Classifying code or document type
ABB Oy PERFORMANCE DATA OF MOTOR
Motors & Generators
Department/Author Date of issue Lang. Rev. date Our ref.
Azouz Ben Chahla 29.4.2022 En
Customer ref. Saving Ident Rev./Changed by Pages
Water pipe line project : 200 MPDS-3994HH200EN-A A 1/1
Driven Motor: Pump
Motor type code AMI 500L6A BAFH
Motor type Squirrel cage motor
Mounting designation IM 1001
Protected by enclosure IP 55
Method of cooling IC 611
Insulation Class F
Standards IEC
Ambient temperature, max. 40 °C
Altitude, max. 1000 m.a.s.l.
Converter supply ACS 880 (min. avg. fsw 2 kHz)
Duty type S1
Temp. rise Class B (RES)
Connection of stator winding Delta
Rated output 0- 2000,0 kW
Voltage 0- 690 V
Frequency 0- 49,85 Hz
Speed 0- 991 rpm
Current 0- 2020 A
Power Factor 0- 0,86
Efficiency 0- 96,2 %
Relat. maximum torque 0- 2,7
Rated torque 0- 19271 Nm
Direction of rotation Bi-directional
Inertia rotor Approx. 87 kgm²
Bearings Antifriction
This performance data is final and the motor will be manufactured accordingly. All motor data is
subject to tolerances in accordance with IEC.
Efficiency based on typical additional load losses acc. measurements.
*) Insulation for high voltage VSD, restricted for application where voltage stress level on the
terminals of the motor is below following values (taking account cable reflections):
- Max. allowed voltage stress phase-to-phase 4 kV peak
- Max. allowed voltage stress phase-to-ground 2.3 kV peak
- Max du/dt phase-to-phase 3 kV/s
ABB Oy
Motors & Generators Visiting Address Postal Address Telephone Telefax
Strömbergintie 1 B P.O.Box 186 +358 10 222 000 +358 10 222 3565
HELSINKI FIN-00381 HELSINKI
FINLAND Finland
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
©Copyright 2018 ABB