Koc MH 001
Koc MH 001
STANDARDS TEAM
DOC. NO. KOC-MH-001 Page 2 of 66 REV. 0
TABLE OF CONTENTS
Page No.
FOREWORD 4
1.0 SCOPE 5
1.1 Exclusions 5
2.0 APPLICATION 5
3.0 TERMINOLOGY 6
3.1 Definitions 6
3.2 Abbreviations 8
13.0 REFRIGERANTS 48
19.0 DOCUMENTATION 58
19.1 General 58
19.2 Deliverables 58
ACKNOWLEDGEMENT 66
DOC. NO. KOC-MH-001 Page 4 of 66 REV. 0
FOREWORD
This document “KOC Standard for HVAC System and Equipment: Direct
Expansion (DX) Type” (KOC-MH-001, Rev. 0) is intended to provide the
minimum technical requirements for design, supply, manufacture, installation and
performance of Direct Expansion (DX) type HVAC systems and Equipment for
KOC Onshore Facilities in Kuwait. This KOC Standard supersedes
015-HH-1101 “HVAC Equipment and Installation”.
This KOC Standard (Rev. 0) has been approved by the Standards Team in
consultation with the ESTC Sub-Committee (Technical) for use throughout the
Engineering and Operational Functions of Kuwait Oil Company (K.S.C).
a) To provide technical guidance and establish the base document for developing project
/ material specifications for HVAC System and Equipment with a view to achieve
uniformity, quality, safety, environment-friendly, reliability and efficiency in an
economical manner.
c) To maintain the Health, Safety and Environment (HSE), including Process Safety
Management (PSM), requirements for the safety, integrity and protection of personnel,
environment and assets.
Feedback as well as any comments or suggestions derived from the application of this
Standard at any stage of design, installation or operation are invited and should be directed
to:
1.0 SCOPE
This KOC Standard covers the minimum technical requirements and the
basic guidelines for design, supply, manufacture, installation, testing and
commissioning of Direct Expansion (DX) type HVAC (Heating, Ventilation
and Air Conditioning) system and equipment intended for use throughout
the KOC Onshore Facilities (Plant and Non-Plant Buildings).
1.1 Exclusions
Note:
i. The requirements of HVAC System and Equipment have been covered in the
following KOC Standard / 015 Series Specification:
2.0 APPLICATION
2.1 The requirements of HVAC System and Equipment: Direct Expansion (DX) type
defined in this KOC Standard shall be applicable to KOC Facilities / Office Buildings
viz. Control Buildings, Electrical Substations, LAN / Telecom Room, Laboratories,
etc.
2.2 The design, construction, performance, inspection and testing of HVAC Systems and
Equipment – Direct Expansion (DX) Type shall fully comply with all the relevant
requirements specified in this KOC Standard and the reference Standards / Codes
mentioned herein.
2.3 Any exceptions or deviations from this KOC Standard, along with their merits and
justification, shall be brought to the attention of KOC Controlling Team for review,
consideration and amendment by the Standards Team (if required).
2.4 Compliance with this KOC Standard does not of itself confer immunity from technical,
legal or statutory obligations.
DOC. NO. KOC-MH-001 Page 6 of 66 REV. 0
3.0 TERMINOLOGY
3.1 Definitions
For the purpose of this Standard, the following definitions shall apply:
3.1.2 Consultant
3.1.3 Contractor
The person, persons, firm or Company contracted by KOC to undertake the execution
of the work defined by the contract.
Total heat required to be removed from the space (area) in order to bring it at the
desired temperature by HVAC equipment is known as Cooling Load.
3.1.6 Designer
Person or persons from KOC or from Consultant / Contractor approved by KOC, who
undertakes the responsibility for the design of HVAC Systems.
In the Direct Expansion (DX) type of air conditioning system, cool a space through
vapour-compression refrigeration cycle.
A term commonly used for the Heating Ventilation and Air Conditioning System.
Any KOC Team authorised to initiate a request for design and execution of a project
or procurement of materials / equipment(s) for KOC.
DOC. NO. KOC-MH-001 Page 7 of 66 REV. 0
All buildings located within the KOC Oil and Gas Facilities are termed as KOC Plant
Buildings and the buildings located outside Oil and Gas Facilities (like Ahmadi
Township) are KOC Non-Plant Building.
3.1.12 Manufacturer
3.1.13 Psychrometry
Psychrometry is the science associated with the study of atmospheric air which is a
mixture of dry air and water vapour (moisture).
3.1.15 Refrigeration
3.1.16 Refrigerant
The refrigerant is the medium that absorbs the heat from the substance to be cooled
and discards the heat so absorbed to the atmosphere. The refrigerant does not
undergo any chemical change; the change is only physical.
The “Temperature Glide” occurs when the refrigerant blend has various temperature
as it evaporates and condenses at a single given pressure. Temperature Glide of a
single component refrigerant is “Zero” whereas “Refrigerant Mixtures” have
measurable “Temperature Glide” when they evaporate (boil) or condense.
‘Ton of Refrigeration’ is used to indicate the capacity of the Refrigeration and Air
conditioning system and is equal to the heat removal required to freeze one metric
ton of water at 0 °C (32 °F) into ice in 24 hours.
3.1.19 Ventilation
3.2 Abbreviations
AC Alternating Current
BS British Standards
DC Direct Current
FD Fire Damper
GI Galvanised Iron
HC Hydrocarbon
HP Horse Power
kW Kilo Watt
MD Motorised Damper
NC Noise Criteria
RH Relative Humidity
TR Ton of Refrigeration
UPS Uninterrupted Power Supply
UV UltraViolet
WG Water Gauge
4.1 Conflicts
In the event of conflicts between this KOC Standard and the latest edition of
standards / codes referred herein or other purchase or contractual requirements,
the most stringent requirement(s) shall apply.
The HVAC System and Equipment: Direct Expansion (DX) type shall conform,
except where otherwise specified, with the current issues and amendments of the
applicable Codes, Standards and Specifications, including but not limited to the
following:
AHRI 210 / 240 Performance Rating of Unitary Air Conditioning & Air Source
Heat Pump Equipment
AHRI 340 / 360 Performance rating of Commercial and Industrial Unitary Air
Conditioning and Heat Pump Equipment
ASTM A90 / A90M Standard Test Method for Weight (Mass) of Coating on Iron and
Steel Articles with Zinc or Zinc-Alloy Coatings
ASTM B280 Standard Specification for Seamless Copper Tube for Air
Conditioning and Refrigeration Field Service
ASTM E 477 Testing of Duct Liner Materials and Sound Attenuators and Air
Flow Performance
DOC. NO. KOC-MH-001 Page 12 of 66 REV. 0
NFPA 259 Standard Test Method for potential Heat of Building Materials
KOC-E-003 Part 1 KOC Recommended Practice for Design Basis and Selection of
Electrical Systems
KOC-P-001 KOC Standard for Painting & Coating of External Metal surfaces
DOC. NO. KOC-MH-001 Page 14 of 66 REV. 0
For environmental conditions in Kuwait, refer to KOC-G-007 “KOC Standard for Basic
Design Data”, which provides the detailed design information regarding the
environmental, site and utility supply conditions prevailing throughout the KOC
Facilities.
6.1 Relevant KOC requirements, including the Process Safety Management (PSM)
requirements and specifically the procedure for Inherently Safer Design (ISD) shall be
adhered to while designing, supplying, manufacturing, installation and performance of
Direct Expansion (DX) type HVAC System and Equipment so as to safeguard
personnel, environment and assets during the use of the equipment.
6.2 All relevant HSE requirements of KPC HSSE Policy and KOC HSE Procedures shall
be complied while performing the works within KOC areas.
6.3 Appropriate Permit to Work (PTW) with applicable Job Safety Analysis (JSA)
document for the work to be carried out shall be prepared by the Contractor in line
with the relevant KOC HSE Procedures and submitted to KOC Controlling Team for
approval prior to commencement of any work within KOC areas. The PTW and JSA
documents shall address all relevant HSE requirements as per KOC “Permit to Work
Procedure” (KOC.SA.004) and “Job Safety Analysis Procedure” (KOC.SA.024).
6.4 Necessary control measures identified through the above risk assessments shall be
implemented in the work location before starting job and shall be discussed /
explained to the work force through Job Safety Analysis (JSA) by the worksite
supervisor.
6.5 Risk assessments (health, safety and environment risks) shall be carried out for the
work to be done in accordance with KOC HSE Procedures (KOC.SA.018,
KOC.EV.018 & KOC.HE.018).
6.6 All personnel carrying out site works, including Supervisors, shall use appropriate
Personal Protective Equipment (PPE) during the execution of works as identified by
the job requirement and in line with the requirements of KOC HSE Procedure for
DOC. NO. KOC-MH-001 Page 16 of 66 REV. 0
6.7 All personnel engaged in site works shall have successfully undergone all the
applicable trainings and awareness courses as per the “Matrix of identified categories
of personnel identified under ‘HSE Training’ and ‘HSE Awareness’ for Contractor’s
Employees” in the KOC HSE procedure “HSE Training, Awareness and Continued
Learning Process” (KOC.GE.028).
6.8 The Contractor shall manage all wastes arising out of all work activities in a safe and
environmental friendly manner in accordance with the KOC HSE Procedure for
“Waste Management Procedure” (KOC.EV.008). All personnel engaged at site work
in KOC areas shall be fully aware of the need for good housekeeping and shall adhere
to KOC “Housekeeping Procedure” (KOC.GE.034) during all work activities.
6.9 The Contractor personnel shall take all necessary precautionary measures to ensure
safe handling of loads during the work as per KOC HSE procedures for “Manual
Handling of Loads” (KOC.SA.003), “Safety Procedure for Mechanical Handling of
Loads” (KOC.SA.029) and “Mobile Equipment Procedure” (KOC.SA.013).
6.10 The Contractor shall take necessary precautionary measures for ensuring the safety
during the activities related to pneumatic test and inspection as per KOC “Safety
Procedure for Electrical, Pneumatic Tools and Equipment” (KOC.SA.009).
7.1 General
HVAC systems shall be in accordance with the requirement of this KOC Standard and
the Standards referred in Clause 4.2 of this Standard.
The “KOC Standard for Basic Design Data” (KOC-G-007) for site conditions,
atmospheric conditions shall be applied as basic design criteria for HVAC design,
selection of HVAC equipment and system in addition to the following consideration:
7.2.1 Location
a) Plant Buildings
i. Summer Season
125 °F (51.7 °C) DBT and 84 °F (28.9 °C) WBT with daily range of 24 °F (13.3 °C) .
