DATA SHEET

MV110

ISOIL
I N D U S T R I A
MV110_IT_EN_DS053REV08_IS

INDEX

TECHNICAL DATA 3
OVERALL DIMENSIONS 4
The manufacturer guarantees only English text available on our web site [Link]

MV110 EXPLODED LAYOUT 7


MAIN PAGES VISUALISATION 8
ELECTRICAL CONNECTIONS 9
DIGITAL INPUT 10
DIGITAL OUTPUTS 10
ANALOG OUTPUTS 11
FUNCTIONS MENU 12
MI-001 OIML R49 CLASS1: MV110 18
MI-001 OIML R49 CLASS 2: MV110 19
MI-004 OIML R75 CLASS1: MV110 22
HOW TO ORDER 24

2/26 MV110_IT_EN_DS053REV08_IS

TECHNICAL DATA

OVERALL FEATURES
Suitable For ‰ All the ISOMAG® sensors up to the DN 1000
Minimum conductivity ‰ 5 µS/cm
Altitude ‰ -200 m up to 4000 m

‰ -20… +60°C / -4… +140 °F - Aluminium housing


Ambient Temperature
‰ -10… +50°C / +14…+122 °F - Reinforced Nylon

Humidity Range ‰ 0÷100%

STANDARD FEATURES
‰ Compact
Version
‰ Separate

‰ Painted Aluminium die casting


Housing materials
‰ Nylon reinforced with 15% of fiber glass

Protection Rate ‰ IP 67

Power Supply/Consumption ‰ 100-240 V~ (20VA) – 44-66 Hz


Cable Gland ‰ N° 5 cable gland PG 11
The manufacturer guarantees only English text available on our web site [Link]

Full scale value ‰ 0,4…10m/s


Dig. Input ‰ N°1 , programmable function (i.e. Totalizer reset)
Data Storage ‰ Values storing system in case of power failure
Galvanic Isolation ‰ All the inputs/outputs are galvanically isolated from power supply up to 250 V
‰ USB port for the connection to PC (USB cable type A/USB MINI B is required for the
Programming Plug In
programmation)
Bi-Directional ‰ Yes
Diagnostic Funct. ‰ Yes
Empty Pipe Detect. ‰ Yes
CE Certification ‰ Yes

OPTIONAL FEATURES
(CHECK HOW TO ORDER, AT LAST PAGE, FOR MORE DETAILS)
Protection Rate ‰ IP 68
Conn. Sensor Cable ‰ CABLE C014 for separate version
LCD Display ‰ Graphic display 128x64 pixels back light, 3 programming keys
‰ Power supply : 24 … 36 VAC/VDC 0...45/66 Hz
‰ Power supply : 12…48 VDC
Power Supply/Consumption ‰ Power supply : 100 ... 240 VAC 44/66 Hz + 1 Rechargeable Battery
‰ Power supply : 24 … 36 VAC/VDC 0...44/66 Hz + 1 Rechargeable Battery
‰ Power supply : 12…48 VDC + 1 Rechargeable Battery
Outputs: ‰ N°1 digital Output , 1250 Hz, 100mA, 30 Vdc
Pulses/Frequence/Alarms ‰ N°2 digital Outputs , 1250 Hz, 100mA, 30 Vdc
‰ n° 1 Analogue output 0/4...20/22 mA (Hart optional)
Analog Output
‰ n° 2 Analogue outputs 0/4...20/22 mA (Hart optional over Out.1)
‰ RS 485
Communication Gateway
‰ Wi-Fi (for programming)

Data Logger ‰ MicroSD Memory Card 4...32 GBytes

‰ Modbus over RS 485


Protocols
‰ HART (Available on analog output n° 1)
‰ MI-001
MID Certifications
‰ MI-004

ACCURACY
‰ Flow rate (volume) = ±0,05% c.r
Measurements tolerance ‰ Out 4/20 mA = ± 0,08 % c.r
‰ Frequency Out = ± 0,08% c.r
Accuracy (Whole System

ISOIL
‰ See table below
Converter+Sensor)

3/26 MV110_IT_EN_DS053REV08_IS I N D U S T R I A
The manufacturer guarantees only English text available on our web site [Link]

4/26
180 200 Compact version
OVERALL DIMENSIONS

114

114

MV110_IT_EN_DS053REV08_IS
195
164
167

290


The manufacturer guarantees only English text available on our web site [Link]

295

5/26
Separate (wall) version

30
Ø7

MV110_IT_EN_DS053REV08_IS
28

I
142

N
D
U
S
T
R
ISOIL
120

I

A

Horizontal version

144 56
200

Junction box

Junction box
The manufacturer guarantees only English text available on our web site [Link]

