The document outlines the design and implementation of photovoltaic (PV) systems, detailing software tools, panel types, configurations, and system types (on-grid and off-grid). It covers essential calculations for sizing panels, inverters, and batteries, as well as guidelines for installation, protection, and earthing. Additionally, it addresses energy yield calculations and the impact of temperature on power production.

Uploaded by

AshikHakkim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views15 pages

Solar Design

The document outlines the design and implementation of photovoltaic (PV) systems, detailing software tools, panel types, configurations, and system types (on-grid and off-grid). It covers essential calculations for sizing panels, inverters, and batteries, as well as guidelines for installation, protection, and earthing. Additionally, it addresses energy yield calculations and the impact of temperature on power production.

Uploaded by

AshikHakkim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

PVSyst Program is the software for designing PV System

Staad Pro software for designing Panel arrangement

CELL
Monocrystalline-cell edge cut diagonally
Polycrystalline
Thin film

60-72 cell in a panel= ie 12 x 6 arrangement


Half cut is 144 cell = ie 12 x 6 x 2
panel size (1 - 1.3) x (1.8 - 2.1) mtr

Solar Power generation

Back side white sheet is of EVA- ethylene vinyl acetate


MC4 connector for joints
On-Grid Solar system
String Inverter, Micro inverter, Mini central inverter, Central inverter

Off-Grid Solar system


Battery system- lead acid
Panel Connection
Series Connection- V increases & I same
Parallel connection- Viseversa
Series & Parallel connection

Protection
PANEL MOUNTING
Southern Hemisphere- South facing wall
Northern Hemisphere- South facing wall

Rafter , Purlin & clamp

CHANNEL STRUCTURE
END CLAMP & MID CLAMP

Earthing
Silicon+Ph - N type panel with extra 1 electron increasing
Less light induced degradation
Better performance in low light & high temperature
Silicon+Boron- P type panel with 1 less atom or hole reduce conductivity
Boron interact with oxygen cause degradation
Residential <10kw commercial <1mw Utility scale
Max system voltage should not exceed 600VDC
DC Shock- 6-9mA
ELV-50Vac/120Vdc
LV-1000Vac/1500Vdc
HV- above LV
mount system
Roof Top
Fixed/Ground mount system
Single axis tracking & dual axis tracking system
DC DC Converters
Buck , Boost & Buck boost converter

SOLAR Panel positioning


Row distance b/w panels(D) = 3 x width of one panel (to avoid shadow for large installation)
for Latitude upto 25 'C, Tilt angle = 0.87 x Latitude
for Latitude b/w 25-50 'C, Tilt angle = (0.87 x Latitude)+ 3.1
for Latitude above 50 'C, Tilt angle = 45'C

ON GRID SOLAR SYSTEM


DCR Panel for subsidy- make in india
Vpeak = Vmean(240) x sqrt 2 = 339.14V

Selection Of panel based on daytime production


PV s/m size = Daytime energy use(kwh) = ______kw
Roof Performance(4.2)
Generation factor or Roof Performance = Peak sun Hour(4.5) x s/m efficiency
Selection Of Inverter
Per Day Consumption = Annual consumption(kwh) = ______kwh
12month x30.4days

If need to reduce 50% of the total bill = Per day consumption x 0.5
Array size = Required per day consumption(kwh) = ______kw
Generation factor(4.2)
Inverter Size = Round(Array Size)
Matching Array & Inverter Voltages
Temp>25 c Power production decreases
Temp<25 c Power production increases

Based on array Size Consider a panel wattage


Required Panel details- Open circuit Voltage(Voc), Temp Coefficient(%/'C), Nominal or ambient temperature
Required Inverter details Inverter max voltage(Vmp)-- some times for low value inverter shows max Voc

Temp coeff in terms of V/'C = %/'C x Voc = ______V/'C


100

Voc based on min temp = Voc+[V/'C x {ambient temp(22) - std temp(25)}] ______Voc at min T

Max no of panel in a string = Inverter max (Vmp) = ______panels


Calculated Voc max

Voc based on max temp = Voc+[V/'C x {ambient temp(41) - std temp(25)}] ______Voc at max T

Min no of panel in a string = Inverter min (Vmp) = ______panels


Calculated Voc min

Matching Array & Inverter Current


Required Panel details- Short circuit current(Isc)
Required Inverter details Max Input current(Imp)

Max no of strings in parallel = Inv max current Imp = ______panels


Panel module Isc

Matching Array & Inverter Power


Required Panel details- Panel watts Wp
Required Inverter details Inverter max Power Kw

No of Panels = Wp = ______panels
Inverter Power Kw

MPPT Inverters
No of DC connection 6 means, 6 strings can connect in one mppt, no need to make array
No of MPPT 2 means, 2 array or strings can connect according to mppt power and dc connection
Battery System
Lead Acid battery - stdby, backup,ups
Gel battery - very deep cycle application(Medical)
Absorber Glass Mat battery - Boat & motorcycle
Hybrid car battery - mechanical
Alkaline battery - household

Each cell gives 2V(+ & -)


12Plate needed for 24V
Charge battery with voltage higher than battery voltage
14.5 volt for 12 volt battery.
Use Hydrometer to check battery charge

Method of charging-
Constant Dc current - slow charging but safer
Constant DC voltage - Fast charging, decreases lifetime of battery

OFF GRID SOLAR SYSTEM


Non-DCR Panel for low budget
Depth of discharge- How much we can discharge the battery

