not include or address the specific instructions and safety warnings of these manufacturers
or any of the other requirements listed above. It is the responsibility of the owners, users and operators of the
Magnetek Products to know, understand and follow all of these requirements. It is the responsibility of the
employer to make its employees aware of all of the above listed requirements and to make certain that all
operators are properly trained. No one should use Magnetek Products prior to becoming familiar with and
being trained in these requirements and the instructions and safety recommendations in this manual.
For information on Magnetek’s product warranties by product type, please visit www.magnetekmh.com.
WA R N I N G
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in
death or serious injury. This signal word is to be limited to the most extreme situations.
WA R N I N G
WARNING indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury. It may also be used to alert against unsafe practices.
Chapter1: Introduction
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
AC Reactor Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
External Resistor Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Chapter 2: Installation
Assessing the System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
System Components and External Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Long Time Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Dimensions/Heat Loss - Open Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Installing the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Chapter 3: Wiring
Wiring Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Typical Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Safe Disable Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Suggested Circuit Protection Specifications and Wire Size . . . . . . . . . . . . . . . . . . . . . . 3-8
Chapter 6: Troubleshooting
Troubleshooting the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Maintenance and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Motor Faults and Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Drive Faults, Alarms and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Fault Display and Corrective Actions at Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Power Section Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Introduction
This page intentionally left blank.
Read and understand this manual before installing, operating, or servicing this drive. All
warnings, cautions, and instructions must be followed. All activity must be performed by
qualified personnel. The Drive must be installed according to this manual and local codes.
Do not touch any circuitry components while the main AC power is on. In addition, you must
wait until the red “CHARGE” LED is out before performing any service on that unit (as you look
at the face of the circuitry, the “CHARGE” LED is located inside the left side of the drive). It
may take as long as ten minutes for the charge on the main DC bus capacitors to drop to a safe
level.
Do not connect the main output terminals (U/T1, V/T2, W/T3) to the incoming, three-phase AC
source.
Before executing Auto-Tuning, ensure that the motor is disconnected from the drive train, and
the electric brake is set (locked) closed to ensure the load does not move. If the electric brake
cannot be released, you must ensure that the brake is disengaged for the entire tuning process.
Do not connect or disconnect wiring while the power is on. Do not remove covers or touch
circuit boards while the power is on. Do not remove or insert the digital operator while power is
on.
Before servicing, disconnect all power to the equipment. The internal capacitor remains charged
even after the power supply is turned off. The charge indicator LED will extinguish when the DC
bus voltage is below 50VDC. To prevent electric shock, wait at least ten minutes after all
indicators are OFF and measure DC bus voltage level to confirm safe level.
Do not perform a withstand voltage test on any part of the unit. This equipment uses sensitive
devices and may be damaged by high voltage.
The drive is suitable for circuits capable of delivering not more than 30,000 RMS symmetrical
Amperes, 240VAC maximum (230V Class) and 480VAC maximum (460V Class). Install
adequate branch circuit short circuit protection per applicable codes. Failure to do so may result
in equipment damage and/or personal injury.
Switching the IMPULSE•G+ Mini to ADVANCED mode enables many additional control features,
including:
• Open-Loop Vector Control
• Micro-Positioning Control™
• Up to 15 Discrete Speed References
• Load Check II™
• Maintenance Timers
• Braketronic™
• Expanded Programmable Input/Output Capabilities
This manual will provide support for the basic operating features of IMPULSE•G+ Mini. For
information on the additional control features, please consult the IMPULSE•G+ Mini Advanced
Instruction Manual (144-25085) found at www.magnetekmh.com/manuals.htm.
2003
2005
2008
2017
2025
2033
2047
2060
2011
Rated current (A) 1.6 3.0 5.0 8.0 11.0 17.5 25.0 33.0 47.0 60.0
Capacity (kVA) 0.6 1.1 1.9 3.0 4.2 6.7 9.5 12.6 17.9 22.9
460V Class
Specification Specification Values and Information for Each 460V-Class Model
4001
4002
4003
4004
4009
4014
4018
4024
4031
Rated current (A) 1.2 1.8 3.4 4.8 9.2 14.8 18.0 24.0 31.0
Capacity (kVA) 0.9 1.4 2.6 3.7 7.0 11.3 13.7 18.3 23.6
AC Reactor Specifications
Reactors, both as input (line) and output (load) devices, protect adjustable frequency drives, motors,
and other load devices against excessive voltage and current.
The following guidelines may help determine input and output reactor requirements:
• Install an input reactor if the power source is greater than 500kVA.
• Ensure the drive-to-motor wiring distance is less than 150 ft. unless appropriate reactors, filters and/or
Inverter Duty motor is used.
• Install an output reactor if a device, such as a power limit switch, is used to disconnect the motor from the
drive.
• Install one output reactor per drive for a multiple-drive arrangement requiring reactor protection.
• For a multiple drive arrangement, an input reactor for each drive is recommended for optimal protection.
However, if the drives are within two drive sizes of each other, a single input reactor can be used. The
reactor must be rated at amperage equal to or greater than the sum of the amperage for all the drives.
230V Class
Model Number 230V Part Number Maximum Amps of Reactor
2001-G+M REA230-1 4
2003-G+M REA230-1 4
2005-G+M REA230-1 4
2008-G+M REA230-2 8
2011-G+M REA230-3 12
2017-G+M REA230-5 18
2025-G+M REA230-7.5 25
2033-G+M REA230-10 35
2047-G+M REA230-15 45
2060-G+M REA230-20 55
Installation
This page intentionally left blank.
WA R N I N G
•When preparing to mount the IMPULSE•G+ Mini drive, lift it by its base. Never lift it by the
front cover.
•Mount the drive on nonflammable material.
