0% found this document useful (0 votes)
58 views27 pages

W Dmans: Works

This document is a material submittal for HVAC works at the Ajman Specialty General Hospital, submitted by Woodmans Meditech LLC. It includes details about the DX FCUS system, specifications of ducted split units, and compliance statements. The document outlines the equipment's features, performance data, and installation requirements.

Uploaded by

noinformation47
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views27 pages

W Dmans: Works

This document is a material submittal for HVAC works at the Ajman Specialty General Hospital, submitted by Woodmans Meditech LLC. It includes details about the DX FCUS system, specifications of ducted split units, and compliance statements. The document outlines the equipment's features, performance data, and installation requirements.

Uploaded by

noinformation47
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

MATERIAL SUBMITTAL FOR

HVAC WORKS

CLIENT

PROJECT

MAINTENANCE AND DEVELOPMENT


WORKS OF AJMAN SPECIALTY
GENERAL HOSPITAL BUILDING

MAIN CONTRACTOR

WOODMANS
TABLE OF CONTENTS

S.NO. DESCRIPTION BRAND

01. DX FCUS SKM, UAE


Client:- Project:- Main Contractor:-
MAINTENANCE AND
DEVELOPMENT WORKS

MATERIAL SUBMITTAL

Client Ajman Specialty General Hospital Serial No. RAD/2025/HVAC/MAR-017


Project Maintenance and Development Works Prev. No. N/A
Main Contractor Woodmans Meditech LLC Date 31-07-25
Medical Eng cont. Woodmans Meditech LLC

Item Description: Material Submittal for DX FCUS List of Enclosure:

Location: All Applicable Area as per the Approved Shop Drawings


□ Compliance Statement
Submittal Description: □ HVAC □ Civil
□ Catalogues / Model
Manufacturer / Supplier: M/s.WOODMANS MEDITECH LLC □ Test Results
Country of Origin / Brand: SKM, UAE □ List of Previous Projects Done

Reason for Alternative: N/A


□ Other - DCL
Contractor's statement: we confirm that we have checked all items submitted herewith and found them in complianceCertificates
with the contract documents and fit to the required purpose
except:

Submitted by ME Contractor: Signature & Stamp: Client Representative : Signature & Stamp

Name: Woodmans meditech LLC Name:

Date: 22-08-2025
Date: 22-08-2025

Civil / MEP Engineer's Instructions and Comments: Date:

Signature:

Client Representative Comments:

The above submittal is: □ Approved □ Approved as noted □ Resubmit □ Rejected

Client Representative : Signature & Stamp: Received by Contractor: Signature & Stamp:
Name: Name:

Date: Date:
CLIENT: WOODMANS

SPECIFIED DATA OFFERED DATA


CALCULATE
Performance @ 115 Deg F Ambient Pipe Size mm (Inch) Max Pipe Length m Dimension (WxDxH) mm Net Weight Kg POWER SUPPLY (V/PH/HZ)
D LOAD Power
TR @ EER @ T3
SN Unit Type QTY TYPE MODEL Fan Speed Input kW @ QTY
Total Nominal Total Sensible Airflow On- Coil (Btuh/W)
ESP Pa T3 Liquid Gas Total Vertical Indoor Outdoor Indoor Outdoor Indoor Outdoor
TR KW KW L/S Deg F

1 DUCTED SPLT UNIT 5 2 Ducted Top Discharge RXVPG-060/DDPPG-060 5.00 14.00 11.70 827 76 / 63 50 Pa Medium 6.360 8.33 Ø9.52 (3/8") Ø22.2 (7/8") 55.0 45.0 1549x760x459 762x762x884 74.0 111.0 220-240/1/50 380-415/3/50 2
RX+DDP (06)
Ducted Split System

50Hz

Range 1.5 TR to 5 TR
( 6 kW to 18 kW)
SKM Ducted Split Units RX+DDP

Contents
Introduction
Introduction..........................................2 Recommended Line Sizes................10
Legend................................................2 Typical Refrigeration Piping...............11 The Ducted Split system from SKM consists
Nomenclature......................................3 Typical Wiring Diagram.....................12 of RX (a high efficiency- TOP discharge Air
Features & Specification................. 4-5 Dimensional Data........................ 13-14 Cooled Condensing Unit); matching with
Combination Ratings....................... 6-7 Outdoor Unit Clearance DDP (a low noise, ceiling suspended indoor
Electrical Data.....................................8 and Spacing......................................15 fan coil unit). This split systems are ideally
Options................................................8 Guide Specification...........................16 suited for apartments, houses, offices, shops,
Fan Performance.................................9 small residences, and in small commercial
establishments.

SKM ducted split system are available in


different models covering 1.5 TR to 5 TR (6
kW to 18 kW) at nominal AHRI condition, which
make them ideally suited for a very small foot
print for space saving and a pleasant exterior
Legend appearance.

The following legends are used throughout this manual: SKM ducted split system are designed in
accordance with ESMA, other GCC regulations.

AFR ...... Air Flow Rate EER.....Energy Efficiency Ratio


SKM ducted split units are suitable to operate
cfm ....... Cubic feet per minute LAWB ... Leaving Air Wet Bulb
in a wide range of ambient temperature.
dB ........ Decibels lbs .........Pounds weight (British units)
EADB ....Entering Air Dry Bulb l/s ..........Liters per second (Minimum outdoor operating ambient in
EAWB ....Entering Air Wet Bulb Mbh ...... 1000 Btuh cooling mode is 55°F (13°C), maximum is
ET ..........Evaporating Temperature OD .........Outside Diameter 125°F (52°C).
Hz ........ Hertz Ph ..........Phase
kW ........ Kilowatts Pa ..........Pascals SKM ducted split units are internally wired
kg ......... Kilograms SC ........ Sensible Capacity and all that required to be done on site is
kPa ...... Kilo Pascals TC .........Total Capacity ducting, refrigerant piping, power supply and
LADB .....Leaving Air Dry Bulb TR ........ Tons of refrigeration = 12 MBH suitable room thermostat installation and field
PSI........Pounds Per Square Inch V ............Volts wiring, which reduces the installation work and
COP......Coefficient of Performance
consequently keeps to a minimum cost.

SKM provides qualified service and stock of


replacement parts in all major cities of the
G.C.C. countries, Egypt, Jordan, and Pakistan.
See back cover for details.

SKM Air Conditioning LLC


SKM reserves the right to change, in part or in
whole the specifications of its Air Conditioning
Equipment at any time in order to add the latest
technology. Therefore, the enclosed information
may change without any prior notice.

You name it.....We cool it

2
R-410A
REFRIGERANT

Nomenclature
Nomenclature
Nomenclature
Ducted Split Nomenclature Outdoor
Ducted Split Nomenclature Outdoor
Ducted Split Nomenclature Outdoor
R X 18 P S1 V C 06
R X 18 P S1 V C 06
Internal Code
Remote Air Cooled Condenser
Internal Code
Remote Air Cooled Condenser
Direct Expansion

Direct Expansion Application


Nominal Capacity in
C : Cooling
18 Application
Nominal Capacity in 24
C : Cooling
18 36
24 48 Air Discharge
36 60 V : Vertical Discharge
48 Air Discharge
60 V : Vertical Discharge
Power Supply
Refrigerant Y: 380-415V/3Ph/50Hz
Power Supply
S1: 220-240V/1Ph/50Hz
P : R410A Y: 380-415V/3Ph/50Hz
Refrigerant
S1: 220-240V/1Ph/50Hz
P : R410A

Ducted Split Nomenclature Indoor


Ducted Split
Ducted Nomenclature
Split Indoor
Nomenclature Indoor
FCU DD P 24 4 P C 06
FCU DD P 24 4 P C 06
Fan Coil Unit Internal Code

Fan Coil Unit Internal Code


Series Name
DD : Direct Driven
Series Name
DD : Direct Driven Application
C : Cooling
Application
Ceiling suspended with
Plenum C : Cooling
Ceiling suspended with
Plenum Refrigerant
Unit Size P : R410A
Refrigerant
18
Unit Size 24
P : R410A
18 36 Number of Rows
24 48
36 60 Number of Rows
48
60

S.K.M Air Conditioning LLC


3
SKM Ducted Split Units RX+DDP

Outdoor fan
General Features
- The fan is direct driven by weatherproof motor (IP44 and
insulation class F) to ensure the reliability & continuous
Outdoor Unit - RX operation.
- Statically and dynamically balanced drive motor design with
Design Features: (Air Cooled units up to 5 Tons easy maintenance-free bearing for outdoor installation.
of Refrigeration) - The fan is multi-blade, Vane-axial type, made of metal material
for quiet operation and durability.

