VANDE BHARAT COACHING COMPLEX AT SHALIMAR

SCHEDULE OF QUANTITY ELECTRICAL INTERNAL & EXTERNAL WORKS


FOR ALL SHED & OTHER ASSOCIATES BUILDING PROPOSED FOR
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
SUB - DESCRIPTION OF ITEMS
HEAD

I ELECTRICAL INTERNAL & EXTERNAL WORKS

A SUB-HEAD-I: POINT WIRING

B SUB-HEAD-II: DISTRIBUTION BOARDS

C SUB-HEAD-III: Installaton OF LIGHT FIXTURES, POLES AND FANS

D SUB-HEAD-IV:INSTALLATIONS OF LIGHT FIXTURES, POLES AND FANS

E SUB-HEAD-V: LIGHTENING PROTECTION SYSTEM

F SUB-HEAD-VI:I 1.1KV L.T. CABLES

G SUB-HEAD-VII:EARTHING SYSTEM

H SUB-HEAD-VIII:CABLE TRAYS & RACE WAY (ELECTRICAL WORK)

I SUB-HEAD-IX:UPS SYSTEM

J SUB-HEAD-X: BUS TRUNKING

K SUB-HEAD-XI: LT PANELs

II EXTERNAL ELECTRIFICATION WORKS


SUB-HEAD-I: POWER SUPPLY DISTRIBUTION ARRANGEMENT (PSS
A WORKS)

B SUB-HEAD-II:DG Set-500 kVA

C SUB-HEAD-III:EXTERNAL LIGHTING

D SUB-HEAD-IV:ESS & LAYING OF 6.6 KV CABLES

E SUB-HEAD-V:SOLAR PHOTOVOTAIC POWER PLANT

III S&T WORKS

A SUB-HEAD- I:STRUCTURED CABLING SYSTEM PASSIVE

B SUB-HEAD- II: IP-PBX SYSTEM

C SUB-HEAD- III: LOCAL AREA NETWORK ( LAN )

D SUB-HEAD- IV: Wi-Fi SYSTEMS

E SUB-HEAD- V: IP CCTV SYSTEM

F SUB-HEAD- VI: FIRE DETECTION SYSTEM

G SUB-HEAD- VII: PA SYSTEM

IV HVAC SYSTEM

A SUB HEAD-I HI-WALL SPLIT UNIT

TOTAL

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

SCHEDULE OF QUANTITY ELECTRICAL INTERNAL & EXTERNAL WORKS FOR ALL SHED & OTHER ASSOCIATES BUILDING FOR VANDE
BHARAT COACHING COMPLEX AT SHALIMAR

S.No. DESCRIPTION OF ITEMS UNIT QTY.


REMARK

Below all item's bill of quantily line specification shall be followed strictly, These specification with
i. supersede tender specifications. Any deviation required due to any causes, prior approval is required
from engineering incharge.
This schedule shall be read in conjunction with its Explanatory Notes and Technical Specifications for
ii.
detailed description for various items included therein
iii. Note:-All Below Electrical Items shall strictly be in adherence to the Technical Specifications

I ELECTRICAL INTERNAL & EXTERNAL WORKS

A SUB-HEAD-I: POINT WIRING

Note:-Point Wiring Items shall strictly be in adherence to the Technical Specifications


1 WIRING SWITCH CONTROL
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2.5 sq.mm LSZH PVC insulated
copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular
1.1 Point 88
plate, suitable GI box and earthing the point with 2.5 sq.mm LSZH PVC insulated copper conductor
single core cable etc. as required.

Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without
independent switch etc.) with 2.5 sq. mm LSZH PVC insulated copper conductor single core cable in
1.2 Point 205
surface/ recessed steel conduit, and earthing the point with 2.5 sq. mm LSZH PVC insulated copper
conductor single core cable etc. as required.

2 WIRING MCB CONTROL


Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2.5 sq.mm LSZH PVC insulated
copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular
2.1 Point 135
plate, suitable GI box and earthing the point with 2.5 sq.mm LSZH PVC insulated copper conductor
single core cable etc. as required.

Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( MCB control
with 2.5 sq. mm LSZH PVC insulated copper conductor single core cable in surface/ recessed steel
2.2 Point 1,218
conduit, and earthing the point with 2.5 sq. mm LSZH PVC insulated copper conductor single core cable
etc. as required. (MCB Cost not included )

Wiring for light/ power plug with 2X6 sq. mm LSZH PVC insulated copper conductor single core cable in
3 surface/ recessed steel conduit alongwith 1 No 6 sq. mm LSZH PVC insulated copper conductor single Mtr 588
core cable for loop earthing as required. (For AC & General Power)

Wiring for light/ power plug with 4X4 sq. mm LSZH PVC insulated copper conductor single core cable in
4 surface/ recessed steel conduit along with 2 Nos. 4 sq. mm LSZH PVC insulated copper conductor single Mtr 2,867
core cable for loop earthing as required.

Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of LSZH PVC insulated
5
copper conductor, single core cable in surface/ recessed steel conduit as required
5.1 2 X 1.5 sq. mm +1 X 1.5 sq. mm earth wire Mtr 750
5.2 2 X 2.5 sq. mm +1 X 2.5 sq. mm earth wire Mtr 7,623
5.3 2 X 4 sq. mm +1 X 4 sq. mm earth wire Mtr 2,867
5.4 2 X 6 sq. mm +1 X 6 sq. mm earth wire Mtr -
5.5 2 X 10 sq. mm +1 X 6 sq. mm earth wire Mtr 400
5.6 4 X 2.5 + 2X 2.5 sq. mm earth wire Mtr 250
5.7 4 X 4 + 2X 4 sq. mm earth wire Mtr 250
5.8 4 X 6 + 2X 6 sq. mm earth wire Mtr 100

Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess
6 including painting in case of surface conduit, or cutting the wall and making good the same in case of
recessed conduit as required.
6.1 20 mm Mtr 650
6.2 25 mm Mtr 4,950
6.3 32 mm Mtr 250
6.4 40 mm Mtr 100

Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box
7 Each 57
including connections but excluding modular plate etc. as required.

Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding
8 Each 100
modular plate as required.

Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,
9 including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, Each -
connection etc. as required. (For light plugs to be used in non residential buildings).

Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,
10 including providing and fixing 3 pin 5/16 amps modular socket outlet and 5/16 amps modular switch, Each 49
connection etc. as required.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Multiplug points (power strip 3 no. 6A socket controlled by 16 A switch) similar to Legrand cat no.
11 Each 86
6745.48 OR as approved by engineer.

13 MOVEMENT CUM PRESENCE DETECTOR


Supply, installation, testing, commissioning and numbering of surface mounted high
performance,Single channel Movement cum Presence Detector with the coverage of min. 4Mx3.5M-
13.1 presence / 13Mx7M-movement at 2.5mtrs height with suitable base box including connection etc. Each 10
complete as required. The unit shall be similar to Make Hager EE810 / Siemens/ Legrand or equivalent as
per approved list of make.
.
Supply, installation, testing, commissioning and numbering of surface mounted (surface) high
performance, dual channel Movement / Presence Detector with 1- 10V ballast and with the coverage of
13.2 min. 4Mx3.5M-presence/13Mx7M-movement at 2.5mtrs height with suitable base box including Each 6
connection etc. complete as required. The unit shall be similar to Make Hager EE811 / Siemens/ Legrand
or equivalent as per approved list of make.

TOTAL CARRIED TO SUMMARY

B SUB-HEAD-II: DISTRIBUTION BOARDS

Note:-Distribution Boards Items shall strictly be in adherence to the Technical Specifications


Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V,
1 on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
1.1 8 way, Double door Each 3
1.2 12 way, Double door Each 4
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution
board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din
2
bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/
Isolator)
2.1 6 way (4 + 18), Double door Each 15
2.2 8 way (4 + 24), Double door Each 6
2.3 12 way (4 + 36), Double door Each -

Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following single pole and
3 neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and
commissioning etc. as required.
3.1 For 8 way, Double door SPN MCBDB Each 3
3.2 For 12 way, Double door SPN MCBDB Each 4

Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral,
4 sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning
etc. as required.
4.1 For 6 way, Double door TPN MCBDB Each 15
4.2 For 8 way, Double door TPN MCBDB Each 6
4.3 For 12 way, Double door TPN MCBDB Each -

Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker
5 suitable for inductive load of following poles in the existing MCB DB complete with connections, testing
and commissioning etc. as required.
5.1 Single pole Each 475
5.2 Triple pole Each -

Supplying and fixing 63 A TP rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for
6 inductive load of following poles in the existing MCB DB complete with connections, testing and Each -
commissioning etc. as required.

Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete
7
with connections, testing and commissioning etc. as required.
7.1 25 amps Each -
7.2 32amps Each -
7.3 40 amps Each -

Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with
8
connections, testing and commissioning etc. as required.
8.1 32 amps Each -
8.2 40 amps Each 18
8.3 63 amps Each 6

Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, Residual
9 Current breaker with Overload protection(RCBO), having a sensitivity current upto 30 milliamperes in the
existing MCB DB complete with connections, testing and commissioning etc. as required.

9.1 32 amps Each -


9.2 40 amps Each 22
9.3 63 amps Each 6

Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP
10 Each 2
MCB complete with connections, testing and commissioning etc. as required.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal
enclosed plug top alongwith 20 amps, 300mA DP RCBO, in sheet steel enclosure, on surface or in
11 Each 2
recess, with chained metal cover for the socket out let and complete with connections, testing and
commissioning etc. as required.

Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal
enclosed plug top alongwith 30 amps 300mA FP RCBO, in sheet steel enclosure, on surface or in recess,
12 Each 4
with chained metal cover for the socket out let and complete with connections, testing and
commissioning etc. as required.

Supply, installation, testing and commissioning of 40 amps 4 pole MCB in MS enclosure of approved
13 No. 4
make, paint and design.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

14 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. Each 30

Supply Fixing testing and commissioning of Industrial power plug socket panel with RCBO consisting of
15 3Ph,440V,63A Industrial power plug sockets-1 nos, 1ph,230V,16A Industrial power plug sockets-3 No Each 137
with MCB's of C curve.

Supply,Erection, Testing and Commissioning of of 40 A, 415 V, Three phase Modified De- contactor Box
16 Each 9
with MCB, RCCB and Earth Continuity monitoring circuit.

TOTAL CARRIED TO SUMMARY

C SUB-HEAD-III: Installaton OF LIGHT FIXTURES, POLES AND FANS

Note:-Light Fixtures Items shall strictly be in adherence to the Technical Specifications.

Installation, Testing & Commissioning of 18W–20W Surface Mounted Linear LED Fitting
1 LED with ≥95 lm/W efficacy, CRI > 80, THD ≤10%, IP ≥ 20, surge protection ≥ 3kV, PF ≥ 0.95. Includes Each 41
prewired electronic driver, extruded aluminium housing, compatible with 170–270V, 50Hz AC..

Installation, Testing & Commissioning of 30–40W Recessed 2'x2' LED Luminaire


CRCA steel housing, >3600 lumens, efficacy ≥100 lm/W, voltage 140–270V AC, CCT 5700K–6500K, PF
2 Each 125
>0.95, THD <10%, surge protection >2.5kV, IP20. Includes LM79 & LM80 reports, reverse polarity,
open/short circuit protection.

Installation, Testing & Commissioning of Recessed Type LED Downlighter


Powder-coated die-cast aluminium housing, high-efficiency PMMA diffuser, >1800 lumens, efficacy ≥100
3 Each 42
lm/W, 140–270V AC, CCT 5700K–6500K, PF >0.95, THD <10%, surge >2.5kV, IP20. Includes LM79 & LM80
reports and standard protections

Installation of 10W Mirror LED Light Luminaire


4 Each 18
(Similar to BCLSB 10W LED Mirror Light or equivalent

Installation, Testing & Commissioning of Waterproof LED Light (IP67, IK08)


5 Vandal-resistant polycarbonate diffuser, >650 lm, efficacy ≥95 lm/W, THD <10%, surge >2.5kV, CCT Each 837
5700K–6500K. Fully protected against water and dust ingress.

Installation, Testing & Commissioning of LED Bulkhead Luminaire (IP65, IK08)


Vandal-resistant polycarbonate body, >650 lm, ≥95 lm/W, THD <10%, surge >2.5kV, CCT 5700K–6500K.
6 Each 222
Includes full protection features.