Vertical version

87
270

75
Junction box Junction box

6/26 MV110_IT_EN_DS053REV08_IS

MV110 EXPLODED LAYOUT Terminal block cover

DESCRIPTION 3
POS.
PA6 VERSION ALUMINIUM VERSION 4

1 SCREW M4x12 SCREW M5x12 Main housing cover


2 GROWER WASHER Ø4 GROWER WASHER Ø5
5
3 TERMINAL BLOCK COVER TERMINAL BLOCK COVER
4 O-RING-4400
5 PROTECTION COVER 6

6 HOUSING COVER HOUSING COVER


7 ORING-4700 7
8 ORING-117x3
9 DISPLAY
The manufacturer guarantees only English text available on our web site [Link]

10 FIXING DISPLAY FRAME (MATERIAL PA06) 8

11 SELF-TAPPING SCREW 4x10 TRILOBULAR SCREW 4x10


9 26
12 SELF-TAPPING SCREW 4x10 TRILOBURAL SCREW 4x10
13 PCB MV110 10
14 PG9 CAP
15 LITHIUM BATTERY
16 ANTICONDESE CAP 11
17 PA6 MAIN HOUSING ALUMINIUM MAIN HOUSING
18 GROWER Ø4 GROWER Ø5 PCB MV210
19 SCREW M4x12 SCREW M5x12
12
20 O-RING-155
21 VERSION CAP (MATERIAL PA06) 25

22 SCREW M6x16
23 GROWER WASHER Ø6 13
24 PG11 CABLE GLAND
CABLE DIAMETER: Ø5-Ø10mm
Main housing
TERMINAL BLOCK 14
SOLID WIRE: 26-16 AWG / 0.129-1.31 mm²
25 STRANDED WIRE: 26-16 AWG / 0.129-1.31 mm² 15
TORQUE: 3.0 [Link] / 0.34 Nm
24
26 DISPLAY FLAT CABLE 16

17

18

19

20

21

22

ISOIL
23

7/26 MV110_IT_EN_DS053REV08_IS I N D U S T R I A

MAIN PAGES VISUALISATION

Different visualization
possibilities by simply
pressing of a key.
The manufacturer guarantees only English text available on our web site [Link]

8/26 MV110_IT_EN_DS053REV08_IS

ELECTRICAL CONNECTIONS

1 2 3 4

ELECTRODES
E1
E2
C SH

29 28 27 26

RS485
B
A
0V SH
The manufacturer guarantees only English text available on our web site [Link]

25 24 23 22 21 20

4-20 OUTPUTS
OUT2 (+) 4-20 SH
OUT1 (+) 4-20* +24V
OUT1-2 (-) 4-20 0V
* If the option HART is enable

19 18 17 16 15 14

DIGITAL OUTPUTS DIGITAL


OUT2 C INPUTS
SH
OUT1 C IN1 +
OUT 1-2 E IN1 -

13 12 11

COILS
C1
C2 SH

POWER SUPPLY

L (+)
N( - )

9/26 MV110_IT_EN_DS053REV08_IS
ISOIL
I N D U S T R I A

DIGITAL INPUT

10k
on/off input
15 (+)
(external power supply)

16 (-)

21 (+)
The manufacturer guarantees only English text available on our web site [Link]

on/off input 10k


(internal power supply)
15 (+)

16 (-)

22 (-)

DIGITAL OUTPUTS

18 OUT 1(+)
19 OUT 2(+)

17 (COM. OUT 1-2)

10/26 MV110_IT_EN_DS053REV08_IS

ANALOG OUTPUTS

mA
24 OUT 1(+)
25 OUT 2(+)

23 (COM. 4-20 OUT 1-2)


The manufacturer guarantees only English text available on our web site [Link]

11/26 MV110_IT_EN_DS053REV08_IS
ISOIL
I N D U S T R I A

FUNCTIONS
MENU

SENSOR
S. model = 0 1.1 Sensors model: Enter the first two characters of the serial number of the sensor
Lining = UNSPEC. 1.2 Flow sensor lining material type
S. type = FULL BORE 1.3 Type of sensor: fullbore or insertion
u. type = METRIC 1.4 Type of measure units for sensor parameter: metric or imperial
Diam mm 00025.0 1.5 Insert ND of sensor (0-2500)
KA = +00.9637
1.6 Calibration data of sensor visualized on sensor’s label
KA- = -04.4904
KZ = +0000000 1.7 Sensor coefficient KZ (zero point)
KD= +0000000 1.8 Sensor coefficient KD
Ins. position= 0 1.9 Insertion position
KP Dinamic= OFF 1.10 KP dynamic, coefficient for insertion
Ki= 01.8727 1.11 Sensor coefficient Ki
SENSOR Kp= 01.0000 1.12 Sensor coefficient Kp
KC= 1.00000 1.13 Sensor coefficient KC
[Link] = 025.0 1.14 CW volume total. decimal point position
The manufacturer guarantees only English text available on our web site [Link]

