CDTA 2N000 LCD - Datasheet

The Series CDTA Communicating Carbon Dioxide Detectors measure CO2, humidity, temperature, and include features like Modbus® and BACnet communications for easy installation. They utilize a dual wavelength NDIR sensor for CO2 measurement and are designed for environments occupied 24/7, with options for calibration and remote displays. The detectors are suitable for applications such as demand control ventilation in various indoor settings and come with a limited warranty.

Uploaded by

moises_perpetuo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
75 views1 page

CDTA 2N000 LCD - Datasheet

The Series CDTA Communicating Carbon Dioxide Detectors measure CO2, humidity, temperature, and include features like Modbus® and BACnet communications for easy installation. They utilize a dual wavelength NDIR sensor for CO2 measurement and are designed for environments occupied 24/7, with options for calibration and remote displays. The detectors are suitable for applications such as demand control ventilation in various indoor settings and come with a limited warranty.

Uploaded by

moises_perpetuo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

®

AIR QUALITY
SERIES CDTA

COMMUNICATING CARBON DIOXIDE DETECTORS


Measures CO2, Humidity, Temperature, Temperature Set Point, and Override YEAR LIMITED
WARRANTY

1.10
[27.96] .552
[14.02]

2x .176
[4.47]
4.50 3.000
[114.30] [76.20]
.573
[14.56]
2.80
[71.12] 1.08
[27.33] 1.18 1.16
[30] [29.39]

VIDEO ON 3.65 .33


European style North American style [92.72] [8.38] 3x .15
LI

3x .37 [3.87]
NE

[9.36]
3.56
[90.42]

The Series CDTA Communicating Carbon Dioxide Detectors combine the function SPECIFICATIONS
of three room sensors into a single, compact housing. Parameters include carbon Sensor (CO2): Single beam, dual wavelength NDIR; Humidity: Capacitive polymer;
dioxide, humidity, temperature, and temperature set point with override. By having Temperature: 10K Ω thermistor.
field selectable Modbus® and BACnet Communications, only four wires are needed Range: CO2: 0 to 2000 or 5000 PPM CO2 (depending on model); Humidity: 0 to
for power and the communication signal. The communicating detectors can be daisy 100% RH; Temperature: 32 to 122°F (0 to 50°C).
chained together to further reduce installation cost. In order to reduce the set up time, Accuracy: CO2: ±40 PPM ±3% of reading; RH: ±2% (10 to 90% RH); Temperature:
the RS-485 MAC address is set up using on board dip switches. A second set of ±1°C @ 25°C.
dip switches are used to select whether output is Modbus® RTU or BACnet MS/TP Temperature Dependence (CO2): ±8 PPM / °C at 1100 PPM.
communication protocols and to limit access to the set up menu. Non-Linearity (CO2): 16 PPM.
Like our Series CDT Carbon Dioxide Transmitter, the Series CDTA uses a Single Pressure Dependence (CO2): 0.13% of reading per mm of Hg.
Beam Dual Wavelength Non-Dispersive Infrared (NDIR) sensor to measure the carbon Response Time (CO2): 2 min= for 99% step change.
dioxide level. This technology can be used in installations that will be occupied 24 Temperature Limits: 32 to 122°F (0 to 50°C).
hours per day. For improved accuracy, the transmitter can be field calibrated to the Humidity Limits: 10 to 95% RH (non-condensing).
environmental conditions of the installation. Also, the barometric pressure can be Power Requirements: 10-42 VDC / 10-30 VAC.
programmed to correct for altitude. The humidity uses a capacitive polymer sensor and Power Consumption: Average: 0.5 watts; Peak: 1.2 watts.
the temperature is measured using a 10KΩ thermistor sensor. The humidity sensor is Output: 2-wire RS-485, Modbus® RTU or BACnet MS/TP communication protocol.
field replaceable without the need for additional calibration. Weight: 4.4 oz (125 g).
Optional local and remote displays are available to display any of the parameters. For Enclosure Rating: IP20.

Carbon Dioxide
applications in which the building occupants aren’t familiar with CO2 concentrations, Agency Approvals: BTL, CE.

Transmitters
the LCD can be programmed to display temperature, humidity, or temperature set
point instead.

FEATURES/BENEFITS
• Digital Intelligent Temperature Compensation Algorithm (DITCA) corrects for
errors due to self heating effects of combination wall sensors
• Field selectable Modbus® and BACnet communications reduces wiring
• Single beam dual wavelength CO2 sensor
• Replaceable humidity/temperature sensor
• Physical hardware lockout ACCESSORIES
• Optional remote display tool Model Description
GCK-200CO-2000CO2 Calibration gas kit includes a 99.99% nitrogen gas cylinder
APPLICATIONS for calibrating the zero point and a 200 PPM CO / 2000
• Demand control ventilation in schools, office buildings, hospitals, and other indoor PPM CO2 gas cylinder for calibrating the span point on
environments Dwyer’s gas sensing transmitters
• LEED® certification A-449 Remote LCD display allows remote indication of
select Dwyer® wall mount transmitters for validation or
certification purposes
MODEL CHART A-CDT-KIT Accessory kit including terminal block and power supply
Model CO2 Concentration Housing Style Display
CDTA-2N000 2000 PPM North American No
CDTA-2N000-LCD 2000 PPM North American Yes
CDTA-2E000 2000 PPM European No
CDTA-2E000-LCD 2000 PPM European Yes
CDTA-5N000 5000 PPM North American No
CDTA-5N000-LCD 5000 PPM North American Yes
CDTA-5E000 5000 PPM European No
CDTA-5E000-LCD 5000 PPM European Yes

GCK-200CO-2000CO2 A-449
OPTIONS
To order add suffix: Description
-FC Factory calibration certificate
LEED® is a registered trademark of the U.S. Green Building Council.
Example: CDTA-2N000-FC Modbus® is a registered trademark of Schneider Automation, Inc.

DWYER INSTRUMENTS, INC. | dwyer-inst.com 229