•The IMPULSE•G+ Mini drive generates heat. For the most effective cooling possible, mount
it vertically. For more details, refer to the “IMPULSE•G+ Mini Dimensions/Heat Loss—
Open Chassis” section in this chapter.
•When mounting units in an enclosure, install a fan or other cooling device to keep the
enclosure temperature below 122°F (50C).
It is important to know how you are going to use the drive before you start installation and wiring.
You will need to know your requirements for the following components:
• Motion (traverse or hoist)
• Motor HP, RPM, and FLA
• Speed control method (2-speed, 3-speed, multistep, etc.)
• Stopping method (Decelerate or Coast to Stop)
• Wire size
• Grounding location and method
Choosing a Location
Be sure the drive is mounted in a location protected against the following conditions:
• Extreme cold and heat. Use only within the ambient temperature range:
Open Chassis: +14 to 122F (-10 to 50C)
• Direct sunlight (not for use outdoors)
• Rain, moisture
• High humidity
• Oil sprays, splashes
• Salt spray
• Dust or metallic particles in the air
• Corrosive gases (e.g. sulfurized gas or liquids)
• Radioactive substances
• Combustibles (e.g. thinner, solvents, etc.)
• Physical shock, vibration
• Magnetic noise (e.g. welding machines, power devices, etc.)
Inverter drives contain large bus capacitors that have the potential to be reformed. However, printed
circuit boards also contain electrolytic capacitors that may not function after several years without
power. Magnetek recommends replacing the PCBs should the drive’s functionality not be restored
after bus cap reforming. Contact Magnetek Service for questions.
The electrical characteristics of aluminum electrolytic capacitors are dependent on temperature; the
higher the ambient temperature, the faster the deterioration of the electrical characteristics (i.e.,
leakage current increase, capacitance drop, etc.). If an aluminum electrolytic capacitor is exposed to
high temperatures such as direct sunlight, heating elements, etc., the life of the capacitor may be
adversely affected. When capacitors are stored under humid conditions for long periods of time, the
humidity will cause the lead wires and terminals to oxidize, which impairs their solderability.
Therefore, aluminum electrolytic capacitors should be stored at room temperature, in a dry location
and out of direct sunlight.
In the event that a capacitor has been stored in a high ambient environment for more than 2 or 3
years, a voltage treatment reformation process to electrolytic capacitors may have to be performed.
When stored above room temperatures for long periods of time, the anode foil may react with the
electrolyte, increasing the leakage current. After storage, the application of even normal voltages to
these capacitors may result in higher than normal leakage currents. In most cases the leakage current
levels will decrease in a short period of time as the normal chemical reaction within the capacitor
occurs. However, in extreme cases, the amount of gas generated may cause the safety vent to open.
Capacitors, when used in inverter drives that are stored for long periods of time, should be subjected
to a voltage treatment/reforming process as noted below, which will reform the dielectric and return
the leakage current to the initial level.
• Inverter Bus Capacitor Reforming Procedure:
• Connect the inverter inputs L1 and L2 to a variac.
• Make sure the variac voltage setting is turned down so that when input power is applied to the
variac, the output of the variac will be at or near 0 volts.
• Apply power to the variac, listening for abnormal sounds and watching for abnormal visual
indications in the drive. If the variac has an output current indication, make sure the current is
very near zero with zero or a steady output voltage applied.
• Slowly turn the variac up, increasing the variac’s output voltage to nominal rated input voltage
over a time period of 2 to 3 minutes. In other words, ramp the voltage up at a rate of
approximately 75 to 100 volts/minute for 230 VAC units, 150 to 200 volts/minute for 460 VAC
units, and 225 to 300 volts/minute for 575 VAC.
• Let the output voltage remain at rated voltage for 30 to 60 minutes while keeping close watch for
If any abnormal indications occur during this process, it is recommended that the process be
repeated. Otherwise, this completes the capacitor reforming procedure.
Wiring
This page intentionally left blank.
WA R N I N G
Before you wire the drive, review the following practices to help ensure that your system is
wired properly.
+2, +1 DC reactor connection When connecting optional DC reactor, remove the main circuit short-circuit bar between +2
and +1.
+1, (–) DC power supply input DC power supply input [+1: positive; (–): negative]
Grounding Ground to local grounding codes
S1 Multi-function input selection 1 FWD run when closed, stop when open H01.01 ~ 120VAC ±10%
S2 Multi-function input selection 2 REV run when closed, stop when open H01.07
S3 Multi-function input selection 3
S4 Multi-function input selection 4
S5 Multi-function input selection 5 Inputs are programmable
S6 Multi-function input selection 6
Sequence
AM +10V
AC Analog monitor common 0V
R+ Communications input (+) H05.01 ~ RS-485/422
Circuit Terminal
communications
R- Communications input (-) MEMOBUS communication H05.08 MEMOBUS protocol, 115.2 kbps max.
MEMOBUS
Removing the voltage from terminal H1 disables the drive output, i.e. the power supply to the motor
is cut by stopping the switching of the output transistors in a safe way. “Hbb” is shown on the
display. Safe Disable is applicable for induction and permanent magnet motors.
Installation
If the Safe Disable function is utilized, the wire link between the terminals HC and H1 that is
installed at shipment must be removed entirely.
Connect the drive to an EN954-1, Safety Category 3 interrupting device so that in case of a Safe
Disable request, the connection between the terminals HC and H1 is opened.
Installation Precautions:
• To ensure the Safe Disable function appropriately fulfills the safety requirements of the
application, a thorough risk assessment for the safety system must be carried out.
• The drive must be installed in an enclosure with a protection degree of at least IP54 in order to
maintain EN954-1, safety category 3 compliance.
• If the safety device and the drive are installed in separate cabinets, install the Safe Disable wires
in a manner preventing short circuits.