[Link]= 004 1.15 Current regulator proportional band


[Link]= 008 1.16 Current regulator derivation constant
S. Freq.= Hz 50 1.17 Measure sampling frequency
Preamplif. OFF 1.18 Enables the preamplifier
E.P Detect= ON 1.19 Enables the empty pipe detection feature
R max= kohm 0500 1.20 Empty pipe detection threshold
El. Cleaning= OFF 1.21 Electrode cleaning
S. cable= m 000 1.22 Sensor connecting cable length
S. err. delay= 010 1.23 Signal error delay (n. sample)
Sens. verify= OFF 1.24 Automatic sensor verify enable
Zero point cal. 1.25 Pipe hydraulic zero calibration
KL 00.00000000 1.27 Coefficient KL values

UNITS
Diam. mm 2.1 Nominal diameter measure unit
[Link] m 2.2 Cable length on separate version
[Link] METRIC 2.3 Flowrate type measure unit: metric or not metric
Pl1 unit METRIC 2.4 Pulse 1 type measure unit: metric or not metric
Pl2 unit METRIC 2.5 Pulse 2 type measure unit: metric or not metric
T+ unit METRIC 2.6 Total direct totalizer measure unit type: metric or not metric
T+ unit g 2.7 Total direct totalizer measure unit
T+ D.P 3 2.8 Total direct totalizer decimal point position
P+ unit METRIC 2.9 Partial direct totalizer measure unit type: metric or not metric
UNITS P+ unit g 2.10 Partial direct totalizer measure unit
P+ D.P 3 2.11 Partial direct totalizer decimal point position
T- unit METRIC 2.12 Total reverse totalizer measure unit type: metric or not metric
T- unit g 2.13 Total reverse totalizer measure unit
T- D.P 3 2.14 Total reverse totalizer decimal point position
P- unit METRIC 2.15 Partial reverse totalizer measure unit type: metric or not metric
P- unit g 2.16 Partial reverse totalizer measure unit
P- D.P 3 2.17 Partial reverse totalizer decimal point position
[Link] °C 2.18 Temperature measure unit
Mass units ON 2.19 Enable/disable the selection of mass units on full scale set
Sg=kg/dm3 1.0000 2.20 Specific gravity coefficient

12/26 MV110_IT_EN_DS053REV08_IS

SCALES
FS1 g/s 4908.7 3.1 Full scale flow rate 1
FS2 g/s 4908.7 3.2 Full scale flow rate 2
Pls1=g 1000.00 3.3 Pulse value on channel 1
SCALES Tpls1=ms 0050.0 3.4 Duration of the pulse generated on channel 1
Pls2=g 1000.00 3.5 Pulse value on channel 2
Tpls2=g 0050.0 3.6 Duration of the pulse generated on channel 2
Frq1=Hz 1000.00 3.7 Full scale frequency for channel 1 (0.1Hz-1000.0Hz)
Frq2=Hz 1000.00 3.8 Full scale frequency for channel 2 (0.1Hz-1000.0Hz)
The manufacturer guarantees only English text available on our web site [Link]

MEASURES
Damping SMART 4.1 Measure filter
4.2 Low flow zero threshold: 0-25% of full scale value
MEASURES Cut-off= %
DT Min.
00.1
ON 4.3 Automatic calibration verify
T1HC enable ON 4.4 Automatic change of measurement range
T1HC OFF 4.5 High immunity inputs

ALARMS
Max+ = dm3/s OFF 5.1 Maximum value alarm set for direct flow rate
Max- = dm3/s OFF 5.2 Maximum value alarm set for reverse flow rate
5.3 Minimum value alarm set for direct flow rate
ALARMS Min+= dm3/s
Min-= dm3/s
OFF
OFF 5.4 Minimum value alarm set for reverse flow rate
Hysterisis=% 03 5.5 Hysteresis threshold set for the minimum and maximum flow rate alarms
mA [Link]=% 000 5.6 Current output value in case of failure
Hz [Link]=% 000 5.7 Frequency output value in case of alarms

INPUTS
T+ reset OFF 6.1 Total direct (positive) flow totalizer reset enable
P+ reset OFF 6.2 Partial direct (positive) flow totalizer reset enable
T- reset OFF 6.3 Total reverse (negative) flow totalizer reset enable
INPUTS P- reset OFF 6.4 Partial reverse (negative) flow totalizer reset enable
Count lock OFF 6.5 Totalizer counting lock command
[Link] OFF 6.6 Measure zero lock command
Calibration OFF 6.7 Calibration external command
Range change OFF 6.8 Range change external command

