TECHNICAL DATA SHEET
for use by Architects & Engineers
Wet Alarm Valve
Model No: LF-WAV100A & LF-WAV150A
Material
1 Body Cast iron (GC200)
2 Cover Cast iron (GC200)
3 Seat ring Bronze(BC6)
4 Clapper Cast iron (GC200)
5 Clapper seat Rubber(Viton)
6 Clapper pin STS 304
7 Latch Cast Iron(GC200)
8 Latch pin Brass(C3604)
9 Cover bolt Steel
10 Setting bolt Steel
11 Knob handle Brass(C3604)
12 Chamber Cast Iron(GC200)
13 Chamber cover Cast Iron(GC200)
14 Chamber Cover Bushing Bronze (BC6)
15 Chamber Cover Piston Brass(C3604)
16 Chamber Cover 1 Cast Iron(GC200)
Features 17 Push Rod Brass(C3604)
18 Push Rod Guide Bronze(BC6)
• Cast iron body for extra hydrostatic strength 19 Push Rod Disc Brass(C3604)
• Quick removal and easy service for rubber-faced clapper 20 Diaphragm Rubber(EPDM)
• UL Listed
• FM Approved Setting Pressure Table Unit: kgf /cm2
Description Water supply pressure Min. Air pressure Max Air pressure
1.5 1.5 2.0
As an essential part of a wet sprinkler system, LIFECO Wet Alarm Valve is used as a device 3 1.5 2.0
that detects water flow in the fire equipment installed in residential area, manufacturing 5 1.5 2.0
area, and so on. 7 1.5 2.0
8.5 1.5 2.0
The valve is designed to initiate an alarm during a sustained flow of water (such as the 10 1.7 2.2
flow required by an open sprinkler) by operating an optional water motor alarm and/or a 10 over 2.2 2.7
pressure switch.
When a sustained flow of water occurs, such as an activated sprinkler, open sprinkler or an Operational Mechanism of Alarm Valve
open authorized person’s test connection, the clapper lifts from its closed position, this
allows water flow into the intermediate chamber through the holes in the seat ring and it
will fill the retarding chamber completely. The water flows from intermediate chamber to
the alarm line and activates the water motor alarm and/or the pressure switch for the
electric alarm. These alarm continue to sound until the flow of water stops.
Technical & Environmental Specification
Direction Vertical
Max working pressure 12.3Kgf/cm²
Test pressure 21Kgf/cm²
Flange size KS B1513 10K FF Flange (or ANSI 150lb)
Color Red In service In activate
Model no. LF-DAV100A LF-DAV150A
Size 100A 150A
Max flowrate (4.5m/sec) 2100 LPM 4800 LPM Variable Pressure Trim
Weight 61Kg 81Kg Retard is required.
Packing 1EA This trim set is used where water supply pressure vary. The retard chamber and
mechanical sprinkler alarm line are drained through a opened test valve line.
HEADQUARTERS Unit 8, Calibre Industrial Park, Laches Close, Four Ashes, Wolverhampton, WV10 7DZ, United Kingdom T +44 1902 798 706 F +44 1902 798 679 E [email protected] lifeco-uk.com
LTDS-10001 Rev. 00 Page 1
TECHNICAL DATA SHEET
for use by Architects & Engineers
Wet Alarm Valve
Model No: LF-WAV100A & LF-WAV150A
A B C D E F G H I J K L
LF-WAV100A 100 175 210 24 250 169 415 8-19D 376 50A 50 153
LF-WAV150A 150 240 280 26 280 199 480 8-23D 391 50A 50 153
HEADQUARTERS Unit 8, Calibre Industrial Park, Laches Close, Four Ashes, Wolverhampton, WV10 7DZ, United Kingdom T +44 1902 798 706 F +44 1902 798 679 E [email protected] lifeco-uk.com
LTDS-10001 Rev. 00 Page 2