Installation, Testing & Commissioning of 200W LED High Bay Industrial Light
7 IP66, die-cast aluminum housing with weatherproof gasket, for industrial use. Includes bracket Each 294
fabrication, materials, and fixing hardware

Installation of 20W Waterproof LED Fitting


8 Each 87
(Details assumed similar to other waterproof fixtures)

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

Installation, Testing & Commissioning of 3W LED Exit Signage Light


9 Unidirectional type with inbuilt 2-hour battery backup. Each 20

Installation, Testing & Commissioning of 1200mm BLDC Ceiling Fan


10 Each 57
BEE 5-star, 3 blades, 215 CMM air delivery, 350 RPM, PF ≥ 0.9, THD <10%, remote/electronic regulator.

Installation of 700–750mm Air Circulator Fan


11 Heavy-duty oscillating type, 3-speed, 1440 RPM with guard and mounting setup. Each 208

Installation of 300mm Exhaust Fan


12 Each 8
With mounting arrangement.

Installation of 450mm Exhaust Fan (1440 RPM)


13 Each 2
With guard and mounting arrangement.

TOTAL CARRIED TO SUMMARY

D SUB-HEAD-IV:INSTALLATIONS OF LIGHT FIXTURES, POLES AND FANS

Installation, testing and commissioning of pre-wired, LED fitting with driver/ fluorescent fitting / compact
fluorescent / street/ Flood light fitting of all types, complete with all accessories . directly on ceiling/ wall/
1 Each 603
surface, including connections with 1.5 sq. mm LSZH PVC insulated, copper conductor, single core cable
and earthing etc. as required.

Installation, testing and commissioning of pre-wired light fitting with driver of all types, complete with all
2 accessories etc. on false ceiling including connections with 1.5 sq. mm LSZH PVC insulated, copper Each 226
conductor, single core cable and earthing etc. as required.

Installation, testing and commissioning of pre-wired light fittings with driverof all types, complete with
all accessories etc., including supplying and fixing ball and socket arrangement, 2 Nos. down rods of 20
3 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and Each 0
connections with 1.5 sq. mm LSZH PVC insulated, copper conductor, single core cable and earthing etc.
as required.

Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length
4 Each 57
(upto 30 cm) with 1.5 sq. mm LSZH PVC insulated, copper conductor, single core cable etc. as required.

Supplying and fixing extra down rod of 10 cm length G.I. pipe,15 mm dia, heavy gauge including painting
5 etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less Each 13
shall be ignored)

Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including
6 painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm Each 13
or less shall be ignored)

7 Numbering of ceiling fan/ exhaust fan/ fluorescent/ LED light fittings etc. as required. Each 1124

TOTAL CARRIED TO SUMMARY

E SUB-HEAD-V: LIGHTENING PROTECTION SYSTEM

Note:-Lightning Protetion system Items shall strictly be in adherence to the Technical Specifications.

Supply, fixing, testing and commissioning of 8mm dia Aluminium Round Conductor including expansion
5.1 Mtr 4,224
piece at every 5 Mtr to meet the requirements as per IS/IEC 62305 and IEC/EN 62561-2.

Supply, fixing, testing and commissioning of Al Round Conductor Holder for Metal / Roof Sheet with
5.2 Each 188
accessories Stainless Steel Self-Threaded Screw With washer to meet requirements to IEC/EN 62561-1

Supply, fixing, testing and commissioning of Round Conductor Holder With Adhesive Pad of 32mm
5.3 Each 3,574
height, as per IEC/EN 62561-4 etc complete as required (for transparent sheet)

Supply, fixing, testing and commissioning of Stainless Steel Universal Clamp as per IEC/EN 62561-1 etc
5.4 Each 752
complete as required

Supply fixing, testing and commissioning of Stainless Steel Clamp for connecting to Down Conductor
5.5 Each 462
through metal column as per IEC/EN 62561-1 etccomplete as required

Supply, fixing, testing and commissioning of Lightning counter indicating date and time of last record
5.6 Each 2
In-addition to this cursor is provided to see previous history of surges etc complete as required.

Supply, fixing, testing and commissioning of Test Clamp For Connecting down conductors with earth
entries or for connecting conductors of different materials (Al round conductor for down conductor to
5.7 Mtr 44
connect 25 mm x 3 mm GI earth strip along with GI Strip holder), as per IEC/EN-62561-1 etc complete as
required.

Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including
5.8 Metre 825
connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.

5.9 Providing and laying G.I. tape 40 mm X 6 mm from earth electrode directly in ground as required. Metre 968
ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing
5.1 masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. Each 44
with charcoal/ coke and salt as required.

TOTAL CARRIED TO SUMMARY

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

F SUB-HEAD-VI:I 1.1KV L.T. CABLES

Note:-Cable Items shall strictly be in adherence to the Technical Specifications.

Laying, & testing and commissioning of 1100 V grade, armoured, FRLSZH, XLPE, aluminium(AL) /
Copper (CU) conductor cables on existing trays/walls/columns/ indoor/ trenches including the cost of
1 supports with suitable clamps, saddles, hooks, bolts etc. and including the cost of proper dressing
of cables, markers providing identification tags,earthing of glands armouring etc. complete as per
specifications, as required and as below.

1.1 4 core 300 sq mm AL conductor Mtr 1,420


1.2 4 core 185-sqmm AL conductor Mtr 2,030
1.3 4 core 70-sqmm AL conductor Mtr 205
1.4 4 core 25-sqmm AL conductor Mtr 490
1.4 4 core 16-sqmm AL conductor Mtr 675
1.5 4 core 150 sq mm CU. Conductor Mtr 860
1.6 4 core 70-sqmm CU Conductor Mtr 470
1.6 4 core 50 sq mm CU Conductor Mtr 520
1.7 4 core 25-sqmm CU Conductor Mtr 285
1.8 4 core 16 sq mm CU Conductor Mtr 3,135
1.8 4 core 10 sq mm CU Conductor Mtr 1,345
1.9 4 core 6 sq mm CU Conductor Mtr 280
2 2 core 10 sq mm CU Conductor Mtr 250
2 3 core 6 sq mm CU Conductor Mtr 275

5 Supply of Straight through jointing kit and jonting of 1.1kv Cables as detailed below

5.1 4 core 300 sq mm AL conductor Each


5.2 4 core 185-sqmm AL conductor Each
5.3 4 core 70-sqmm AL conductor Each
5.4 4 core 25-sqmm AL conductor Each
5.5 4 core 16-sqmm AL conductor Each
5.6 4 core 150 sq mm CU. Conductor Each
5.7 4 core 70-sqmm CU Conductor Each
5.8 4 core 50 sq mm CU Conductor Each
5.9 4 core 25-sqmm CU Conductor Each
6 4 core 16 sq mm CU Conductor Each
6.1 4 core 10 sq mm CU Conductor Each
6.2 4 core 6 sq mm CU Conductor Each
6.3 2 core 10 sq mm CU Conductor Each
6.4 3 core 6 sq mm CU Conductor Each
6.5 3 core 6 sq mm CU Conductor Each

Supply of End termination kit for 1.1kv Cables as detailed below and carrying out the termination work.
6
Required gland ,Lugs and other materials to be provided by vendor
6.1 4 core 300 sq mm AL conductor Each
6.2 4 core 185-sqmm AL conductor Each
6.3 4 core 70-sqmm AL conductor Each
6.4 4 core 25-sqmm AL conductor Each
6.5 4 core 16-sqmm AL conductor Each
6.6 4 core 150 sq mm CU. Conductor Each
6.7 4 core 70-sqmm CU Conductor Each
6.8 4 core 50 sq mm CU Conductor Each
6.9 4 core 25-sqmm CU Conductor Each
7 4 core 16 sq mm CU Conductor Each
7.1 4 core 10 sq mm CU Conductor Each
7.2 4 core 6 sq mm CU Conductor Each
7.3 2 core 10 sq mm CU Conductor Each
7.4 3 core 6 sq mm CU Conductor Each
7.5 3 core 6 sq mm CU Conductor Each

HDPE PIPE
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket,
bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in
8
ground (75 cm below ground level) including excavation and refilling the trench but excluding sand
cushioning and protective covering etc., complete as required.
8.1 63 mm dia (OD-63 mm & ID-51 mm nominal) Meter 650
8.2 200 mm dia (OD-200 mm & ID-175 mm nominal) Meter 500
Erection of GI pipe - class' B' ISI marked with accessories including bends etc. for support of cable with
9
erected pole/recessing in wall/floor/passing earth strip OR passing cable as required:
9.1 (ii) 50 mm dia Meter 250
9.2 (iv) 100 mm dia Meter 180

10 Trench
10.1 Trenching for single cable Meter 60
10.2 Trenching for multiple cables Meter 80

TOTAL CARRIED TO SUMMARY

G SUB-HEAD-VII:EARTHING SYSTEM

Note:-Earthing system Items shall strictly be in adherence to the Technical Specifications.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing
1 masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. Set 9
with charcoal/ coke and salt as required.

Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing
2 masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. Set 30
with charcoal/ coke and salt as required.

Providing & making earthing stations including testing at locations as called for, including providing and
laying of 4.50m long 40mm dia GI 'B' class pipe electrode, 20mm dia medium class GI pipe, CI funnel
with 18 gauge GI wire mesh, masonry chamber with concrete base, heavy duty manhole cover, lockable
3 Set 9
cover with frame 300 x 300mm and bitumastic paint , packing of mixture of charcoal & common salt
around plate electrode including test joint complete with digging earth and back filling required as per
IS:3043 (Depth as per site conditions, however, not less than 4.5m)

4 Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.. Mtr 400

5 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. Mtr 8,250

Providing and fixing 40 mm X 6 mm Cu. strip in 80 mm dia G.I. pipe from earth electrode including
6 Mtr 22
connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.

7 Providing and fixing 40 mm X 6 mm Cu..strip on surface or in recess for connections etc. as required. Mtr 22

Providing and fixing 40 mm X 6 mm G.I. strip in 80 mm dia G.I. pipe from earth electrode including
8 Mtr 22
connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.

9 Providing and fixing 40 mm X 6 mm G.I.strip on surface or in recess for connections etc. as required. Mtr 22

Providing and fixing 75 mm X 6 mm Cu. strip in 80 mm dia G.I. pipe from earth electrode including
10 Mtr 33
connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.

11 Providing and fixing 75m X 6 mm Cu..strip on surface or in recess for connections etc. as required. Mtr 33

TOTAL CARRIED TO SUMMARY

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

H SUB-HEAD-VIII:CABLE TRAYS & RACE WAY (ELECTRICAL WORK)

Supplying and installing following size of perforated painted with powder coating MS cable tray with
perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the
ceiling with MS suspenders including bolts & nuts, painting suspenders etc. as required.
9.1 150 mm width X 50 mm depth X 1.6 mm thickness Mtr 1,591
9.2 300 mm width X 50 mm depth X 1.6 mm thickness Mtr 252
9.3 450 mm width X 62.5 mm depth X 2.0 mm thickness Mtr 63
9.4 600 mm width X 62.5 mm depth X 2.0 mm thickness Mtr 158
9.5 750 mm width X 62.5 mm depth X 2.0 mm thickness Mtr -

Supplying and installing following size of perforated painted with powder coating MS cable trays
9.2 “bends” with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with
MS suspenders including bolts & nuts, painting suspenders etc. as required.
9.2.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 22
9.2.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 10
9.2.3 450 mm width X 62.5 mm depth X 2.0 mm thickness Each 4
9.2.4 600 mm width X 62.5 mm depth X 2.0 mm thickness Each 2
9.2.5 750 mm width X 62.5 mm depth X 2.0 mm thickness Each -

Supplying and installing following size of perforated painted with powder coating MS cable trays “Tees”
9.3 with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with MS
suspenders including bolts & nuts, painting suspenders etc. as required.
9.3.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 12
9.3.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 3
9.3.3 450 mm width X 62.5 mm depth X 2.0 mm thickness Each 2
9.3.4 600 mm width X 62.5 mm depth X 2.0 mm thickness Each 3
9.3.5 750 mm width X 62.5 mm depth X 2.0 mm thickness Each -

Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross
9.4 Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with
M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
9.4.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 4
9.4.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 2
9.4.3 450 mm width X 62.5 mm depth X 2.0 mm thickness Each 1
9.4.4 600 mm width X 62.5 mm depth X 2.0 mm thickness Each 2
9.4.5 750 mm width X 62.5 mm depth X 2.0 mm thickness Each

Supplying and installing following size of perforated painted with powder coating MS cable trays
9.5 “Reducer” with perforation not more than 17.5%, joined with connectors, suspended from the ceiling
with MS suspenders including bolts & nuts, painting suspenders etc. as required.
9.5.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 3
9.5.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 3
9.5.3 450 mm width X 62.5 mm depth X 2.0 mm thickness Each 2
9.5.4 600 mm width X 62.5 mm depth X 2.0 mm thickness Each -
9.5.5 750 mm width X 62.5 mm depth X 2.0 mm thickness Each -

9.6 MULTI COMPARTMENTISED RACEWAYS

Supply and fixing of following size of under floor GI raceways for distributing cabling in screed floor
installations particularly suitable for application requiring EMC screening. Raceway should be made up
of Pre galvanized sheet with minimum thickness of 1.5mm consist of body and cover. It should be zinc
coating. Raceway should have top Cover. Raceway should be supplied with required accessories such
as fixing brackets and coupling plates as required. Raceway should be confirmed with the standard EN
50085-2-2 including all accessories complete as required
9.6.1 250 mm wide x 38 mm deep raceway (1 compartment) Mtr 42
9.6.1 150 mm wide x 38 mm deep raceway (1 compartment) Mtr 68
9.6.2 100 mm wide x 38 mm deep raceway (1 compartment) Mtr 32

Supply and fixing of following size of Height adjustable under floor crossover Junction box with flyover
for Raceways for direct access to cables at the intersection of Raceways supplied completely with base
and cover plate(lid). Junction box should be made of Pre galvanized sheet consist of body and cover.
9.7
Height of the junction box should be adjustable from minimum 60mm. Junction box should be supplied
with the metal cover for protecting the junction box during constructions at site. It should be confirmed
with the standard EN 50085-2-2s including all accessories complete as required:

9.7.1 ADJ JB 300 X 300 X 50 MM Each 13


9.7.2 ADJ JB 200 X 200 X 50 MM Each 6
9.7.2 ADJ JB 150 X 150 X 50 MM Each 4

Important Notes for raceways:-

Contractor to get the samples of floor and ceiling raceways to be approved from the Architect/ Project
Manager/ Consultant/ Client before supply & erection.