Electrical control box


- Electrical control box with the PCB board, wiring internal to the
unit colored and numbered for simplified identification.
- The PCB parts can be coated with double-side moisture proof
paint, and the outer side of electric box metal cover is spray-
painted (Customized).

General
Indoor Unit - DDP
- The outdoor units are top-discharge type. The units with
weatherproof heavy gauge base are factory assembled, Design Features
internally wired, fully charged refrigerant and 100% run tested
to check cooling operation, fan rotation and control sequence
before leaving the factory.

Casing
- Unit casing constructed from Zinc coated, heavy gauge
Galvanized Steel. Casing
- G90 galvanized heavy gauge plate conforming to ASTMA
653, followed by baked on electrostatic polyester dry powder - The unit constructed from Heavy Gauge Zinc coated steel
coat paint on all external panels, completely weatherized for sheets.
outdoor installation and properly reinforced and brazed. - The sheet steel zinc coated by hot dip process confirming to
- Salt spray test for steel sheet under 1,000 hours, special standard ASTMA 653.
treatment can be up to 2,000 hours and even more
(Customized). Evaporator
- Cabinet construction designed to be easy for maintenance. - Internally finned.
- Service panels are easily removable and re-installed by - Copper tubes mechanically bonded to a configured hydrophilic
removing the screws. Aluminum fin, which is a standard.
- Coils are leak tested in factory to ensure that the pressure
Compressor integrity. The evaporator coil is already leak tested to 3,100
kPa (450 psig).
- All are Copeland - totally enclosed hermetically scroll
- Anti-corrosion treatment for coils is optional.
compressor.
- The Compressors have internal overload relay, High-pressure
Drain pan
switch, low-pressure switch and discharge temperature sensor
as a standard. - The condensate drain pan fabricated from EPS. The inner of
the drain pan adopts vacuum forming technology.
Condenser
Indoor fan
- Internally finned.
- Copper tubes mechanically bonded to a configured hydrophilic - The indoor units have centrifugal fan, which is direct driven
Aluminum fin shall be standard. Coils are leak tested at the by indoor fan motor.
factory to ensure the pressure integrity. The evaporator coil
is already leak tested to 3,100kPa (450 psig). Anti-corrosion Filter
treatment for coils is optional. - The Nylon washable type filter already fixed in the frame of
air return.

4
R-410A
REFRIGERANT

Specification (Outdoor Unit RX)


Outdoor Unit Model RX 18 (06) RX 24 (06) RX 36 (06) - 1ph RX 36 (06) - 3ph RX 48 (06) RX 60 (06)
Power supply 220 - 240V/1Ph/ 50Hz 220 - 240V/1Ph/ 50Hz 220 - 240V/1Ph/ 50Hz 380-415V/50Hz/3Ph 380-415V/50Hz/3Ph 380-415V/50Hz/3Ph
Ambient temperature in cooling °C 17 - 54 17 - 54 17 - 54 17 - 54 17 - 54 17 - 54
Max. Power Input W 2,400 3,000 4,000 4,000 6,000 7,450
Max. Input Current A 11.5 14.5 20 8 12 15
Type Scroll Scroll Scroll Scroll Scroll Scroll
Brand Copeland Copeland Copeland Copeland Copeland Copeland
Capacity Btu/h 16,300 20,300 30,000 29,300 41,500 50,000
Qty. 1 1 1 1 1 1
Input Power W 1,750 2,110 2,940 2,940 4,040 4,750
Compressor
Capacitor 40µF/450V 40µF/450V 80µF/450V \ \ \
Rated current (RLA) A 10 12.5 17.7 6.6 8.6 10.9
Locked rotor Amp. (LRA) A 52 60 98 46 51.5 64
Thermal protector Internal Internal Internal Internal Internal Internal
Refrigerant oil ml 739 739 1,242 (POE) 1,242 1,240 1,685 (POE)
Type Axial fan Axial fan Axial fan Axial fan Axial fan Axial fan
Motor brand Welling Welling Welling Welling Welling Welling
Qty. 1 1 1 1 1 1
Outdoor Fan Capacitor 6µF/450V 6µF/450V 6µF/450V 6µF/450V 15µF/450V 15µF/450V
Motor input W 150 150 230 230 320 320
Air Flow cfm 1,400 3,000 5,100 5,100 5,770 6,850
Speed r/min 970 970 900 900 900 900
Fin type Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum
Coil (W H) mm 1,371 580 1,565 588 2,005 714 2,005 714 2,005 798 2,125 798
Coil
mm 5 7 7 7 7 7
Tube outside Dia. and type
\ Inner grooved Inner grooved Inner grooved Inner grooved Inner grooved Inner grooved
Outdoor noise level dB(A) 58 62 64 64 68 68
m3/h 1,400 3,000 5,100 5,100 5,770 6,850
Air flow
CFM 824 1,765 3,000 3,000 3,394 4,029
Type \ R410A R410A R410A R410A R410A R410A
Refrigerant
Charge g 1,920 2,420 3,320 3,420 4,120 4,320
Design pressure MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6
Liquid side mm 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8")
Refrigerant pipe
Gas side mm 19.1 (3/4") 19.1 (3/4") 19.1 (3/4") 19.1 (3/4") 22 (7/8") 22 (7/8")
Power wire (Outdoor unit) \ 3 2.5mm2 3 2.5mm2 3 4.0mm2 5 2.5mm2 5 2.5mm2 5 2.5mm2
Connection wire

Table 1
Signal wire \ 2 0.75mm2 2 0.75mm2 2 0.75mm2 2 0.75mm2 2 0.75mm2 2 0.75mm2
Dimension (W H D) mm 554 633 554 600 633 600 710 759 710 710 759 710 710 843 710 740 843 740
Net / Gross weight kg 55/58 59/62 86/90 81/85 89/93 98/102

Specification (Indoor Unit DDP Matched with Outdoor Unit RX)


Matching Outdoor Unit Model RX 18 (06) RX 24 (06) RX 36 (06) - 1ph RX 36 (06) - 3ph RX 48 (06) RX 60 (06)
Indoor Unit Model DDP 18 (06) DDP 24 (06) DDP 36 (06) DDP 48 (06) DDP 60 (06)
Power supply 220-240V/1ph/50Hz 220-240V/1ph/50Hz 220-240V/1ph/50Hz 220-240V/1ph/50Hz 220-240V/1ph/50Hz
Btu/h 18000 23800 35000 34400 48000 57000
Capacity
W 5274 6975 10258 10082 14068 16706
Cooling (T1) Input W 1552 2050 2865 2970 4140 4870
W/W 3.4 3.4 3.58 3.4 3.4 3.43
EER
Btu/h.W 11.6 11.6 12.2 11.6 11.6 11.7
Btu/h 16000 20600 30200 29800 41500 50000
Capacity
W 4690 6038 8851 8734 12163 14654
Cooling (T3) Input W 1975 2512 3512 3634 5123 6173
W/W 2.37 2.4 2.52 2.4 2.37 2.37
EER
Btu/h.W 8.1 8.2 8.6 8.2 8.1 8.1
Rated input W 120 332 393 393 740 930
Rated current A 0.6 1.53 1.8 1.8 3.27 4.1
Brand Welling Welling Welling YONGAN YONGAN
Indoor Fan Motor Input (Hi/Med/Lo) W 152/125/117 332/278/234 393/332/278 930/660/592 930/660/592
Capacitor \ 3.5µF/450V 10µF/450V 10µF/450V 15µF/450V 15µF/450V
Fin type \ Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum
Tube size mm 7 7 7 9.52 9.52
Indoor coil
Tube type \ Inner Grooved Copper Pipe Inner Grooved Copper Pipe Inner Grooved Copper Pipe Inner Grooved Copper Pipe Inner Grooved Copper Pipe
Coil(W H) mm (955 147) + (955 147) 955 336 955 336 996 355.6 996 355.6
3
m /h 1,125/901/831 1,743/1,530/1,338 1,850/1,675/1,472 2,759/2,536/2,332 3,312/2,759/2,536
Indoor Air Flow
CFM 662/530/489 1,025/900/787 1,088/985/866 1,623/1,492/1,372 1,948/1,623/1,492
External static pressure Pa 25 (0 - 87) 25 (0 - 100) 37 (0 - 75) 50 (0 - 125) 50 (0 - 125)
Indoor noise level dB(A) 42/38/37 49/46/44 51/49/46 52/51/50 54/52/51
Refrigerant Type \ R410A R410A R410A R410A R410A
Design pressure MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6
Liquid side 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8")
Refrigerant mm
Gas side 19.1 (3/4") 19.1 (3/4") 19.1 (3/4") 22 (7/8") 22 (7/8")
Max. equivalent Pipe length m 55 55 55 55 55
Connection Pipe
Max. difference in level m 46 46 46 46 46
Connecting Power wire (Indoor unit) \ 3 2.5mm2 3 2.5mm2 3 2.5mm2 3 2.5mm2 3 2.5mm2
wire Signal wire \ 2 0.75mm2 2 0.75mm2 2 0.75mm2 2 0.75mm2 2 0.75mm2
Drain Pipe size (OD) mm 25 (1") 25 (1") 25 (1") 25 (1") 25 (1")
Operation temperature °C
Table 2