• The Safe Disable function does not cut the power supply to the drive and does not provide
electrical isolation. Before any installation or maintenance work is done, the power supply of
the drive must be switched off.
• The wiring distance for the Safe Disable inputs should not exceed 30 m.
• The time from opening the Safe Disable input until the drive output is switched off is less than 1
ms.
• When utilizing the Safe Disable function use the recommended filters manufactured by
Schaffner only.
CAUTION:
The following guidelines are only suggested values. Always conform to local electrical
codes and wiring practices.
Getting Started
This page intentionally left blank.
WA R N I N G
Because of the additional potential hazards that are introduced when any drive is operated
locally, we advise you to avoid operating it this way. If you do operate the drive locally, be
aware that the crane or hoist will move when you press the RUN button. If you have questions,
contact Magnetek.
WA R N I N G
Precautions
• Only start the motor if motor shaft rotation is stopped.
• Even with small loading, never use a motor whose nameplate amperage exceeds the inverter
rated current.
DANGER
Extreme caution should be used if braking method is set to decelerate to stop. If deceleration
time is too long, equipment could run into end stop device, causing damage to equipment or
injury to personnel.
Keypad Functions
The keypad has a 5-digit alpha-numeric LED display.
Indicators and keys on the keypad are described in Figure 4-1 and the following tables.
NOTE: The STOP key is always active and will immediately cause the motor to stop following the
B03.03 Stopping Method.
4 RUN Key Pressing the key initiates the RUN command when
LOCAL mode operation is selected.
Starts the auto-tuning process.
9 LO/RE Selection Key Pressing the key once displays support phone
number 866-624-7378.
Pressing the key again shows control method,
motion, and reference speed.
Pressing the key again will show RESET. Pressing
the ENTER Key afterwards will reset the
maintenance timers.
Function LEDs
After applying power to the drive, the display will show the output frequency of 0.00.
Navigation Keys:
The above figure shows the keypad on the G+ Mini. These keys are used for navigation and for
changing various settings within the drive.
Use the and keys to change the dispay and/or change the value of a parameter.
Use the key to move the cursor to the right and to reset the drive after a fault.
Use the key to view and save any parameter changes or the key to exit without
saving changes.
Setting Motion:
From the output frequency display, press the key five times until the display shows the
parameter menu (PAr).
Press .
A01.03 - Motion
Data Value Function
00 Traverse
01 Hoist (Default)
Press to save your changes. The display will temporarily show , then A01.03.
Use the following table to select the speed reference for your application:
Press to save your changes. The display will temporarily show , then A01.04
Locate the nameplate on your motor to find the Full Load Amps (FLA), and the motor RPM.
Press the key once to move the cursor to the left most spot. Use the and
keys to navigate to the “E” menu. The display should show E01.01.
Press the key once to move the blinking digit to the right.
Press the key once to change from E01 to E02. The display now shows E02.01 (Motor
FLA). Press twice.
NOTE: If more than one motor is bieng controlled by the drive, enter in the total of all the
motor full load amp ratings. This step is important to provide proper motor overload
protection.
Use the , , and keys to enter the FLA from the motor nameplate.
Press to save your changes. The display will temporarily show , then E02.01.
By default, the IMPULSE•G+ Mini is configured for a common crane system. If you find it
necessary to change the intial settigs, it is recommended that you only allow qualified crane system
technicians to program the drive. This can be accomplished by using the Password and Access
Level features. For more information on these security features, see “User Parameters (A02.XX),”
in the IMPULSE•G+ Mini Advanced Instruction Manual (P/N 144-25085).
Operation Mode
Drive operation is enabled. Drive status LED lights.
Programming Mode
Parameter access levels, control method, motion, speed control mode, and passwords are selected.
Parameters are set/read. Items to be set/read vary depending on the access level setting.
Auto-Tuning Mode
Motor parameters are automatically set by entering tuning data (motor nameplate values) when using
V/f control method.
Changing the access level to USER (A01.01 = 0000) limits access to only parameters stored in the
A02.xx table (up to 32). To set up the A02.xx group, refer to the G+ Mini Advanced Instruction
manual.
Setting Description
0000 User Program - Allows read/write capabilities for parameters selected by OEM
(A02.01 to A02.32).
0001 Basic Level - Access to parameters for general crane applications
Setting Description
00 V/f Control—For general purpose and multiple motor applications.
Setting Description
00 Traverse - Decelerate to stop upon removal of RUN command.
01 Standard Hoist - Immediate stop upon removal of RUN command
Setting Description
00 2-SPD Multi-step — Defines Terminal S3 = 2nd speed.
01 3-SPD multi-step — Defines Terminals S3 and S4 as speeds 2 and 3
respectively.
02 5-SPD Multi-step — Defines Terminals S3-6 as speeds 2-5.
03 2-Step infinitely variable — Terminals S1 and S2 = B01.01 (Reference 1) and
speed hold. Terminal S3 = Accelerate.
04 3-Step infinitely variable — Terminals S1 and S2 = B01.01 (Reference 1).
Terminal S3 = Speed Hold. Terminal S4 =Accelerate.
05 Uni-polar analog — Terminals S1 and S2 = A directional input. Terminal A1 =
0-10V. Terminal A2 = 4-20mA for speed reference.