Depth of the floor raceway is to be decided by the contractor after checking/ examining screed depth
available at site. For this purpose chipping to be carried out at various places on the floor/ floors to
carefully assess the depth/ floor margin available. Final approval is to be obtained from the Architect/
Project Manager/ Client before ordering/ fabricating raceway. The sizes & depths of raceways given in
the BOQ are only tentative & indicative.

Contractor is also supposed to check and confirm the adequacy of raceway sizes by calculating the
exact number of electrical circuit wires & N/W wires for respective Electrical & N/W raceways.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

TOTAL CARRIED TO SUMMARY

I SUB-HEAD-IX:UPS SYSTEM

Note:- UPS shall strictly be in adherence to the Technical Specifications (Volume 4 of 5) VI-3.

Supply, installation, testing and commissioning of 10kVA/ 8kW ( Input 3Phase / output 3 Phase) Floor
Mount Type, Compact & modulat design, Conforming to IEC EN 62040 (All Parts), ISO 9001 certified,
True On-Line, double conversion, IGBT on the input and output with multiple digital signal processor
controlled for Rectifier/ charger, Battery, 2 Level IGBT Inverter, Static Switch, with parallel redundent,
compatible with 0.7 lagging to 0.7 leading PF loads without deration, power factor >0.8, THDi< 3-5%,
1 Input voltage 380-415V, Output voltage 415V, 50Hz frequency, efficiency >95%, 0-40 deg C, with inbuilt Set 2
overload, short circuit, Input low voltage, output over voltage, battery over charging, battery over
discharging protections, Parallel kit, 30 min battery back-up with 12 V Maintenance Free Sealed Lead
Acid batteries alongwith Powder Coated M.S. Rack with unidirectional wheels for housing the Batteries
alongwith all accessories including interconnecting cables, lugs, Base Frames, Battery Rack & Battery
Circuit breaker complete as required.

Supply, installation, testing and commissioning of 6kVA, 240V, Pure sine wave Inverter alongwith lead
acid batteries CSB/Exide make giving a back up of min. 8.0 hrs. at full load as per specification alongwith
2 Set 1
PVC/M.S Poweder coated cabinet with unidirectional wheels for housing the inverter and batteries,
complete as required and as per specifications. (5% Police light in shed area & Other building)

TOTAL CARRIED TO SUMMARY

J SUB-HEAD-X: BUS TRUNKING

Note:- Bus trunking shall strictly be in adherence to the Technical Specifications

Three Phase Lighting Bus way


Supply of Three Phase Lighting Bus way 40 Amps Double Circuit (8 conductors),Straight length with
1 Mtrs 1,433
Tap-off provision, along with blanking plate.( Quote for 1 mtr length)

Supply of End Feed units with cover suitable for Lighting Bus bay, 40 Amps Double
1.1 Set 14
Circuit ( 8 conductors) .

Supply of Fixing Bracket suitable for Wall/ Suspension mounting of Lighting bus bay 40
1.2 Set 1,433
Amps Double Circuit ( 8 conductors).

1.3 Supply of 16 Amps Three phase Tap-off unit with fuse, 3L+N+E . Set 139

Supply and Erection of 6"x 4"x 3" MS Junction Box with 3 Terminal SMC Terminal pad
1.4 consisting of 3 nos of 6mm studded terminal suitable for 16 amps rating. With one no. Nos 250
of 10 amps double pole MCB

Erection( laying, Fixing, suspension), Testing and Commissioning of Lighting Bus way 40 Amps of
1.5 Straight length with all accessories like, End feed unit, fixing bracket, Tap-off units, Mtrs 1,433
12mm threaded rod and all other accessories.

2 SANDWICH TYPE, 250A BUS BAR TRUNKING SYSTEM

Supply of Sandwich type, 250A bus bar trunking system with Aluminium bus bar, minimum 50 18kA, for
1 Sec, mini IP54, 690V, plug in bus duct with 100% neutral, 50% integral earth without external earthstrip,
minimum Class F insulation, 1.6mm thickness electo galvanized sheet steel enclosure, painting Straight
length with 3 tap-off point in a 3mtr length, along with necessary joints, elbow joints & expansion joints
and bends, copper flexible for joints, integral earthing including, G.I. clamping brackets, suspenders,
angle iron bracket, steel fasteners, connecting to earthing system etc. complete as required. 5.4.1The
housing shall be made with 1.6mm thick electro-galvanized sheet steel of superior grade with RAL 7015
Epoxy powder coating form both sides (internal & external) to withstand stringent site conditions; e.g.
Humid, Costal, Acidic, etc. OEM shall submit all type test test report at the drawaing /Technical data
sheet approval.
The Busbar Trunking System shall be suitable for operational Voltage of 415V / 690V / 1000V with supply
frequency of 50Hz / 60Hz, minimum insulation voltage of 1000V & impulse withstand voltage of 8kV &
higher.
Each bus bar shall be individually insulated by means of Multi layer Class-F PET Insulation, Each layer
shall have withstand breakdown voltage of minimum 6kV. The insulation material used shall be of
minimum Class F (155 deg. C) The insulation should be UL certifiedInsulation must be Halogen free &
RoHS compliance. Busduct should be tested for Seismic Zone-5 & High Seismic Qualification level as
per IEEE:693. Busbar trunking system should be offered with Temperature monitoring sensors to avoid
manual monitoring of temperature on regular basis.
Temperature monitoring sensors should be offered with connected software for temperature records
monitoring and automatic Trigger setting for abnormality in temperature.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

Supply of Sandwich type, 250A bus bar trunking system with Aluminium bus bar, minimum 50kA, for 1
Sec, mini IP54, 690V, plug in bus duct with 100% neutral, 50% integral earth without external earthstrip,
2.1 Mtr 1,455
minimum Class B insulation, 1.6mm thickness electo galvanized sheet steel enclosure, painting Straight
length with 3 tap-off point in a 10mtr length. (Quote for 1 mtr length)

Supply of Cable Tap Box-End (End Feed Unit) (suitable for Sandwich type, 250A busbar trunking system
2.2 with Aluminium bus bar with minimum 36kA,mini IP54, 690V and to connect 5 nos of 240 sqmm copper Each 14
lugs per Phase & Neutral.

Supply of End Cover (suitable for Sandwich type, 250A busbar trunking system with Aluminium bus bar
2.3 Each 14
minimum 36kA,mini IP54, 690V).

2.4 Supply of Fixing Hanger suitable for hanging 250 amps Bus bar trunking system. Each 1,455

Supply of 250 amps Tap-Off Box fitted with 63 amps MCCB suitable for plugging to 250amps copper
2.5 Each 139
contact bus bar trunking system

Erection of 250/63 amps Tap-Off Box fitted with MCCB suitable for plugging to 250amps copper contact
2.6 Each 139
bus bar trunking system

Erection( laying, Fixing, suspension), Testing and Commissioning of Bus way 250 amps ( R,Y,B,N & E
2.7 conductors),Straight length with all accessoties like, End feed unit, fixing bracket, Tap-off units, 16 mm Mtr 1,455
threaded rod and all other accessories.

TOTAL CARRIED TO SUMMARY

K SUB-HEAD-XI: LT PANELs

Installation,Testing & commissioning correct aligned position, grouting with dash fasteners, GI nuts-
bolts, testing and commissioning of the following bolted fabricated in compartmentalized (Form-3B
construction) conform to IS: 8623/1993, Suitable for 415V, 3Phase, 4 Wire 50 Hz Ac supply, are housed in
design from CRCA sheet steel of 2mm thick for frame work and door covers, 3mm thick for gland plate,
i/c cleaning & finishing complete, having extensible type bus bars of high conductivity, SMC bus bar
supports, the maunfacturer shall be certified from CPRI for short circuit withstand capacity of min. 70kA
for 1 Sec., fabrication shall be done in transportable sections and all front and back doors shall be
1 hinged type and earth with frame, Entire panel shall have a common earth bar as specified below at the
rear with 2 Nos. earth stud each side, bus bars and control wiring with suitable size of FRLS PVC
insulated copper conductor cable, cable alleys, cable gland plates in two half, i/c providing following
switch gears :-

The Bus bars will be Copper purity 99.9% / electrolytic grade E91 Aluminium duly sleeved with Helogen
Free heat shrink coloured Insulated tube confirming to IEC 60684-3-247 Standard. The powder coating
(70-80micron as per IS:13871 for indoor and 100-120 micron for outdoor), include one size higher
terminal block in cable alley and interconnecting wires between bus bars and terminals via MCB.

OR
Installation,Testing & commissioning in correct aligned position, grouting with dash fasteners, GI nuts-
bolts, testing and commissioning of Totally Type Tested Panels (Form-4B construction) complying to
IEC:61439 -1/2 cubical with Internal arc withstand of 50 70 kA for 0.3 0.5 second and minimum impact
resistance IK09 10 as per IEC:62262 with each compartment front & back unbreakable glazed door cover.
Panels shall be tested for an Impulse Withstand Voltage of upto 12 8 kV. Suitable for 415V, 3Phase, 4
Wire 50 Hz Ac supply system bolted fabricated in compartmentalized (preferably) design from CRCA
sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plate, i/c cleaning & finishing
complete, SMC bus bar supports, the manufacturer/ OEM shall be certified for short circuit withstand
capacity of 70kA for 1 Sec., fabrication shall be done in transportable sections and all front and back
doors shall be hinged type and earth with frame, Entire panel shall have a common as specified below at
the rear with 2 Nos. earth stud each side, bus bars and insulated control wiring with suitable size of
FRLS PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, i/c providing
following switch gears :-

The Bus bars will be Copper purity 99.9% / electrolytic grade E91 Aluminium duly sleeved with Helogen
Free heat shrink coloured Insulated tube confirming to IEC 6068-3-247 Standard. The powder coating (70-
80micron as per IS:13871 for indoor and 100-120 micron for outdoor), include one size higher terminal
block in cable alley and interconnecting wires between bus bars and terminals via MCB.The busbars
shall be supported of regular intervals using SMC or DMC insulators as per the tested design. It should
have minimum Comparative Tracking Index (CTI) of 600 V as per IS 2824). The LV panel manufacturer
shall be ISO 9001 / 9002 certified. The LV panel shall be factory manufactured by OEM or by
manufactured by authorized Franchisee of OEM based on design given by OEM and should provide test
reports of IEC 61439 part -1 & 2 at the time of drawing approval. Switchgear & Panel make should be of
same brand.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
All MCCB's shall be with Extended type Front door operating handle, Phase Spreaders & Phase Barriers.
MCCB above 63A should be provided with silver plated copper spreader terminals. All MCCB's shall have
adjustable O/L setting from 0.25In for microprocessor based release and 0.67In for thermal magnetic
release, along with adjustable S/C setting. All MCCB's shall have indivisual LED's for fault indication. All
MCCB's shall have Impulse Withstand Voltage of 8kV, rated operational voltage upto 690V, rated
insulation voltage upto 1000V. Neutral Overload protection shall be provided for 3 pole MCCBs with
provision for external neutral CT sensing. Earth Fault whereever required should be integral to the
micrprocessor release. In view of Standardization and Uniformity, mixing of two series of switchgear
(even from the same manufacturer) for either MCCB or ACB will not be permitted. MCCBs above 160A
shall be equipped with microprocessor-based trip units for O/L, S/C and inbuilt earth fault protection.

The MCB shall give visible flag indication when MCB trips on Short Circuit Fault. The MCB shall have
electrical life 20,000 operations up to 32A and 12,000 operation up to 63A. The MCB shall have safety
shutter to avoid any wrong insertion of cable. The RCCB shall give an indication for leakage fault when
tripping.

