HELIOS (FPC)
HELIOS (FPC)
The Helios Standard Duty, One Bolt, High Temperature
Fire Rated Stainless Steel single cable cleat is a fabricated
metallic cleat which has been designed, constructed,
and tested in accordance with the International Standard
‘Cable Cleats for Electrical Installations’ (IEC 61914).
These Fire Rated cable cleats can be used with fire
performance cables to ensure the safe retention and
securing of single cables in the event of a wiring system
being affected by fire. These fire resisting supports help
to maintain the electrical systems integrity for any critical
circuits during an emergency situation to enable safe
evacuation. The cable cleat is fabricated from Stainless FEATURES
Steel 316L making it suitable for both indoor and outdoor
Fabricated Stainless Steel 316L
applications.
Operating temperature -60°C to +250°C
The Helios High Temperature Stainless Steel 316L cable Surpasses requirements of Fire testing
cleat is available in eleven sizes suitable for cable diameters BS5839 / BS8491 / EN50200 / BS8434 /
of 10mm up to 65mm. The cable cleat has an M10 clearance AS-NZS 3013 (1,200°C) (Fire, shock & water)
hole for securing it to a mounting surface. 10 - 65mm cable range take in 11 sizes
Single bolt fixing design
C an be stacked
Corrosion resistant
BS 5839 ‘Fire detection and fire alarm systems for buildings. Code of practice
for design, installation, commissioning and maintenance of systems
in non-domestic premises’
States that “Methods of cable support should be non-combustible and such TECHNICAL DATA & CLASSIFICATION
that circuit integrity will not be reduced below that afforded by the cable used,
and should withstand a similar temperature and duration to that of the cable, 6.1.1 Metallic SDHT -
while maintaining adequate support” TYPE One Bolt Fabricated High Temperature Stainless Steel
To adhere to this BSI standard fire rated Cable Cleats must be used to support Cable Cleat
the cable in the event of a fire. DESIGN SPECIFICATION IEC 61914
CABLE CLEATS
TEMPERATURE FOR
PERMANENT APPLICATION -60°C to +250°C IEC 61914
Surpasses requirements of Fire testing BS5839/BS8491/
FIRE TESTED EN50200/BS8434/AS-NZS 3013 (1,200°C)(Fire, shock &
water)
Pass - 120 second flame application time
E
NEEDLE FLAME TEST
A IEC 61914, IEC 60695-11-5
LATERAL LOAD TEST 480N IEC 61914
AXIAL LOAD TEST 28N IEC 61914
IMPACT RESISTANCE Pass - Very heavy IEC 61914
MATERIAL Stainless Steel 316L
H
MATERIAL COLOUR Silver / grey
PARALLEL FORMATION
A
One short circuit 600mm fixed cleat Two short circuit 600mm fixed cleat
W D
centres 100mm cable centres centres 100mm cable centres
SECTION A-A
0.1 sec 0.1 sec
60kA Peak 60kA Peak
29kA r.m.s 29kA r.m.s
CABLE CLEAT SELECTION TABLE
HELIOS CABLE Ø RANGE DIMENSIONS MM
WEIGHT (g)
PART NO. TAKE (MM) W H D E FIXING HOLE Ø
FPC1013 10-13 38 19 40 14 1 x M10 88
FPC1316 13-16 41 22 40 14 1 x M10 103
FPC1619 16-19 45 25 40 14 1 x M10 114
FPC1923 19-23 50 29 40 14 1 x M10 128
FPC2327 23-27 55 33 40 14 1 x M10 143
FPC2732 27-32 61 38 40 14 1 x M10 165
FPC3238 32-38 67 44 40 14 1 x M10 182
FPC3846 38-46 74 52 40 14 1 x M10 210
FPC4651 46-51 80 57 40 14 1 x M10 233
FPC5157 51-57 86 63 40 14 1 x M10 252
FPC5765 57-65 94 71 40 14 1 x M10 274
Coatings are available upon request by adding the following suffixes to the ordering reference – EC for epoxy coating, PC for polyester coating and TC for thermoplastic coating. Example order reference
for epoxy coating suffix EC (FPC2327EC). Fasteners required to secure the cable cleat to the support structure are not included but can be supplied upon request - see cleat fixing pack page 64-65.
Isolation/separation pads (to prevent corrosion between two dissimilar metals) are not included but can be supplied on request - see isolation/separation pad page 66.
www.cmp-products.com TDS716 REV 3 03/18