0% found this document useful (0 votes)
85 views1 page

HRVU - Control Systems Lindab

The document outlines the control systems available for HRVU units, including EVO, EVO+, and CTR08, detailing their functionalities such as fan management, air defrosting, alarms, home automation, and other features. It emphasizes the ease of switching between control systems post-installation by replacing the remote panel. Key functions include manual fan speed selection, automatic adjustments based on environmental sensors, and remote monitoring capabilities.

Uploaded by

stomakos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
85 views1 page

HRVU - Control Systems Lindab

The document outlines the control systems available for HRVU units, including EVO, EVO+, and CTR08, detailing their functionalities such as fan management, air defrosting, alarms, home automation, and other features. It emphasizes the ease of switching between control systems post-installation by replacing the remote panel. Key functions include manual fan speed selection, automatic adjustments based on environmental sensors, and remote monitoring capabilities.

Uploaded by

stomakos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

lindab | we simplify construction

All of our HRVU units (excepted URU and DELI with specific controls) could be equipped with EVO or EVO+ control system. Only for residential HRVU
it’s also available CTR08 control system. It is possible to change from one system to the other included after installation (easy and quick) by simply
replacing the remote panel:

FAN MANAGEMENT
CTR08 EVO EVO+
1 Manual selection of the fan speed
a) OFF + 3 speed levels
b) OFF + adjustment between [MIN-MAX]
2 Imbalance between supply and return airflows: for electronic or dual-inverter fans
3 Unit power reduction: reduction of the fan maximum speed
(not available for units equipped with 3-speed fans)
4 Automatic fan speed selection, if coupled to a CO2 , CO2 /VOC, UR sensor or to a 0-10V remote signal
5 Booster function (fans at maximum speed); time can be set by the User
6 PIR function (presence detector), time can be set by the User
7 Humidity function: fans at maximum speed if the humidistat exceeds the threshold
8 Fire function: return fan at maximum speed, supply fan turned off
9 Independent control of the single fans
10 Fan automatic speed selection if coupled with a pressure/constant volume Kit

AIR DEFROSTING AND/OR POST-TREATMENT MANAGEMENT


11 Prevention of heat exchanger freezing
a) Imbalance between airflows (MAX extraction/ MIN introduction)
b)Air flow balance (progressive, then MAX)
c) On-off electric pre-heating
12 Control of recovery airflow temperature (or supply air)
a) On-off or proportional electric post-heating
b) On-off or proportional water pre-heating
c) On-off or proportional water post-cooling

ALARMS (DIAGNOSTICS)
13 Visualization of the machine operation status
a) Simplified (LED)
b) Detailed (digital display)
14 Remote signal of the unit operation status
Closed contact = fans ON; open contact = fans OFF
15 Check the status of the filters through the unit maintenance timer or by reading the signal from the
differential pressure switches
16 Check the status of the fans through direct tachometric signal or differential pressure switches
17 Remote signalling of general alarm or clogged filters
Closed contact = no alarms; open contact = ongoing alarm

HOME AUTOMATION
18 Publishing of all status and alarm signals on the bus line
19 Receipt of all remote management controls from the bus line

OTHER FUNCTIONS
20 Bypass management on-off or modulating

21 Remote fan switch ON/OFF


22 Weekly chrono-programming
23 “Master & slave” management of more identical units (up to 4) with a single control panel
24 Possibility to change the language of the remote control panel (English, Italian etc.)
25 Web server

26 Management recirculation dampers

27 Alternate or contemporary management of two H2O batteries or electric (cold warm / dehumidification)