MFM on Incomer : 96 X 96 mm size multifunction meter as per IEC 62053-21 for Class 0.5S, Total
Harmonics Distortion – Phase wise Voltage and Phase wise Current, Battery backed RTC with 2 years of
power down time, Data Logging with configurable interval (preferable 15 mins) and duration for a period
of minimum 2 years, Sampling rate of 128 samples / cycle, Measuring circuit burden should be lesser
than 0.2 VA , Meters shall have RS485 port with MODBUS RTU protocol , IP51.

A MAIN SHOP

1 MDB-1
Incomer-I,II&III
Incoming-I From CSS-1
1 Nos. 630A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.

Incoming-II From SOLAR


1 Nos. 250A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.

Incoming-III From DG PANEL


1 Nos. 400 TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
B/C-1 Nos. 400A 4P MCCB
METERING, INDICATOR AND RELAYs
2 Set of phase indicating LED lamps with 2 amp back up MCB.
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
2 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB
Electrical & Mechnical Interlocking between both incomers
TVSS & BUSBARS SECTIONS
800 Amps TP+N, 50kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount
on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper
flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium
Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.
OUTGOINGS CONNECTED AS SHOWN IN SLD:
5 Nos. 250A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
3 Nos. 160A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.

2 Nos. 125A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
3Nos. 63A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
2 Nos. 40A DP MCB
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

MDB-1- MAIN SHOP PLAN as described above and shown in SLD. Set 1

2 SDB- 1-LIGHTING & POWER (LEFT SIDE)


Incoming-I From MDB-1
1 Nos. 125A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended
2 Set of phase indicating LED lamps with 2 amp back up MCB.
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
TVSS & BUSBARS SECTIONS
200Amps TP+N, 35kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount
on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper
flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium
Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.
OUTGOINGS CONNECTED AS SHOWN IN SLD:
2 Nos. 63A 4P MCB
06 Nos. 40A 4P MCB
05 Nos. 32A 4P MCB
03 Nos. 32A DP MCB
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

SDB- 1-LIGHTING & POWER (LEFT SIDE) as described above and shown in SLD Set 1

3 MDB-3 (AIR COMPRESSOR ROOM)


Incoming-I From CSS-1
1 Nos. 400A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
2 Set of phase indicating LED lamps with 2 amp back up MCB.
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
2 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB For MCCB
Electrical & Mechnical Interlocking between both incomers
TVSS & BUSBARS SECTIONS
500Amps TP+N, 35kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount
on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper
flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium
Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
OUTGOINGS CONNECTED AS SHOWN IN SLD:
4 Nos. 250A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

MDB-3 (AIR COMPRESSOR ROOM) as described above and shown in SLD Set 1

4 MDB-2
Incomer-I,II&III
Incoming-I From CSS-1
1 Nos. 800A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
Incoming-II From SOLAR
1 Nos. 250A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
Incoming-III From DG PANEL
1 Nos. 400 TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
B/C-1 Nos. 400A 4P MCCB
METERING, INDICATOR AND RELAYs
2 Set of phase indicating LED lamps with 2 amp back up MCB.
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
2 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB
Electrical & Mechnical Interlocking between both incomers
TVSS & BUSBARS SECTIONS
800 Amps TP+N, 50kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount
on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper
flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium
Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.
OUTGOINGS CONNECTED AS SHOWN IN SLD:
5 Nos. 250A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
3 Nos. 160A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
5 Nos. 125A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
2 Nos. 63A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
2 Nos. 40A DP MCB
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

MDB-2- MAIN SHOP PLAN as described above and shown in SLD. Set 1

5 SDB- 1-LIGHTING & POWER (RIGHT SIDE)


Incoming-I From MDB-2
1 Nos. 125A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
2 Set of phase indicating LED lamps with 2 amp back up MCB.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
TVSS & BUSBARS SECTIONS
200 Amps TP+N, 35kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount
on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper
flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium
Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.
OUTGOINGS CONNECTED AS SHOWN IN SLD:
2 Nos. 63A 4P MCB
07 Nos. 40A 4P MCB
07 Nos. 40A 2P MCB
02 Nos. 32A 2P MCB
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

SDB- 1-LIGHTING & POWER (RIGHT SIDE) as described above and shown in SLD Set 1

5 MDB-4
Incoming-I From CSS-1
1 Nos. 630A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
METERING, INDICATOR AND RELAYs
2 Set of phase indicating LED lamps with 2 amp back up MCB.
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
1 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB For MCCB
TVSS & BUSBARS SECTIONS
800 Amps TP+N, 50kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount
on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper
flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium
Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.
OUTGOINGS CONNECTED AS SHOWN IN SLD:
2Nos. 400A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
2Nos. 250A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
2Nos. 160A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

MDB-4 as described above and shown in SLD. Set 1

7 MDB-5 (ESS)
Incoming-I From CSS-1
1 Nos. 400A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
METERING, INDICATOR AND RELAYs
1 Set of phase indicating LED lamps with 2 amp back up MCB.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
1 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB For MCCB
TVSS & BUSBARS SECTIONS
500 Amps TP+N, 50kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount
on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper
flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium
Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.
OUTGOINGS CONNECTED AS SHOWN IN SLD:
1Nos. 250A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
1 Nos. 250A TP+NL CHANGEOVER SWITCH
2 Nos. 160A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
1 Nos. 160A TP+NL CHANGEOVER SWITCH
2 Nos. 125A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
02 Nos. 40A 4P MCB
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

MDB-5 as described above and shown in SLD. Set 1

8 STREET LIGHT PANEL-1


Incoming-I From MDB-5 (ESS)
1 Nos. 125A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
METERING, INDICATOR AND RELAYs
1 Set of phase indicating LED lamps with 2 amp back up MCB.
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
1 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB For MCCB
TVSS & BUSBARS SECTIONS
200 Amps TP+N, 50kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount
on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper
flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium
Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.
OUTGOINGS CONNECTED AS SHOWN IN SLD:
03Nos. 63A TP+NL MCCB
05Nos. 40A TP+NL MCB
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

STREET LIGHT PANEL-1 as described above and shown in SLD. Set 1

9 MDB-6 (L&P ADMIN OFFICE BUILDING )


Incoming-I From CSS-1
1Nos. 250A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Incoming-II From DG PANEL-1
1Nos. 250A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
METERING, INDICATOR AND RELAYs.
2 Set of phase indicating LED lamps with 2 amp back up MCB.
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
2 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB For MCCB
Electrical & Mechnical Interlocking between both incomers
TVSS & BUSBARS SECTIONS
300 Amps TP+N, 50kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount
on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper
flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium
Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.

Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.

OUTGOINGS CONNECTED AS SHOWN IN SLD:


11Nos. 63A 4P MCB
02 Nos. 40A 4P MCB
02 Nos. 40A 4P MCB
03 Nos. 25A 2P MCB
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

MDB-6 (L&P ADMIN OFFICE BUILDING ) as described above and shown in SLD. Set 1

10 MAIN D.G PANEL-1


Incoming-I From DG SET-500 kVA
1 Nos.800A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
METERING, INDICATOR AND RELAYs
2 Set of phase indicating LED lamps with 2 amp back up MCB.
Provide 3Nos. Resin Filled Nylon 66 Casing CTs, Class-1.0 and Dual source MFM with min. features of
True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW,
KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd
Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each
phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all
outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.
2 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB For MCCB
TVSS & BUSBARS SECTIONS
1000 Amps TP+N, 50kA, 500volts grade busbar chamber of suitable length with Aluminium busbars
mount on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated
copper flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above
Aluminium Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium
and 2 Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode,
spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up < 4.0kV, Operating Temperature -
40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos.
neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model:
Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting
SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than
500mm for per mode connection with each busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.
OUTGOINGS CONNECTED AS SHOWN IN SLD:
2 Nos. 400A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
3 Nos. 250A 4P MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking
capacity 50KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock
for door interlock with Phase spreader & Phase Barriers at both sides. MCCBs neutral shall be protected
& adjustable as a Neutral unprotected / Neutral protected at 0.5 In/ Neutral protected at In. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
3 Nos. 200A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
1 Nos. 160A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
2Nos. 125A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault
breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with
castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

MAIN D.G PANEL-1 as described above and shown in SLD. Set 1

11 MCCB in enclosure of following rating:

1 Nos. 200/160/125/100/63A 4P MCCB built in thermal magnetic based release (fixed O/L & fixed S/C) of
fault breaking capacity 25KA (Ics=Icu=100%) upto 415V manually operated with door Knob for door
11.1 Set 6
interlock with Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 IEC-60947 (2016)
as amended.

1 Nos. 630/400/300/250A 4P MCCB built in thermal magnetic based release (fixed O/L & fixed S/C) of fault
breaking capacity 25KA (Ics=Icu=75%) upto 415V manually operated extended rotary handle for door
11.2 Set 2
interlock with indications for breaker On/Off with Phase separators & Phase Barriers at both sides.
MCCB shall conforming to IS-1397-2 1993 IEC-60947 (2016) as amended.

TOTAL CARRIED TO SUMMARY

II EXTERNAL ELECTRIFICATION WORKS

A SUB-HEAD-I: POWER SUPPLY DISTRIBUTION ARRANGEMENT (PSS WORKS)

11 KV HT DP STRUCTURE
1
Supply, Installation, testing and commissioning of 11 kV DP structure as per CEI & MSEB norms &
comprising of the following, but not limited to it for completion of works

RSJ pole of 9.15 mt length of size 175 x 90 mm complete with suitable M.S. base plate welded at
bottombase plate - 2 Nos.

MS Channel of size 100 x 50 mm, length 4 mts (approx)

11 KV AB switch - 1 set

11 KV Horn Gap fuse Unit - 1 set

11 KV Lightning Arrestor

11 KV Disc insulator

11 KV Pin insulator

6 SWG copper wire for jumpering

Supply and erection of Stay set complete with necessary foundation, excavation and refilling of earth
etc. as required.

Concrete foundation for RSJ poles burrioed upto a depth of 1830 mm in ground in a pit of size 450X450
mm in CC 1:3:6 along with 200 mm copping above ground inclusive of earth work.

Necessary Nut, Bolts, clamps, operating handle for AB switch, clamping welding etc. complete as
required.

Painting the RSJ poles complete with two coat of Red Oxide and two coats of GI enamel paints complete
as required.

Transportation of all materials and accessories at site

Complete erection, testing and commissioning.


Set 1

2 6 kV HT VCB PANEL
Supply, installation, testing and commissioning of 6.6 KV,Metal clad Vaccum circuit breaker panel totally
enclosed and fully intorlocked drawout type breaker, 800A/25KA/3Sec, with inter connecting busbar
rating of 800A, PT, CT, Numerical, with confirming to IEC 61850, Digital energy meter, Digital Ammeter
and Digital Volt meter with RTU Unit (Remote Terminal Unit) suitable for Ethernet Communication
compactability with hardware components for SCADA application. (One Set contains 3 nos of 6.6KV
2.1 Panels)Panel should have suitable VAMP-57 relays and Surge Protection for configuration of load Set 2
currents of first transformer attaining 80%,the second transformer get automatically switched "ON" for
sharing the electrical load demand and Synchronous relays for parallel operations of Transformers as
per the load demands. (1-I/C+2O/G)

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
3 Package/Compact Substation PSS/ CSS: Compact Substation (CSS) -6kV /433V
Erection, testing and commissioning of 6.6kV/433V,with suitable rating of HV & LV switchgear in
weatherproof enclosure as per IS:1180 Similar to Make of Schnider, CG & L&T.1000kVA CSS with
following configurations (HT – 2 LBS Manual operated + 1VCB Motorized), Transformer –oil immersed,
LT – 01 Nos. ACB – 1600Amps + 300kVAr APFC & 1 Nos. 800 MCCBs+4 Nos. 630Amps
3.1 MCCBs+3Nos.400Amps+2 Nos. 250Amps in weather proof enclosure as per IS:1180 or latest suitable for Set 1
parallel operations of Transformers .The 6.0/0.4KV Panels built with suitable synchrounus relays &
suitable VAMP-57 relays for configuration of load current of first Transformer after attainning 80%,the
second Transfoemer get automatically switched "ON" according to electric load demands. (1W+1S).

Supply & Erection/fixing of (Safety Items) Fire extinguishing equipments (ISI) Marked, 6kV/11KV/LT
Rubber mat (ISI marked),6KV/11KV/LT Hand gloves (ISI marked), GI fire buckets filled with clean dry
sand held on free standing steel stand,First Aid Box with medicines (ISI marked) and associated
4 materials,shock treatment chart on aluminum frame,Schematic diagram of HT/LT installation & Set 1
transformer data on white hylem sheet with aluminium frame & fixing / providing in the sub
station/Panel room areas as per details in explanatory notes.