13/26 MV110_IT_EN_DS053REV08_IS
ISOIL
I N D U S T R I A

OUTPUTS
Out1 PULSES+ 7.1 Output 1 functions
Out2 PULSES- 7.2 Output 2 functions
OUTPUTS Out mA1 4_22 +/- 7.3 Choice of the function and the range of current output n.1
Out mA2 4_22 +/- 7.4 Choice of the function and the range of current output n.2
A1S 4.9087 7.5 Full Scale value for analog out1
A2S 4.9087 7.6 Full Scale value for analog out2
The manufacturer guarantees only English text available on our web site [Link]

COMMUNICATION
HART pr. 05 8.1 HART packet byte preambles
HART O. C. ON 8.2 HART bus output control
8.3 Device communication address number
COMMUN. Dev. Addr
Speed=bps
001
9600 8.4 MODBUS link speed
Parity= NO 8.5 MODBUS link parity
Delay=ms 00 8.6 MODBUS reply delay
C. timeout 2 8.7 Maximum delay between chars (frames) MODBUS

DISPLAY
Language EN 9.1 Choice of the language
Contrast 5 9.2 Display contrast
[Link]=s 020 9.3 Display/keyboard inactivity time
[Link]=Hz 5 9.4 Display updating frequency: 1-2-5-10 Hz
9.5 Display function number
DISPLAY Disp. Fn.
[Link] ON
1
9.6 Display function selection lock
Part. Tot ON 9.7 Partial totalizer enable
Neg. Tot. ON 9.8 Negative totalizer enable
Net tot. ON 9.9 Net totalizer enable
[Link] ON 9.10 Time and date display enable
Quick start ON 9.11 Quick start menu visualization

14/26 MV110_IT_EN_DS053REV08_IS

DATA LOGGER
[Link] en. ON 10.1 Data logger enabling
Meas. units ON 10.2 Measure units recording enable
Field separat. ; 10.3 Field separator character
Decimal separ. . 10.4 Decimal separator character
Interv. [Link] 10.5 Sampling interval
Log T+ ON 10.6 Enable logging of total direct totalizer
Log P+ ON 10.7 Enable logging of partial direct totalizer
Log T- ON 10.8 Enable logging of total reverse totalizer
Log P- ON 10.9 Enable logging of partial reverse totalizer
DATA Log TN ON 10.10 Enable logging of total net totalizer

LOGGER Log PN ON 10.11


10.12
Enable logging of partial net totalizer
Enable logging of flow rate in measure unit
Log Q (UM) ON
Log Q (%) ON 10.13 Enable logging of flow rate in percentage
Log [Link] ON 10.14 Enable logging of alarm events
Log STR ON 10.15 Enable logging of sensor test results
Log BTS ON 10.16 Enable logging of board temperature
Log IBV ON 10.17 Enable logging of internal board voltage
Log EDC ON 10.18 Enable logging of electrodes DC voltage
Log EAC ON 10.19 Enable logging of electrodes AC voltage
Log EIZ ON 10.20 Enable logging of electrodes impedance
Log SCV ON 10.21 Enable logging of sensor coils value
The manufacturer guarantees only English text available on our web site [Link]

FUNCTIONS
T+ reset 11.1 Execute immediate reset of total direct totalizer
P+ reset 11.2 Execute immediate reset of partial direct totalizer
T- reset 11.3 Execute immediate reset of total reverse totalizer
11.4 Execute immediate reset of partial reverse totalizer
FUNCTIONS P- reset
Load Sens. f. def 11.5 Load sensor factory default
Load Conv. f. def 11.6 Load converter factory default
Save Sens. f. def 11.7 Save sensor factory default values
Save Conv. f. def 11.8 Save converter factory default values
Calibration 11.9 Execute immediate internal circuit calibration

DIAGNOSTIC
Self test 12.1 Self test diagnostic function
Test display 12.2 Function tests physical display
Sens. verify 12.3 Sensor verify diagnostic function
Flow sim. = ON 12.4 Flow rate simulation enabling
Display measures 12.5 Display internal measured value
DIAGNOSTIC Disp. Coom. Vars 12.6 Display comm. diagnostic values
Display graphs 12.7 Display measure as graphs
Gen. sens. set 12.8 Generic sensor parameters set
SD card info 12.9 Sd card status informations
Firmware info 12.10 Firmware version/revision
S/N= 999001 12.11 Board serial number
WT= 0002 : 21 : 00 : 2 2 12.12 Total working time