18 - 30 18 - 30 18 - 30 18 - 30 18 - 30
Dimension (W H D) mm 1,220 210 500 1,230 270 775 1,230 270 775 1,300 420 691 1,300 420 691
Wired Controller KJR-90H/BMWC-E KJR-90H/BMWC-E KJR-90H/BMWC-E KJR-90H/BMWC-E KJR-90H/BMWC-E

Notes:
1. Capacity ratings are based on AHRI Standard 210/240. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb
and condenser entering air temperature of 95ºF (35ºC) dry bulb.
2. Evaporator entering air conditions of 84.2°F/66.2°F (29.0°C/19.0°C) dry bulb/wet bulb and condenser entering air temperature of
114.8°F(46°C) dry bulb, (Net Capacity).
3. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb and condenser entering air
temperature of 118.4ºF (48ºC) dry bulb.

S.K.M Air Conditioning LLC


5
SKM Ducted Split Units RX+DDP

Combination Ratings - DDP with RX Units


RX 18 - DDP 18
Indoor air ODU IWB °C (°F) 15 (59) 17.2 (63) 19.4 (67) 21.7 (71)
flow
Temp.
cfm (m3/h) (DB) IDB °C (°F) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 23.9 (75) 26.7 (80) 29.4 (85)

TC kBtu/h (kW) 16.6 4.9 16.9 5.0 17.2 5.0 17.5 5.1 17.7 5.2 17.7 5.2 18.1 5.3 18.5 5.4 18.8 5.5 18.8 5.5 18.8 5.5 19.2 5.6 20 5.9 20 5.9 20 5.9

29.4 (85) SC kBtu/h (kW) 13.6 4.0 16.9 5.0 17.2 5.0 17.5 5.1 10.6 3.1 14.2 4.2 18.1 5.3 18.5 5.4 7.5 2.2 11.1 3.3 14.9 4.4 18.6 5.5 8 2.3 11.6 3.4 15.4 4.5

PI kW 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37

TC kBtu/h (kW) 15.9 4.7 16.2 4.7 16.5 4.8 16.8 4.9 16.9 5.0 16.9 5.0 17.2 5.0 17.5 5.1 18 5.3 18 5.3 18 5.3 18.4 5.4 19.1 5.6 19.1 5.6 19.1 5.6

35 (95) SC kBtu/h (kW) 13.2 3.9 16.2 4.7 16.5 4.8 16.8 4.9 10.3 3.0 13.9 4.1 17.2 5.0 17.5 5.1 7.2 2.1 10.8 3.2 14.4 4.2 18.2 5.3 7.6 2.2 11.3 3.3 15.1 4.4 Airflo

PI kW 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55

TC kBtu/h (kW) 15.1 4.4 15.4 4.5 15.7 4.6 16 4.7 16.1 4.7 16.1 4.7 16.4 4.8 16.7 4.9 17.1 5.0 17.1 5.0 17.1 5.0 17.4 5.1 18.2 5.3 18.2 5.3 18.2 5.3

40.6 (105) SC kBtu/h (kW) 12.8 3.8 15.4 4.5 15.7 4.6 16 4.7 9.8 2.9 13.5 4.0 16.4 4.8 16.7 4.9 6.8 2.0 10.4 3.0 14 4.1 17.4 5.1 7.5 2.2 11.1 3.3 14.7 4.3

PI kW 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.76 1.76 1.76 1.76 1.76 1.76
660 (1120)
TC kBtu/h (kW) 14.2 4.2 14.5 4.2 14.8 4.3 15.1 4.4 15.1 4.4 15.1 4.4 15.4 4.5 15.7 4.6 16.1 4.7 16.1 4.7 16.1 4.7 16.4 4.8 17.1 5.0 17.1 5.0 17.1 5.0

46.1 (115) SC kBtu/h (kW) 12.5 3.7 14.5 4.2 14.8 4.3 15.1 4.4 9.5 2.8 13.1 3.8 15.4 4.5 15.7 4.6 6.4 1.9 10 2.9 13.7 4.0 16.4 4.8 7 2.1 10.6 3.1 14.2 4.2

PI kW 1.95 1.95 1.95 1.95 1.95 1.95 1.95 1.95 1.96 1.96 1.96 1.96 1.96 1.96 1.96 1.96 1.97 1.97 1.97 1.97 1.97 1.97 1.97 1.97 1.98 1.98 1.98 1.98 1.98 1.98

TC kBtu/h (kW) 13.1 3.8 13.4 3.9 13.7 4.0 14 4.1 14 4.1 14 4.1 14.3 4.2 14.6 4.3 14.9 4.4 14.9 4.4 14.9 4.4 15.2 4.5 16 4.7 16 4.7 16 4.7

47.8 (118) SC kBtu/h (kW) 11.9 3.5 13.4 3.9 13.7 4.0 14 4.1 9 2.6 12.6 3.7 14.3 4.2 14.6 4.3 6 1.8 9.5 2.8 13.3 3.9 15.2 4.5 6.6 1.9 10.2 3.0 13.9 4.1

PI kW 2.02 2.02 2.02 2.02 2.02 2.02 2.02 2.02 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.06 2.06 2.06 2.06 2.06 2.06
5)
TC kBtu/h (kW) 12.1 3.5 12.3 3.6 12.5 3.7 12.8 3.8 13 3.8 13 3.8 13.3 3.9 13.6 4.0 13.9 4.1 13.9 4.1 13.9 4.1 14.2 4.2 14.8 4.3 14.8 4.3 14.8 4.3
5.9
51.7 (125) SC kBtu/h (kW) 11.5 3.4 12.3 3.6 12.5 3.7 12.8 3.8 8.6 2.5 12.2 3.6 13.3 3.9 13.6 4.0 5.6 1.6 9.2 2.7 12.8 3.8 14.2 4.2 6.1 1.8 9.8 2.9 13.5 4.0

Table 3
4.5
PI kW 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.23 2.23 2.23 2.23 2.23 2.23 2.23 2.23 2.24 2.24 2.24 2.24 2.24 2.24
.37