B01.01 B01.02 B01.03 B01.04 B01.05 B01.18 B02.03 B03.03 B05.01 B05.02 C01.01 D09.01 D09.02 D09.03
A01.04 Description Speed Speed Speed Speed Speed Ref. Lower Stopping Accel Time Decel Time S-Curve S-Curve S-Curve
Ref Priority Quick Stop
1 2 3 4 5 Limit Method 1 1 Accel at Start Accel at End Decel at Start
00 2-Speed Multi-Step 6.00 60.00 0.00 0.00 0.00 00 2.0 00 5.0 5.0 00 1.50 1.50 1.50
01 3-Speed Multi-Step 6.00 30.00 60.00 0.00 0.00 00 2.0 00 5.0 5.0 00 1.50 1.50 1.50
02 5-Speed Multi-Step 6.00 15.00 30.00 45.00 60.00 00 2.0 00 5.0 5.0 00 1.50 1.50 1.50
03 2-Step Infinitely Variable 6.00 0.00 0.00 0.00 60.00 00 2.0 00 5.0 5.0 00 1.50 1.50 1.50
04 3-Step Infinitely Variable 6.00 0.00 0.00 0.00 60.00 00 2.0 00 5.0 5.0 00 1.50 1.50 1.50
05 Uni-Polar Analog 0.00 0.00 0.00 0.00 0.00 01 2.0 00 5.0 5.0 00 1.50 1.50 1.50
E01.03 H01.01 H01.02 H01.03 H01.04 H01.05 H01.06 H01.07 H02.01 H02.02 H02.03 H03.01
B01.01 B01.02 B01.03 B01.04 B01.05 B01.18 B02.03 B03.03 B05.01 B05.02 C01.01 D09.01 D09.02 D09.03
E01.03 H01.01 H01.02 H01.03 H01.04 H01.05 H01.06 H01.07 H02.01 H02.02 H02.03 H03.01
A01.04 Description Terminal Terminal Terminal Terminal Terminal Terminal Terminal Terminal Terminal
Terminal S1 Terminal S2
V/f Selection S3 S4 S5 S6 S7 MA/MB/MC P1 P2 A1
Select Select
Select Select Select Select Select Select Select Select Signal
00 2-Speed Multi-Step 04 80 81 00 0F 0F 0F 0F 00 0F 0F 00
01 3-Speed Multi-Step 04 80 81 00 01 0F 0F 0F 00 0F 0F 00
02 5-Speed Multi-Step 04 80 81 00 01 02 03 0F 00 0F 0F 00
03 2-Step Infinitely Variable 04 80 81 05 0F 0F 0F 0F 00 0F 0F 00
04 3-Step Infinitely Variable 04 80 81 04 05 0F 0F 0F 00 0F 0F 00
05 Uni-Polar Analog 04 80 81 0F 0F 0F 0F 0F 00 0F 0F 00
Setting Description
0000 No Initialize (no action)
1110 User Initialize - Restores the drive to user-specified initial values.
5550 Copies saved parameters back from the terminal board to the drive’s memory.
Once the drive is configured and the system is running, set parameter O02.03 = 01 to save all
modified parameters to the User Initialized memory. Once this has been done, the setting of 1110
“User Initialize” will be visible for A01.05. Changing A01.05 = 1110 will recall all modified
parameters back to what they were the last time they were saved using O02.03.
oPE04 Fault (A01.05 = 5550)
The oPE04 fault indicates the parameters in the terminal board do not match the parameters of the
control board. To reset the oPE04 fault, set A01.05 = 5550. This will copy the parameters from the
terminal board to the control board. Check and verify your kVA setting (O02.04) before operating
the drive. Please contact Magnetek support for assistance.
To program a password, access the programming menu, “PAr,” and navigate to parameter A01.06.
Press the STOP and UP arrow keys at the same time to change the display from A01.06 to A01.07.
Press ENTER and program a password number into A01.07.
When parameters A01.06 A01.07, only parameters A01.01, A01.06, and A01.08 are visible and
cannot be modified. The Access Level is set to User Program (A01.01 = 0000). Parameters
programmed into A02.xx can be viewed in the “USEr” menu with read/write accessibility. When
A01.06 = A01.07, then A01.01 to A01.08 can be modified, along with the remaining parameters in
the drive.
When A01.06 A01.07, then A01.06 will show “LoC.” When A01.06 = A01.07, then A01.06 will
show “UnLoC.”
CAUTION
Using Auto-Tuning
With the keypad, use the UP or DOWN arrow keys to show the auto-tuning menu . Press
the ENTER key and scroll through the tuning parameters using the UP Arrow key and enter each of
the required parameter settings. Press the RUN key when the RUN12 message is shown. The
display will flash the RUN12 message during the tuning process. When complete, the drive will
display END, indicating the tuning was successful. Press the ESC key twice to exit. If there is a
fault during the tuning process, the drive will display an error message. Refer to the “Fault Display
and Corrective Actions at Auto-Tuning” in Chapter 6.
NOTE: If the STOP key is pressed during tuning or the auto-tuning is interrupted, the motor will
coast to stop and the inverter display will show ER-03. The data changed during tuning
returns to its original values.
Programming Features
This page intentionally left blank.
Preset Reference
STOP Off -- -- -- --
B01.01
On Off Off Off Off
Speed Ref 1
B01.02
On On Off Off Off
Speed Ref 2
B01.03
On On On Off Off
Speed Ref 3
B01.04
On On On On Off
Speed Ref 4
B01.05
On On On On On
Speed Ref 5
An alternate upper limit frequency can be used during operation when a Multi-Function Input (MFI)
is set to 59 (Alt F-Ref UpLimit) and the MFI is on. Alternate Upper Limit Frequency = (B02.04) %
x (E01.04).
100% (E01.04)
B02.02 x (E01.04)
HZ
0 E01.04
Set Frequency Reference
WA R N I N G
Because of the additional potential hazards that are introduced when any drive is operated
locally, we advise you to avoid operating it this way. If you do operate the drive locally, be
aware that the crane or hoist will move when you press the RUN button. If you have questions,
contact Magnetek.
Stopping Method
B03.03 selects the stopping method suitable for the particular application.
Parameter Access
Code Name Function Range Initial Value Level
B05.01 Accel Time 1 Sets acceleration time. 0.0–25.5 sec 5.0* Basic
B05.02 Decel Time 1 Sets deceleration time. 0.0–25.5 sec 3.0* Basic
B05.03 Accel Time 2 Sets alternate accel time. 0.0–6000.0 sec 2.0 Basic
Enabled by multi-function input=1A.