15/26 MV110_IT_EN_DS053REV08_IS
ISOIL
I N D U S T R I A

SYSTEM
Dayl. Saving = ON 13.1 Daylight saving time change
Time zone = h + 01.00 13.2 Localized time zone
2016/04/04-16:07 13.3 System date and time
L1 code = ******** 13.4 Access level 1 code
L2 code = ******** 13.5 Access level 2 code
L3 code = ******** 13.6 Access level 3 code
L4 code = ******** 13.7 Access level 4 code
L5 code = ******** 13.8 Access level 5 code
L6 code = ******** 13.9 Access level 6 code
Restr. Access= ON 13.10 Restricted access level
SYSTEM 010 . 011 . 012 . 013 13.11 Device IP network address
010 . 011 . 012 . 014 13.12 Client IP network address
255 . 255 . 255 . 000 13.13 Network mask
KT 0.96469 13.14 Calibration coefficient KT
KS 1.00000 13.15 Calibration coefficient KF
KR 1.00000 13.16 Calibration coefficient KR
DAC1 (°C) 13.17 DAC1 out 4mA calibration point
DAC1 (°C) 13.18 DAC1 out 20mA calibration point
DAC2 661 13.19 DAC2 out 4mA calibration point
The manufacturer guarantees only English text available on our web site [Link]

DAC2 3327 13.20 DAC2 out 20mA calibration point


Stand-by 3453 13.21 Stand-by
FW update 14718 13.22 firmware update

16/26 MV110_IT_EN_DS053REV08_IS

ACCURACY

e%
Typical error profile (pure indication only)

0,1 0,5 5,0 10,0


m/s m/s m/s m/s
The manufacturer guarantees only English text available on our web site [Link]

SPEED
0,33 1,64 16,4 32,8
ft/sec ft/sec ft/sec ft/sec

speed ≥ 0,5 m/s (1,64 ft/s) ⇒ e = +/- A % (reading value)


speed < 0,5 m/s (1,64 ft/s) ⇒ e = +/- (B/V) % (reading value)

minimum flow (l/s): DN x DN x 0,008/1000( DN expressed in mm )

where:

e = ACCURACY

V = WORKING SPEED

(A and B values: see below table according to CONVERTER model)

Full bore Sensor


MS501/MS1000/MS2410/MS2500 MS600 MS5000

A B(m/s) B(ft/s) A B(m/s) B(ft/s) A B(m/s) B(ft/s)

0,8* 0,4** 1,31** 0,8* 0,4** 1,31** 2 1 3,28

* = 0,4 ( special )
**= 0,2(m/s) ; 0,66(ft/s) - special

Insertion sensor
See sensor DATA SHEET

Reference conditions below and as per internal testing procedures:

‰ Constant flow rate during the test


‰ Pressure: >30 Kpa
‰ Flow condition : fully developed flow profile
‰ Zero stability +/- 0,005 %

17/26 MV110_IT_EN_DS053REV08_IS
ISOIL
I N D U S T R I A

MI-001 OIML R49 CLASS1: MV110


The MS2500 sensor’s diameters listed below, coupled with MV110 comply with the European directive:
DIRECTIVE 2014/32/EU (MID) ANNEX III (MI-001) AND 2015/13/EU- OIML R49

SIZE Q3 Q2 Q1 R SIZE Q3 Q2 Q1 R

mm inch m3/h Q3/Q1 mm inch m3/h Q3/Q1


25 1 16 0,26 0,16 25 1 16 0,10 0,064
32 1¼ 25 0,40 0,25 32 1¼ 25 0,16 0,10
40 1½ 40 0,64 0,40 40 1½ 40 0,26 0,16
50 2 63 1,01 0,63 50 2 63 0,40 0,25
65 2½ 100 1,6 1,00 65 2½ 100 0,64 0,40
The manufacturer guarantees only English text available on our web site [Link]

80 3 160 2,6 1,60 80 3 160 1,0 0,64


100 4 250 4,0 2,50 100 4 250 1,6 1,0
125 5 400 6,4 4,00 125 5 400 2,6 1,6
150 6 630 10,1 6,30 150 6 630 4,0 2,5
200 8 1000 16 10,00 200 8 1000 6,4 4,0
250 10 1600*** 26 16,0 100 250 10 1600*** 10 6,4 250
300 12 2500** 40 25 300 12 2500** 16 10
350 14 2500** 40 25 350 14 2500** 16 10
400 16 4000** 64 40 400 16 4000** 26 16
450 18 4000** 64 40 450 18 4000** 26 16
500 20 6300 101 63 500 20 6300 40 25
600 24 10000 160 100 600 24 10000 64 40
700 28 10000 160 100 700 28 10000 54 40
800 32 16000* 256 160 800 32 16000* 102 64
900 36 16000* 256 160 900 36 16000* 102 64
1000 42 25000* 400 250 1000 42 25000* 160 100

(*) : Calibration flowrate 14000 m3/h - as for max rig flowrate L8

(**) : Calibration flowrate 1400 m3/h - as for max test rig flowrate L7

(***) Calibration flowrate 1100 m3/h - as for max test rig flowrate L6

18/26 MV110_IT_EN_DS053REV08_IS

MI-001 OIML R49 CLASS 2: MV110


The MS2500 sensor’s diameters listed below, coupled with MV110 comply with the European directive:
DIRECTIVE 2014/32/EU (MID) ANNEX III (MI-001) AND 2015/13/EU- OIML R49