PV SIZING
Per Day usage of Load in Kwh or Energy = Appliance(kw) x Running Hour(h) = ______kwh/D

PV Sizing based on Inverter = Pout / Pin = Efficiency


Pout is the per day usage of load (Kw)

per day energy required from PV(Kwh) = Power Input = ______kwh


Charger & Battery losses(0.85)

Required PV size(Considering losses) = Per day Kwh x 1.3 = ______kw


4.32(Generation factor-India)

Generation Factor = Peak Sun Hour(PSH) x s/m eff(.75)


Select No. of panel in series & Parallel by selecting a panel and divide the total pv size by individual pv size
No. of panel in series based on Voc & Parallel based on Isc
INVERTER SIZING
Per Day usage of Load in Kw = Appliance(kw) x 1.2 = ______kw
Select Inverter based on the value & Note down the inverter efficiency
Inverter shall be considered based on max & min Voc, Isc

BATTERY SIZING
AH Size = Per Day usage in Kwh x No. of days backup required = ______Ah
DOD(0.5) x Losses(0.85) x Nominal battery Voltage
Select battery voltage based on s/m voltage, So that we can find no. of battery in Series

= Total Ah = _____No.
No. of battery in series x Selected battery Ah

SOLAR CHARGE CONTROLLER


Should match the charge controller voltage with PV system & Batteries
Charge controller should withstand the max array Isc & Voc
= No. of strings in parallel(Np) x Isc x 1.3
Check for Voc & Vdc = No. of module in series(Ns) x (Module voltage)Vm

Charging current(cc) = Panel Wattage(Wp) x 1.2


Nominal battery Voltage
PV SYSTEM PROTECTION
Breaker rating 1.56 x Current
1.2 x Voltage

Panel protection
Max series fuse rating or Imod reverse
Calculation for string & array protection are same
No of strings in parallel(Np)
If Np<3 and dc cable rated 1.56 x Isc, protection not necessory
if, Isc module x {Np - 1} > Module Max series fuse rating or Np>3 , then protection is required

DC Breaker rating for module protection = 2fuse/string(+ & -)

Current rating 1.56 x Isc module < Itrip current of breaker selected < 2.4 x Isc module
Voltage rating 1.2 x Voc x Ns

DC Breaker rating for Inverter protection = 1.25 x Isc array = ______Adc

When considering I trip current, consider series Voc also.


Each MPPT shall be protected

Inverter protection
Load side = Imp of inverter(AC) x 1.25 = ______Aac

Ground fault, Under Voltage(27), Anti-islanding, Over frequency(81O),


Under frequency(81U), Instantaneous over current & Earth
fault(50/51), IDMT over current & Earth fault(50N/51N)

Overload, Over Temp, Short Circuit- Fuses & MCB


Over voltage(59) -SPD

Selection of AC Bbusbar = 1.25 x Inverter max current + Main breaker < Busbar rating X 1.2
Inverter max current x 240V = System size in AC

Earthing
SPD to limit transient over voltages
If array voltage>120 , min wire size 4 mm2
allowed dc cable drop 3%
allowed ac cable drop 3-5%
Separate earthing for DC, AC & LA and make it a grid
Earth pit depth- 1 - 2.5mtr, Distance - 3 -5 mtr

Imax of the pv system = Isc x 1.25 x Np


A(Area of earthing conductor) = Isc x sqrt t(operating time of disconnection device- 1 or 3) = ___mm2
K(current rating of earthing material Cu or Al or GI)
or Isc or fault current / sqrt of ( soil resistivity x fault current time)

Consider corrosion factor also- ug=1.3, Air= 1.15 = ___mm2


A(Area of earthing conductor) = A(Area of earthing conductor) x Corrosion factor

Total earth resistance due to earth pit =

Total earth resistance due to earth strip =

Lightening
Min earth spike distance to maintain from solar panel- 2.5 mtr
Required earth pit of LA for safe operation- 3 No.
DC Cable Sizing
Imax through cable = Isc x 1.25 x Np
Derated CCC = Derating factor(1/sqrt n) x Rated CCC of selected cable
n is the no. of cable in a conduit
DCCC > Imax through cable
Power loss % = (max nominal current of array) Imp2 x R(ohm/mtr) x L(cable) x 100
Total power

Voltage drop (Vd) = (max nominal current of array) Imp x R(ohm/mtr) x L(cable)
No. of runs

Voltage drop % = Vd x 100


Max nominal voltage of string(Vms)

AC Cable Sizing =
Imax through cable = Isc x 1.25 x Np
Derated CCC = Derating factor(0.8 in air, 0.7 in UG) x Rated CCC of selected cable
n is the no. of cable in a conduit
DCCC > Imax through cable
Power loss % = (max nominal current of array) Imp2 x R(ohm/mtr) x L(cable) x 100
Inverter Power

Voltage drop (Vd) = (max nominal current of array) Imp x R(ohm/mtr) x L(cable)
No. of runs

Voltage drop % = Vd x 100


Max nominal voltage of inverter(Vms)

Energy Yield
= Rated power(Wp) x site irradiation(PSH) x s/m eff(.75) ______kwh/year
Annual irradiation(PSH) = 365 x shading(.95) x 4.5PSH = ______kwh/year

Size of array = Energy Needed(kwh/day) = ______kwh/year


Energy Yield in days(kwh/year/365)

Energy yield based on selected PV panel = Total PV area(A) x PV eff x annual irradiation x Perf Ratio ______kwh/year