B05.04 Decel Time 2 Sets alternate decel time. 0.0–6000.0 sec 2.0 Basic
Enabled by multi-function input=1A.
* Initial value is determined by X-Press Programming (Table 4.1 to 4.2).
Run Command
MFI=1A
Accel / Decel
Changeover
B05.04
B05.01 B05.02 B05.03
Frequency Output B05.02
B05.01
Brake Output
Motion (A01.03)
Special Function Traverse (A01.03=0) Standard Hoist (A01.03=1)
C1: Quick Stop
C6: Swift-Lift
Quick Stop
The Quick Stop Function provides an automatic Alternate Deceleration at Stop Command.
NOTE: The Quick Stop Deceleration time differs from the normal deceleration time and is applied
only when the RUN command is removed.
Parameter Access
Code Name Function Range Initial Value Level
C01.01 Quick Stop 0/1 Determines whether Quick 00, 01 00* Basic
Stop is enabled
00 Disabled
01 Enabled
C01.02 Quick Stop Time Deceleration time during 0.0–25.5 sec 1.0 Basic
Quick Stop function.
* Initial value is determined by X-Press Programming (Table 4.1 to 4.2).
Parameter Access
Code Name Function Range Initial Value Level
C01.03 Reverse Plug Determines whether 00, 01 00 Basic
Reverse Plug Simulation is
enabled.
00 Disabled
01 Enabled
C01.04 Reverse Plug Decel Deceleration time during 0.0–25.5 sec 2.0 Basic
Time Reverse Plug Simulation.
C01.05 Reverse Plug Accel Acceleration time during 0.0–25.5 sec 2.0 Basic
Time Reverse Plug Simulation
When the crane reaches either the Upper Limit 1 (UL1) or Lower Limit 1 (LL1), the drive will
decelerate to the Upper and Lower Limit speeds C03.01 and C03.04 respectively. When the crane
reaches either the Upper Limit 2 (UL2) or Lower Limit 2 (LL2), the drive will come to a stop based
on the Limit Stopping Method (C03.07). If C03.07 is set to 00, the deceleration time will use Upper
Limit 2 Stop Time (C03.03) or Lower Limit 2 Stop Time (C03.06).
Parameter Access
Code Name Function Range Initial Value Level
C03.01 Upper Limit 1 Speed Speed at Upper Limit input. 0–150 Hz 6.00 Basic
C03.02 Upper Limit 1 (UL1) Decel Decel time to Upper Limit 0.0–25.5 sec 1.0 Basic
Time Speed.
C03.03 Upper Limit 2 (UL2) Stop Decel time to STOP when 0.0–25.5 sec 1.0 Basic
Time Upper Limit is Input.
C03.04 Lower Limit 1 Speed Speed at Lower Limit input. 0–150 Hz 6.00 Basic
C03.05 Lower Limit 1 (LL1) Decel Decel time to Lower Limit 0.0–25.5 sec 1.0 Basic
Time Speed
C03.06 Lower Limit 2 (LL2) Stop Decel time to STOP when 0.0–25.5 sec 1.0 Basic
Time Lower Limit is input.
C03.07 Limit Action @ LL2/UL2 Determine the stop method at 00–02 02* Basic
Upper Limit 2 and Lower
Limit 2 Input.
00 Decel to Stop
01 Coast to Stop
02 Use B03.03 Method
* Initial value is determined by X-Press Programming
WA R N I N G
Motors and drive machinery must be capable of operating above motor base speed. Consult
the motor/gearbox/hoist manufacturer before enabling Swift-Lift function. Failure to observe
this warning may result in damage to equipment and possible injury or death to personnel.
or
DC Injection
DC Injection can be used to stop a motor whose rotational direction is uncertain at start-up.
With Decel to Stop enabled (B03.03 = 00), upon removal of the run command the IMPULSE•G+
Mini drive controls motor deceleration according to the Decel Time setting, until output frequency
reaches the DC Injection Braking Start Frequency (D01.01 setting). Then the drive output is turned
off and DC injection current is applied to the motor. The effective DC injection time and current
should be set to provide adequate stopping without excessive motor heating. The DC injection
voltage is determined by the DC injection braking current and motor impedance.
Parameter Access
Code Name Function Range Initial Value Level
D01.01 DC Injection Start Frequency DC Injection braking 0.0–10 Hz 0.5 Basic
frequency start.
D01.02 DC Injection Current % of Inverter rated current 0–75% 50 Basic
D01.03 DC Injection Time @ Start DC Injection braking time. 0.00–10.00 sec 0.00 Basic
D01.04 DC Injection Time @ Stop DC Injection braking time at 0.00–10.00 sec 0.05 Basic
stop.
Decrease the torque compensation time constant in 10ms increments when the motor’s output
current is unstable. Increase this value when speed response is slow.
Parameter Access
Code Name Function Range Initial Value Level
D09.01 S-Curve Accel @ Start Sets S-Curve time at Accel 0.00–10.0 sec Basic
start
D09.02 S-Curve Accel @ End Sets S-Curve time at Accel 0.00–10.0 sec Basic
end
D09.03 S-Curve Decel @ Start Sets S-Curve time at Decel 0.00–10.0 sec Basic
start
D09.04 S-Curve Decel @ End Sets S-Curve time at Decel 0.00–10.0 sec 0.20 Basic
end
*Initial value is determined by X-Press Programming (Table 4.1 to 4.2).
Figure 5-11 shows FWD/REV run switching during deceleration to stop. The S-Curve function will
add time to the acceleration and deceleration.