5.6 Air flow TC SC kW

4.4 Airflow Correction Factors Low Spead 580CFM (990m /h) 3 0.98 0.96 0.99

.55 High Spead 740CFM (1,260m3/h) 1.02 1.06 1.01

5.3

4.3 RX 24 - DDP 24
.76 Indoor air
ODU IWB °C (°F) 15 (59) 17.2 (63) 19.4 (67) 21.7 (71)
flow
5.0 Temp.
cfm (m3/h) (DB) IDB °C (°F) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 23.9 (75) 26.7 (80) 29.4 (85)
4.2
TC kBtu/h (kW) 22.3 6.5 22.7 6.7 23.2 6.8 23.7 6.9 23.7 6.9 23.7 6.9 23.7 6.9 24.2 7.1 25.1 7.4 25.1 7.4 25.1 7.4 25.1 7.4 26.7 7.8 26.7 7.8 26.7 7.8
.98
29.4 (85) SC kBtu/h (kW) 17.2 5.0 21.6 6.3 23.2 6.8 23.7 6.9 13.5 4.0 17.8 5.2 22 6.4 24.2 7.1 9.8 2.9 14.1 4.1 18.3 5.4 22.6 6.6 10.1 3.0 14.4 4.2 19 5.6
4.7
kW kW 1.84 1.84 1.84 1.84 1.84 1.84 1.84 1.84 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.86 1.86 1.86 1.86 1.86 1.86
4.1
TC kBtu/h (kW) 21 6.2 21.4 6.3 21.8 6.4 22.2 6.5 22.4 6.6 22.4 6.6 22.8 6.7 23.3 6.8 23.8 7.0 23.8 7.0 23.8 7.0 23.8 7.0 25.3 7.4 25.3 7.4 25.3 7.4
.06
35 (95) SC kBtu/h (kW) 16.4 4.8 21 6.2 21.8 6.4 22.2 6.5 12.8 3.8 17 5.0 21.7 6.4 23.3 6.8 9 2.6 13.3 3.9 17.6 5.2 22.1 6.5 9.6 2.8 13.9 4.1 18.2 5.3
4.3
kW kW 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05 Air
4.0
TC kBtu/h (kW) 19.7 5.8 20.1 5.9 20.5 6.0 20.9 6.1 21 6.2 21 6.2 21.4 6.3 21.8 6.4 22.4 6.6 22.4 6.6 22.4 6.6 22.8 6.7 23.8 7.0 23.8 7.0 23.8 7.0
.24
40.6 (105) SC kBtu/h (kW) 15.8 4.6 20.1 5.9 20.5 6.0 20.9 6.1 12.2 3.6 16.6 4.9 21 6.2 21.8 6.4 8.5 2.5 12.8 3.8 17.2 5.0 21.7 6.4 9 2.6 13.3 3.9 17.6 5.2
kW kW 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.26 2.26 2.26 2.26 2.26 2.26 2.26 2.26 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.29 2.29 2.29 2.29 2.29 2.29
780 (1326)
TC kBtu/h (kW) 18.3 5.4 18.7 5.5 19.1 5.6 19.5 5.7 19.5 5.7 19.5 5.7 19.9 5.8 20.3 5.9 20.8 6.1 20.8 6.1 20.8 6.1 21.2 6.2 22.2 6.5 22.2 6.5 22.2 6.5
46.1 (115) SC kBtu/h (kW) 15.2 4.5 18.7 5.5 19.1 5.6 19.5 5.7 11.5 3.4 15.8 4.6 19.9 5.8 20.3 5.9 7.9 2.3 12.3 3.6 16.4 4.8 21 6.2 8.4 2.5 12.9 3.8 17.1 5.0
kW kW 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.51 2.51 2.51 2.51 2.51 2.51 2.51 2.51 2.53 2.53 2.53 2.53 2.53 2.53 2.53 2.53 2.54 2.54 2.54 2.54 2.54 2.54
TC kBtu/h (kW) 17.8 5.2 18.2 5.3 18.6 5.5 19 5.6 19 5.6 19 5.6 19.4 5.7 19.8 5.8 20.3 5.9 20.3 5.9 20.3 5.9 20.7 6.1 21.7 6.4 21.7 6.4 21.7 6.4
47.8 (118) SC kBtu/h (kW) 15 4.4 18.2 5.3 18.6 5.5 19 5.6 11.4 3.3 15.6 4.6 19.4 5.7 19.8 5.8 7.7 2.3 12 3.5 16.2 4.7 20.7 6.1 8.2 2.4 12.6 3.7 16.9 5.0
5) kW kW 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.61 2.61 2.61 2.61 2.61 2.61 2.61 2.61 2.63 2.63 2.63 2.63 2.63 2.63
.8 TC kBtu/h (kW) 16.7 4.9 17 5.0 17.3 5.1 17.6 5.2 17.8 5.2 17.8 5.2 18.2 5.3 18.6 5.5 19.1 5.6 19.1 5.6 19.1 5.6 19.5 5.7 20.4 6.0 20.4 6.0 20.4 6.0
.6 51.7 (125) SC kBtu/h (kW) 14.4 4.2 17 5.0 17.3 5.1 17.6 5.2 10.9 3.2 15.1 4.4 18.2 5.3 18.6 5.5 7.3 2.1 11.5 3.4 15.9 4.7 19.5 5.7 7.8 2.3 12 3.5 16.5 4.8
Table 4

86 kW kW 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.81 2.81 2.81 2.81 2.81 2.81 2.81 2.81 2.82 2.82 2.82 2.82 2.82 2.82 2.82 2.82 2.84 2.84 2.84 2.84 2.84 2.84
.4
.3 Air flow TC SC kW
05 Airflow Correction Factors Low Spead 680CFM (1,156m3/h) ×0.98 ×0.96 ×0.99
.0 High Spead 880CFM (1,496m3/h) ×1.02 ×1.06 ×1.01
.2
29
.5
6
R-410A
REFRIGERANT

Combination Ratings - DDP with RX Units


RX 36 - DDP 36 (1ph)
Indoor air
ODU IWB °C (°F) 15 (59) 17.2 (63) 19.4 (67) 21.7 (71)
flow
Temp.
cfm (m3/h) (DB) IDB °C (°F) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 23.9 (75) 26.7 (80) 29.4 (85)

TC kBtu/h (kW) 32.8 9.6 32.8 9.6 33.5 9.8 34.2 10.0 34.9 10.2 34.9 10.2 34.9 10.2 35.6 10.4 37.1 10.9 37.1 10.9 37.1 10.9 37.1 10.9 39.3 11.5 39.3 11.5 39.3 11.5
29.4 (85) SC kBtu/h (kW) 24.3 7.1 29.8 8.7 33.5 9.8 34.2 10.0 19.5 5.7 25.1 7.4 30.7 9.0 35.6 10.4 14.8 4.3 20.4 6.0 26 7.6 31.5 9.2 15.7 4.6 21.2 6.2 26.7 7.8
kW kW 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.58 2.59 2.59 2.59 2.59 2.59 2.59 2.59 2.59 2.6 2.6 2.6 2.6 2.6 2.6
TC kBtu/h (kW) 30.9 9.1 30.9 9.1 31.5 9.2 32.1 9.4 32.9 9.6 32.9 9.6 32.9 9.6 33.6 9.8 35 10.3 35 10.3 35 10.3 35 10.3 37.2 10.9 37.2 10.9 37.2 10.9
35 (95) SC kBtu/h (kW) 23.5 6.9 28.7 8.4 31.5 9.2 32.1 9.4 18.8 5.5 24.3 7.1 29.6 8.7 33.6 9.8 14 4.1 19.6 5.7 25.2 7.4 30.5 8.9 14.9 4.4 20.5 6.0 26 7.6 A
kW kW 2.84 2.84 2.84 2.84 2.84 2.84 2.84 2.84 2.85 2.85 2.85 2.85 2.85 2.85 2.85 2.85 2.86 2.86 2.86 2.86 2.86 2.86 2.86 2.86 2.86 2.86 2.86 2.86 2.86 2.86
TC kBtu/h (kW) 28.9 8.5 29.5 8.6 30.1 8.8 30.7 9.0 30.8 9.0 30.8 9.0 30.8 9.0 31.4 9.2 32.8 9.6 32.8 9.6 32.8 9.6 32.8 9.6 34.9 10.2 34.9 10.2 34.9 10.2
40.6 (105) SC kBtu/h (kW) 22.3 6.5 28.3 8.3 30.1 8.8 30.7 9.0 17.9 5.2 23.4 6.9 29 8.5 31.4 9.2 13.1 3.8 18.7 5.5 24.3 7.1 29.8 8.7 14 4.1 19.5 5.7 25.1 7.4
kW kW 3.13 3.13 3.13 3.13 3.13 3.13 3.13 3.13 3.14 3.14 3.14 3.14 3.14 3.14 3.14 3.14 3.16 3.16 3.16 3.16 3.16 3.16 3.16 3.16 3.18 3.18 3.18 3.18 3.18 3.18
1,000 (1700)
TC kBtu/h (kW) 26.7 7.8 27.2 8.0 27.7 8.1 28.3 8.3 28.5 8.4 28.5 8.4 29.1 8.5 29.7 8.7 30.4 8.9 30.4 8.9 30.4 8.9 30.4 8.9 32.4 9.5 32.4 9.5 32.4 9.5
46.1 (115) SC kBtu/h (kW) 21.4 6.3 27.2 8.0 27.7 8.1 28.3 8.3 16.8 4.9 22.2 6.5 27.9 8.2 29.7 8.7 12.2 3.6 17.6 5.2 23.1 6.8 28.6 8.4 13 3.8 18.5 5.4 24 7.0
kW kW 3.47 3.47 3.47 3.47 3.47 3.47 3.47 3.47 3.49 3.49 3.49 3.49 3.49 3.49 3.49 3.49 3.51 3.51 3.51 3.51 3.51 3.51 3.51 3.51 3.53 3.53 3.53 3.53 3.53 3.53
TC kBtu/h (kW) 26.4 7.7 26.9 7.9 27.4 8.0 27.9 8.2 28.2 8.3 28.2 8.3 28.8 8.4 29.4 8.6 30.1 8.8 30.1 8.8 30.1 8.8 30.7 9.0 32.1 9.4 32.1 9.4 32.1 9.4
47.8 (118) SC kBtu/h (kW) 21.1 6.2 26.9 7.9 27.4 8.0 27.9 8.2 16.6 4.9 22.3 6.5 27.9 8.2 29.4 8.6 12 3.5 17.5 5.1 23.2 6.8 28.9 8.5 12.8 3.8 18.3 5.4 24.1 7.1
.4 (85) kW kW 3.59 3.59 3.59 3.59 3.59 3.59 3.59 3.59 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.62 3.62 3.62 3.62 3.62 3.62 3.62 3.62 3.65 3.65 3.65 3.65 3.65 3.65
TC kBtu/h (kW) 24.8 7.3 25.3 7.4 25.8 7.6 26.3 7.7 26.5 7.8 26.5 7.8 27 7.9 27.5 8.1 28.3 8.3 28.3 8.3 28.3 8.3 28.9 8.5 30.2 8.9 30.2 8.9 30.2 8.9
3 11.5
51.7 (125) SC kBtu/h (kW) 20.3 5.9 25.3 7.4 25.8 7.6 26.3 7.7 15.9 4.7 21.5 6.3 27 7.9 27.5 8.1 11.3 3.3 16.7 4.9 22.4 6.6 28 8.2 12.1 3.5 17.8 5.2 23.3 6.8
7 7.8

