1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. AIR VALVE CHAMBERS SHALL BE COVERED WITH APPROVED VENTILATED HEAVY DUTY DUCTILE IRON COVERS TO IS EN 124 RATING
DIAMETER OF MAIN UP TO 250 (mm) 250 TO 350 (mm) D400. COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY WASAC.
3. AIR VALVES SHALL COMPLY WITH THE REQUIREMENTS OF IS EN 1074-4. AIR VALVES SHALL BE DOUBLE ORIFICE TYPE AND SHALL INCLUDE
AN ISOLATING VALVE. THE ISOLATING VALVE SHALL BE EITHER A GATE VALVE CONFORMING TO IS EN 1074-2 & SHALL BE OF A BOLTLESS
DIAMETER OF BRANCH 80mm 100mm BONNET DESIGN, OR A BUTTERFLY VALVE TO IS EN 1074-2.
5. AIR VALVE CHAMBERS TO BE OF IN-SITU CASTED CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVE CONCRTE
BORE OF VALVE INLET 80mm 100mm
HOLLW BRICKS CHAMBER UNITS MAY ALSO BE USED.
6. IN-SITU CASTED CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED MATERIAL AS PER
200 600 200 STD-W-13.
7. DUCTILE IRON PIPES / FITTINGS AND HDPE PIPES / FITTINGS TO BE IN ACCORDANCE WITH IS EN 545 AND IS EN 12201:2011.
200 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING RICA WSS-CD-13 AT ALL TEES, BENDS, TAPERS,
DEAD ENDS AND PIPES AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. THE LOCATION OF THE AIR VALVE SHALL BE THE SUBJECT OF PARTICULAR AGREEMENT WITH WASAC TO ENSURE THAT THE RISK
OF CONTAMINATION THROUGH THE VALVE IS ELIMINATED.
BULL NOSE 12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
FINISH 13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO RTDA'S REQUIREMENTS.
RICA-AV
600
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS BY RTDA
200
PLINTH DETAIL IN SEE NOTES 13,15
FINISHED GROUND LEVEL GRASS AREA
MAXIMUM
COVER TO BE SET IN CEMENTITIOUS
MAXIMUM
COVER TO BE SET IN CEMENTITIOUS
250
REFER TO NOTE 2 ON RICA WSS-CD-4
EPOXY RESIN/POLYESTER MORTAR EPOXY RESIN/POLYESTER MORTAR
250
30N/mm2 1 TO 2 COURSES OF CLASS B 30N/mm2
SOLID ENGINEERING BRICK
IN-SITU CASTED CONCRETE UNIT SET IN M30 MORTAR
(REFER TO NOTE 6.) 215mm THICK 20N/mm² CONCRETE
TO IS EN 998
BLOCKWORK IN ACCORDANCE
WITH IS EN 771-3
DOUBLE AIR VALVE
900 MIN.
DOUBLE AIR VALVE
ISOLATING VALVE ISOLATING VALVE
D.I. RISER PIPE TO SUIT D.I. RISER PIPE TO SUIT
DEPTH OF COVER TO MAIN & DEPTH OF COVER TO MAIN &
TO ENABLE ROTATION OF TO ENABLE ROTATION OF
100
100
HANDLE (90° DOWNWARDS) HANDLE (90° DOWNWARDS)
WITH ENOUGH CLEARANCE WITH ENOUGH CLEARANCE
LOCALLY
LOCALLY
TO CONCRETE BEARING SLAB TO CONCRETE BEARING SLAB
MIN.
MIN.
REFER TO RICA WSS-CD-4
150
150
(RISER CAN BE PE FITTING). (RISER CAN BE PE FITTING).
FOR BEDDING AND
C25 / 30 PRECAST BACKFILLING DETAILS C25 / 30 PRECAST
CONCRETE BEARING CONCRETE BEARING
SLAB SLAB
HDPE PIPE HDPE PIPE
FUSION WELD FUSION WELD FUSION WELD FUSION WELD
FUSION WELD HDPE TEE FUSION WELD POLYETHYLENE TEE
SECTION WITH FLANGED BRANCH SECTION WITH FLANGED BRANCH
1030
800
600 600
RICA-AV 75mm HIGH
RICA-AV 75mm HIGH
1030
800
600
600
LETTERING LETTERING
HEAVY DUTY DUCTILE IRON
COVER AND FRAME, STAMPED
''RICA-AV'' CLASS D400 (ALL CLASS
D400 COVERS TO HAVE A FRAME
DEPTH OF 150 - 100mm AND OPE
SIZE TO BE 600mm x 600mm)
ROOF PLAN ROOF PLAN
900 50 215 600 215 50
50
50 100 100 50
600
50
215
215mm THICK 20N/mm² CONCRETE
100
IN-SITU CASTED CONCRETE
BLOCKWORK IN ACCORDANCE
UNITS
108
105
WITH IS EN 771-3
180
180
(REFER TO NOTE 6.)
67 67 67
900
600
600
67
DOUBLE DOUBLE
AIR VALVE AIR VALVE
180
180
100
215
SECTION
50
FLOOR PLAN
DOUBLE AIR VALVE
50
FLOOR PLAN
DOUBLE AIR VALVE
(IN-SITU CASTED CONCRETE
(BLOCKWORK CONSTRUCTION)
CONSTRUCTION)
SCALE: 1:50 DATE
RICA WSS-CONSTRUCTION DRAWING DETAILS MAY-2025
TITLE DRAWING No. REV
IN-LINE AIR VALVE RICA WSS-CD-5
(Sheet 1 of 2)
No. Date Drn Chk Description App