Total time to acceleration from minimum frequency to maximum frequency (total acceleration) is:
Total time to deceleration from maximum frequency to minimum frequency (total deceleration) is:
CAUTION
Voltage/Frequency Pattern
An OPE10 error will occur if the following conditions are not met:
The setting E01.01 adjusts the overvoltage level, braking transistor turn on level, and the stall
prevention level during deceleration.
Digital Inputs
The IMPULSE•G+ Mini has seven multi-function contact inputs for the set-up of numerous
functions. The following table lists the function selections for the multi-function contact inputs
(terminals S1 to S7) and indicates the control modes during which each function can be enabled. An
OPE03 error will occur if the same function is programmed in more than one terminal at the same
time.
Reference
Parameter Page Initial Access
Code Name Function Number Range Value Level
H01.01 Terminal S1 Select Selects the multi-function -- 00–81 80* Basic
inputs. Setting for S1.
H01.02 Terminal S2 Select Setting for S2. -- 00–81 81* Basic
H01.03 Terminal S3 Select Setting for S3. -- 00–81 00* Basic
H01.04 Terminal S4 Select Setting for S4. -- 00–81 01* Basic
H01.05 Terminal S5 Select Setting for S5. -- 00–81 0F* Basic
H01.06 Terminal S6 Select Setting for S6. -- 00–81 0F* Basic
H01.07 Terminal S7 Select Setting for S7. -- 00–81 0F* Basic
00 Multi-Step Ref 2 Multi-Step Speed 2. 5-3
01 Multi-Step Ref 3 Multi-Step Speed 3. 5-3
02 Multi-Step Ref 4 Multi-Step Speed 4. 5-3
03 Multi-Step Ref 5 Multi-Step Speed 5. 5-3
04 Speed Hold 2 Hold function (2nd step of --
Three-Step Infinitely Variable).
05 Accel Command Acceleration function (2nd step 5-3
of Two-Step Infinitely Variable
or 3rd step of Three-Step
Infinitely Variable).
06 Upper Limit 1 N.O. Upper Limit - SLOW DOWN; 5-12
Normally Open. UL1 - blinking
07 Upper Limit 2 N.O. Upper Limit - STOP; Normally 5-12
Open. UL2 - blinking
08 Lower Limit 1 N.O. Lower Limit - SLOW DOWN; 5-12
Normally Open. LL1 - blinking
09 Lower Limit 2 N.O. Lower Limit - STOP; Normally 5-12
Open. LL2 - blinking
0A Upper Limit 1 N.C. Upper Limit - SLOW DOWN; 5-12
Normally Closed. UL1 -
blinking
Table 5-6:
External Fault Selection
Input Level MFI Setting
Selection Detection Method External Fault Action Result
During Ramp to Alarm
N.O.(1) N.C.(1) Always Run Stop Coast to Stop Only
20
24
28
2C
22
26
2A
2E
21
25
29
2D
23
27
2B
2F
Reference
Parameter Page Initial Access
Code Name Function Number Range Value Level
H02.01 Output Contactor (MC- Digital Output 1 Function -- 000–117 000 Basic
MB-MA) select
H02.02 Output Terminal P1 Select Digital Output 2 Function -- 000–117 000 Basic
H02.03 Output Terminal P2 Select Digital Output 3 Function -- 000–117 00F Basic
000 Brake Release Closed when the drive --
provides a voltage or
frequency is output
001 Zero Speed Closed when the output 5-4
frequency is below B02.02 or
D01.01
004 Freq Detect 1 Closed when the output 5-36
frequency is < L04.01.
005 Freq Detect 2 Closed when the output 5-36
frequency is > L04.01.
00B Trq Det 1 N.O. Closed when torque > L06.02 5-38
00E Fault Closed during a major fault. --
00F Not Used No function --
017 Trq Det 1 N.C. Open when torque > L06.02 5-38
for longer than L06.03 time
101 Inverse Zero Speed Open when the output 5-4
frequency is below B02.02 or
D01.01
104 Inverse Freq Detect 1 Open when output frequency 5-36
is < L04.01.
105 Inverse Freq Detect 2 Open when output frequency 5-36
is > L04.01.
10B Inverse Trq Det 1 Open when torque > L06.02 5-38
N.O.
10E Inverse Fault Open during a major fault --
117 Inverse Torque Detect Closed when torque > L06.02 5-38
1 N.C. for longer than L06.03 time
Motor Overload
The IMPULSE•G+ Mini protects against motor overload with a UL-recognized, built-in electronic
thermal overload function, so an external thermal overload relay is not required for single motor
operation.
The electronic thermal overload function estimates motor temperature, based on inverter output
current, frequency and time to protect the motor from overheating. This time is based on a “hot start”
for the motor (see Figure 5-13: Motor Protection Operation Time). When the thermal overload fault
is activated, an “OL1” fault occurs, shutting OFF the inverter output and preventing excessive
overheating in the motor. As long as the inverter is powered up, it continues to calculate the motor
temperature.
When operating several motors with one inverter, use the internal thermal protection from the motor
in accordance with NEC 430.126 (6) or install an external thermal overload relay on each motor, and
disable the motor overload protection, L01.01 = “00”.
CAUTION
This function automatically adjusts the output frequency, acceleration and/or deceleration
rates in order to continue operation without tripping or “stalling” the inverter.
When a motor is used above rated speed (E01.06), the output characteristics change from constant
torque to constant HP (see Figure 5-15). During acceleration above rated speed, the stall prevention
current limit level is automatically reduced for smoother acceleration. The parameters (L03.02 and
L03.03) limit the stall prevention current limit level in this region. The current limit during
acceleration is changed according to the following equation:
CAUTION
This function automatically adjusts the output frequency, acceleration and/or deceleration
rates in order to continue operation without tripping or “stalling” the inverter.
Sets a function to prevent stalling during an overload condition while running at constant speed.