Table 5
kW kW 3.88 3.88 3.88 3.88 3.88 3.88 3.88 3.88 3.89 3.89 3.89 3.89 3.89 3.89 3.89 3.89 3.91 3.91 3.91 3.91 3.91 3.91 3.91 3.91 3.94 3.94 3.94 3.94 3.94 3.94
6 2.6
2 10.9 Air flow TC SC kW
6 7.6 Airflow Correction Factors Low Spead 880CFM (1,496m3/h) ×0.98 ×0.96 ×0.99
6 2.86 High Spead 1,130CFM (1,921m3/h) ×1.02 ×1.06 ×1.01
9 10.2
1 7.4 RX 36 - DDP 36 (3ph)
8 3.18 Indoor air
ODU IWB °C (°F) 15 (59) 17.2 (63) 19.4 (67) 21.7 (71)
flow
4 9.5 Temp.
cfm (m3/h) (DB) IDB °C (°F) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 23.9 (75) 26.7 (80) 29.4 (85)
7.0
TC kBtu/h (kW) 32.2 9.4 32.2 9.4 32.8 9.6 33.5 9.8 34.2 10.0 34.2 10.0 34.2 10.0 34.9 10.2 36.3 10.6 36.3 10.6 36.3 10.6 36.3 10.6 38.6 11.3 38.6 11.3 38.6 11.3
3 3.53
29.4 (85) SC kBtu/h (kW) 23.8 7.0 29.3 8.6 32.8 9.6 33.5 9.8 18.8 5.5 24.6 7.2 30.1 8.8 34.9 10.2 14.2 4.2 19.6 5.7 25 7.3 30.9 9.1 15.1 4.4 20.5 6.0 25.9 7.6
1 9.4
kW kW 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.68 2.68 2.68 2.68 2.68 2.68 2.68 2.68 2.69 2.69 2.69 2.69 2.69 2.69
1 7.1
TC kBtu/h (kW) 30.4 8.9 30.4 8.9 31 9.1 31.6 9.3 32.3 9.5 32.3 9.5 32.3 9.5 32.9 9.6 34.4 10.1 34.4 10.1 34.4 10.1 34.4 10.1 36.5 10.7 36.5 10.7 36.5 10.7
5 3.65
35 (95) SC kBtu/h (kW) 22.8 6.7 28.3 8.3 31 9.1 31.6 9.3 18.1 5.3 23.6 6.9 29.1 8.5 32.9 9.6 13.4 3.9 18.9 5.5 24.4 7.2 29.9 8.8 13.9 4.1 19.7 5.8 25.2 7.4
2 8.9
kW kW 2.95 2.95 2.95 2.95 2.95 2.95 2.95 2.95 2.96 2.96 2.96 2.96 2.96 2.96 2.96 2.96 2.97 2.97 2.97 2.97 2.97 2.97 2.97 2.97 2.97 2.97 2.97 2.97 2.97 2.97
3 6.8
TC kBtu/h (kW) 28.5 8.4 29.1 8.5 29.7 8.7 30.3 8.9 30.4 8.9 30.4 8.9 30.4 8.9 31 9.1 32.3 9.5 32.3 9.5 32.3 9.5 32.3 9.5 34.4 10.1 34.4 10.1 34.4 10.1
4 3.94
40.6 (105) SC kBtu/h (kW) 21.9 6.4 27.6 8.1 29.7 8.7 30.3 8.9 17.3 5.1 22.8 6.7 28.3 8.3 31 9.1 12.6 3.7 18.1 5.3 23.6 6.9 29.1 8.5 13.1 3.8 18.6 5.5 24.1 7.1

kW kW 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.27 3.27 3.27 3.27 3.27 3.27 3.27 3.27 3.29 3.29 3.29 3.29 3.29 3.29 3.29 3.29 3.31 3.31 3.31 3.31 3.31 3.31
1,000 (1,700)
TC kBtu/h (kW) 26.4 7.7 26.9 7.9 27.4 8.0 27.9 8.2 28.2 8.3 28.2 8.3 28.8 8.4 29.4 8.6 30.1 8.8 30.1 8.8 30.1 8.8 30.1 8.8 32.1 9.4 32.1 9.4 32.1 9.4
46.1 (115) SC kBtu/h (kW) 20.9 6.1 26.6 7.8 27.4 8.0 27.9 8.2 16.1 4.7 21.7 6.4 27.4 8.0 29.4 8.6 11.4 3.3 17.2 5.0 22.6 6.6 28 8.2 12.2 3.6 17.7 5.2 23.4 6.9

4 (85) kW kW 3.62 3.62 3.62 3.62 3.62 3.62 3.62 3.62 3.64 3.64 3.64 3.64 3.64 3.64 3.64 3.64 3.66 3.66 3.66 3.66 3.66 3.66 3.66 3.66 3.68 3.68 3.68 3.68 3.68 3.68

TC kBtu/h (kW) 25.7 7.5 26.2 7.7 26.7 7.8 27.2 8.0 27.5 8.1 27.5 8.1 28.1 8.2 28.7 8.4 29.4 8.6 29.4 8.6 29.4 8.6 30 8.8 31.3 9.2 31.3 9.2 31.3 9.2
6 11.3
47.8 (118) SC kBtu/h (kW) 20.6 6.0 26.2 7.7 26.7 7.8 27.2 8.0 16 4.7 21.5 6.3 27.3 8.0 28.7 8.4 11.2 3.3 16.8 4.9 22.3 6.5 27.9 8.2 11.9 3.5 17.5 5.1 23.2 6.8
9 7.6
kW kW 3.75 3.75 3.75 3.75 3.75 3.75 3.75 3.75 3.76 3.76 3.76 3.76 3.76 3.76 3.76 3.76 3.78 3.78 3.78 3.78 3.78 3.78 3.78 3.78 3.81 3.81 3.81 3.81 3.81 3.81
9 2.69
TC kBtu/h (kW) 24.1 7.1 24.6 7.2 25.1 7.4 25.6 7.5 25.8 7.6 25.8 7.6 26.3 7.7 26.8 7.9 27.6 8.1 27.6 8.1 27.6 8.1 28.2 8.3 29.4 8.6 29.4 8.6 29.4 8.6
5 10.7
51.7 (125) SC kBtu/h (kW) 19.8 5.8 24.6 7.2 25.1 7.4 25.6 7.5 15.2 4.5 20.6 6.0 26.3 7.7 26.8 7.9 10.5 3.1 16 4.7 21.5 6.3 27.4 8.0 11.2 3.3 16.8 4.9 22.3 6.5
Table 6

2 7.4
kW kW 4.05 4.05 4.05 4.05 4.05 4.05 4.05 4.05 4.07 4.07 4.07 4.07 4.07 4.07 4.07 4.07 4.09 4.09 4.09 4.09 4.09 4.09 4.09 4.09 4.11 4.11 4.11 4.11 4.11 4.11
7 2.97