Erection, testing & commissioning of 300 kVAR Automatic Power Factor Controller panel (capacitor
5 bank) complete and connection with the main panel as per site requirement. No. 1

TOTAL CARRIED SUMMARY-SECTION-E

B SUB-HEAD-II:DG Set-500 kVA

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Installation , testing and commisioning of DG set complete with engine,alternator base
1 frame,radiator/heat exchanger , fuel tank, control panel , EMF panel , fuel piping, foundation, all electrical Set 1
inter connections , loop earthing , silencer pipe/exhaust chimney as per CPCB norms, standard
accessories and acoustic enclosure.
1.1 500 KVA DG set with 800A , 4-Pole,ACB(MDO),1000A Copper bus bars , 4-pole contactors 1000A

TOTAL CARRIED SUMMARY-SECTION-E

C SUB-HEAD-III:EXTERNAL LIGHTING
Supply and erection of GI Octagonal pole including digging of pit, making foundation with cement, sand
1 and concrete in ratio 1:2:6, muffing, accmodating GI pipe in foundation for cable loop in loop out of
suitable size as required.
1.1 5 meters long No. -
1.2 7 meters long No. 35
1.3 Additional cost of single arm bracket suitable for street light fixture No. -
1.4 Additional cost of double arm bracket suitable for street light fixture No. 35

HIGH MASTS

Supply, erection, testing & commissioning of hot dipped galvanised(inside & outside) high mast system
complete with all accessories, foundation, carriage arrangement suitable for LED luminaries
symmetrically arranged & control gear boxes and lighting fittings etc, twin dome aviation obstruction
2 lights, control panel , multi core flexible copper conductor cable,connection to Earthing sysytem and
fencing panel as per explonotary notes follows to RVNL technical specifications(RVNL/E/GS/05,
CHAPTER A-5)

2.1 16 Meter high mast system, suitable for 6 to 9 nos luminaires. Job 2
25 Meter high mast system, suitable for 9 to 12 Nos. 2X200 watts IP65 LED luminaries (RVNL approved
2.2 Job -
brands only).

HDPE PIPE

Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket,
bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in
3
ground (75 cm below ground level) including excavation and refilling the trench but excluding sand
cushioning and protective covering etc., complete as required.

3.1 200 mm dia (OD-200 mm & ID-175 mm nominal) Meter 221

TOTAL CARRIED SUMMARY-SECTION-E

D SUB-HEAD-IV:ESS & LAYING OF 6.6 KV CABLES

Laying of 6KV(E)/3core,300sq.mm XLPE(E) insulated, armoured, aluminium conductor HT cable.


1

Under Rail Track by mechanically molling method


1.1 Meter 1895
By Underground
1.2 Meter 75
1.3 By Trenching RCC Meter 75

2 supply and erection of MS cable route marker. Nos. 12

Erection of RFID based electronic Cable/pipe marker of reputed make suitable to work upto
1.5m depth, min dia of 22 CMs, having inbuilt GPS module for storing GPS coordinates, each marker
identification with 10 digits Hexadecimal Code, 134.0 KHZ frequency with self generated power
source having capability to receive signals and transmit back, working life >= 40 yrs. Marker to be
3 similar to Smart RFID marker SM 1500 or superior as approved by Nos. 2
Engineer.

4 Erection of MS cable route marker. Nos. 50

Installation outdoor type, heat shrinkable, end termination kit, suitable for following cable sizes XLPE(E)
3 Core 6 KV 300Sq.mm insulated, armoured aluminium conductor cable and making termination,
5 connections with overhead conductor, testing & commissioning etc.

5.1 Supply of Jointing Kit and Jointing Each 4


5.2 Supply of End Termination and End Each 10

Laying of HDPE pipe as per IS:4984-1995 (PN-4/PE-80, with minimum wall thickness of 6.2mm) of
6 different sizes under the Railway track/road etc after digging of trench and back filling with excavated
earth after laying of pipe and making good the damages as required
6.1 Outer dia-63 mm Meter 560
6.2 Outer dia-110 mm Meter 300
6.3 Outer dia-160 mm Meter 150
6.4 Outer dia-200 mm Meter 150

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
6.5 Extra for hard rock soil/soft rock locations Meter 250

Supply and laying of HDPE pipe as per IS:4984-1995 (PN-4/PE-80, with minimum wall thickness of 6.2mm)
7 of different sizes under the Railway track with trench less boring method and making good the damages
as required
7.1 Outer dia-160 mm Meter 150
7.2 Outer dia-200 mm Meter 300
7.3 Extra for hard rock soil/soft rock locations Meter 100

Laying of DWC HDPE pipe (either single piece of full round or two half round split piece set) as per IS
8 14930 part-II or latest (ISI marked) along with all accessories, digging of trench and back filling with
excavated earth after laying of pipe and making good the damages as required
8.1 Outer dia-200 mm Meter 150
8.2 Extra for hard rock soil/soft rock locations Meter 125

TOTAL CARRIED SUMMARY-SECTION-I

E SUB-HEAD-V:SOLAR PHOTOVOTAIC POWER PLANT

Supply, Installation, Testing and Commissioning of ongrid Solar Photovoltaic Power Plant conforming to
MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering
1
facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with
following components complete as required:-

a) Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conforming to IS


14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion
efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be
warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years
and 80% at the end of 25 years.
b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase, 4
wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC Power with efficiency not less than 97%,
total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The
PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency.
c) Data Monitoring System complete with accessories.
d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement
for incoming and outgoing cable along with glands, lugs and other accessories etc. as required.
e) Lightning and surge voltage protection.
f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor
1.1 kV grade armoured power and control cables between solar modules, main power cable to grid
1.1 kWH 100
supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories
etc. as required.

1.2 Providing & Fixing Water Cleaning arrangements for solar panels cleaning works as per the requirement. Meter 225

Note:- The cost should include of providing necessary arrangements for cleaning solar panels. The
arrangement shall be providing water at every 10 meters with valve on roof top.

TOTAL CARRIED TO SUMMARY

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

III S&T WORKS

SCHEDULE OF QUANTITIES FOR SUPPLYING, INSTALLATION, TESTING & COMMISSIONING OF


STRUCTURE CABLING, IP-PBX, LAN, Wi-Fi, FA-PA SYSTEM AND ACCESS CONTROL SYSTEM FOR
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
A SUB-HEAD- I:STRUCTURED CABLING SYSTEM PASSIVE

Supply, Installation, Testing & Commissioning of Armoured 06 Core Singlemode (OS2) 9/125 Fiber Cable,
1 ITU G.652.D, G.657A1, Outdoor ECCS Armored Fiber Cable with PBT Loose Tube Filled With Thixotropic Mtr 1250
Jelly, Uni-Tube, Glass Yarn, Water Swellable Tape Under Armor, UV-HDPE Jacket.

Supply, Installation, Testing & Commissioning of 6 Port 1U x 19” LIU Loaded with Singlemode OS2 LC
Adapters & LSZH Pigtails along with Splice Trays, Min. 4 No of Circular Cable Entry with Rubber
Groummet/Glands to close any open entry, Cable Holders for Cable Entry Inside Panel, Heat Shrink
2 Tubes for Splices, Tube for open fibers, Ties, Panel shall be Powder Coated with Min. 1.2mm Metal Nos. 18
Sheath, 30 Years Channel Warranty. Factory Loaded LC Type LSZH Pigtails should meet IEC 61034-
1 ,IEC-60332-1, IEC-60754-1, Insertion loss <= 0.35 dB, Return Loss >= 50, Attenuation: 1310/1550 : 0.3/0.2
dB/KM, Repeatability: <= 0.2DB 1000 Times Mating Cycles, RoHS Complied, Meets ANSI/TIA 568.3-D.

Supply, Installation, Testing & Commissioning of 24 Port 1U x 19” LIU Loaded with Singlemode OS2 LC
Adapters & LSZH Pigtails along with Splice Trays, Min. 4 No of Circular Cable Entry with Rubber
Groummet/Glands to close any open entry, Cable Holders for Cable Entry Inside Panel, Heat Shrink
3 Tubes for Splices, Tube for open fibers, Ties, Panel shall be Powder Coated with Min. 1.2mm Metal Nos. 0
Sheath, 30 Years Channel Warranty. Factory Loaded LC Type LSZH Pigtails should meet IEC 61034-
1 ,IEC-60332-1, IEC-60754-1, Insertion loss <= 0.35 dB, Return Loss >= 50, Attenuation: 1310/1550 : 0.3/0.2
dB/KM, Repeatability: <= 0.2DB 1000 Times Mating Cycles, RoHS Complied, Meets ANSI/TIA 568.3-D

Supply, Installation, Testing & Commissioning of Fiber Patch Cord, LC - LC, Spiral Steel Armored,
4 Nos. 370
9/125μm OS2 Singlemode Round Cord (4.0 +/- 0.2mm), Duplex.

Supply, Installation, Testing & Commissioning of Cat 6A, 23 AWG (0.57  0.03mm ) Bare Copper Solid
5 Conductor UTP Unshielded LSZH Jacket, ANSI/TIA 568 C.2 Category 6A, Cable shall not have any kind of Mtr 13425
Non Metallic Barrier Tape or Metallic Shield inside. Connectivity of Hub room to End Point.

Supply, Installation, Testing & Commissioning of Category 6A RJ45 Unshielded Modular Jack, ISO/IEC
11801:2nd edition, EN 50173-1, ANSI/TIA/EIA 568-C.2 Category 6A, IEC 60603-7 (603-7), Universal 110
6 Nos. 179
Impact Tool & Tooless (Both) Termination, Min. 500Mhz Bandwidth, Without Any OEM Proprietary Tool
Termination for Data, Voice, & Wi-Fi at user end.

Supply, Installation, Testing & Commissioning of loaded 24 port CAT 6A UTP, Transparent shutter jack
7 Nos. 1
panel, 1U height, UL-94V-0, clear label marks and earthing plug for CAT6A cable termination at rack end.

Supply, Installation, Testing & Commissioning of Cat6A Patch Cord UTP Unshielded LSZH 24AWG Patch
8 Cord, Diameter < 6.2mm, 3 Meter, Operating Temperature -20 to +60 Deg C. Patch cord 1 Mtr for rack Nos. 179
side switch to jack panel connectivity.

Supply, Installation, Testing & Commissioning of Cat6A Patch Cord UTP Unshielded LSZH 24AWG Patch
9 Cord, Diameter < 6.2mm, 3 Meter, Operating Temperature -20 to +60 Deg C. Patch cord 2 Mtr for rack Nos. 179
side switch to end user connectivity.

Supply, Installation, Testing & Commissioning of 1, 2 and 4 port Style (Square) Keystone-Type Shuttered
10 Nos. 179
Faceplates for I/O fixing at user side.

Supply, Installation, Testing & Commissioning of 42 U (600W/1000D) floor mount rack with fans , 2 cable
11 Nos. 1
managers , satationary shelf , 2 Nos. of hardware pkts.

Supply, Installation, Testing & Commissioning of 22 U floor mount rack with fans , 2 cable managers ,
12 Nos. 2
satationary shelf , 2 Nos. of hardware pkts.

Supply, Installation, Testing & Commissioning of 15U wall mount rack with fans , 2 cable managers ,
13 Nos. 4
satationary shelf , 2 Nos. of hardware pkts.

Supply, Installation, Testing & Commissioning of 9U wall mount rack with fans , 2 cable managers ,
14 Nos. 7
satationary shelf , 2 Nos. of hardware pkts.

Supply, Installation, Testing & Commissioning of 6U wall mount rack with fans , 2 cable managers ,
15 Nos. 33
satationary shelf , 2 Nos. of hardware pkts.

TOTAL CARRIED TO SUMMARY

B SUB-HEAD- II: IP-PBX SYSTEM

Supply, Installation, Testing & Commissioning of Pure IP at core server Based voice solution with 04
Port Voicemail ,04 Port FXS ,04 Port FXO ,2 PRI Trunk lines (30 Ch) Circuit with CLIP Facility ,241 IP
1 users License ,01 Nos. IP Operator Console, 100 Party Conference ,Speed Dial, Music on Hold , Internal/ Set. 1
External ring difference ,Call Barring, Call Pickup, TEC should be with GR Number, - Should Support
Redundant server in active-Active mode.

Supply, Installation, Testing & Commissioning of Type 1 IP Phone 2 VoIP account, 120x40 Dot-matrix
2 Nos. 77
screen with backlight, Full HD duplex speaker phone, IPV6, Gigabit Ethernet, PoE .

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Supply, Installation, Testing & Commissioning of Type 2 IP Phone with 4 Voip accounts, 4 line keys, 3.5-
3 inch (480x320) Colour Screen display with backlight, GigE, colour displays for 6 DSS keys, IPV6, 2 x Nos. 4
Gigabit Ethernet , PoE.