DOC. NO. KOC-MH-001 Page 17 of 66 REV. 0
40.1 °F (4.5 °C) DBT and 36.6 °F (2.0 °C) WBT with daily range of 24 °F (13.3 °C).
i. Summer Season
117.3 °F (47.4 °C) dry bulb / 89.2 °F (31.8 °C) wet bulb temperature
with daily range of 24 °F (13.3 °C) for the coastal areas of Kuwait
(within 2.5 km from the coast) and 118.4 °F (48 °C) dry bulb / 77.9 °F
(25.5 °C) wet bulb temperature with daily range of 24 °F (13.3 °C) for
the interior areas (beyond 2.5 km from the coast).
40.1 °F (4.5 °C) dry bulb / 36.6 °F (2.0 °C) wet bulb temperature with
daily range of 24 °F (13.3 °C) for the coastal and interior areas of
Kuwait (coastal is within 2.5 km and interior is beyond 2.5 km from the
coast).
The imperial system shall be used for all calculations carried out in accordance with
the ASHRAE design procedures. However, where SI Systems are used, the imperial
equivalents shall be provided in the parenthesis.
The indoor design conditions for specific applications shall conform to the
requirements of Table-1 of this standard, unless otherwise specified in project
documents.
TABLE -1
Noise
% RH
Space / Zone Summer Winter Criteria Remarks
±5 %)
[NC]
(75±2) °F / (70±2) °F / Cooling &
Auditorium 55 20 ~ 25
(24±1) °C (21±1) °C Heating both
Control Room
(75±2) °F / (70±2) °F /
Offices, UPS Room, Training 55 30 ~ 35 Cooling &
(24±1) °C (21±1) °C
Room, Security Post Building Heating both
(75±2) °F / (70±2) °F / Cooling &
Library, Mosque 55 25 ~ 30
(24±1) °C (21±1) °C Heating both
(75±2) °F / (70±2) °F / Cooling &
Dining Rooms, Cafeteria, Pantry 55 40 ~ 45
(24±1) °C (21±1) °C Heating both
Store Rooms, Janitor Room, (78±2) °F / (70±2) °F / Cooling &
55 40 ~ 45
Locker Room (25.6±1) °C (21±1) °C Heating both
Cooling &
Heating both
(78±2) °F / (70±2) °F /
Toilet, Corridors 55 30 ~ 35 RH not
(25.6±1) °C (21±1) °C
controlled for
Toilet
DOC. NO. KOC-MH-001 Page 18 of 66 REV. 0
Note-1: Sound level of spaces (Noise Criteria [NC]) shall be maintained at levels not exceeding those
listed above by utilising acoustical devices. Noise level inside the conditioned spaces, resulting
from HVAC System, shall be measured by an approved sound level meter at 1.0 meter distance
from air outlet.
Note-2: Workshop, Utility and Generator Building shall be provided with Mechanical Ventilation only
unless otherwise specified in the project document.
Note-3: ASHRAE Fundamental Handbook shall be referred for the indoor design conditions of Space /
Zone which are not listed under Table-1 of this Standard.
Note-4: Indoor design conditions for all internal spaces shall be fully compliant with the latest
requirements of KEPA.
b) The design calculations / reports shall include all the input data used,
referenced, utilised for the estimation and proof of license of the computer
program.
The following design parameters (indicative) for the Building Envelop as stipulated by
Energy Conservation Program Code of Practice “MEW / R-7” (latest version as
applicable) shall be followed :
a) The overall heat transfer coefficient (U – value) for external wall / exposed floor
shall not exceed 0.1 Btu / hr.sq.ft °F { 0.568 W / (m2.K)} and that of Roof shall
not exceed 0.07 Btu / hr.sq.ft °F {0.398 W / (m2.K)}.
d) Floors exposed to ambient conditions shall have U-values similar to roofs and
partitions exposed to unconditioned areas shall have U-values similar to walls.
e) The type of external glazing for building shall be as specified in the architectural
details of the project specific document. The heat gain is less for coloured /
tinted glass, double panel glass, shaded glass (with ventilation blinds, shading
etc.) and shall be chosen accordingly to conserve energy.
f) The exterior envelope of building shall be made air tight with no cracks or
openings in order to prevent air and dust infiltration or unnecessary
ex-filtration.
a) The fresh air requirement and Indoor Air Quality (IAQ) shall be determined
generally in accordance with ASHRAE standard 62.1-2016 or the required
make up air for exhaust systems, whichever is greater. All buildings (Plant &
Non- Plant) shall have 0.5 Air Change Per Hour (ACPH) minimum
pressurisation unless otherwise specified.
b) Table-2 of this Standard presents the outdoor air requirements for ventilation
of common applications as a general guidance.
TABLE - 2
e) The ventilation system for Generator Room shall have intake sand trap
motorised louvers and fixed blade exhaust louvers. The intake louvers shall be
sized for generator combustion and ventilation requirement as per
Manufacturer’s instruction. Generator radiator exhaust shall be connected
through duct to the exhaust louvers.
f) The exhaust from Kitchen area shall be through compensation type kitchen
hood and the volume of air exhausted through the hood shall be based on the
higher value of item-(i) or item-(ii) below:
i. Toilets
ii. Wash Rooms
iii. Locker Rooms
iv. Battery Rooms
v. Pantry
vi. Laboratory.
Air intake and discharge system shall be in accordance with requirement specified in
KOC Guidelines for Risk-Based Field Spacing of Onshore Facilities “KOC.PS.025”.
8.1 General
8.1.1 The HVAC system for various KOC buldings shall be designed in accordance with
this KOC Standard, project specific requirement as specified in the project document
and the Standards referred in clause 4.2 of this KOC Standard.
8.1.2 Direct Expansion (DX) type HVAC System shall be used for buildings of total cooling
load not exceeding 300 TR. The type of Equipment for Direct Expansion (DX) type
DOC. NO. KOC-MH-001 Page 21 of 66 REV. 0
HVAC System shall be Aircooled Ducted Package Unit, Aircooled Ducted Split Unit,
Fan Coil Unit and Room / Mini Split Units.
8.1.3 The HVAC System shall be designed to operate in the ambient (outside) temperature
range of 25 °F (-3.5 °C) to 125 °F (51.7 °C).
8.1.4 The supply of HVAC Equipment and system shall include but not limited to detailed
design and layout coordinated with other services, controls, cabling, pipe work, duct
work, insulation, adhesives, supports, fittings, duct work accessories and all
equipment and fittings necessary to allow satisfactory installation and functioning for
the complete HVAC systems.
8.1.5 Air conditioned buildings shall be provided with required pressurisation to prevent
ingress of dirt / dust and sand into the internal environment. The effects of
pressurisation on building air leakage shall be taken into account when calculating
fresh air loads.
8.1.6 The Gas detectors (H2S, HC, etc.) in the outdoor air intake shall be provided for KOC
Plant Buildings or the location where presence of such gases are envisaged and shall
comply KOC Recommended Practice for Design, Selection and Location of Fire &
Gas Detection System “KOC-L-036”.
8.1.7 Outdoor air intake shall be a minimum of One (1) meter above the flat surface on
which they are located. Sand trap louvers shall be used on all air intakes unless
otherwise specified.
8.1.8 Position of inlet and outlet openings shall be selected to minimise the effect of wind-
driven sand on the air conditioning and ventilations systems.
8.1.9 Fire dampers shall be provided in ductwork for all fire wall penetrations to maintain
the integrity of the fire wall.
8.1.10 The operation of the HVAC System shall be fully integrated with the Electrical,
Instrumentation, Gas detection and Fire protection systems to provide a safe building
environment under all foreseeable working conditions and shall comply with the
requirements of the applicable codes and standards.
8.1.11 The general description of HVAC System {Direct Expansion (DX) Type} described in
this KOC Standard is limited to KOC Facilities / Office Buildings, Electrical Substation,
Blast Resistant Control Room, Control Buildings, Battery Room, LAN / Telecom
Room, Laboratories and Electrical Room in KOC. The type of Air conditioning system
and equipment for other KOC Buildings / Facilities shall be based on the type of
application, building utility as specified in the project document.
8.1.12 The requirement for redundancy of control system shall be reviewed and specified in
project specific requirements for control buildings, substations and security equipment
buildings.
DOC. NO. KOC-MH-001 Page 22 of 66 REV. 0
The HVAC System along with Pressurisation unit(s) of complete Substation Building
shall consist but not limited to the following:
8.2.1 The HVAC System of Substation building shall consist of Air Handling Unit (AHU)
located in AHU Room or on roof and aircooled condensing units (working + standby),
located on roof / ground floor with dual compressors of equal capacity and with a
holding charge of environmentally friendly refrigerant from the factory and field
installed refrigerant piping(s) to the associated direct expansion cooling coil(s).
8.2.2 Each Air Handling Unit (AHU) shall comprise the following components assembled
and mounted on a common frame:
8.2.3 The pressurisation unit shall be located on roof of the building or as specified in the
project document and should comprise the following:
The HVAC System along with Pressurisation unit(s) of complete Control Building shall
consist but not limited to the following:
8.3.1 The HVAC System of Control Building shall be served by Aircooled ducted Packaged
Unit(s) and / or Aircooled ducted Split Unit(s) complete with insulated supply ducts,
air terminals, electrical duct heater, insulated return air duct, outside / fresh air
connection in the return air duct with sand louvers, return air filters and related
electrical work & controls or as specified in the project document.
DOC. NO. KOC-MH-001 Page 23 of 66 REV. 0
8.3.2 HVAC Equipment(s) {Packaged Unit and / or Ducted Split Units} shall be provided
along with 100 % Standby HVAC unit(s) and 100 % Standby pressurisation unit(s) for
KOC Plant / Non-Plant Buildings.
8.3.3 The aircooled DX ducted split unit(s) (if provided) for HVAC System of Control
Building, then the system shall consist of Air Handling Unit (AHU) located in AHU
Room or on Roof and aircooled condensing units (working + standby), located on roof
/ ground floor with dual compressors of equal capacity and with a holding charge of
environmentally friendly specified refrigerant from the factory and field installed
refrigerant piping(s) to the associated direct expansion cooling coil(s).
8.3.4 Each Air Handling Unit (AHU) shall comprise the following components assembled
and mounted on a common frame:
8.3.5 The pressurisation unit shall be located on roof of the building or as specified in the
project document and shall comprise the following:
The HVAC System along with Pressurisation unit(s) of complete Blast Resistant
Control Building shall consist but not limited to the following:
8.4.1 The HVAC System shall consist of Air Handling Unit (AHU) located suitably in AHU
Room (inside the blast resistant building) or explosion proof AHU on roof / ground and
explosion proof aircooled condensing units ( working + standby), located on roof /
ground floor with dual compressors of equal capacity and with a holding charge of
environmentally friendly refrigerant from the factory and field installed refrigerant
piping(s) to the associated direct expansion cooling coil(s).