4 10.1 Air flow TC SC kW

1 7.1 Airflow Correction Factors Low Spead 880CFM (1,496m3/h) ×0.98 ×0.96 ×0.99

1 3.31 High Spead 1,130CFM (1,921m3/h) ×1.02 ×1.06 ×1.01

1 9.4

4 6.9

8 3.68 S.K.M Air Conditioning LLC


3 9.2

2 6.8
7
SKM Ducted Split Units RX+DDP

Combination Ratings - DDP with RX Units


RX 48 - DDP 48
Indoor air
ODU IWB °C (°F) 15 (59) 17.2 (63) 19.4 (67) 21.7 (71)
flow
Temp.
cfm (m3/h) (DB) IDB °C (°F) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 23.9 (75) 26.7 (80) 29.4 (85)

TC kBtu/h (kW) 44.9 13.2 45.8 13.4 46.7 13.7 47.6 14.0 47.7 14.0 47.7 14.0 47.7 14.0 48.7 14.3 50.7 14.9 50.7 14.9 50.7 14.9 50.7 14.9 53.8 15.8 53.8 15.8 53.8 15.8
29.4 (85) SC kBtu/h (kW) 34.1 10.0 43.1 12.6 46.7 13.7 47.6 14.0 26.7 7.8 35.3 10.3 43.9 12.9 48.7 14.3 19.8 5.8 27.9 8.2 36.5 10.7 45.1 13.2 20.4 6.0 29.1 8.5 37.7 11.0

kW kW 3.72 3.72 3.72 3.72 3.72 3.72 3.72 3.72 3.73 3.73 3.73 3.73 3.73 3.73 3.73 3.73 3.74 3.74 3.74 3.74 3.74 3.74 3.74 3.74 3.75 3.75 3.75 3.75 3.75 3.75

TC kBtu/h (kW) 42.4 12.4 43.2 12.7 44.1 12.9 45 13.2 45.1 13.2 45.1 13.2 46 13.5 46.9 13.7 48 14.1 48 14.1 48 14.1 48 14.1 51 14.9 51 14.9 51 14.9
35 (95) SC kBtu/h (kW) 33.1 9.7 41.9 12.3 44.1 12.9 45 13.2 25.7 7.5 34.3 10.1 43.2 12.7 46.9 13.7 18.2 5.3 26.9 7.9 35.5 10.4 44.2 13.0 19.4 5.7 28.1 8.2 36.7 10.8

kW kW 4.11 4.11 4.11 4.11 4.11 4.11 4.11 4.11 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.14 4.14 4.14 4.14 4.14 4.14 4.14 4.14 4.14 4.14 4.14 4.14 4.14 4.14

TC kBtu/h (kW) 39.7 11.6 40.5 11.9 41.3 12.1 42.1 12.3 42.4 12.4 42.4 12.4 43.2 12.7 44.1 12.9 45.1 13.2 45.1 13.2 45.1 13.2 46 13.5 48 14.1 48 14.1 48 14.1 Airflo

40.6 (105) SC kBtu/h (kW) 31.8 9.3 40.5 11.9 41.3 12.1 42.1 12.3 24.6 7.2 33.1 9.7 41.9 12.3 44.1 12.9 17.1 5.0 25.7 7.5 34.3 10.1 43.2 12.7 18.2 5.3 26.9 7.9 35.5 10.4

kW kW 4.54 4.54 4.54 4.54 4.54 4.54 4.54 4.54 4.56 4.56 4.56 4.56 4.56 4.56 4.56 4.56 4.59 4.59 4.59 4.59 4.59 4.59 4.59 4.59 4.62 4.62 4.62 4.62 4.62 4.62
1,550 (2635)
TC kBtu/h (kW) 36.9 10.8 37.6 11.0 38.4 11.3 39.2 11.5 39.4 11.5 39.4 11.5 40.2 11.8 41 12.0 42 12.3 42 12.3 42 12.3 42.8 12.5 44.7 13.1 44.7 13.1 44.7 13.1
46.1 (115) SC kBtu/h (kW) 30.3 8.9 37.6 11.0 38.4 11.3 39.2 11.5 23.2 6.8 31.9 9.3 40.2 11.8 41 12.0 16 4.7 24.4 7.2 33.2 9.7 41.9 12.3 17 5.0 25.5 7.5 34.4 10.1

kW kW 5.05 5.05 5.05 5.05 5.05 5.05 5.05 5.05 5.07 5.07 5.07 5.07 5.07 5.07 5.07 5.07 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.13 5.13 5.13 5.13 5.13 5.13

TC kBtu/h (kW) 35.9 10.5 36.6 10.7 37.3 10.9 38 11.1 38.4 11.3 38.4 11.3 39.2 11.5 40 11.7 41 12.0 41 12.0 41 12.0 41.8 12.3 43.7 12.8 43.7 12.8 43.7 12.8
5)
47.8 (118) SC kBtu/h (kW) 29.8 8.7 36.6 10.7 37.3 10.9 38 11.1 22.7 6.7 31.5 9.2 39.2 11.5 40 11.7 15.6 4.6 24.2 7.1 32.8 9.6 41.4 12.1 16.6 4.9 25.3 7.4 33.6 9.8
5.8
kW kW 5.22 5.22 5.22 5.22 5.22 5.22 5.22 5.22 5.24 5.24 5.24 5.24 5.24 5.24 5.24 5.24 5.27 5.27 5.27 5.27 5.27 5.27 5.27 5.27 5.3 5.3 5.3 5.3 5.3 5.3
1.0
TC kBtu/h (kW) 33.6 9.8 34.3 10.1 35 10.3 35.7 10.5 36 10.6 36 10.6 36.7 10.8 37.4 11.0 38.4 11.3 38.4 11.3 38.4 11.3 39.2 11.5 41 12.0 41 12.0 41 12.0
75
51.7 (125) SC kBtu/h (kW) 28.9 8.5 34.3 10.1 35 10.3 35.7 10.5 21.6 6.3 30.2 8.9 36.7 10.8 37.4 11.0 14.6 4.3 23 6.7 31.5 9.2 39.2 11.5 15.6 4.6 24.2 7.1 32.8 9.6
4.9
kW kW 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.67 5.67 5.67 5.67 5.67 5.67 5.67 5.67 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.74 5.74 5.74 5.74 5.74 5.74
0.8

14 Air flow TC SC kW
Table 7
4.1 Airflow Correction Factors Low Spead 1,360CFM (2,312m3/h) ×0.98 ×0.96 ×0.99

0.4 High Spead 1,740CFM (2,958m3/h) ×1.02 ×1.06 ×1.01

62

3.1

0.1

13

2.8

.8

.3

2.0

.6

74

8
R-410A
REFRIGERANT

Combination Ratings - DDP with RX Units


RX 60 - DDP 60
Indoor air flow ODU Temp. IWB °C (°F) 15 (59) 17.2 (63) 19.4 (67) 21.7 (71)
(DB)
cfm (m3/h) IDB °C (°F) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 21.1 (70) 23.9 (75) 26.7 (80) 29.4 (85) 23.9 (75) 26.7 (80) 29.4 (85)

TC kBtu/h (kW) 53 15.5 53 15.5 54.1 15.9 55.2 16.2 56.4 16.5 56.4 16.5 56.4 16.5 57.5 16.9 60 17.6 60 17.6 60 17.6 60 17.6 63.6 18.6 63.6 18.6 63.6 18.6
29.4 (85) SC kBtu/h (kW) 39.8 11.7 49.3 14.4 54.1 15.9 55.2 16.2 32.1 9.4 41.2 12.1 50.8 14.9 57.5 16.9 24 7.0 33.6 9.8 42.6 12.5 52.2 15.3 25.4 7.4 35 10.3 43.9 12.9

kW kW 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.31 4.31 4.31 4.31 4.31 4.31 4.31 4.31 4.33 4.33 4.33 4.33 4.33 4.33

TC kBtu/h (kW) 50.3 14.7 51.3 15.0 52.3 15.3 53.3 15.6 53.6 15.7 53.6 15.7 53.6 15.7 54.7 16.0 57 16.7 57 16.7 57 16.7 57 16.7 60.6 17.8 60.6 17.8 60.6 17.8
35 (95) SC kBtu/h (kW) 38.7 11.3 48.2 14.1 52.3 15.3 53.3 15.6 30.6 9.0 40.2 11.8 49.3 14.4 54.7 16.0 22.8 6.7 32.5 9.5 41.6 12.2 50.7 14.9 24.2 7.1 33.3 9.8 43 12.6

kW kW 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.85 4.85 4.85 4.85 4.85 4.85 4.85 4.85 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87