SIZE Q3 Q2 Q1 R SIZE Q3 Q2 Q1 R

mm inch m3/h Q3/Q1 mm inch m3/h Q3/Q1


25 1 16 0,16 0,10 25 1 16 0,10 0,06
32 1¼ 25 0,25 0,16 32 1¼ 25 0,16 0,10
40 1½ 40 0,40 0,25 40 1½ 40 0,26 0,16
50 2 63 0,63 0,39 50 2 63 0,40 0,25
65 2½ 100 1,0 0,63 65 2½ 100 0,64 0,40
80 3 160 1,6 1,0
The manufacturer guarantees only English text available on our web site [Link]

80 3 160 1,0 0,64


100 4 250 2,5 1,6
100 4 250 1,6 1,0
125 5 400 4,0 2,5
125 5 400 2,6 1,6
150 6 630 6,3 3,9
150 6 630 4,0 2,5
200 8 1000 10 6,3
200 8 1000 6,4 4,0
250 10 1600*** 16 10 160
250 10 1600*** 10 6,4 250
300 12 2500** 25 15,625
300 12 2500** 16 10
350 14 2500** 25 15,625
350 14 2500** 16 10
400 16 4000** 40 25
400 16 4000** 26 16
450 18 4000** 40 25
450 18 4000** 26 16
500 20 6300 63 39,375
500 20 6300 40 25
600 24 10000 100 62,5
700 28 10000 100 62,5 600 24 10000 64 40

800 32 16000* 160 100 700 28 10000 54 40

900 36 16000* 160 100 800 32 16000* 102 64


1000 42 25000* 250 156,25 900 36 16000* 102 64
1000 42 25000* 160 100

(*) : Calibration flowrate 14000 m3/h - as for max rig flowrate L8

(**) : Calibration flowrate 1400 m3/h - as for max test rig flowrate L7

(***) Calibration flowrate 1100 m3/h - as for max test rig flowrate L6

19/26 MV110_IT_EN_DS053REV08_IS
ISOIL
I N D U S T R I A

SIZE Q3 Q2 Q1 R
mm inch m3/h Q3/Q1
25 1 16 0,06 0,04
32 1¼ 25 0,10 0,06
40 1½ 40 0,16 0,10
50 2 63 0,25 0,16
65 2½ 100 0,40 0,25
80 3 160 0,64 0,40
100 4 250 1,0 0,63
The manufacturer guarantees only English text available on our web site [Link]

125 5 400 1,6 1,0


150 6 630 2,5 1,6
200 8 1000 4,0 2,5
250 10 1600*** 6,4 4,0 400
300 12 2500** 10 6,3
350 14 2500** 10 6,3
400 16 4000** 16 10
450 18 4000** 16 10
500 20 6300 25 16
600 24 10000 40 25
700 28 10000 40 25
800 32 16000* 64 40
900 36 16000* 64 40
1000 42 25000* 100 63

(*) : Calibration flowrate 14000 m3/h - as for max rig flowrate L8

(**) : Calibration flowrate 1400 m3/h - as for max test rig flowrate L7

(***) Calibration flowrate 1100 m3/h - as for max test rig flowrate L6

20/26 MV110_IT_EN_DS053REV08_IS

MPE - MI 001 - OIML R49 ACCURACY CLASS 1


(OIML R 49-1:2013 (E) - ISO4064-1:2017 )

0,1°C≤T≤30°C

3 T>30°C

1
MPE

0
/%

Q(1) Q(2) Q(3) Q(4)

-1

-2
The manufacturer guarantees only English text available on our web site [Link]

-3

-4

MPE - MI 001 - OIML R49 ACCURACY CLASS 2


(OIML R 49-1:2013 (E) - ISO4064-1:2017 )

0,1°C≤T≤30°C
5
T>30°C
4

1
MPE

0
/%

Q(1) Q(2) Q(3) Q(4)


-1

-2

-3

-4

-5

-6

21/26 MV110_IT_EN_DS053REV08_IS
ISOIL
I N D U S T R I A

MI-004 OIML R75 CLASS1: MV110


The MS2500 sensor’s diameters listed below, coupled with MV110 comply with the European directive:
DIRECTIVE 2014/32/EU (MID) ANNEX VI (MI-004) - OIML R75

SIZE qp (10m/s) qs 0,1 qp qi MC SIZE qp (10m/s) qs 0,1 qp qi MC

mm inch m3/h qp/qi mm inch m3/h qp/qi


25 1 16 16 1,6 0,16 25 1 10 16 1 0,2
32 1¼ 25 25 2,5 0,25 32 1¼ 16 25 1,6 0,32
40 1½ 40 40 4 0,40 40 1½ 25 40 2,5 0,5
50 2 63 63 6,3 0,63 50 2 40 63 4 0,8
65 2½ 100 100 10 1,00 65 2½ 63 100 6,3 1,26
100
80 3 160 160 16 1,60 80 3 100 160 10 2
100 4 250 250 25 2,50 100 4 160 250 16 3,2
125 5 400 400 40 4,0 125 5 250 400 25 5
50
150 6 630 630 63 6,3 150 6 400 630 40 8
200 8 1000 1000 100 10 200 8 630 1000 63 12,6
The manufacturer guarantees only English text available on our web site [Link]