DOC. NO. KOC-MH-001 Page 24 of 66 REV. 0
8.4.2 Each Air Handling Unit (AHU) (explosion proof or non explosion proof) shall comprise
the following components assembled and mounted on a common frame:
a) Mixing Box section
b) Type C Filter section
c) Cooling Coil Section comprising two sets of coil, each set of coil to be based on
actual calculated requirements and engineering design allowances
d) Supply fan section with spare motor
e) Inspection section.
8.4.3 The fresh air intake unit shall be located on roof of the building or as specified in the
project document and shall comprise the following:
a) Explosion Proof (E/P) fresh air fans (one working + one standby).
b) Fresh air intake duct, plenum box & common duct to be provided with Blast
sleeve / valves on roof top opening.
c) Fresh air-filter box shall be equipped with inertial dust filter and Type C Filter.
d) Chemical filter suitable for absorbing toxic gases (HC, H2S) and flammable
gases (if present) of 99 % efficiency as recommended by OSHA.
e) Fire detection linked with shut off motorised damper, fan motor trip and alarm
signal.
8.5 Battery Room
8.5.1 Battery room shall be provided with once through (supply and exhaust) air
conditioning system. The exhaust fan shall be provided with 100 % standby
arrangement.
8.5.2 Battery room ventilation rate shall ensure that hydrogen gas content does not exceed
1.5 % of room volume and shall not be less than 12 ACPH. Adequate arrangement
shall be made to ensure that that the Hydrogen emitted by batteries, if any, shall not
travel back to its adjacent rooms.
Telecom (LAN), Security Equipment and Electrical Rooms shall be provided with
airconditioning system (cooling only) with 100 % standby arrangement. In case,
Telecom (LAN) Room(s), Security Equipment Room(s) and Electrical Room(s) are
provided with the central air conditioning system, independent Split type Air
conditioning unit(s) (Cooling only) shall also be provided as 100 % standby Air
conditioning unit.
DOC. NO. KOC-MH-001 Page 25 of 66 REV. 0
Gas cylinder room shall be provided with once through (supply & exhaust) air
conditioning system. The exhaust fan shall be provided with 100 % standby
arrangement. Gas cylinder room ventilation rate shall not be less than Four (4) ACPH.
HVAC equipment shall be in accordance with the requirement of this KOC Standard
and the Standards referred in Clause 4.2 of this KOC Standard.
9.1.1 General
b) The package unit shall be furnished with multiple compressors and designed
for dual refrigeration system providing exceptional part load performance. The
complete independent refrigeration systems and associated electrical circuits
shall provide continuous operation if one refrigeration circuit fails.
9.1.2 Casing
The Package unit(s) shall be mounted on structural steel skid base(s) and support
frame. The support shall be painted with epoxy paint suitable for heavy industrial,
marine application and suitable for environmental condition specified in Clause 5.0 of
this KOC Standard. The unit shall be completely sealed against dust, rain and
corrosive gases and suitable for outdoor condition.
9.1.3 Compressor
The condenser coils shall be constructed with seamless copper tubes mechanically
expanded into aluminum fins. The fins shall have full drawn collars to completely
cover the copper tube and protect against atmospheric corrosion. The entire fin area
shall have a factory applied corrosion treatment designed for maximum protection in
severe chemical atmosphere environment. The coating shall have an extremely high
durability factor. The coils shall be designed to provide liquid sub-cooling and shall
be leak tested to 450 psig (3.1 Mpa). Fin spacing shall not exceed 12 fins per inch.
Condenser coils shall be protected by wire mesh guard.
9.1.6 Evaporator
The evaporator section shall be as per project specific requirement (double / single
skin construction), manufactured from zinc-coated steel, degreased and coated with
anti-corrosive paint. Panel shall be removable type and shall be with minimum 50 mm
thick fibre glass insulation or injected polyurethane insulation complying with
NFPA 90 A. The condensate drain pan shall be insulated.
a) The evaporator coil shall be of the direct expansion type. The coil shall be
constructed with seamless copper tubes mechanically expanded with
aluminum fins. The fins shall have full drawn collars to completely cover the
copper tube and protect against atmospheric corrosion. The entire fin area
shall have a factory applied corrosion treatment.
b) The coils shall be supplied with strainer, expansion valve, distributors and
suction gas headers. The face velocity of coil shall not exceed 550 FPM and
fin spacing shall not exceed 12 fins per inch. Coils shall be leak tested to
350 psi.
DOC. NO. KOC-MH-001 Page 27 of 66 REV. 0
a) The unit shall be equipped with supply air fan. Fan shall be centrifugal Double
Inlet, Double Width (DIDW) type. Impeller shall be dynamically balanced and
resiliently mounted. Fan casing and impeller shall be of galvanised steel
construction. Fans shall be selected for their maximum efficiency to operate
quietly when handling the required air volume without overloading the fan
motor. Shaft bearing shall be permanent lubricated self-aligning type. Pulleys
suitable for use with V-belts drive to be fitted to motor and fan shaft. Fan total
static pressure shall suite the system in which it works.
b) The fan motor shall be suitable for power supply as specified in the project
document with Class F insulation, Class B temperature rise and to IP55
protection. The motor shall be mounted on slide rails to permit adjustment of
belt drive. The fan and motor assembly shall be completely isolated from the
cabinet by flexible connectors at the fan outlet and spring isolators under the
base plate assembly.
The unit shall be delivered with full operating charge of environmental freindly
refrigerant (Refer Clause 13.0 of this KOC Standard). Refrigeration piping shall be
fabricated from refrigeration grade seamless copper tubes. Refrigeration circuit shall
include an accessible manual shut off valve, filter / drier, liquid line solenoid valve,
liquid sight glass / moisture indicator and thermostatic expansion valve.
b) Panel access door shall be lockable. The control panel shall be factory wired.
Control function and component labeling shall comprise machine engraved
Traffolyte laminate with beveled. Stick on labels shall not be acceptable.
Circular interlocking plastic ferrules shall be used to identify all control wiring.
iv. Circuit breakers for compressor motor. Overload relays for condenser
and evaporator fan motors.
DOC. NO. KOC-MH-001 Page 28 of 66 REV. 0
vi. Compressor oil failure and high-pressure safety switch, one per
compresor, manual reset types.
vii. Switches to Manual pump-down & Refrigerant charging valve for each
circuit.
xi. Signal from airflow switch (mounted in the supply duct) in case of
“No flow” or “Low flow” of supply air.
xii. Provision for shutting down the package unit when smoke / fire is
detected in any zone (one potential free contact for each package unit
shall be provided in the fire alarm panel for this purpose).
a) Each unit shall be provided with complete set of return air filters. These filters
shall be sized to perform their duty with the specified face velocity at the rated
flow. The filters shall be installed with gaskets and clips to maintain a positive
pressure seal between filter and frame in order to prevent leakage; by-pass
unfiltered air and facilitates installation.
b) Filters shall be installed in such a manner that they can be quickly and easily
removed and that no special tools are required. Filters shall be arranged in
straight bank arrangement installation. Filter-sections shall be equipped with
removable access panels or doors for replacement & service of the filters.
DOC. NO. KOC-MH-001 Page 29 of 66 REV. 0
Each fresh air intake shall be provided with a Four (4) inch thick air filter. These filters
shall be of the permanent cleanable metallic type. The media shall be constructed of
layers of crimped galvanised steel wire mesh enclosure in galvanised steel enclosing
channel. The enclosing channel shall be provided with slots to retain heavy bail-wire
collapsible handles. Initial pressure drop shall not exceed 0.10 IWG and face velocity
300 FPM. Filters shall have not less than 80 % efficiency as measured by the
ASHRAE Weight Arrestance Test or equivalent.
9.3.1 The electric heater shall consist of a slip-in type heater, mounted in the flanged duct.
Frame dimensions shall be made to match supply duct section. The frame shall be
attached directly to external flanges of the duct where the slip-in portion can be pulled
out without removing flanges from duct. All controls are mounted in the terminal box
of the slip-in portion.
9.3.2 The heater shall consist of finned tubular heating element accomplished by encasing
the heating coil in a ground metal sheath. Copper plated steel fins shall be brazed to
steel tubular sheath which includes an 80 / 20-nickel chrome resistant wire connected
to terminal pins. The tubular sheath shall be filled with high quality magnesium oxide
compressed to ensure a rapid and even heat transfer. The terminal pins shall form a
non heated section of the element and shall be insulated from the sheath by ceramic
bushes.
9.3.3 The frame or brackets shall be heavy gauge galvanised steel. Terminal bolts, nuts
and washers shall consist of corrosion resistant material and the terminal boxes are
to be metal protected against corrosion. A provision for earthing the terminal box and
casing shall be made. The control compartment shall be both dust and weatherproof.
9.3.4 The elements shall be suitable for power supply as specified in the project document
and shall be controlled by two or more steps depending on load demand using a zone
temperature sensor / controller. The heating load shall be balanced equally across all
three (3) phases.
9.3.5 Disconnect switch, thermal safety cut out, automatic & manual reset limit controls,
pilot light and airflow switches shall be provided with the heaters. The electric heaters
shall be interlocked with a static pressure switch.
The ducted split air conditioning unit shall consist of an Air Handling Unit and an Air
Cooled Condensing Unit (outdoor unit) with interconnecting piping, cabling, controls
and other accessories.
Air Handling Unit (AHU) shall be factory built, packaged modular design, on a non-
corrosive rigid structural steel base frame with unit mounted control panel including
starter with all operating and safety controls.
DOC. NO. KOC-MH-001 Page 30 of 66 REV. 0
Each unit shall be complete with air tight insulated casing with double skinned panels,
insulated condensate drain pan, cooling coil, fan, fan motor, V belt drive with standby
electric motor (for Plant Buildings), removable panel access doors, air filters, fan
vibration isolators and any other accessories necessary for satisfactory operation.
a) Casing:
ii. Panel insulation medium shall consist of an inert long fiber bacteria
resistant glass fiber slabs secured within the panel cavity using 100 %
coverage of adhesive applied to both panel. Adhesive shall be odorless
fire/smoke rated and suited for the application. Insulation shall be
minimum 2.0 lbs/ft3 density (32 kg/m3), thermal conductivity of
0.23 BTU in/ft2.F.h (0.033 W/mK) and 0.552 W/m2/°C heat transfer
coefficient.
iv. All service panels shall be fitted with a neoprene sealing gasket and
secured in place with stainless steel fasteners. All other panels shall be
permanently secured by concealed stainless steel fasteners and sealed
with silicon sealant.
b) Cooling Coil
i. The evaporator coil shall have two separate circuits; each equipped with
a refrigerant distributor. Coils shall be made of 5/8" and (or) 3/8" OD
copper tubes expanded into aluminum fins. Coil face velocity shall not
exceed 500 FPM and fin spacing shall not exceed 12 fins per inch.
ii. The entire fin area shall have a factory applied corrosion treatment
designed for maximum protection in severe chemical atmosphere
environment. The coating shall have an extremely high durability factor.