TC kBtu/h (kW) 47.4 13.9 48.3 14.2 49.3 14.4 50.3 14.7 50.6 14.8 50.6 14.8 51.6 15.1 52.6 15.4 53.8 15.8 53.8 15.8 53.8 15.8 53.8 15.8 57.3 16.8 57.3 16.8 57.3 16.8
40.6 (105) SC kBtu/h (kW) 37.4 11.0 46.9 13.7 49.3 14.4 50.3 14.7 29.3 8.6 39 11.4 48.5 14.2 52.6 15.4 21.5 6.3 30.7 9.0 40.4 11.8 49.5 14.5 22.9 6.7 32.1 9.4 41.8 12.3

kW kW 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.45 5.45 5.45 5.45 5.45 5.45 5.45 5.45 5.48 5.48 5.48 5.48 5.48 5.48 5.48 5.48 5.51 5.51 5.51 5.51 5.51 5.51
1,700 (2,890)
TC kBtu/h (kW) 44.3 13.0 45.2 13.2 46.1 13.5 47 13.8 47.3 13.9 47.3 13.9 48.2 14.1 49.2 14.4 50.3 14.7 50.3 14.7 50.3 14.7 51.3 15.0 53.6 15.7 53.6 15.7 53.6 15.7
46.1 (115) SC kBtu/h (kW) 35.9 10.5 45.2 13.2 46.1 13.5 47 13.8 27.9 8.2 37.4 11.0 47.2 13.8 49.2 14.4 20.1 5.9 29.7 8.7 38.7 11.3 48.7 14.3 21.4 6.3 31.1 9.1 40.2 11.8

kW kW 6.11 6.11 6.11 6.11 6.11 6.11 6.11 6.11 6.13 6.13 6.13 6.13 6.13 6.13 6.13 6.13 6.17 6.17 6.17 6.17 6.17 6.17 6.17 6.17 6.21 6.21 6.21 6.21 6.21 6.21

TC kBtu/h (kW) 42.1 12.3 42.9 12.6 43.8 12.8 44.7 13.1 45 13.2 45 13.2 45.9 13.5 46.8 13.7 48.1 14.1 48.1 14.1 48.1 14.1 49.1 14.4 51.3 15.0 51.3 15.0 51.3 15.0
47.8 (118) SC kBtu/h (kW) 34.5 10.1 42.9 12.6 43.8 12.8 44.7 13.1 27 7.9 36.5 10.7 45.9 13.5 46.8 13.7 19.2 5.6 28.4 8.3 38 11.1 47.6 14.0 20.5 6.0 30.3 8.9 39.5 11.6
4 (85)
kW kW 6.33 6.33 6.33 6.33 6.33 6.33 6.33 6.33 6.36 6.36 6.36 6.36 6.36 6.36 6.36 6.36 6.39 6.39 6.39 6.39 6.39 6.39 6.39 6.39 6.43 6.43 6.43 6.43 6.43 6.43
6 18.6
TC kBtu/h (kW) 39.2 11.5 40 11.7 40.8 12.0 41.6 12.2 42 12.3 42 12.3 42.8 12.5 43.7 12.8 44.9 13.2 44.9 13.2 44.9 13.2 45.8 13.4 48 14.1 48 14.1 48 14.1
9 12.9
51.7 (125) SC kBtu/h (kW) 33.3 9.8 40 11.7 40.8 12.0 41.6 12.2 25.6 7.5 34.9 10.2 42.8 12.5 43.7 12.8 18 5.3 27.4 8.0 36.8 10.8 45.8 13.4 19.2 5.6 28.8 8.4 38.4 11.3
3 4.33
kW kW 6.89 6.89 6.89 6.89 6.89 6.89 6.89 6.89 6.92 6.92 6.92 6.92 6.92 6.92 6.92 6.92 6.95 6.95 6.95 6.95 6.95 6.95 6.95 6.95 7 7 7 7 7 7
6 17.8

12.6 Air flow TC SC kW


Table 8
7 4.87 Airflow Correction Factors Low Spead 1,550CFM (2,635m3/h) ×0.98 ×0.96 ×0.99

3 16.8 High Spead 2,000CFM (3,400m3/h) ×1.02 ×1.06 ×1.01

8 12.3

1 5.51 Notes:
6 15.7
1. For matched conditions,at entering condition other than shown;consult SKM.
2 11.8
2. Direct interpolation is permissible but extrapolation is prohibited.
1 6.21

3 15.0
3. Combination ratings are based on indoor and outdoor units at the same elevation and connected by 25 ft. (7.6 m) of refrigerant
tubing.For tubing in excess of 25 feet,slight capacity reduction will occur. Do not exceed 120 feet tubing length without checking
5 11.6
with SKM.
3 6.43
4. Cooling capacities listed do not include a deduction for fan motor heat.
14.1

4 11.3 5. TC - total cooling capacity in Mbh (1000 Btuh).


SC - sensible cooling capacity in Mbh (1000 Btuh).
7
PI - Power input in kW.
To convert Mbh to kW,divide by 3.413. / To convert cfm to L/s,divide by 2.12.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data page (10) should be referred for the same.

S.K.M Air Conditioning LLC


9
SKM Ducted Split Units RX+DDP

Electrical Data - RX & DDP

Outdoor Unit Power Supply Compressor OFM


Model
Hz Voltage Min. Max. MCA TOCA MFA MSC RLA KW FLA
RX 18 50 220-240V 198V 254V 12 20 25 52 9 0.085 0.68
RX 24 50 220-240V 198V 254V 14.5 25.7 30 60 11.2 0.085 0.68
RX 36 - 1ph 50 220-240V 198V 254V 21 36.9 40 98 15.9 0.13 1
RX 36 - 3ph 50 380-415V 342V 440V 8.6 15 20 46 6 0.13 1
RX 48 50 380-415V 342V 440V 11.2 19 25 51.5 7.8 0.23 1.1
RX 60 50 380-415V 342V 440V 15.1 26 30 64 10.9 0.23 1.4
Table 9

Indoor Unit Power Supply IFM


Model
Hz Voltage Min. Max. MCA MFA kW FLA
DDP 18 50 220-240V 198V 254V 0.67 15 0.144 0.67
DDP 24 50 220-240V 198V 254V 1.53 15 0.332 1.53
DDP 36 50 220-240V 198V 254V 1.8 15 0.393 1.8
DDP 48 50 220-240V 198V 254V 3.27 15 0.74 3.27
DDP 60 50 220-240V 198V 254V 4.1 15 0.93 4.1
Table 10

Thermostat (Wired Controller)

SKM Wired Controller is a wall mounted decorative type controller, with a large backlit LCD
screen.

KJR-90H/BMWC-E Thermostat features microprocessor-based control. The LCD display


modes include operation status (cooling and ventilation), fan speed, room temperature and
set-point.

the Soft touch keys include on/off and mode, clock / timer on-off / sleeping mode, fan speed /
fan mode and temperature adjustment.

10
R-410A
REFRIGERANT

Service Manual 2015-07 TROPICAL SEER 13 DUCT

Air Flow Performance


4. Airflow Performance
Curve diagram of static pressure, air flow volume.

DDP 18

Service Manual 2015-07 TROPICAL SEER 13 DUCT


DDP 24, 36

11

S.K.M Air Conditioning LLC

12
11
SKM Ducted Split Units RX+DDP

Air Flow Performance

Service Manual 2015-07 TROPICAL SEER 13 DUCT


DDP 48

13

12
R-410A
REFRIGERANT

Air Flow Performance

Service Manual 2015-07 TROPICAL SEER 13 DUCT


DDP 60

14

S.K.M Air Conditioning LLC


13
SKM Ducted Split Units RX+DDP

Piping Limitation & Recommended Sizing


Indoor unit Outdoor unit Max. Total Length (m) Max. Vertical Length (m)
DDP 18 RX 18 55 46
DDP 24 RX 24 55 46
RX 36 - 1ph 55 46
DDP 36
RX 36 - 3ph 55 46
DDP 48 RX 48 55 46
DDP 60 RX 60 55 46

Notes : Table 8
1. Pipe diameters are based on equivalent length of copper tubing sizes.
2. Pipe sizes are based on 2ºF (1.1ºC) or less temperature losses for liquid and suction line in equivalent pipe length.
3. If the condensing unit is below the evaporating unit, the maximum lift should not exceed to 66 feet.
4. Do not exceed 120 feet piping length without checking with SKM.
5. These sizes are for guidance only. For detailed proper piping, refer to recognized piping references like ASHRAE
Guide and Data Book.
The recommended or required suction and liquid line sizes do not necessarily correspond with the refrigerant
connections available on the outdoor or indoor unit. Necessary transformation may be required and it’s field performed.