TOTAL CARRIED TO SUMMARY

C SUB-HEAD- III: LOCAL AREA NETWORK ( LAN )


Supply , Installation , Testing and Commissioning of Core Switch with switching capacity of 6.4Tbps
with 32 QSFP28 ports from day 1, dual hot swappable internal power supply. Should support advance
1 layer 3 (OSPF, BGP and MPLS). 200k MAC address, 100K IPv4 routes and 100k IPv6 routes entries in the Nos. 1
routing table with 48000 Multicast Routes, Switch OEM should be leader in Gartner data centre
Quadrant.
Supply , Installation , Testing and Commissioning of Distribution Switch with switching capacity of
3.2Tbps, forwarding performance of 2Bpps with 48 x 1/10G/25G SFP28 ports plus 4x 40/100G QSFP28
2 ports from day 1, dual hot swappable internal power supply, MAC address 200k, 100k IPv4, 100K IPv6 Nos. 2
routes and 48K IPv6 multicast routes. Should support advance layer 3 (OSPF, BGP and MPLS) with 1
year support. Stack Module/40 Gig Optics and all other Cables should be included in Day 1.

Supply, Installation, Testing & Commissioning of 24 Port PoE Access Switches with switching capaticy
of 300 Gbps, forwarding performance 240 Mpps, having 24 x 10/100/1000BASE-T PoE-plus(RJ45) with
3 minimum PoE budget of 720W and 4x 10G SFP+ uplink ports . Should support min 4GB internal DRAM, Nos. 3
8GB internal Flash memory, 64K MAC address, 8K Multicast Routes, Should have static Routes from day
1.

4 Supply, Installation, Testing & Commissioning of fiber Modules 10G BASE Nos. 1

5 Supply, Installation, Testing & Commissioning of fiber Modules 40GBASE Nos. 1

Supply, Installation, Testing & Commissioning of Appliance based customised ITAM for asset inventory
management with ability to map physical locations and exact rack elevations for audit and support
6 control. Appliance shall be Intel x86 based device with secure intranet server with Linux Based operating Nos. 1
system and relational databases for long term storage. Appliance includes license for 500 units under
control.

Supply, Installation, Testing & Commissioning of Appliance based customised NMS for Network
Monitoring & management with ability to map Health of Active Network devices. Appliance shall be Intel
7 Nos. 1
x86 based device with secure intranet server with Linux Based operating system and relational
databases for long term storage.

Supply, Installation, Testing & Commissioning of Appliance based customised Network Analyser for
Network Traffic Analysis Appliance shall be Intel x86 based device with secure intranet server with
8 Nos. 1
Linux Based operating system and relational databases for long term storage. Appliance includes
license for 100 units under control.

TOTAL CARRIED TO SUMMARY

D SUB-HEAD- IV: Wi-Fi SYSTEMS

Supply, Installation, Testing & Commissioning of Wireless Indoor Access Point Combined data rate
support Dual 5GHz : 4.8Gbps , 802.11ax , 2.4 GHz / 5GHz: 4x4 : 4SS WiFi 6, data rate upto 2400 Mpbs,
Four 2.4GHz omnidirectional antennas with 4 dBi peak gain, Four 5GHz omnidirectional antennas with 6
dBi peak gain, vBLE 16-element Directional Antenna Array + Omni Bluetooth Antenna, Transmit
Beamforming and Maximal Ratio Combining the WLAN Access Point solution should have integrtaed
1 dynamic packet capture, WIPS, Dedicated Third Radio, detection of rougue and honeypot Access Point Nos. 7
detection, able to create WxLAN policies . The solution should be artifical intelligence based self healing
soltion. Bluetooth® LE and IoTsensor support Humidity Pressure Temperature, should also support
Asset Tracking if required in future without any change in Hardware. Omni-directional Bluetooth Antenna
, superbeacon mode with iBeacon and Eddystone, OFDMA & BSS Coloring support. Operating temp. 0
to 40 degree. Wireless OEM should be leader in Gartner Wired Wireless & Data Centre latest reports.

Supply, Installation, Testing & Commissioning of Outdoor Access Point solution should have integrated
dynamic packet capture, WIPS, detection of rouge and honeypot Access Point detection, able to create
WxLAN policies and the cloud controller should be scalable to handle around 5000 APs or more in
future. Should be able to extend API to integrate with other systems as well. AP indoor 4x4 with 802.11
2 Nos.
a/b/g/n/ac support. The solution should be artificial intelligence based self healing soltion.The solution
should support Location Based services via Bluetooth low energy and should also support Asset
Tracking if required in future without any change in Hardware. Enclosure - IP67 / NEMA 4 compliant,
Operating Temp. - -20° to 65° C; no solar loading -20° to 55° C; with solar loading.

TOTAL CARRIED TO SUMMARY

E SUB-HEAD- V: IP CCTV SYSTEM

Supply, Installation, Testing & Commissioning of Cat 6A, 23 AWG (0.57  0.03mm ) Bare Copper Solid
1 Conductor UTP Unshielded LSZH Jacket, ANSI/TIA 568 C.2 Category 6A, Cable shall not have any kind of Mtr 1575
Non Metallic Barrier Tape or Metallic Shield inside. Connectivity of Hub room to End Point.

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Supply, Installation, Testing & Commissioning of Category 6A RJ45 Unshielded Modular Jack, ISO/IEC
11801:2nd edition, EN 50173-1, ANSI/TIA/EIA 568-C.2 Category 6A, IEC 60603-7 (603-7), Universal 110
2 Nos. 21
Impact Tool & Tooless (Both) Termination, Min. 500Mhz Bandwidth, Without Any OEM Proprietary Tool
Termination for CCTV & IP Speaker at user end.

Supply, Installation, Testing & Commissioning of loaded 24 port CAT 6A UTP, Transparent shutter jack
3 Nos. 18
panel, 1U height, UL-94V-0, clear label marks and earthing plug for CAT6A cable termination at rack end.

Supply, Installation, Testing & Commissioning of Cat6A Patch Cord UTP Unshielded LSZH 24AWG Patch
4 Cord, Diameter < 6.2mm, 3 Meter, Operating Temperature -20 to +60 Deg C. Patch cord 1 Mtr for rack Nos. 18
side switch to jack panel connectivity.

Supply, Installation, Testing & Commissioning of Cat6A Patch Cord UTP Unshielded LSZH 24AWG Patch
5 Cord, Diameter < 6.2mm, 3 Meter, Operating Temperature -20 to +60 Deg C. Patch cord 2 Mtr for rack Nos. 18
side switch to end user connectivity.

Supply, Installation, Testing & Commissioning of 1, 2 and 4 port Style (Square) Keystone-Type Shuttered
6 Nos. 18
Faceplates for I/O fixing at user side.

Supply, installation, testing and commissioning of 5 MP (2592 x 1944) Dome camera , ONVIF profile S ,
G& T BIS,UL , CE , FCC Certified ,1/2.7” Progressive Scan CMOS ,2.7 mm to 13.5 mm motorized
varifocal lens , Quad stream with each stream support H.265 compression simultaneously ,min
illumination : Color 0.05lux @ F1.2(AGC ON) ; B/W 0 lux @ IR ON , Shutter speed : 1 / 5s ~ 1 / 100,000
s ,WDR , Compression : H.265/H.265+/H.264/H.264+ .SD card support upto 256GB, Cloud Storage , Alarm
trigger - 1 input / 1 output , frame rate : Main stream should support 25 &30 fps@5MP, , ROI Min. 8
7 Nos. 17
Region, Two Way Audio, Hardware reset, Edge analytics : Face Detection, Customer Flow staistics, Heat
Map, Human & Vehicle Detection, Pedestrian Intrusion Detection & Line cross Detection. Queue length
detection, Regional population statistics, SOD-Stationaary Object Detection, Tempering detection, Rare
Sound Detection, Defog, Motion Detection, License plate detection. Protocol:- TCP/IP, HTTP, DHCP,
DNS, DDNS, RTP, RTSP,SMTP, NTP, UPnP, SNMP, HTTPS,FTP PPPOE, NFS/SMB/CIFS, P2P , In built IR
LED , IR Distance upto 45 meters , IP 66 ,IK10,POE/12V DC.

Supply, installation, testing and commissioning of 5 MP (2592 x 1944) Bullet camera , ONVIF profile S ,
G& T BIS,UL , CE , FCC Certified ,1/2.7” Progressive Scan CMOS ,2.7 mm to 13.5 mm motorized
varifocal lens , Quad stream with each stream support H.265 compression simultaneously ,min
illumination : Color 0.01lux @ F1.2(AGC ON) ; B/W 0 lux @ IR ON , Shutter speed : 1 / 5s ~ 1 / 100,000
s ,WDR , Compression : H.265/H.265+/H.264/H.264+ .SD card support upto 256GB, Cloud Storage , Alarm
trigger - 1 input / 1 output , frame rate : Main stream should support 25 &30 fps@5MP, Net HDD, ROI Min.
8 Nos. 2
8 Region, Two Way Audio, Hardware reset, Edge analytics : Face Detection, Customer Flow staistics,
Heat Map, Human & Vehicle Detection, Pedestrian Intrusion Detection & Line cross Detection. Queue
length detection, Regional population statistics, SOD-Stationaary Object Detection, Tempering detection,
Rare Sound Detection, Defog, Motion Detection, License plate detection. Protocol:- TCP/IP, HTTP, DHCP,
DNS, DDNS, RTP, RTSP,SMTP, NTP, UPnP, SNMP, HTTPS,FTP PPPOE, NFS/SMB/CIFS, P2P , In built IR
LED , IR Distance upto 45 meters , IP 67 ,IK10,POE/12V DC.

Supply, installation, testing and commissioning of 5 MP PTZ camera , UL,CE,FCC,BIS Certified , ONVIF
profile S,G & Q , Quad stream, 4.3-141.9mm focal length , 33 X Optical Zoom , 12 X digital Zoom ,Frame
rate : 25/30 fps ,Shutter Speed : 1/5 ~ 1/100,000s , Inbuilt IR , IR distance upto 200 mtr , 2D / 3D noise
reduction ,120 dB WDR , 360 deg endess pan , tilt -10 to 90 deg , auto flip support ,255 presets , Min. 32
9 Nos. 2
preset add in each tour, Auto pan, Edge analytics : Pedestrian Intrusion Detection, Line cross Detection,
Stationaary Object Detection, Vehicle Detection, face Detection, Sound Detection, Auto Tracking,
Tempering detection, Defog, SD Card supportup to 128GB , Two Way, Auto white balance, Auto iris ,
Alarm : 1 IN , 1 Out , IK10,IP 67 weather proof , Power : POE+ /DC12V.

Supply, installation, testing and commissioning of professional video moniter software, VMS should
have ONVIF & RTSP competibilty, Support in windows, Windows server 2012, 2016, 2019, Linux CentOS,
MAOS, Mojave, Catalina(64 bit). support ONVIF video encoder. Compression format: H.265, H.264,
H.264+, Axis Zipstream, MPEG4. Support PTZ: ONVIF, RS485 (PTZ should control via mouse, Keyboard
or joystick. VMS should able to search Camera via ONVIF or UPnP and change camera ecode setting like
resolution, FPS, Bitrate, image setting. Hardware decoding: NVDIA graphics processing unit or Intel
graphics processing unit. support USB HID joystick, Axis T8311/8312. support & provide view of 360°
cameras. VMS should provide mobile view, playback view or PTZ control in android or iOS. support
Digital I/O. Audio recording & playback.VMS have multiple storag Selection or NAS options. Record
10 camera by contineue, schedule, event. VMS should able to provide multiple client access on LAN/WAN Nos. 1
from administator VMS. VMS mobile app should be available in Play store or App Store. Vms should
have multiple tab selection option. timeline display in live view for display recordings of camera as bars.
VMS should have multiple user options and each user define seperate permission. VMS should have
redundancy feature when main server goes down or disconnected then autometicaly start failover server
and work as a main server. VMS should have atleast one own analytics function for no dipendancy on
camera AI and support camera analytics by ONVIF profile M. VMS provide MAP view options (in JPG or
PNG image as a background) and able to add multiple MAP and add camera, moniter camera, I/O input
on map view. Provide live alarm, AI notification in FIFO format. VMS provide License plate recognition
punction on predefine camera. Built in Motion detection.

Supply, installation, testing and commissioning of Network PTZ joystick Keyboard, support 5.0 "LCD HD
real-time display, up port HDMI output to achieve the main console screen, Support ONVIF 2.4, back-end
11 Nos. 1
PTZ not restricted by manufacturer , wide compatibility,with PTZ tour, Pan Tilt, Add, delete preset, A-B
scan, 360°, pattern and so on functions. USB Port.

12 Supply, Installation, Testing & Commissioning of Server for VMS. Nos. 1

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
13 Supply, Installation, Testing and Commissioning of Full HD 55" LED Professional Display Panel. Nos. 2

Supply, Installation, Testing & Commissioning of L2+ managed industrial PoE fiber switch with
24*10/100/1000M RJ45 ports and 4*1//10G SFP slot ports, Port 1-24 can support IEEE802.3af/at PoE.
Switching capaticy of 128Gbps, forwarding Rate 95.23 Mpps, having 24 x 10/100/1000BASE-T PoE-
plus(RJ45) with maximum PoE output power is 400W, 1 RS232 Console port. 32K MAC address. Should
14 Nos. 1
have Static Routing , system logging, Telnet, SSH, SNMP, Network Time Protocol (NTP), and IPv6
features from day 1, Security Feature: Port Isolation, VLAN, MAC, Spanning tree, Multicast, DDM, ACL,
QoS: 802.1p (COS), DSCP, SP, WRR, Classification based on source IP, destination IP, and port number
etc.