Coils shall be leak tested to 450 psi (3.1 MPa). Bottom drain pan shall
DOC. NO. KOC-MH-001 Page 31 of 66 REV. 0
be insulated double wall galvanised steel sloped towards left and right
drain fitting.
c) Fan
ii. Fans shall be selected for their maximum efficiency and minimum noise
generation. Outlet velocity shall not exceed 2000 FPM unless otherwise
specified. Rotation speed shall be selected to minimise impeller-
generated noise over the operating range of the fan. Shaft bearing shall
be permanent grease lubricated, self-aligning type and shall be
designed for a minimum 2,00000 hours average running life based on
full time operation.Minimum required efficiency shall be 70 %. Forward
curved centrifugal fans shall be selected for capacity of 5000 CFM or
less but with required efficiency of 75 % approximately.
iii. All exposed parts shall be well protected against corrosion or made from
corrosion resistant materials and shall not support bacterial growth. An
approved synthetic resin (white epoxy) coating minimum 100-micron
factory applied, in complete accordance with coating Manufacturer’s
recommendations shall be provided.
iv. Pulleys and V-belts shall be selected at 200 % maximum motor start-
up torque and have a minimum of two (2) V-belts. Fixed drive pulleys
shall be used on any drives over 5 HP and variable pitch type under
5 HP. Extra fixed pulleys shall be supplied to permit final balancing
adjustments of ± 15 % of specified conditions. Drive belts shall be
adjusted by repositioning the motor on rigid slide rails.
vi. AHU (serving the electrical substation and control room) shall include a
blower section with duty and standby motor(s). The standby motor with
drive package (Spare pulleys fixed on blower and motor shafts, belts
and electrical power supply to the standby motor) shall be provided
within the blower section in such a way that the same can be connected
manually by fixing the belt & electrical connection, whenever the duty
blower motor fails.
DOC. NO. KOC-MH-001 Page 32 of 66 REV. 0
d) Filters
i. Filters shall consist of a type “A” (refer clause 12.2.1 of this KOC
Standard) pre filter and a high efficiency filter type “C”. All filters shall be
mounted in slide out frames for ease of service. Access doors shall be
fully gasketed and secured in place with cam access type fasteners.
Filter shall be suitable for ambient temperature range of 3 °C to 60 °C
and relative humidity upto 100 %.
ii. Each air filter shall be fitted with a pressure differential indicator and
switch. In the event of reaching a high-pressure differential across any
filter, a common indicating lamp shall be lit. Indicator lamp shall be
located on the control panel.
The mixing section shall be provided with dampers on return air and fresh air
connections with contra-rotating feature as per the specifications in clause
10.3.3 of this KOC Standard. The dampers shall be arranged to operate
automatically with one set of linkage. Suitable length operating rods and
linkage for connection to an electric damper motor shall be provided.
The units shall be complete with compressor(s), air cooled condenser(s), condenser
fans with motor(s), starter(s), refrigerant piping, charging valves, protection / safety
devices, controls, vibration isolators and all other required accessories. The
condensing units shall be located on the ground / roof level as specified in the project
document.
a) Cabinet:
Room type / Mini split units shall comprise of matched systems, consisting of outdoor
units suitable for mounting at the ground / roof level and indoor units suitable for
mounting on the wall. The unit shall comprise of the following main components:
DOC. NO. KOC-MH-001 Page 33 of 66 REV. 0
c) Condenser Fan Motor: Shall be a PSC (Permanent Split Capacitor) single end
shaft type with permanently sealed bronze bearings and be suspended from
unit to fan.
d) Condenser Fan: Shall be a rust resisting aluminum blade, propeller type. Air
discharge shall be directly out from the top or the side of the unit.
a) The indoor unit shall comprise of a cooling coil, circulating air fan thermostatic
expansion valve or capillary tube and any other required accessories. The
cooling coil shall be a series of seamless copper tubes with copper or
aluminum plate fins mechanically bonded to the tube.
b) The fan shall be of the centrifugal type with forward curved multi-vane
impeller(s) mounted on a mild steel shaft. The fan shall be directly driven by
electric motor. The fan shall be complete with multi speed remote switch to
control supply air volume.
c) The indoor unit shall be complete with removable front panel with twin outlet
flaps enabling precise adjustment of airflow direction to assure that warm or
cold air quickly reaches all corners of a room / space.
d) The unit shall be complete with cleanable cartridge type air filters accessible
from the front of the unit without removing the front panel. The condensate
drain shall include a drain pan.
a) Fan coil units shall be ceiling suspended cabinet for exposed installation,
complete with stamped supply grille, one inch thick cleanable filter and return
grille. Unit casing shall be zinc coated galvanised steel with electrostatic
polyester powder coating. The unit casing shall be lined with ½" thick fiber
glass acoustic and thermal insulation.
c) Fan coil units serving the stores shall have provision for winter heating.
Heating elements shall be constructed from high quality 80 / 20 nickel chrome
resistance wire connected to terminal pins and centered in a metal tube with
galvanised steel fin. The elements shall be isolated from the casing. Heating
elements shall be factory built.
d) Drain pan shall be double skin type from galvanised steel. Pans shall be full
width and fully insulated with Styrofoam coated with bitumen / rubber adhesive
and vapour barrier for maximum protection against corrosion and sweating. A
drain connection shall be provided for removal of condensate.
e) Fan shall be provided with centrifugal double inlet double width for operation
with low noise. Fan shall be direct driven by single phase, multi speed
permanent split capacitor motor operating almost noiselessly with permanent
lubricated sleeve bearings.
a) Twin Cabinet fans shall be of the centrifugal direct drive type. The fan housing
shall be constructed of heavy gauge galvanised steel and shall include pre-
punched mounting brackets. The housing interior shall be lined with ½"
acoustical insulation. The outlet duct collar shall include an aluminum back draft
damper and shall be adaptable for horizontal or vertical discharge. The access
for wiring shall be external.
b) The motor disconnect shall be internal and of the plug in type. The motor shall
be mounted on vibration isolators. The fan wheels shall be of the forward
DOC. NO. KOC-MH-001 Page 35 of 66 REV. 0
Fan shall be direct driven axial flow type with non-overloading characteristics, selected
for high efficiency and quiet running. The fan shall be of the heavy-duty type with
durable construction and suitable for continuous operation. Motor shall be totally
enclosed fitted with thermal cut out. Fan accessories shall include gravity type louver
shutter on the discharge side.
9.6.3 Wall Mounted Propeller Fans (with Flame Proof / Explosion Proof Motor)
The fan shall include the following features in addition to the normal Wall unit
described under clause 9.6.2 of this Standard.
a) Centrifugal or mixed flow roof Exhaust fan unit shall be direct driven, with spun
aluminum wheel and shall be with weatherproof housing incorporating an
integral weather shield; resilient mounted motor; ½ inch (13 mm) mesh,
16 gauge GI or Aluminum bird screen, square base to suit roof curb with
continuous curb gaskets; secured with Cadmium plate bolts and screws.
b) Roof curb shall be 10 inch high concrete up-stand built-in situ with 2 inch wood
block fasten to it.
f) Bird screens shall be welded galvanised steel wire grid with framing suitable
for bolting to prevent entry of birds when the fans are not in operation.
g) Operation of the fans shall be achieved from control panel as specified in the
project document. Control panel shall have provision for ON / OFF push button
controls, fan run indication lamp for individual fans and a lamp test button as a
minimum.
a) This type shall be direct drive type Axial Aerofoil Bifurcated with motor outside
the air stream. Casing shall be long type complete with motor mounted
electrical terminal box, shall be constructed from spun steel with hot dip
DOC. NO. KOC-MH-001 Page 36 of 66 REV. 0
galvanised finish suitable for use against corrosive fluids. Fit with inlet and
outlet flanges of quick fit type.
b) Impeller shall be aerofoil type with disc cast aluminum hub and cast aluminum
blades. Assemble impellers using plated set screws and self locking units.
Pitch angle shall be adjustable and factory set to provide the required duty. All
castings shall be inspected by X-Ray prior to assembly.
c) Motor shall be totally enclosed protected to IP55 with “Class F” insulation and
“Class B” temperature rise. Operating Temperature shall be 200 °C fluid
temperature.
a) Fan shall be axial flow type (direct drive) with non-overloading characteristics,
selected for high efficiency and quiet running. The fan shall be of the heavy-
duty type and shall be of durable construction and proven performance. Casing
shall be manufactured from mild steel with powder coat finish. Fans shall be
supplied with motor side guard. Fan accessories shall include wall cowl,
impeller side guard and back draft gravity damper.
b) Fan motor shall be explosion proof, suitable for ambient temperature of 50 °C,
EExd Zone-1,Group IIC (Hydrogen), T3 classification and suitable for electrical
power supply as specified in the project document.
9.6.7 All the Fans shall bear a permanently affixed Manufacturer's name plate containing
model number and individual serial number for identification. “Sticks on” labels shall
not be acceptable.
10.1 The refrigerant pipings shall be designed to ensure that the acceptable pressure drops
in each refrigerant piping of refrigeration cycle shall not exceed 2 °F (1.12 °C) for
suction line / hot gas line and 1 °F (0.56 °C) for liquid lines. All field piped (refrigerant)
systems have compressor oil passing through the refrigerant circuit and back to the
compressor. A minimum velocity shall be maintained in the refrigerant piping so that
sufficient oil is returned back to compressor sump at full and part load conditions. A
minimum velocity of 500 FPM for horizontal suction / hot gas lines and 1000 FPM for
suction / hot gas risers.
10.2 Refrigerant pipes assembled in the field shall consist of copper tubing and recessed
solder joint fittings. Tubing shall be type `ACR' (Air Conditioning and Refrigeration)
hard drawn in accordance with ASTM B 280. Fittings shall be wrought copper or
tinned cast brass. Where required for connection to gauges and control devices,
tubing with OD not larger than 3/8 inch (9.5 mm) shall be type “K”, soft (annealed) with
flared tube or double ferrule compression fittings suitable for high pressure.
10.3 On all joints in refrigeration piping flux and solder shall be used. Tubing shall be
protected against oxidation during silver soldering by use of dry nitrogen flowing
through the tubing. Refrigerant piping shall be installed so as to ensure continuous
automatic return of oil to the compressors. Gauges, thermometers and the like
supported directly on pipes shall be leveled.
DOC. NO. KOC-MH-001 Page 37 of 66 REV. 0
10.4 Refrigerant stop valves shall be of the back seating, key operated, steel cap type.
Valves, which must be opened and closed in a regular operation, shall have hand
wheels and shall be of the backless type. Valves connected to copper tubing shall
have solder type ends or flanged ends and soldered flange adapters.