Liquid Line Size


Liquid Line Size - Outdoor unit higher than indoor unit
Total Equivalent Length (m)
Model No. Liquid /gas pipe (mm)
7.62 15.24 22.86 30.48 38.1 45.72 54.86
Maximum Vertical Separation (m)
18 Φ9.52/Φ15.9 7.62 15.24 22.86 18.9 18.59 17.98 17.37
24 Φ9.52/Φ15.9 7.62 15.24 18.9 18.59 18.29 17.68 17.06
36 Φ9.52/Φ15.9 7.62 15.24 17.98 17.37 16.76 16.15 15.54
48 Φ9.52/Φ22 7.62 15.24 15.85 14.63 13.11 11.58 9.75
60 Φ9.52/Φ22 7.62 15.24 14.33 12.5 10.36 8.53 6.7

Liquid Line Size - Outdoor unit lower than indoor unit


Total Equivalent Length (m)
Model No. Liquid /gas pipe (mm)
7.62 15.24 22.86 30.48 38.1 45.72
Maximum Vertical Separation (m)
18 Φ9.52/Φ15.9 7.62 15.24 22.86 18.9 18.59 17.98
24 Φ9.52/Φ15.9 7.62 15.24 18.9 18.59 18.29 17.68
36 Φ9.52/Φ15.9 7.62 15.24 17.98 17.37 16.76 16.15
48 Φ9.52/Φ22 7.62 15.24 15.85 14.63 13.11 11.58
60 Φ9.52/Φ22 7.62 15.24 14.33 12.5 10.36 8.53

Sound Levels (Outdoor Unit RX)


Model Sound pressure level
RX 18 58dB(A)
RX 24 62dB(A)
RX 36 - 1ph 64dB(A)
RX 36 - 3ph 64dB(A)
RX 48 68dB(A)
RX 60 68dB(A)

Sound Levels (Indoor Unit DDP)


Sound pressure level
Model
High Medium Low
DDP 18 42dB(A) 38dB(A) 37dB(A)
DDP 24 49dB(A) 46dB(A) 44dB(A)
DDP 36 51dB(A) 49dB(A) 46dB(A)
DDP 48 52dB(A) 51dB(A) 50dB(A)
DDP 60 54dB(A) 52dB(A) 51dB(A)

14
R-410A
REFRIGERANT

MCAC-UTSM-201712 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz
Typical Wiring Diagram
4.UNIT
OUTDOOR Wiring
RX Diagrams

MOVTB-18CN1-13C:
RX18

64

S.K.M Air Conditioning LLC


15
SKM Ducted Split Units RX+DDP

Typical Wiring Diagram


OUTDOOR UNIT RX

Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201712

RX24 & RX36 - 1Ph


MOVTB-24CN1-13C, MOVTB-36CN1-13C:

65

16
R-410A
REFRIGERANT

Typical Wiring Diagram


OUTDOOR UNIT RX
MCAC-UTSM-201712 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz

RX36-3Ph,MOVTB-60CN1-R13C:
MOVTB-36CN1-R13C, MOVTB-48CN1-R13C, RX48 & RX60

66

S.K.M Air Conditioning LLC


17
SKM Ducted Split Units RX+DDP

Typical Schematic Diagram


CONNECTION OF INDOOR UNIT & OUTDOOR UNIT
MCAC-UTSM-201712 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz

MTA-18WN1 + MOVTB-18CN1-13C RX18 + DDP18

RX24 + DDP24 & RX36-1Ph + DDP36


MTA-24WN1 + MOVTB-24CN1-13C, MTA-36WN1 + MOVTB-36CN1-13C

92

18
R-410A
REFRIGERANT

Typical Schematic Diagram


CONNECTION OF INDOOR UNIT & OUTDOOR UNIT

Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201712

MTA-36WN1 + MOVTB-36CN1-R13C, MTA-48WN1 + MOVTB-48CN1-R13C

RX36 + DDP36-3Ph, RX48+ DDP48 & RX60+ DDP60


MTA-60WN1 + MOVTB-60CN1-R13C

7. Trial Run

The trial run must be carried out after the entire installation has been completed. Please confirm the

following points before the trial run:

9 The indoor unit and outdoor unit are installed properly.

9 Piping and wiring are correctly completed.

9 The drainage is unimpeded.

9 The ground wiring is connected correctly.

9 The lengths of the piping and the amount of recharged refrigerant have been recorded.

9 The power voltage fits the rated voltage of the air conditioner.

9 There is no obstacle at the air outlet and inlet of the indoor and outdoor units.

9 Check whether all valves are opened.

9 Pre-heated the air conditioner by power on.

93 S.K.M Air Conditioning LLC


19
SKM Ducted Split Units RX+DDP
Service Manual 2015-07 TROPICAL SEER 13 DUCT

Dimensional Data
2. Dimensions
OUTDOOR UNIT RX

Dimensions Refrigerant Connection Service Valve Size


Sale Model
"H" in (mm) "W" in (mm)
Dimensions "L" in (mm) Liquid in (mm)
Refrigerant connectionSuction in(mm)
valve size
Model
MOVTA-24CN1-13C 24-15/16”(633)
H (mm) 23-5/8”(600)
W (mm) 23-5/8”(600)
L (mm) Liquid3/8 (9.53)
(mm) 3/4 (mm)
Gas (19.1)

RX 18
MOVTA-36CN1-13C 633
29-7/8”(759) 554 28”(710) 554 28”(710) Φ9.52
3/8 (9.53) Φ19.1
3/4 (19.1)
RX 24
MOVTA-36CN1-R13C 633
29-7/8”(759) 600 28”(710) 600 28”(710) Φ9.52
3/8 (9.53) Φ19.1
3/4 (19.1)
RX 36-1PH
MOVTA-48CN1-R13C
759
33-3/16”(843)
710 28”(710) 710 28”(710) Φ9.52
3/8 (9.53)
Φ19.1
7/8 (22.2)
RX 36-3PH 759 710 710 Φ9.52 Φ19.1
MOVTA-60CN1-R13C 33-3/16”(843) 29-1/8”(740) 29-1/8”(740) 3/8 (9.53) 7/8 (22.2)
RX 48 843 710 710 Φ9.52 Φ22.2
RX 60 843 740 740 Φ9.52 Φ22.2
21

20
R-410A
REFRIGERANT

Dimensional Data
MTA-18WN1 MTA-24WN1 MTA-36WN1
INDOOR UNIT - DDP 18K , 24K & 36K Models:

Outline dimension and air outlet opening size Unit: mm

Air return opening size Position size of descensional ventilation opening

Air filter
Air filter

Size of mounted lug


Electric control cabinet

Electric control cabinet

Outline dimension Air outlet opening size

A B C D E F G H I

DDP 18 1140 210 500 450 1220 45 950 17 145

DDP 24 1140 270 775 710 1230 65 933 35 179

DDP 36 1140 270 775 710 1230 65 933 35 179

Air return Fresh air


Size of mounted lug
opening size inlet

J K L Filter thickness M N O P T

DDP 18 1040 200 - 10 1180 350 50 20 Φ92

DDP 24 1035 260 20 10 1180 490 26 20 Φ125

DDP 36 1035 260 20 10 1180 490 26 20 Φ125

S.K.M Air Conditioning LLC


21
SKM Ducted Split Units RX+DDP

Dimensional Data
INDOOR UNIT - DDP 48K & 60K Models:
MTA-48WN1 MTA-60WN1 (Unit: mm)
135 930 88

29

56
82

82
249

420
270
PLASTIC COVER

68 24
46 ELECTRICAL CONTROL BOX

CONNECTING POINT OF 169


DRAIN PIPE

15
52
189

179
REFRIGERAN T-PIPE FLANED 43
28
CONNECTION Φ9.52(3/8)
123

123
11
REFRIGERAN T-PIPE FLANED

691
CONNECTION Φ16(5/8)

61
75

35

SAFETY DRAIN CONNECTING PIPE


136
125
339

82
82

31

64 1073

22
R-410A
REFRIGERANT

CONTACT US
HEAD OFFICE

P.O Box: 6004, Sharjah,


United Arab Emirates

Tel: +971 6 514 3333


Fax: +971 6 514 3300

Email: sales@skmaircon.com
Email: info@skmaircon.com

Spare Parts Division


spareparts.skm@skmaircon.com

Service Center
aftersales.skm@skmaircon.com

For SKM Regional Offices & Distributors


visit: www.skmaircon.com

S.K.M Air Conditioning LLC


154/2018
23

You might also like