250 20 160 1600* 160 16 250 10 1000 1600 100 20


300 31 250 2500* 250 25 300 12 1600* 2500 160 32
80
350 31 250 2500* 250 25 350 14 2500* 2500 250 50
400 50 400 4000* 400 40 400 16 2500* 4000 250 50

SIZE qp (10m/s) qs 0,1 qp qi MC SIZE qp (10m/s) qs 0,1 qp qi MC

mm inch m3/h qp/qi mm inch m3/h qp/qi


25 1 10 16 1 0,4 25 1 10 16 1 1
32 1¼ 16 25 1,6 0,64 32 1¼ 16 25 1,6 1,6
40 1½ 25 40 2,5 1 40 1½ 25 40 2,5 2,5
50 2 40 63 4 1,6 50 2 40 63 4 4
65 2½ 63 100 6,3 2,52 65 2½ 63 100 6,3 6,3
80 3 100 160 10 4 80 3 100 160 10 10
100 4 160 250 16 6,4 100 4 160 250 16 16
125 5 250 400 25 10
25 125 5 250 400 25 25
10
150 6 400 630 40 16 150 6 400 630 40 40
200 8 630 1000 63 25,2 200 8 630 1000 63 63
250 10 1000 1600 100 40 250 10 1000 1600 100 100
300 12 1600* 2500 160 64 300 12 1600* 2500 160 160
350 14 2500* 2500 250 100 350 14 2500* 2500 250 250
400 16 2500* 4000 250 100 400 16 2500* 4000 250 250

(*) : Flow rates reduced to the limits of the system

22/26 MV110_IT_EN_DS053REV08_IS

MI 004 - MPE - ACCURACY CLASS 1


(UNI EN 1434-1:2016)
3,00

2,00

1,00

qi 0,1 qp qp
MPE

0,00
/%

q/qp [%]

-1,00
The manufacturer guarantees only English text available on our web site [Link]

-2,00

Ef class1

-3,00
1,0 10,0 100,0

23/26 MV110_IT_EN_DS053REV08_IS
ISOIL
I N D U S T R I A

HOW TO ORDER
CODE
EXAMPLE CODE/DESCRIPTION
Display
A Blind version (without display and programming keys, cable USB type A/USB MINI B is REQUIRED TO PROGRAMMING)
A
B Graphic LCD WSTN - B/W - back light display, point matrix 128 x 64, 8 line/16 characters and 3 programming keys (mandatory for MI001)

Housing material / Protection rate


0 Nylon PA6 with fiber glass, protection rate IP 67

1 Painted aluminum die casting, protection rate IP67

Painted aluminum die casting, protection rate IP68 1,5 meters under water, Compact Version, n° 1 IP 68 MIL connector for power supply (CONNECTORS
2 SUPPLIED: MALE + FEMALE)

Painted aluminum die casting, protection rate IP68 1,5 meters under water, Compact Version, Complete of n° 1 of 10 poles IP68 MIL connector (outputs
0 3 connections to be specified) and n° 1 IP 68 MIL connector for power supply (CONNECTORS SUPPLIED: MALE + FEMALE)

Painted aluminum die casting, protection rate IP68 1,5 meters under water, Separate Version, Complete of n° 1 IP 68 MIL connectors for cable from the sensor
4 and n° 1 IP 68 MIL connector for power supply (CONNECTORS SUPPLIED: MALE + FEMALE)

Painted aluminum die casting, protection rate IP68 1,5 meters under water, Separate Version, Complete of n° 1 IP 68 MIL connectors for cable from the sensor,
5 n° 1 of 10 poles IP68 MIL connector (outputs connections to be specified) and n° 1 IP 68 MIL connector for power supply (CONNECTORS SUPPLIED: MALE +
FEMALE)

Version
The manufacturer guarantees only English text available on our web site [Link]

A Compact version with sensor MS.... (liquid maximum temperature 100 °C)

A B Separate version for wall monting, complete with mounting accessories ( CABLE C014 )

C Compact version with display visible from the top

Power supply
1 Power supply : 100 ... 240 VAC 44/66 Hz (NOT FOR MI001)

2 Power supply : 24 … 36 VAC/VDC 0...44/66 Hz (NOT FOR MI001)

3 Power supply : 12…48 VDC (NOT FOR MI001)

Power supply : 100 ... 240 VAC 44/66 Hz + 1 Rechargeable back-up Battery ( the use of battery supports only the measure UP TO 30 days; all the outputs are
4 set to OFF) (NOT FOR MI001)