10.5 Each refrigerant circuit shall include a liquid line sight glass with moisture indicator, a
replaceable core type filter drier with a bypass valve, solenoid valve and high / low
pressure controller. The system shall have arrangement for pump down control with
cycling relay or any other approved arrangement.
10.6 Refrigerant pipes, valves, strainers and the like & fitting shall be insulated with rigid
fiberglass of not less than 6 lb./ft3 density, performed sectional insulating material split
longitudinally into two halves with factory applied reinforced aluminum foil coating with
the following minimum thickness:
10.7 The insulation shall be secured to the piping by an adequate number of non-corrosive
straps drawn tight and neatly cut. The straps shall not damage the insulation or vapour
seal. Wires shall not be used.
10.8 The hot gas lines shall be insulated wherever there is a possibility of personnel safety
hazard.
10.9 All insulated pipes shall be aluminum clad after reinforced aluminum foil vapour
sealing with anodized 0.016 inch (0.4 mm) thick aluminum sheets. Painting is not
required above the aluminum cladding. All insulated refrigerant pipes exposed to
ambient conditions shall be aluminum cladded for mechanical protection.
11.1.1 ‘Equal Friction Methods’ shall be followed for sizing the duct systems unless
otherwise specified in the project document. The friction loss per unit length of duct
shall be kept constant through out the system and shall not exceed 0.1 IWG per
100 ft. of duct length.
11.1.2 The rectangual duct shall be so sized as to have low aspect ratio – the ratio in any
case shall not exceed 4:1.
11.1.3 The recommended maximum duct velocities for low velocities system shall be as
given in Table-3 of this Standard.
DOC. NO. KOC-MH-001 Page 38 of 66 REV. 0
TABLE - 3
( Recommended Maximum Duct Velocity (in FPM))
11.2.1 Ducts shall be designed, fabricated, assembled and connected in accordance with
the ASHRAE & SMACNA recommendation for the type of construction (low pressure)
or as specified in the project document.
11.2.2 All sheet metal ductwork shall be of lock forming quality galvanised steel and
produced from cold rolled, close annealed, plain, un-salted, galvanised mild steel
sheets of soft bending quality especially suitable for air conditioning / ventilation work
complying to BS EN 10346 and BS EN 10143 unless otherwise specified.
11.2.3 Galvanised steel shall be with G90 Zinc Coating in accordance with ASTM A653 /
ASTM A90.
11.2.4 The thickness of galvanised steel sheet for duct fabrication (rectangular / square
duct), maximum sizes of ducting, transverse joint and bracing details shall be in
accordance with the Table – 4 of this Standard.
DOC. NO. KOC-MH-001 Page 39 of 66 REV. 0
TABLE - 4
13" - 18" 24 1" pocket joint at 8 ft. center with cross breaking.
19" - 30" 22 1" pocket joint at 4 ft. centers with cross breaking.
31" - 42" 22
1" pocket joint at 4 ft. centers with cross bracing and
1 x 1 x 1/16-inch angle girth at 8 ft. centers bolted to the
pocket joints.
43" - 54" 20 1½" pocket joint at 4 ft. centers with cross bracing and
1½" x 1½" x 3/16 inch angle girth at 8 ft. center bolted
to the pocket joints.
55" - 72" 20 1½" pocket joint 4 ft. centers with cross bracing and
1½" x 1½" x 3/16 inch angle girth at 8 ft. centers bolted
to the pocket joints.
11.2.5 Openings for instrument connections shall be provided with all standard fittings as
approved by KOC.
11.2.6 All openings in ductwork shall be sealed to prevent intrusion of dust and foreign
materials.
11.2.7 All bracing and reinforcement angles shall be made of black steel, of anti-rust paint
prior to installation.
11.2.8 Pocket locks, deflectors and all branch ducts which require joints between two (2)
sheet metal pieces shall be made using aluminum rivets having a round head at one
side. Alternatively, blind pop rivets of appropriate size shall be used. Ductwork shall
be so constructed that when erected it shall be airtight and shall be free from
movement, sagging or drumming under all operating conditions.
11.2.9 Wherever ducts require to clear structural members, the overall dimension of the duct
shall be changed provided the cross-sectional area is not reduced and aspect ratio
shall be within operable range. All duct elbows having an inside radius smaller than
the width of the elbow shall be equipped with approved guide vanes tightly riveted to
the duct.
11.2.10 Duct-turns shall be installed in all cases where 90-degree square elbows are used
and short take-off are used on large ducts. Guide splatter vanes shall not be spaced
more than 150 mm apart.
11.2.11 The throat radius of a bend shall not be less than half the width of the associated side
of the duct. When it is not possible to comply with this, duct turning vanes or right
angle bends shall be used.
DOC. NO. KOC-MH-001 Page 40 of 66 REV. 0
11.2.12 All right angle bends must be fitted with turning vanes. The vanes shall be spaced in
such a way that the aspect ratio of each of the individual elbows will be in the region
of 6:1.
11.2.13 All side outlet take-offs (outlet collars) shall have a throat radius of not less than half
the width of take-off and are to be fitted with fixed turning vanes.
11.2.14 All ductwork reducers shall have a slope or taper of one to seven, unless this slope
cannot be maintained. In any case, a maximum slope of one in four shall not exceed.
11.2.15 Access doors shall be provided wherever necessary to facilitate inspections, cleaning
and maintenance. Duct doors shall be suitably stiffened and located in accessible
positions.
11.2.16 Ductwork supports shall be of mild steel angle sections spaced at 1800 mm
maximum and projecting 50 mm on either side of duct insulation. The hanger rods
shall be suspended from the steel structure / slab with hexagonal headed bolts and
double nuts with flat steel washers.
11.2.17 Where ductwork passes through openings in the steel structure of the buildings, no
metal link shall exist between ductwork and structure. Ducts are to be supported
either side of the steel structure penetration. Where ductwork or equipment has to be
supported from the steel structure (i.e. hanging below the structure in plant rooms,
corridors and the like), spring hangers or vibration isolation mounts shall be used.
11.2.18 All steelwork (supports) shall be coated prior to erection with base coat of red oxide
primer and top coat of grey paint applied after erection on exposed metal parts. All
steelworks such as angle iron, hanging rods, brackets, bolts, nuts, locknuts and the
like which are necessary for the support of the ductwork shall be supplied and
installed.
Manual volume control damper shall be of the butterfly or multiple blade type, with 16
gauge galvanised steel frame, stainless steel blades, sleeves, bearings as required
for balancing purposes. Multiple blade dampers shall have interlocking blades.
At each point of division in a supply duct where a branch duct is taken off, an
adjustable splitter or deflecting damper shall be fitted to the full depth of the duct, with
operating rod and locking quadrant. These deflecting dampers shall be permanently
set and locked in position after completion of the installation and adjustment with fans
running. Operating rods shall be full blade length extending through the duct to
externally mounted bearing plates.
DOC. NO. KOC-MH-001 Page 41 of 66 REV. 0
Motorised dampers shall be of the multiple blade type and shall be provided with
galvanised steel frame and interlocking blades, sleeves, bearings as required for shut-
off purposes. Blades shall be fabricated from stainless steel with seamed edge and
suitable length operating rods and linkage for connection to an electric damper motor
shall be provided. Damper shall close on loss of power.
a) Fire dampers shall be installed in all ductwork, crossing over to the other fire
zones whether indicated in the drawings or not.
b) Fire dampers shall be of curtain type with blades out side the air stream. Frames
shall be of galvanised steel; Blades and closure spring shall be of stainless
steel. Fusible link shall be rated for 160 °F (71 °C). Multi section fire dampers
will be considered for larger sized opening.
c) Motorised fire dampers shall be multiple blade type with actuators connected to
the control panel. In the event of fire or release of fire suppressant, the fire
damper shall be actuated through a signal from the control panel. Motorised fire
dampers shall also be provided with the fusible rod as specified above.
d) Fire dampers shall conform to NFPA 251, NFPA 255, NFPA 259,
BS 476 (Parts 20-23) and UL 555. Fire dampers shall maintain their integrity
for a period similar or exceeding the structure where it is installed.
Gravity back draft dampers shall be multi blade parallel action dampers. Blades shall
be maximum 6” wide and of 16 gauge galvanised steel or Aluminum and edges will
be sealed with felt or flexible vinyl. The blades shall be pivoted using steel pivot pins
and linked to open for 90 degrees without rattling.
b) Turning Vanes: Provide turning vanes and vane runners as shown in the
relevant drawings.
c) Test Holes: Provide duct test holes consisting of slot and cover for testing
purpose wherever required.
a) The electric duct heater shall consist of a slip-in type heater, mounted in the
flanged duct. Frame dimensions are made to match supply duct section. The
frame is attached directly to external flanges of the duct where the slip-in portion
could be pulled out without removing flanges from duct. All controls are mounted
in the terminal box of the slip-in portion.
c) Frame / brackets, nuts, bolts, washers and electrical terminal box shall be hot
dip galvanised. Terminal box and casing shall have provision for earthing.
d) The control pannel shall be suitably constructed to prevent the entry of dust and
water shall have an ingress protection of IP 42 in accordance with IEC 60529,
unless otherwise specified.
e) The elements shall operate on electrical power supply as specified in the project
document and shall be controlled by two or more steps depending on load
demand using a zone temperature sensor / controller. The heating load shall
be balanced equally across all 3 phases.
f) Disconnect switch, thermal safety cut out, automatic and manual reset limit
controls, pilot light and airflow switches shall all be provided with the heaters.
The electric heaters shall be interlocked with a static pressure switch.
Flexible ducting shall be factory fabricated from a stainless steel wire spiral tube,
externally and internally coated with a reinforced PVC foil and 50 mm thick external
insulation with vapour barrier. Tubes shall be fitted closely with clamps and be secured
in an airtight fashion to duct take-off and terminal units. The unclasped section of the
flexible tube shall be kept straight or shall be bent with the maximum radius possible
DOC. NO. KOC-MH-001 Page 43 of 66 REV. 0
to prevent noise generation and to reduce pressure drop. The flexible tube shall be
kept as short as possible. Flexible tubes shall not be painted.
Attenuators and sound absorbent material shall be provided where required in the
duct work systems to ensure that noise ratings do not exceed those specified. The
attenuators and sound absorbent materials shall be so designed and installed in the
duct work that they offer low resistance to airflow, have adequate strength and
cohesion to resist erosion by air and do not produce dust. They shall be free from
odour and proof against rot, damp, vermin and shall be capable of withstanding
environmental corrosive conditions as per “KOC Standard for Basic Design Data”
(KOC-G-007). Adhesive shall be compatible with the sound absorbent materails and
shall be non-flammable.