The stall prevention/current limit level during running is set as a percentage of inverter rated current.
A setting of L03.05 = 00 disables current limit during running. During speed agree, if the output
current exceeds this current limit level (L03.06) during running, deceleration starts. When the output
current decreases below this current limit level (L03.06), acceleration starts, up to the set frequency.
See Figure 5-16 below.
Sets the detection level for the desired frequency agree 1 and frequency detection 1 and 2 functions.
The set detection level is effective during both FWD and REV operation.
When frequency detection is enabled using the multi-function contact outputs (H02.XX = “004,”
“005,” “104,” or “105”), the contact will open or close whenever the output frequency is less than or
more than the speed agree detection level.
Hardware Protection
Table 5-11: Auto Reset Table with UV2 and CE Faults (modified)
Digit 4 Digit 3 Digit 2 Digit 1
HEX 0 0 0 3
Binary 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1
L09.04 E - - - L P U - O S O G O U U U
F - - - F F T - H C V F C V V V
0 - - - 1 - 1 3 2 1
HEX E 0 8 0
Binary 1 1 1 0 0 0 0 0 1 0 0 0 0 0 0 0
L09.05 B* B* C F* O O O O C C - E E E E E
E E O B L L T T E A - F F F F F
1 2 F L 1 2 1 2 L - 7 6 5 4 3
L
* Only available when A01.01 = 02 (Advanced); see the G+ Mini Advanced Manual for further
explanation.
Fault Trace
Parameter
Code Name Function Units
U02.01 Current Fault Displays the most recent fault detected before being reset --
U02.02 Last Fault Displays the most recent fault after being reset (Same as U03.01) --
U02.03 Frequency Reference @ Freq ref when fault was detected Hz
Fault
U02.04 Output Frequency @ Output freq when fault was detected Hz
Fault
U02.05 Output Current @ Fault Output current when fault was detected A
U02.07 Output Voltage @ Fault Output voltage when fault was detected V
U02.08 DC Bus Voltage @ Fault DC Bus voltage when fault was detected V
U02.09 Output Power @ Fault Output power when fault was detected kW
U02.11 Input Terminal Status @ Input terminal status when fault was detected --
Fault
U02.12 Output Terminal Status @ Output terminal status when fault was detected --
Fault
U02.13 Operation Status @ Fault Inverter status before fault was detected --
U02.14 Elapsed Time @ Fault Elapsed time when fault was detected hr
U02.15 Speed Reference During Speed reference during soft start at previous fault %
Soft Start @ Fault
Troubleshooting
IMPULSE•G+ Mini
This page intentionally left blank.
CALL (flashing) Serial Communication Transmission Error. 1. Check serial device connections.
Control data is not received correctly after 2. Ensure drive is properly programmed for
power supply is turned ON for 2 sec. serial communication.
CE MEMOBUS/Modbus Communication
Error. Serial communications data corrupted.
1. Check serial connections (R+, R-, S+, & S-).
CPF03 PWM Data Error. There is a problem with the 1. Cycle power to the drive.
PWM data.
2. Replace the control board.
CPF06 EEPROM Data Error. There is an error in the 1. Cycle power to the drive.
data saved to EEPROM.
2. If the problem continues, replace the drive.
CPF16 Clock Fault. Standard clock error. 1. Cycle power to the drive.
2. Replace the drive.
CPF20 and RAM fault, FLASH memory error, watchdog 1. Cycle power to the drive.
circuit exception.
2. Replace the drive.
CPF21
CPF22 A/D Conversion Fault. A/D conversion error. 1. Cycle power to the drive.
2. Ensure that the control board terminals and
wiring are shielded from electrical noise.
3. Check resistance of potentiometer.
CPF23 PWM Feedback Fault. PWM feedback error. 1. Cycle power to the drive.
2. Replace the drive.
CRST Cannot reset. External fault occurred and reset 1. Wait for motor to come to complete stop.
button was pressed before motor was
completely stopped. 2. Reset fault before issuing a RUN command.
Fault reset was being executed when a RUN
command is executed during a fault.
DNE User is trying to give a run command while a 1. Check input terminals.
FWD or REV is present at Power Up.
Drive not ready 2. Check H01.01 to H01.07 programming.
EF0 External fault input from communication option 1. Check communication option card
card. connection and signals.
Optional External
Fault 2. Check external device for any fault(s).
EF1 External fault occurs on Terminal S1. 1. Check constant H01.01 for proper
programming.
External
Fault 1 2. Check the conditions for input terminal S1
(U01.10).
EF2 External fault occurs on Terminal S2. 1. Check constant H01.02 for proper
programming.
External
Fault 2 2. Check the conditions for input terminal S2
(U01.10).
EF3 External fault occurs on Terminal S3. 1. Check constant H01.03 for proper
programming.
External
Fault 3 2. Check the condition for input terminal S3
(U01.10).
EF4 External fault occurs on Terminal S4. 1. Check constant H01.04 for proper
programming.
External
Fault 4 2. Check the condition for input terminal S4
(U01.10).
EF5 External fault occurs on Terminal S5. 1. Check constant H01.05 for proper
programming.
External
Fault 5 2. Check the condition for input terminal S5
(U01.10).
EF6 External fault occurs on Terminal S6. 1. Check constant H01.06 for proper
programming.
External
Fault 6 2. Check the condition for input terminal S6
(U01.10).
EF7 External fault occurs on Terminal S7. 1. Check constant H01.07 for proper
programming.
External
Fault 7 2. Check the condition for input terminal S7
(U01.10).
LF An open phase occurred at the inverter output. 1. Check for broken wires in output cable.
Output Phase Loss 2. Check for open winding in the motor.
3. Check for loose terminals.
Lower Limit 2 Err changed). 2. Check the position of the Limit Switch.