Power supply : 24 … 36 VAC/VDC 0...44/66 Hz + 1 Rechargeable back-up Battery ( the use of battery supports only the measure UP TO 30 days; all the outputs
5 are set to OFF) (NOT FOR MI001)

Power supply : 12…48 VDC + 1 Rechargeable back-up Battery ( the use of battery supports only the measure UP TO 30 days; all the outputs are set to OFF)
6 (NOT FOR MI001)

1 Power supply : 100 ... 240 VAC 44/66 Hz + n° 1 SETTINGS FOR Rechargeable back-up Battery ( the Rechargeable Battery is NOT included) (NOT FOR
7 MI001)

Power supply : 24 … 36 VAC/VDC 0...44/66 Hz + n° 1 SETTINGS FOR Rechargeable back-up Battery ( the Rechargeable Battery is NOT included) (NOT FOR
8 MI001)

9 Power supply : 12…48 VDC + n° 1 SETTINGS FOR Rechargeable back-up Battery ( the Rechargeable Battery is NOT included) (NOT FOR MI001)

Power supply : 100 ... 240 VAC 44/66 Hz + 1 Pack of n° 2 SUPERCAP ( the use of it supports only the measure UP TO 3 minutes; all the outputs are set to
a OFF) Suitable for MI001

Power supply : 24 … 36 VAC/VDC 0...44/66 Hz + 1 Pack of n° 2 SUPERCAP ( the use of battery supports only the measure UP TO 3 minutes; all the outputs are
b set to OFF) Suitable for MI0011

Power supply : 12…48 VDC + 1 Pack of n° 2 SUPERCAP ( the use of battery supports only the measure UP TO 3 minutes; all the outputs are set to OFF)
C Suitable for MI001

Analogue output
A Without Analogue output

A B n° 1 Analogue output 0/4...20/22 mA (Hart optional)

C n° 2 Analogue outputs 0/4...20/22 mA (Hart optional over Out.1)

Digital Input/Output
0 With Digital Input only

0 1 With n° 1 PROGRAMMABLE Digital Output/n°1 Digital Input (mandatory for MI004)

2 With n° 2 PROGRAMMABLE Digital output/n°1 Digital Input

24/26 MV110_IT_EN_DS053REV08_IS

Communication Gateway
A Without Gateway

B RS485 port - Protocol MODBUS required

A C Hart ( 4/20 mA/ Analog OUT n° 1 is required)

D Wi-Fi (for programming)

E Others

Protocols
0 Without Protocol
0
1 Modbus (over RS485) requires RS485 port

Accuracy
A Standard accuracy 0,8 %

A B Special accuracy 0,4 %

C Special accuracy (to be defined)

Data Logger
0 Without Data Logger
The manufacturer guarantees only English text available on our web site [Link]

1 MicroSD Memory 4 GB : Data Logger + RTC (Real Time Clock)

0 2 MicroSD Memory 4 GB : Data Logger + RTC (Real Time Clock) + BIV (Built In Verificator)

3 MicroSD Memory 4 GB : Data Logger + RTC (Real Time Clock) + Meter Data (Real Time Converter & Sensor Data on SD Memory)

4 MicroSD Memory 4 GB : Data Logger + RTC (Real Time Clock) + BIV + Meter Data

Special Features
A NONE

B WITH ANTICONDENSE CAP


A
C n° 5 CABLE GLAND 1/2" NPT - Nickel plated brass CODE 1.609.1200.70 ( CABLE 6 - 12 mm )

D n° 5 HOLES FOR CABLE GLAND 1/2" NPT (WITHOUT CABLE GLAND)

MID Approval
0 NONE

1 MI-001/OIMLR49-CLASS 1 (Pover Supply Code shall be a or b or c)


0
2 MI-001/OIMLR49-CLASS 2 (Pover Supply Code shall be a or b or c)

3 MI-004-CLASS 1

Complete code
MV110-A0A1A0A0A0A0
example for
order

25/26 MV110_IT_EN_DS053REV08_IS
ISOIL
I N D U S T R I A

ISOIL INDUSTRIA S.p.A.


HEAD OFFICE SERVICE
Via Fratelli Gracchi, 27 isomagservice@[Link]
20092 Cinisello Balsamo (MI)
Tel +39 02 66027.1
Fax +39 02 6123202
sales@[Link]

If you want to find the complete list of our distributors access at the following link:
[Link]

If you want to find the complete list of our distributors access at the following link:
[Link]
The manufacturer guarantees only English text available on our web site [Link]

BEFORE returning any material, please


contact our SERVICE at the e-mail adress:
isomagservice@[Link]

Due to the constant technical development and improvement of its products, the man-
ufacturer reserves the right to make changes and/or modify the information contained
in this document without notice.