Air outlets and air inlets shall be constructed from extruded Aluminum with polyster
powder coated finish to a colour approved by KOC. A sponge rubber gasket shall be
provided behind the frames and nylon bushings at the blade connection to the frame,
and wherever applicable wall frame shall also be provided. The recommended terminal
velocity range for air outlets shall be 500-700 FPM.
The supply air register shall be provided with adjustable horizontal front blades,
vertical rear blades and opposed blade dampers.
b) Return Air Grilles
Return air grilles shall be provided with fixed horizontal front blades.
Exhaust air register shall be provided with fixed horizontal front blades and
volume control dampers.
Diffusers shall be square louver face type made from extruded Aluminum.
Diffusers shall be fitted with supply volume dampers and equalising grids as
furnished by the diffuser Manufacturer. Volume controls for these outlets shall
be accessible through the outlet from below the diffuser and shall maintain their
setting when adjusted. Each diffuser shall be provided with sponge rubber or
felt gasket and angle ring or frame for securing the ductwork.
The number of slots for linear bar supply / return grille shall be as specified in the
project document. Frame wall thickness shall be 1 / 16 inch minimum. Blades
spaced ½" on center and ¼" thickness at face.
DOC. NO. KOC-MH-001 Page 44 of 66 REV. 0
f) Door Grilles
Door Grilles shall be inverted V-blade which will not permit vision through the
grille blades. Blades shall not be more than 13 mm apart. The minimum free
area shall be at least 70 %. Louvers shall be of the double frame type with a
frame on each side of the door.
i. Fresh air inlet louvers shall be sand trap type consisting of vertical channel
separator vanes mounted in enclosure / frame having self-emptying sand /
moisture discharge opening in base. The louver shall be selected to have a
maximum face velocity of 300 FPM.The exhaust air louvers shall be of the
inclined blade gravity shutter louver selected to have a maximum face
velocity of 600 FPM. Trapped sand shall be discharged beyond the face of
the wall on which the louver is mounted.
ii. All inlet and outlet louvers shall be supplied complete with bird wire mesh
guards and shall be designed to minimise the penetration of wind driven
dust, sand and moisture into the HVAC system.
i. The variable air volume boxes (bypass type) with controls shall be ceiling
mounted and capable of modulating airflow to maintain zone / room
temperature. Casing of VAV boxes shall be double skin of 22 gauge
(minimum) galvanised steel with minimum 25 mm thick glass fiber insulation
and complying with NFPA 90A and UL 181.
ii. Motorised air volume damper assembly shall be inside unit casing and
control components inside protective metal shroud. Mount damper operator
to position damper normally open. Volume damper shall be of galvanised
steel with peripheral gasket & self-lubricating bearings and maximum
damper leakage 2 % of design air flow at 250 Pa rated inlet static pressure.
11.4.1 General
a) All the insulation products and their application shall comply with NFPA 90A.
b) Insulation shall be applied in such a manner that there will be no air circulation
within the insulation and the applied surface. Surface imperfections in such as
chipped edges, small joints or cracks and small voids or holes shall be filled
with light insulating material or with insulating cement.
d) No ducts, piping or equipment shall be insulated until leak tested and approved
by KOC.
The type of insulation to be used for the various services and equipment shall be
detailed hereinafter.
b) The insulation shall be provided with an integral fire retardant vapour barrier
jacket with the following minimum recommended thickness in Table-5 of this
Standard.
TABLE-5
c) Thermal duct insulation shall be factory manufactured and flexible roll type
glass fiber with glass reinforced Aluminum foil facing. Insulation shall be fixed
to the entire surface of the ducts with suitable fire-resistant adhesive applied
as recommended by the insulation Manufacturer. For sealing insulating joints,
a 4-inch wide reinforced adhesive and vapour proofed tape shall be used.
d) Duct insulation shall be continuous through duct sleeves and openings. The
insulation shall be secured to the ducts with fold over type overhead slips at
12" (300 mm) to 18" (450 mm) centers / approved equivalent and vapour seal
all punctures.
e) Alternatively, galvanised sheet metal angle strips of 24 gauge fixed to all with
wire shall be used. Where ducts are run inside plant rooms or where they are
exposed to view indoors, they shall be wrapped with an 8-oz. canvas jacket in
place with suitable adhesive.
DOC. NO. KOC-MH-001 Page 46 of 66 REV. 0
a) Internal duct lining for acoustic insulation where applicable shall not be less
than 1 inch thick fiberglass mat faced flexible blanket of fine fibber having a
thermal conductivity of not greater than 0.275 BTU/hr/ft2/°F/inch thickness
measured at an average temperature of 100 °F (37.8 °C) with minimum density
of 1.5 lb/ft3 and accurately banded surface mat coated with clear or black
neoprene / as specified in the project document.
12.1 General
a) The outside (fresh) air and the recirculated air contain dust and suspended
impurities. So, each Air Handling Unit (AHU) shall be provided with a complete
set of air filters cell. These filters shall be sized to perform their duty with a face
velocity of 350 FPM at the rated air flow.
b) The filters shall be installed with gaskets and clips to maintain a positive
pressure seal between filter and frame in order to prevent leakage, by-pass
unfiltered air and facilitate installation.
c) Filters shall be installed in such a manner that they shall be quickly and easily
removed. Filters shall be arranged in straight or V bank.
d) Filters section shall be equipped with removable access panels or doors for
replacement and service of the filters.
f) The efficiency of the air filters shall be in accordance with ASHRAE 52.2
arrestance and dust spot efficiency tests.
DOC. NO. KOC-MH-001 Page 47 of 66 REV. 0
12.2.1 Type A
a) Filters shall be of the permanent cleanable metallic type. The media shall be
constructed of layers of crimped, galvanised steel wire mesh enclosure in
galvanised steel enclosing channel. The enclosing channel shall be provided
with slots to retain heavy bailwire collapsible handles. The initial pressure drop
shall not exceed 7.5 mm WG and face velocity 350 FPM.
12.2.2 Type B
a) Filters shall be disposable type, high efficiency and 300 mm minimum depth.
The initial pressure drop shall not exceed 7.5 mm WG and face velocity
350 FPM.
b) Filters shall have dust spot test efficiency of not less than 90 %.
12.2.3 Type C
b) Filters shall have dust spot test efficiency of not less than 95 %.
b) The housing with side access construction shall be qualified and tested in
accordance with the requirements of ASHARE and certified to have a minimum
rating of “Class B” at 1,000 Pa (4.02 IWG) negative pressures.
c) Side Access Housing (SAH) shall have a corrosion resistant casing consisting
of a rigid coated steel and structural frame and 1" thick fitted foam-filled double
wall panels. The SAH unit panels shall provide a Thermal Resistance (R value)
of 6.5 ft² °F h/BTU and a minimum Insulation Thermal Conductivity (K value)
of 0.15 BTU/hr in/ft² °F.
d) Access doors shall be provided on the filter sections to allow ease of access to
and installation and removal of chemical (gas-phase) filters.
g) The efficiency of chemical media shall be 92 % or higher and face velocity shall
not exceed 500 FPM for rated air flow.
h) The chemical filters shall have media re-filling ports, covered and sealed using
reinforced injection molded polypropylene.
j) The pressure drop, test results etc. for the chemical filter housing from
reputable independent air filter testing laboratories shall be provided to KOC.
13.0 REFRIGERANTS
13.1 Many of the refrigerants in use for the past several decades have impact on the
environment in two ways - Ozone Depletion and Global Warming Potential
(Greenhouse Effect). Considering this, the selected environmental friendly
refrigerants shall have zero ODP and low GWP. The environmental impact of the
currently used refrigerants are indicated in Table -6 of this Standard.
TABLE-6
Temp.
Chemical Boiling Point
Refrigerants ODP (GWP)*100 Glide
Composition (°C)
(°C )
Blend of
R-407C 0 1610 7.4 - 43.7
R32/125/134a
Blend of
R-410A 0 1800 < 0.2 -52.7
R32/125
* Global Warming Potential (GWP) has a time component spreads from 20 to 100 years and is written as (GWP)100
{100 years life time}. It means that the emission of one kg of R134a is roughly equivalent to 1300 kg of CO2 in 100
years.
13.2 In case of phasing out or ban of the currently used refrigerants alternative
environmental friendly refrigerants shall be used, duly approved by KOC.
DOC. NO. KOC-MH-001 Page 49 of 66 REV. 0
The HVAC control system using Direct Digital Controller (DDC) technology shall be
provided. DDC shall be programmed and logic shall be written for the control
sequence, logic interlock and protection scheme.
14.1 General
All components and controls shall be suitable for 24 Volt DC and designed, selected,
installed, tested and commissioned in accordance with the following requirements:
14.1.1 The HVAC system components and controls shall be designed and the equipment /
materials selected to preclude interaction between associated electrical circuits. The
system shall be immune to radio frequency interference. The HVAC control system
shall generally of electric mode operation and will have the indications for major
parameters monitoring and alarming facilities local and remote.
14.1.2 All indoor equipment shall be designed to withstand ambient temperature between
26.6 °F (-3 °C) to 122 °F (50 °C) and relative humidity of 20-100 %. In addition, the
equipment design shall consider the ingress of salt polluted sand in the form of grains
or fine dust into the building and the occurrence of condensation.
14.1.3 All outdoor equipment, including those located in the non-controlled atmosphere area
such as HVAC / mechanical rooms shall be weather proof with a minimum degree of
protection IP 55 in accordance with IEC 60529.
14.1.4 The HVAC Control panel shall have audible alarm with reset facility and the following
minimum points shall be available on the panel for monitoring:
14.1.5 The HVAC System shall be hard wired interlocked with fire alarm system and fire
suppression system (if any) and in case of signal either from fire alarm and / or fire
suppression system, the complete HVAC system will trip (Except the Battery Room
Exhaust Fans in Substation) and shall have to be reset manually for restarting. Such
interlock can be achieved through an interposing relay panel, if necessary.
14.1.6 The fire alarm signal and the fire suppression system alarm shall shutdown the
complete HVAC System. Also, all motorised fire dampers shall be closed. Fire alarm
shutdown and fire suppression alarm shall be displayed on HVAC Control Panels. On
reset of the above alarms, all the fire dampers shall open and HVAC system starts.
DOC. NO. KOC-MH-001 Page 50 of 66 REV. 0
14.1.7 The HVAC Control panel shall have the following minimum contacts for each of the
Annunciation Panel, DCS Panel and SCADA / DAP. Any further additions can be done
to the below list as specified in the project document:
14.1.8 Full access to all instruments / detectors and control equipment shall be provided.
14.1.9 The operation of all fresh air motorised dampers shall be through HVAC Control
Panels. All the gas detectors (HC, H2S and H2) shall be supplied from the KOC
approved list.