3. Check the condition of the Limit Switch.
4. Check the conditions of/for input terminal
H01.XX (U01.10).
Heatsnk Over temp exceeded the setting in L08.02. 2. Reduce the ambient temperature.
OH1 Overheat Fault. There are two situations that 1. Ensure that the heat sink cooling fans are
result in an overheat fault. The first occurs when functioning.
Heatsink MaxTemp the measured heat sink exceeded 105°C. The
second is a result of a fault in the internal 2. Ensure that the heat sink is free from dirt and
24VDC cooling fan. debris.
3. Ensure that the inverter’s ambient
temperature is within specification.
4. Replace the 24VDC fan
5. Replace the heat sink thermistor(s)
OH3 Motor Overheating 1. Thermistor analog input 1. Check the motor rated current value, E02.01.
detected motor overheating. See L01.03
Motor Overheat 1 2. Increase cycle time or reduce the load.
OPE04 Parameters do not match. The drive, control 1. Press ENTER to view the parameter.
board, or terminal board has been replaced, and
Terminal the parameter settings between the controller 2. Change parameter(s) to appropriate settings.
board or terminal board do not match. 3. Set A01.05 = 5550.
OPE07 Multi-Function Analog Input Setting Fault. 1. Check setting for H03.02 and H03.10. Verify
that the same value is not used twice.
Analog Selection Set values other than 00 and 0F are duplicated.
OV (flashing) Overvoltage Fault. Overvoltage occurs during 1. Check the line voltage.
stop. Main circuit DC voltage rises above the
DC Bus Overvolt detection level while the drive output is off.
Detection level: 410V or more for 230V, 820V
or more for 460V.
Upper Limit 1 Err switch status is changed. 2. Check the position of the Limit Switch.
3. Check the condition of the Limit Switch.
4. Check the conditions of/for terminal H01.XX
(U01.10).
DC Bus Undervolt voltage drops below 190V DC or less for 230V 2. Replace any bad branch fuses.
AC class, 380V DC or less for 460V AC class. 3. Check collector system.
Er-09 Acceleration Fault (rotating auto-tuning only). • Increase B05.01 (acceleration time).
The motor did not accelerate at the expected time. • If C07.01 and C07.02 (torque limit value) are
Accelerate decreased, increase values.
• Disconnect motor from load.
Er-11 Motor Speed Fault (rotating auto-tuning only). • Increase B05.01 (acceleration time).
• Disconnect motor from load.
The motor speed was over 100% at auto-tuning
Motor Speed (vector control without PG only).
End 1 Excess V/f setting * (rotating auto-tuning only). • Check the T1 parameters.
The torque reference exceeded 20% and no load • Disconnect the motor from the load.
V/f Oversetting current exceeded 80%.
End 2 Motor Iron Core Saturation Coefficient Fault • Check the T1 parameters.
(rotating auto-tuning only). Since the motor iron • Check motor wiring.
Saturation core saturation coefficient could not be auto-tuned
within the set time, tentative value is set in the iron • Disconnect the motor from the load.
core saturation coefficient.
WA R N I N G
Do NOT touch any circuit components while AC main power is on or immediately after the main
AC power is disconnected from the unit. You must wait until the red “CHARGE” lamp is
extinguished. It may take as long as 10 minutes for the charge on the main DC bus capacitors to
drop to a safe level. Failure to adhere to this warning could result in serious injury.
Reference
Parameter Parameter Name Default Range Units Page
A01.01 Access Level 0001 0000–0001 -- 4-13
0000: User
0001: Basic
A01.02 Control Method 00 00 -- 4-13
00: V/f
A01.03 Motion 01 00, 01 -- 4-14
00: Traverse
01: Hoist
A01.04 Speed Reference 01 00–05 -- 4-14
00: 2-Speed Multi-Step
01: 3-Speed Multi-Step
02: 5-Speed Multi-Step
03: 2-Step Infinitely Variable
04: 3-Step Infinitely Variable
05: Analog - UniPolar
A01.05 Initialize 0000 0000–5550 -- 4-17
0000: No Initialize
1110: User Initialize
5550: Moves modified parameters from
terminal board to control board
A01.06 Password 1 0000 0000–9999 -- 4-17
A01.08 Password 2 0000 0000–9999 -- 4-18
B01.01 Frequency Reference 1 15.00* 0.00–150.00 Hz 5-3
B01.02 Frequency Reference 2 30.00* 0.00–150.00 Hz 5-3
B01.03 Frequency Reference 3 60.00* 0.00–150.00 Hz 5-3
B01.04 Frequency Reference 4 0.00* 0.00–150.00 Hz 5-3
B01.05 Frequency Reference 5 0.00 0.00–150.00 Hz 5-3
B01.18 Reference Priority 00* 00–02 -- 5-3
00: Digital Reference Only
01: Analog Reference Only
02: Higher Reference Select
B02.01 Frequency Reference Upper Limit 100.0 0.0–110.0 % 5-4
B02.02 Frequency Reference Lower Limit 0.0 0.0–110.0 % 5-4
B02.03 Reference 1 Lower Limit 2.0* 0.0–110.0 % 5-4
B02.04 Alt Upper Limit 100.0 0.0–110.0 % 5-4
B03.01 Reference Source 01 00, 01 -- 5-5
00: Digital Operator
01: Terminal
B03.02 Run Source 01 00, 01 -- 5-5
00: Digital Operator
01: Terminal
B03.03 Stop Method 01* 00, 01 -- 5-5
00: Decel to Stop
01: Coast to Stop
B05.01 Accel Time 1 5.0* 0.0–25.5 sec 5-8
B05.02 DecelTime 1 3.0* 0.0–25.5 sec 5-8
* Parameters defaults changed by X-Press Programming
** Parameters changed by E01.03
*** Value depends on drive model