Supply, Installation, Testing & Commissioning of L2+ managed full Gigabit managed industrial PoE
switch. 8*10/100/1000M PoE ports and 2*10/100/1000M RJ45 ports and 4*100/1000M SFP fiber slot ports ,1
RS232 Console port. Port 1-8 can supports IEEE 802.3af/at standard POE power supply, single port POE
power up to 30W, and the maximum POE output power is 120W (at-240W). Switching capaticy of
15 Nos. 1
28Gbps, forwarding Rate 20.83 Mpps, . 8K MAC address, 4K VLAN, Should have Static Routing ,
system logging, Telnet, SSH, SNMP, Network Time Protocol (NTP), and IPv6 features from day 1,
Security Feature: Port Isolation, VLAN, MAC, Spanning tree, Multicast, DDM, ACL, QoS: 802.1p (COS),
DSCP, SP, WRR, Classification based on source IP, destination IP, and port number etc.

Supply, Installation, Testing & Commissioning of L2+ managed industrial PoE fiber switch with
4*10/100/1000M RJ45 ports and 2*100/1000M SFP slot ports, Port 1-4 can support IEEE802.3af/at PoE.
Switching capaticy of 12Gbps, forwarding Rate 8.93 Mpps, having 4 x 10/100/1000BASE-T PoE-
plus(RJ45) with maximum PoE output power is 60W (at-120W) , 1 RS232 Console port. 8K MAC address.
16 Nos. 1
Should have Static Routing , system logging, Telnet, SSH, SNMP, Network Time Protocol (NTP), and
IPv6 features from day 1, Security Feature: Port Isolation, VLAN, MAC, Spanning tree, Multicast, DDM,
ACL, QoS: 802.1p (COS), DSCP, SP, WRR, Classification based on source IP, destination IP, and port
number etc.

Supply, Installation, Testing and Commissioning of Workstation PC: Intel(R) Core(TM) i7-3770 Processor
(8M Cache, up to 3.90 GHz); RAM: 8GB (1x8GB) Non-ECC DDR3 1600MHz ; Keyboard: 12 function keys;
17 Chassis: Tower/Workstation; DVD: 8X Slimline DVD+/-RW, Data Only; Dual Graphics Card; Network Nos. 1
interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000; Hard disk: 250GB, 7200
RPM 3.5" SATA 6Gb/s Hard Drive; Operating system: Windows 10 Professional 64 Bit or latest.

TOTAL CARRIED TO SUMMARY

F SUB-HEAD- VI: FIRE DETECTION SYSTEM


Supply ,erection testing & commissioning of Fire Alaram and Public addressing system for
Adminstrative building as per the requirement and Approval of Client.
Supply, erection,testing and commossioning of fire alarm system consisting of following items:

Supply, Installation, Testing & Commissioning of Addressable Multi-criteria Photo-Thermal Detector


with sensitivity range of 0.5 to 4.0% obs/ft.The intelligent multi criteria detection device shall include the
ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort
to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish
1 between a fire condition and a false alarm condition by examining the characteristics of the thermal and Nos 70
smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena.
The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly
rotary decimal switches. UL268, 7th Edition & FM Approved.
Approved Makes : Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell / Honeywell

Supply, installing, testing and commissioning of Rise Heat Detector rated at 8.3 deg C/min. The detector
shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal
2 Nos 0
switches UL268, 7th Edition & FM Approved.
Approved Makes : Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell / Honeywell

3 MANUAL CALL POINT


Supply , Installation , Testing and Commissioning of Addressable Manual Call Point (Pull down / Break
Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to
Nos 15
monitor the heath status of the device UL & FM Approved.
Approved Makes : Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell / Honeywell

4 MONITOR MODULES

Supply, Installation, Testing & Commissioning of Addressable Monitor Module for Sprinklers, Panic Bars
& other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall
have an LED which shall blink in normal state & get steady on activation to monitor the heath status of
Nos 8
the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with
mounting plate from OEM for ease of installation & maintenance UL & FM Approved.
Approved Makes : Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell / Honeywell

5 CONTROL MODULES

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

Supply, Installation, Testing & Commissioning of Addressable Control Module for Sounders / Strobes /
Sounder cum Strobes. The control module shall provide supervised NAC output rated at 24v DC, 2A. The
device shall have an LED which shall blink in normal state & get steady on activation to monitor the
Nos 8
heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall
be supplied with mounting plate from OEM for ease of installation & maintenance UL & FM Approved.
Approved Makes : Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell / Honeywell

Supply, Installation, Testing & Commissioning of Isolator Module for Isolating short / dewired / loose
circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case
6 needs to be considered with each detector & module. The device shall have an LED which shall blink in Nos 6
normal state & get steady on activation to monitor the heath status of the device. Module shall be
supplied with mounting plate from OEM for ease of installation & maintenance.

7 Hooter cum strobe


Supply , Installation , Testing and Commissioning of Sounder cum Strobe rated at 80 dBA @ 3m for
Audible annunciation and 115cd flashintg at 1 Hz for visual indication. UL & FM Approved. Nos 18
Approved Makes : Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell / Honeywell

8 FIRE ALARM CONTROL PANEL

Supply , Installation , Testing and Commissioning of Microprocessor based Multi-loop, True Peer-to-Peer
Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000
event plus 1000 alarm log history events, QWERTY keypad for programming. The panel should be
equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall
have a capacity of minimum 300 analog addressable devices. The panel shall work in degrade mode in
case of CPU failure, Products not having this feature may offer Redundant CPU. Four access levels, flash
EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries
sufficient for 24 hours normal working and 30 mins in alarm condition. The panel shall be complete with
2 ways Communication Fire Fighters System capable of supervising all the speaker circuits with
adequate zone control and accessories. Failure of Fire Panel CPU shall not result in failure of DVC
operation. The Fire Fighters Telephone System shall be capable of having minimum 30 Telephones in
conference in multiple FFT Risers. Designed to meet UL864, 10th Edition & FM approved.
Approved Makes : Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell / Honeywell

02Loop
Nos 1
Approved Makes : Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell / Honeywell

9 REPEATER PANEL
Supply , Installation , Testing and Commissioning of Network Repeater Panel with minimum 10" Color
Touch Screen display with QWERTY Keypad, mapping minimum 2,00,000 points on network. The NRP
shall act as an independent node communicating on the peer to peer network and shall not be dependant
Nos 1
on the Fire Panel CPU for operation. Failure of Fire Panel CPU shall not result in failure of NRP operation
UL & FM Approved. Approved Makes : Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell /
Honeywell

Supply, laying & testing of 1000 V grade 2 core 1.5 sq mm stranded Copper Conductor XLPE Low Smoke
Halogen Free Insulated with Fire-Rated Glass Mica Tape, LSZH Inner & Outer Sheathed, Armoured Fire
10 Survival Cable conforming to BS 7846:2015, Fire Resistance as per BS 8434-2:2003, 930°C rating for Nos 3003
three hours for fire alarm system.
Approved makes : Polycab/ RR Kabel/ Paramount/ Parasheild

TOTAL CARRIED TO SUMMARY

G SUB-HEAD- VII: PA SYSTEM

1 SPEAKERS
Supply, Installation, Testing & Commissioning of 6W Ceiling Speaker with max SPL1M/1W 96dB .
Frequency response of 80Hz-20KHz with a dispersion angle of 160 deg. The speaker should have
tappings at 6W/3W/1.5W

Nos. 46
Ceiling Mounted Speakers
Supply, Installation, Testing & Commissioning of 6W Wall mount with max SPL1M/1W 96dB . Frequency
2
response of 160Hz-20KHz. The speaker shoud have tappings at 6W/3W.
Wall Mounted Speakers Nos. 0

3 PA CONTROLLER
Supply, Installation, Testing & Commissioning of 8 zone IP based, digital Voice Alarm controller
expandable upto 128 zones. The voice alarm controller should be able to connect directly over Ethernet.
It should have functions like the audio playing, zone control, fault monitoring, log recording, volume
control and amplifier switchover. The Voice alarm controller should also have the following functions:
. 255 Priorities Nos. 1
. Time schedule broadcasts
. Its own PTT microphone
. Capable of amplifier redundancy
. 8 trigger inputs/outputs

4 DIGITAL AMPLIFIERS

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Supply, Installation, Testing & Commissioning of 1X500W Class-D Amplifier with 2 independent
channels and can provide automatic re-settable overcurrent, overload, overheating, overvoltage, under-
voltage and DC protection.
500 Watts Nos. 1

5 PAGING STATION

Supply, Installation, Testing & Commissioning of IP based Networkable touch screen paging station for
selection of zones, supervision of system status, setting of scheduled broadcasts with the following
functions:
. Built-in monitoring loudspeaker Nos. 1
. Detachable goose-neck microphone
. LCD touchscreen display
. Audio input

6 Supplying and Laying of 2 C X 1.5 Sq mm multi stranded twisted shielded FRLS Copper cable. RM 624

TOTAL CARRIED TO SUMMARY

IV HVAC SYSTEM
Note:-Air conditioner conference rooms & other room in office building, are to be provided with 5-star
rated split AC as applicable. Provision for future fitment of AC in all other rooms of admin building in
terms of making provision of power outlets points shall
also be ensured.
Below all item's bill of quantily line specification shall be followed strictly, These specification with
supersede tender specifications. Any deviation required due to any causes, prior approval is required
from engineering incharge.

A SUB HEAD-I HI-WALL SPLIT UNIT

Supply, Installation, testing and commissioning of Air-cooled Hi-wall split air conditioners each
comprising an outdoor unit(s) consisting of inverter driven compressor, air cooled condenser,
condenser fan along with Cooling thermostats etc. with outer casing and indoor fan coil unit consisting
of centrifugal fans, fan motor, DX cooling / Heating coil, outer casing, filter, control and power panel
with remote etc. entire cabling and wiring from indoor to outdoor, insulation and with full charge of
1 refrigerant gas and oil, supports, canvas connection etc. complete as per drawings. The indoor and
outdoor units shall be with structural steel supports, angles, rods etc. The quoted price shall also
include 24 G soft copper refrigerant piping with 13mm "O" class factory backed nitrile rubber with
aluminium foil from outdoor unit to indoor unit complete with insulation, refrigerant charging, PVC drain
piping with 6mm thick nitrile rubber insulation, supports, clamps, fittings, connections, sleeves,
supports, MCB, stabilizer etc from main panel to the unit. (Minimum 5-star rating). The refrigerant used
shall CFC Free R-410 A.
1.1 1.5 TR Unit Nos. 8
1.2 2.0 TR Unit Nos. 12

TOTAL CARRIED TO SUMMARY

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

INVENTORY FOR POWER POINT WIRING

WITH SWITCH ON
SCOKET(Comput
PLUG & SOCKET

32A(PP32A) 6PIN
63A INDUSTRIAL

DE-CONTACTOR

(NORMAL & HD)

100 MCCB BOX

125 MCCB BOX

250 MCCB BOX


WITH 1NO. 16A
6AMP SOCKET

SOCKET WITH

SOCKET WITH
2X6A SOCKET
6/16A SWITCH

6/16A SWITCH
SCOKET(UPS)
3x6A SOCKET
WITH SWITCH

2X6A SWITCH

ISOLATOR

ISOLATOR

ISOLATOR
S.No. DESCRIPTION

15A 3PIN

SCOKET
SWITCH

SWITCH

SWITCH
BOX

UPS
er)
i. SHED

MAIN SHED (INSPECTION SHED, HEAVY


A REPAIR SHED,WHEEL & BOGIE SHOP &
STORE WARD

1 MAIN SHED AREA 130 9

TOTAL 0 0 0 130 9 0 0 0 0 0 0 0 0

ii. BUILDINGS

B OFFICE BUILDING

1 GROUND FLOOR 41 21 2

2 MEZZANINE FLOOR 41 21 2

TOTAL 0 82 0 0 0 0 42 0 0 4 0 0 0

C TOILET BLOCK
1 MALE TOI 1
2 FEMALE TOI 1
3 COMMON AREA 2

TOTAL 0 0 0 0 0 0 2 0 0 2 0 0 0

D SUBSTATION (ESS) 2

TOTAL 0 0 0 0 0 0 2 0 0 0 0 0 0

E PUMP ROOM 1

TOTAL 0 0 0 0 0 0 1 0 0 0 0 0 0

TOTAL 0 82 0 130 9 0 47 0 0 6 0 0 0
CONT. 5% 0 4.1 0 6.5 0.45 0 2.35 0 0 0.3 0 0 0
OVERALL GRAND TOTAL 0 86 0 137 9 0 49 0 0 6 0 0 0

ELECTRICAL TENDER
i.