14.1.10 The exhaust fans in battery room shall start and stop automatically through HVAC
Control Panel. In case of failure of working fan, standby fan shall start automatically
and audible, visual alarm shall be generated on the HVAC Control Panel for failure of
the working fan.
14.1.11 In case of hydrogen gas detection inside battery room, both working and standby
battery room exhaust fans shall be running. In case, both battery room exhaust fans
fail, the UPS battery boost charging shall be stopped.
14.1.12 In case of toxic gas detection, the fresh air intake shall be closed automatically by
motorised damper and the system shall operate in re-circulation mode.
14.1.13 Gas detectors (H2S & HC) shall be provided if specified in the project document. In
case of flammable gas detection, the complete HVAC system shall shut down without
any re-circulation of air. Fire & Gas detection system shall comply KOC
Recommended Practice for Design, Selection and Location of Fire & Gas Detection
System (KOC-L-036).
14.1.14 Complete drawings shall be submitted to KOC for review / approval before any field
installation is started. Such drawings shall give a complete description of all control
elements and shall show complete schematic and wiring diagrams, including
functional description.
14.1.15 Laptop with all necessary software, firmware and hardware including cables are
required to maintain HVAC control system shall be reviewed and specified in project
document.
14.2 Thermostat
14.2.1 Digital display thermostat shall be fully proportioning type with feedback (unless
otherwise specified) and shall have adjustable sensitivity or throttling range and a
scale range of at least 15 °C. It shall be cooling / heating (Heating blocked if not
required) temperature control type thermostat for year round operation. The control
point shall be adjustable 5 °C above & below its intended setting.
DOC. NO. KOC-MH-001 Page 51 of 66 REV. 0
14.2.2 Thermostat shall be of indicating adjustable type and shall have a lockable acrylic
cover. The location shall be as specified in the project document.
14.3 Detectors
The Gas detectors (H2S & HC) shall be interlocked with HVAC System in such a way
that in case of energisation of gas detection system as described above, the fresh air
supply shall cut off through closing of motorised damper and HVAC system shall shut
down without any re-circulation of air.
H2S sensor of 0-100 ppm range shall be installed for measuring the H2S concentration
in the Outdoor air intake unit duct. The H2S sensor shall have a local digital display
and potential free relay contacts to activate closure of motorised damper when H2S
concentration in the fresh air reaches preset alarm set point. The damper shall open
automatically when the concentration of gas becomes normal.
14.3.2 HC Detector
Hydrogen detector for measuring the Hydrogen concentration inside the Battery
Room shall be provided. The Hydrogen detector shall have a local digital display and
potential free relay contacts.
The HVAC Contractor shall supply and install all electrical & control equipment and
wiring required for satisfactory operation of HVAC System. Electrical works shall
comply with KOC Standards for Electrical Engineering.
15.1.1 The main power supply for all HVAC equipment shall have either of the below
mentioned characteristics (Refer KOC Standard KOC-E-003, Part-1 for details), as
mentioned in the project document.
15.1.2 Power supply for “Building Services” (like Office Complex, Housing) shall be 415V,
3 phase, 4 wire with solidly earthed neutral is generally available.
DOC. NO. KOC-MH-001 Page 52 of 66 REV. 0
15.1.3 All electrically operated equipment and accessories shall be designed and
constructed to operate efficiently without damage to the equipment with the following
voltage and / or frequency percentage variations:
15.1.4 Arrangement for electrical power supply for the various HVAC equipment of various
areas shall be as specified in the project document. In addition, a local isolator (TPN)
shall be provided near to all outdoor HVAC units (like air cooled condensing units,
etc.) for outdoor application pad locking arrangement.
15.1.5 All the explosion proof fans / motors shall be provided with electrical panel suitable for
hazardous area.
Select and rate all equipment and materials at the following conditions:
15.3.1 Unless otherwise specified, all motors over ½ kW shall be three (3) phase
(1 phase, TEFC for ½ kW and less) squirrel cage induction type. Totally Enclosed Fan
Cooled (TEFC) having “Class F” insulation with “Class B” temperature rise, for using
in all non-hazardous areas.
15.3.2 Each motor shall be provided with heavy duty type Direct on Line (DOL) starter. As
mentioned below, red and green indication lamps shall be provided for motors rated
1 HP and above.
15.3.3 All motors of battery room exhaust fans shall be suitable for Zone 1 (Group IIC,
Hydrogen, T3).
15.3.4 Electrical equipment for hazardous area shall conform to the relevant parts of “KOC
Recommended Practice for Selection, Installation and Maintenance of Electrical
Equipment in Hazardous Areas” (KOC-E-004) and / Project Specification.
15.3.5 The copies of relevant hazardous area certification documents shall be submitted to
KOC for review and approval.
DOC. NO. KOC-MH-001 Page 53 of 66 REV. 0
15.4.1 All motor starters shall be suitable for direct online starting. Each motor starter shall
comprise of fuse switch or MCCB protected contactors with utilisation category of
AC3. Minimum enclosure protection of IP 43 for indoor and IP 55 for outdoor in
open area / IP 54 under shelter in outdoor areas shall be provided. Each starter
(with inherent under-voltage release) shall be provided with hand reset thermal
overload relays in each phase, having an adjustable range and ambient temperature
compensated, complete with single phasing preventer.
15.4.2 Suitable motor duty type switch (capable of breaking the motor locked rotor current),
lockable type interlocked with the starter cover shall be provided for incoming supply
isolation. HRC fuses, suitable for motor starting duty shall be provided for short circuit
protection. Start and stop push buttons shall be provided on the starter. Start push
button shall be shrouded type - green coloured - momentary type. Stop push button
shall be enshrouded type - red coloured - stay put type.
15.4.3 Motor control circuit shall be suitable for operation at 110V AC (Alternating Current)
derived internally through a transformer unless otherwise specified.
15.4.4 Motors less than 15 kW shall be provided with direct connected 3 pole inverse time
ambient temperature compensated thermal type overload relay and single phasing
protection. For motors of 15 kW to 30 kW, inclusive the same features but current
transformer fed.
15.4.5 Motors above 30 kW shall be fitted with electronic / static motor protection relay having
overload definite earth fault, stalling, phase imbalance protection. All motors above
15 kW shall have core balance current transformers with definite time delay earth fault
delays.
15.4.6 In general, the requirement given in the Project Specification for Electrical shall be
followed for the motor starters except that the motor starters shall be non draw out
type. The rating and numbers of feeders required shall be suitable for the power
capacity of HVAC equipment with 25 % spare.
All cabling shall be copper conductor, XLPE insulated armoured, overall PVC
sheathed. All wiring inside the distribution boards / starters shall be carried out using
1000V grade flame retardant PVC wires. The rating and numbers of feeders required
shall be suitable for the power capacity of HVAC equipment with 25 % spare.
All cabling shall comply with the requirement specified in “KOC Standard for Electric
Cables” (KOC-E-023).
15.6 Earthing
15.6.3 All package units shall be provided with at least two (2) earthing bosses suitable for
cables to be connected to the main earthing system
15.6.4 For details of earthing and bonding requirements, “KOC Recommended Practice for
Earthing and Bonding” (KOC-E-024) shall be referred.
16.1 General
16.1.1 Inspection and testing shall be performed in accordance with the requirement
specified in this KOC Standard, KOC approved Inspection and Test Plan (ITP) and
the requirement specified in “KOC Standard for Project QA / QC Requirements”
(KOC-Q-014).
16.1.2 Testing, adjusting and balancing of air distribution system, refrigerant piping system
and associated HVAC equipment shall include but not limited to the following:
16.1.3 Testing, adjusting and balancing of HVAC system and equipment shall be in
accordance with ASHRAE Application Handbook unless otherwise specified in project
document.
16.2 Pre-commissioning
16.2.1 Contractor shall carry out the checks which shall include but not limited to the
following:
The control systems shall be checked as per the KOC approved drawings /
documents. HVAC plant shall successfully pass through its full range of heating and
cooling cycles under complete automatic control. Equipment required to operate
under fire conditions shall be tested as specified in the project document.
i. Supply : ± 5 % of design.
ii. Return : ± 10 % of design.
Noise level tests of the installation shall be carried out with a calibrated
sound level meter. Noice level shall be recorded for all HVAC equipment
under ON and OFF condition (Refer to Clause 7.2.4 of this KOC
Standard).
The Contractor shall carry out tests and readings / results and submit to KOC for
review / approval, which shall include but not limited to the following:
a) Outside Conditions
e) Air Filters
f) Cooling Coils
h) Electric Motors
i. Speed (rpm).
ii. Amperes for Each Phase.
iii. Supply Voltage.
i) Any other test required as specified in the Project document / KOC approved ITP.
DOC. NO. KOC-MH-001 Page 57 of 66 REV. 0
The performance parameters (like capacity, Airflow, Static Pressure, etc.) of each
HVAC equipment shall be prepared by Contractor and submit to KOC for review &
approval.
16.4.2 In the event of any stoppage, adjustment or repair (normal running adjustment
excluded), the test shall be void and started all over again after completion of
adjustment and / or repair.
16.4.3 Summer reliability test for complete HVAC system shall take place between 1st of July
and 31st of August and winter reliability test for system between 16th of November and
15th of February or as specified in the project document.
16.4.5 During reliability tests, Contractor shall take spot readings as directed by KOC to
confirm that the system balance is maintained. Contractor shall prepare and fill in log
sheets / test format, recording test results as approved by KOC and submit the same
at the end of the test.
16.4.6 Completion certificates for HVAC system shall be issued by KOC only after successful
completion of Mechanical / HVAC works and Reliability Test.
The HVAC equipment / system shall be guaranteed / warranteed for One (1) year as
whole in accordance with KOC General Conditions of the Contract. In addition to this,
the warranty for the Compressors of HVAC units shall be Five (5) years from the date
of completion of works in writing by KOC. The original warranty certificate from the
Manufacturer or its authorised local agent shall be submitted to KOC after completion
of works.
18.1 Contractor shall develop specific Inspection & Test Plan (ITP) and test report formats
for HVAC system and equipment and submit to KOC for approval. Testing shall
comprise of Factory Acceptance Test (FAT), Site Acceptance Test (SAT) and
Performance Acceptance Test (PAT). All inspection and testing shall be as per
approved Inspection and Test Plan (ITP).
18.2 Contractor shall operate a quality system based on the latest ISO 9000 series of
standards to satisfy the requirements of this Standard.
DOC. NO. KOC-MH-001 Page 58 of 66 REV. 0
19.0 DOCUMENTATION
19.1 General
19.1.2 All dimensions, units of measurement, physical constants, etc. shall be in accordance
with the caluse 7.2.3 (System of Measurements) of this KOC Standard,unless
otherwise specified in the Project document.
19.1.3 All design calculations shall clearly mention the applicable codes and standards
referenced.
19.1.4 In addition to the hard copies, all documents (texts, specifications, data sheets,
drawings, etc.) shall be provided with electronic files in the approved software
(MS Word, Excel, Auto-CAD, etc.). Design calculations shall be submitted using a
duly licensed computer program complying with copyright laws of the State of Kuwait
and approved by KOC.
19.2 Deliverables
19.2.1 The Designer / Contractor shall submit the necessary documents for KOC review /
approval, which shall include, but not limited to the following:
a) Design Philosphy
19.2.2 The Designer / Contractor shall submit the necessary drawings for KOC review /
approval, which shall include, but not limited to the following:
e) P & IDs
b) These drawings shall be on approved scale indicating the work as installed. These
drawings shall clearly indicate HVAC plant room layouts, ducting, piping layout,
location of wiring and sequencing of automatic control, location (distance from
reference point as applicable) of all concealed piping, valves, controls, wiring and
other services.
c) The HVAC Plant room shall be provided with schematic and electrical wiring
diagrams of the HVAC control systems.
a) Six (6) copies of the operating, servicing and maintenance instruction manuals
shall be submitted to KOC prior to the issuance of a Certificate of Completion of
the Works. The operating instructions shall detail the way in which the mechanical
/ HVAC installation shall be operated and the procedures are to be adopted for
the testing and adjusting of components. The operating instructions shall include
copies of all equipment test and performance data.
b) The servicing and maintenance instructions shall include detailed instructions for:
iii. Diagrams of each equipment item clearly indicating all points requiring
attention at periodic intervals and with full instructions for work to be
carried out.
c) The manuals shall be bound in plastic folders and shall include the following:
i. Index
iii. Detailed conditions for the plant together with description of control
systems and all control instrument settings
vi. A list of equipment, giving the details for Manufacturers, agents and
nameplate data
19.2.5 Packing, Marking and Shipping Documentation shall comply the requirements of
“KOC Standard for Packing, Marking and Documentation” (KOC-G-004).
The Manufacturer shall comply with the requirements of “KOC Standard for Spare
Parts and Maintenance Data (KOC-G-009)”.
21. 0 Appendices:
GENERAL
1 No. Required / Operation / Stand-by set / Applicable Code
2 Manufacturer Explosion Protection Type
3 Type (Floor Mounted / Roof Mounted) Total Power Rating kW
4 Model No. Max. Start Current / Operating Current /
5 Electric Power Source V / Ph / Hz / /
COIL PART
16 COOLING COIL Fin Density & Tube Dia.
17 Total Cooling Capacity TR Heating Capacity kW
18 Refrigerant Power Rating kW
19 Material, Tube / Fin / Electric Power Source V/Ph/Hz
20 Connection Size, Liquid / Gas Inch / No. of Control Stage
HUMIDIFIER PART
21 Type Electric Power Rating kW
22 Capacity Kg / hr Electric Power Source V / Ph / Hz / /
FILTER PART
23 Type Pressure Drop IWG
24 Type Pressure Drop IWG
CASING
31 Material Painting (Mfr / Job Spec.)
32 Thickness mm Job Specification No.
33 Insulation Colour
34 No. of Access Door
ACCESSORY REQUIRED
37 Vibration Isolating Pad (Yes / No)
38 Fixing Anchor Bolt / Nut (Yes / No)
39 NOTES:
DOC. NO. KOC-MH-001 Page 62 of 66 REV. 0
Data to Be Completed: By Purchaser By Mfr. By Mfr. If not by Purchaser By Purchaser & confirmed by Mfr.
GENERAL
1 No, Required, Operation / Stand-by set Applicable Code
2 Duty (Continuous / Intermittent) Explosion Protection Type
3 Manufacturer Total Power Rating kW
4 Type (Vertical / Horizontal) Max. Start Current / Operating Current /
5 Model No. Dimensions, Length / Width / Height mm x x
6 Weight, Operating / Shipping kg /
FAN SECTION
15 SUPPLY FAN RETURN FAN (Yes / No)
16 No. Required per AHU, Operation / Stand-by set / No. Required, Operation / Stand-by set /
17 Type Type
18 Supply Air Flow Rate CFM Return Air Flow Rate CFM
19 Fresh Air Flow Rate CFM External Static Pressure IWG
20 Return Air Flow Rate CFM Total Static Pressure IWG
21 External Static Pressure IWG Allowable Speed, Max. / Min. rpm /
22 Internal Static Pressure IWG Power Rating kW
23 Total Static Pressure IWG Electrid Power Source V / Ph / Hz / /
24 Fan Speed rpm Space Heater (Yes / No)
COIL SECTION
30 COOLING COIL HEATER
31 Type Type
32 Total Cooling Capacity TR Heating Capacity kW
33 Air Flow Rate CFM Air Flow Rate CFM
34 Entering Air Temperature, DB / WB °F / Entering Air Temperature, DB / WB °F /
35 Leaving Air Temperature, DB / WB °F / Leaving Air Temperature, DB / WB °F /
36 Refrigerant Power Rating kW
37 Refrigerant Suction Temperature °F Electric Power Source V / Ph / Hz / /
38 Material, Tube/Fin / Thyristor Heater Panel (Yes / No)
39 Fin Spacing each / inch No. of Step
40 Limit of Coil Face Air Velocity fpm Pressure Drop Pa
41 Droplet Eliminator Type
42 Material
43 Corrosion Protection
HUMIDIFIER
47 Type Electric Power Source V / Ph / Hz / /
48 Capacity Kg / hr Pressure Drop IWG
49 Electric Power Rating kW
DOC. NO. KOC-MH-001 Page 63 of 66 REV. 0
Data to Be Completed: By Purchaser By Mfr. By Mfr. If not by Purchaser By Purchaser & confirmed by Mfr.
FILTER SECTION
50 PREFILTER FINAL FILTER
51 Type Type
CASING
57 Type Thickness, Inner / Outer mm /
58 Material No. of Access Door
59 Mixing Box (Yes / No) Painting (Mfr. / Job Spec.)
60 Insulation Job Specification No.
61 Thickness mm Colour
62 Pressure Drop (Motorised Damper / Mixing Box) IWG /
ACCESSORY REQUIRED
Manual Volume Damper, Suction / OA / PDIS for Filter Pres. Drop
63 (Yes / No) / / (Yes / No)
Discharge
Motorised Damper, Suction / OA Vibration Isolating Pad
64 (Yes / No) / / (Yes / No)
Discharge
65 Actuator Type Room Thermostat (Yes / No)
66 Manufacturer Humidity Sensor (Yes / No)
67 Model No. Fixing Anchor Bolt / Nut (Yes / No)
68 Electric Power Source V / PH / Hz / /
69 NOTES
DOC. NO. KOC-MH-001 Page 64 of 66 REV. 0
Data to Be Completed: By Purchaser By Mfr. By Mfr. If not by Purchaser By Purchaser & confirmed by Mfr.
GENERAL
1 Required, Operation / Stand-by set / Explosion Protection Type
2 Duty (Continuous / Intermittent) Total Power Rating kW
3 Manufacturer Max. Start Current / Operating Current A /
4 Type Electric Power Source V / Ph / Hz / /
5 Model No. Dimensions, Length / Width / Height mm x x
6 Applicable Code Weight, Operating / Shipping kg /
COMPRESSOR
15 COP (Coefficient of Performance) Power Rating kW
(Reciprocating / Screw / Motor Insulation/Temp. Rise/Enclosure
16 Compressor Type / /
Rotary)
17 (Hermetic / Semi-hermetic) No. of Compressor per ACCU each
18 Net Cooling Capacity MBH Capacity Control Steps
19 Vibration Isolator (Yes / No) Minimum Operating Capacity %
REFRIGERANT
20 Refrigerant Type Refrigerant Charge kg
CONDENSER COIL
21 Applicable Code Material, Tube/Fin /
22 No. of Coils each Corrosion Protection (Yes / No)
23 Coil Face Area Ft2 Connection Size, Liquid/Gas Inch /
24 No. of Refrigerant Circuits per ACCU each
CONDENSER FAN
25 Fan Type Fan Speed Rpm
26 No. of Fans Each Fan Diameter Mm
27 Airflow Rate per One (1) Fan Total Power Rating of Fans kW
28 Type Motor Insulation/Temp. Rise/Enclosure / /
CASING
29 Material Painting (Mfr. / Job Spec.)
30 Thickness mm Job Specification No.
31 Insulation Colour
ACCESSORY REQUIRED
33 Coil Protection Grille (Yes / No) Vibration Isolating Pad (Yes / No)
34 Control Panel (Yes / No) Fixing Anchor, Bolt / Nut (Yes / No)
37 NOTES:
DOC. NO. KOC-MH-001 Page 65 of 66 REV. 0
Data to Be Completed: By Purchaser By Mfr. By Mfr. If not by Purchaser By Purchaser & confirmed by Mfr.
GENERAL
1 Required, Operation / Stand-by set / Applicable Code
2 Manufacturer Explosion Protection Type
3 Model No. Type (Centrifugal / Axial)
FAN
12 Blade Type (Airfoil / Backward curved) Power Rating kW
13 (Radial / Forward curved) Electric Power Source V / Ph / Hz / /
14 (Propeller / Tubeaxial / Vaneaxial) Motor Insulation / Temp. Rise / Enclosure / /
Installation (Wall Mounted / In-Line / Roof Max. Start Current / Operating Current
15 /
Ventilator)
16 Driver System (Direct Coupled / V-Belt) Dimensions, Length / Diameter mm x
17 Supply Air Flow Rate Weight, Operating / Shipping Kg /
18 External Static Pressure IWG Painting (Mfr. / Job Spec.)
19 Total Static Pressure IWG Job Specification No.
ACCESSORY REQUIRED
22 Sand Trap Louver (Yes / No) Pre-Filter (Yes / No)
23 Job Specification No. Efficiency (ASHRAE Weight Test %
24 Anti-Vibration Material (Yes / No) Final Filter (Yes / No)
Counter Flange Efficiency
25 (Yes / No) %
(ASHRAE Dust Spot Test)
26 Flexible Connector (Yes / No) Backdraft Damper (Yes / No)
27 Support Bracket (Yes / No) Weatherproof Louver (Yes / No)
28 On/Off Switch (Yes / No) Wire Mesh Guard (Yes / No)
29 Access Door (Yes / No)
30 NOTES:
DOC. NO. KOC-MH-001 Page 66 of 66 REV. 0
ACKNOWLEDGEMENT
The draft of this document “KOC Standard for HVAC System and Equipment: Direct
Expansion (DX) Type” (KOC-MH-001, Rev. 0) has been circulated to KOC User Teams
for their review & comments and the responses received were suitably resolved and
incorporated into the document.