2
1
1

ii.

A.
A.
S.No.

SHED

BUILDINGS
STORE WARD
DESCRIPTION

GRAND TOTAL

GROUND FLOOR
MAIN SHED AREA

OFFICE BUILDING

MEZZANINE FLOOR
REPAIR SHED,WHEEL & BOGIE SHOP &
MAIN SHED (INSPECTION SHED, HEAVY
20W LED TUBE LIGHT FITTING

0
0
0

23
30-40W 2x2 RECESSED MOUNTED LED
0 LIGHT

60
59
1*18 RECCESSED CIRCULAR FIXTURE
0

15
15

10W MIRROR LIGHT


6
6
0

0
0

20-25 W FLOOD LIGHT


797
797

0
0

BULK HEAD LIGHT


211
211

200W LED HIGH BAY LIGHT


0
0
280
280

20W WATER PROOF LIGHT


INVENTORY FOR LIGHT FIXTURE & FANS

0
0
83
83

1200 MM DIA CEILING FAN


0

22
30

700-750 MM AIR CIRCULATING FAN


0
0
198
198

300 MM EXHAUST FAN WITH 6AMP


SOCKET
2
2
0

450 MM EXHAUST FAN WITH 6AMP


SOCKET
0
0
0
0

32
28

FIRST POINT SWITCH CONTROL


0

96
84

SWITCH CONTROL LOOP POINT

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
TOTAL 23 119 30 12 0 0 0 0 52 0 4 0 60 180

B. TOILET BLOCK
1 MALE TOI 6 3 2 5 6
2 FEMALE TOI 4 2 2 5 3
3 COMMON AREA 1 1

TOTAL 1 0 10 5 0 0 0 0 0 0 4 0 11 9

C. SUBSTATION (ESS) 10 2 2 10 4

TOTAL 10 0 0 0 0 0 0 0 2 0 0 2 10 4

D. PUMP ROOM 5 3 2

TOTAL 5 0 0 0 0 0 0 0 0 0 0 0 3 2

TOTAL 39 119 40 17 797 211 280 83 54 198 8 2 84 195


CONT. 5% 1.95 5.95 2 0.85 39.85 10.55 14 4.15 2.7 9.9 0.4 0.1 4.2 9.75
OVERALL TOTAL 41 125 42 18 837 222 294 87 57 208 8 2 88 205

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
RY FOR LIGHT FIXTURE & FANS

FIRST POINT MCB CONTROL

MCB CONTROLLOOP POINT


129 1160

129 1160

0 0

0 0

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

0 0

0 0

0 0

0 0

0 0

129 1160
6.45 58
135 1218

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
INVENTORY FOR WIRINGS
2X2.5+1X2.5 FOR 6A 2X4+1X4 SQMM 2X6+1X6 SQMM 2X6+1X6 SQMM FOR 4X10+2X6 SQMM
POINTs FOR 6/16A POWER FOR AC 20/25 A SINGLE FOR CAR
POINT PAHSE INDUSTRIAL CHARGING POINTS
Sr.No. SOCKET & OTHER 3-PHASE
INDUSTRIAL
DESCRIPTION SOCKET

TOTAL LENGTH

TOTAL LENGTH

TOTAL LENGTH

TOTAL LENGTH

TOTAL LENGTH
AV. LENGTH

AV. LENGTH

AV. LENGTH

AV. LENGTH

AV. LENGTH
NO. OF CKT

NO. OF CKT

NO. OF CKT

NO. OF CKT

NO. OF CKT
(FROM) (TO)
i. SHED

MAIN SHED (INSPECTION SHED,


A. HEAVY REPAIR SHED,WHEEL & BOGIE
SHOP & STORE WARD
1 LDB-01 POLICE LIGHT 6 70 420
2 LDB-01 POLICE LIGHT 6 70 420
1 L+PDB LEAN TO SHED AREA 6 70 420
2 LDB-01 INSPECTION PIT-1 6 70 420
3 LDB-02 INSPECTION PIT-2 12 45 540
4 LDB-01 INSPECTION PIT-5 12 45 540
5 LDB-02 INSPECTION PIT-7 12 45 540
6 LDB-03 INSPECTION PIT-3 12 45 540
7 LDB-04 JACK PIT-2 12 45 540
8 LDB-08 INSPECTION BAY LINE-1 12 45 540
9 LDB-09 INSPECTION BAY LINE-1 12 45 540
10 LDB-06 INSPECTION BAY LINE-2 12 45 540

TOTAL 120 640 6000 0 0 0 0 0 0 0 0 0 0 0 0

ii. BUILDINGS

A. OFFICE BUILDING
GROUND FLOOR
1 LDB-1 6 30 180
2 LDB-2 6 30 180
3 PDB-1 12 35 420
4 PDB-2 12 35 420
5 UPSDB-1 6 30 180 6 35 210
6 AC DB-1 8 35 280

MEZANINE FLOOR
1 LDB-1 6 30 180
2 LDB-2 6 30 180
3 PDB-1 12 35 420
4 PDB-2 12 35 420
5 UPSDB-1 6 30 180 6 35 210
6 AC DB-1 8 35 280

TOTAL 0 36 180 1080 60 210 2100 16 70 560 0 0 0 0 0 0

B. TOILET BLOCK
1 L+PDB-1 2 30 60 6 35 210

TOTAL 0 2 30 60 6 35 210 0 0 0 0 0 0 0 0 0

C. SUBSTATION (ESS)

1 L+PDB-1 2 30 60 6 35 210

TOTAL 0 2 30 60 6 35 210 0 0 0 0 0 0 0 0 0

D. PUMP ROOM

1 L+PDB-1 2 30 60 6 35 210

TOTAL 0 2 30 60 6 35 210 0 0 0 0 0 0 0 0 0

OVER ALL TOTAL 0 162 910 7260 78 315 2730 16 70 560 0 0 0 0 0 0


CONT. 5% 0 8.1 45.5 363 3.9 15.75 136.5 0.8 3.5 28 0 0 0 0 0 0
GRAND TOTAL 0 170 7623 82 2867 17 588 0 0 0 0

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

INVENTORY FOR MCB, RCCB & DBs

32 AMP SP IND SOCKET


32A DP RCBO(30 mA)
16A DP RCBO(30 mA)
63A DP RCBO(30mA)

40 AMP 4 P ISO BOX


6-32A SP MCB
40A DP RCBO
S.No. DESCRIPTION

12-WAY SPN

40A DP MCB

32A DP MCB

25A DP MCB
12-WAY TPN

63A 4P MCB

40A 4P MCB

32A 4P MCB

25A 4P MCB
8-WAY SPN
8-WAY TPN

6-WAY TPN
i. SHED

MAIN SHED (INSPECTION SHED,


HEAVY REPAIR SHED,WHEEL &
A. BOGIE SHOP & STORE WARD
1 LDB-1 POLICE LIGHT 1 1 1 8
2 LDB-2 POLICE LIGHT 1 1 1 8
3 L+PDB LEAN TO SHED AREA 1 1 1 18
4 LDB-01 INSPECTION PIT-1 1 1 1 18
5 LDB-02 INSPECTION PIT-2 1 1 1 18
6 LDB-01 INSPECTION PIT-5 1 1 1 18
7 LDB-02 INSPECTION PIT-7 1 1 1 18
8 LDB-03 INSPECTION PIT-3 1 1 1 18
9 LDB-04 JACK PIT-2 1 1 1 18
10 LDB-08 INSPECTION BAY LINE-1 1 1 1 18
11 LDB-09 INSPECTION BAY LINE-1 1 1 1 18
12 LDB-06 INSPECTION BAY LINE-2 1 1 1 18
4 2
OVER ALL TOTAL 0 0 10 0 1 1 0 0 10 0 0 0 2 0 0 0 0 12 0 0 196 4 2

ii. BUILDINGS

A. OFFICE BUILDINGS
GROUND FLOOR
1 LDB-1 1 1 1 18
2 LDB-2 1 1 1 18
3 PDB-1 1 1 1 24
4 PDB-2 1 1 1 24
5 UPSDB-1 1 1 8
6 AC DB-1 1 1 1 24

MEZZANINE FLOOR
1 LDB-1 1 1 1 18
2 LDB-2 1 1 1 18
3 PDB-1 1 1 1 24
4 PDB-2 1 1 1 24
5 UPSDB-1 1 1 8
6 AC DB-1 1 1 1 24

TOTAL 0 6 4 0 0 2 0 6 4 0 0 0 0 0 0 0 6 6 0 0 232 0 0

B. TOILET BLOCK

1 L+PDB-1 1 1 1 8

TOTAL 0 0 0 0 1 0 0 0 1 0 0 0 0 0 0 0 0 1 0 0 8 0 0

C. SUBSTATION (ESS)

1 L+PDB-1 1 1 1 8

TOTAL 0 0 0 0 1 0 0 0 1 0 0 0 0 0 0 0 0 1 0 0 8 0 0

D. PUMP ROOM

1 L+PDB-1 1 1 1 8

TOTAL 0 0 0 0 1 0 0 0 1 0 0 0 0 0 0 0 0 1 0 0 8 0 0

OVER ALL TOTAL 0 6 14 0 4 3 0 6 17 0 0 0 2 0 0 0 6 21 0 0 452 4 2


CONT. 5% 0 0.3 0.7 0 0.2 0.15 0 0.3 0.85 0 0 0 0.1 0 0 0 0.3 1.05 0 0 22.6 0.2 0.1
GRAND TOTAL 0 6 15 0 4 3 0 6 18 0 0 0 2 0 0 0 6 22 0 0 475 4 2

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
INVENTORY FOR CABLE TRAY
PERFORATED CABLE TRAY RACEWAYS JUNCTION BOX
100 mm wide x 150 mm wide x
38 mm deep 38 mm deep 250 mm wide x
S.No. DESCRIPTION 60x60x150 60x60x300 60x60x450 60x60x600 raceway raceway 38 mm deep 300X50 200X50 150X50
i. SHED

MAIN SHED (INSPECTION SHED, HEAVY


A. REPAIR SHED,WHEEL & BOGIE SHOP & 1480 150 60 150
STORE WARD

TOTAL 1480 150 60 150 0 0 0 0 0 0

ii. BUILDINGS

A. OFFICE BUILDINGS

i. GROUND FLOOR 15 30 15 35 20 6 3 2

ii. MEZZANINE FLOOR 20 15 15 30 20 6 3 2

B. TOILET BLOCK 10

C. SUBSTATION (ESS) 25

D. PUMP ROOM 10

TOTAL 35 90 0 0 30 65 40 12 6 4

OVER ALL TOTAL 1515 240 60 150 30 65 40 12 6 4


CONT. 5% 75.75 12 3 7.5 1.5 3.25 2 0.6 0.3 0.2
GRAND TOTAL 1591 252 63 158 32 68 42 13 6 4

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

INVENTORY FOR EARTHING WORK FOR PROPOSED DEVELOPMENT FOR VANDEBHARAT DEPOT AT SHALIMAR STATION YARD
S.No. FROM TO G.I. CU. PIPE GI Strip on GI Strip in CU. Strip CU Strip GI Strip on GI Strip in CU. Strip CU Strip GI Strip GI Strip in 6 SWG IN 6 Sq 2.5 Sq
EARTHING EARTHING EARTHING surface pipe on surface in pipe surface pipe on in pipe on pipe SURFAC mm. mm.
(75x6mm) (75x6mm) (75x6mm) (75x6mm) (40x6mm) (40x6mm) surface (40x6mm) surface (32x6mm) E
(40x6mm) (32x6mm)

6.6 kV 800A VCB PANEL-1 EP 2 20 20


1
11 kV HT VCB/TWO POLE STRUCTURE
EP 2 20 20
(400A AB SWITCH)
2

6.6 kV 800A VCB PANEL-2 EP 2 20 20


3

CSS-1 BODY (1000 kVA) EP 2 20 20


4

CCS-1 NEUTRAL (1000 kVA) EP 2 15 15


5

CSS-2 BODY (1000 kVA) EP 2 20 20


6

CCS-2 NEUTRAL (1000 kVA) EP 2 15 15


7

DG SET-1 BODY (500kVA) EP 2 20 20


8
DG SET-1 NEUTRAL (500 kVA) EP 2 20 20
9

MDB-1 LEFT SIDE EP 2 25 25


10

MDB-2 RIGHT SIDE EP 2 20 20


11

MDB-3 AIR COMPRESSOR ROOM EP 1 15 15


12

MDB-4 (MECHANICAL EQUIPMENT) EP 1 20 20


13

MDB-5 (ESS) EP 2 25 25
14

MDB-6 (L&P OFFICE BUILDING ) EP 1 25 25


15
STP PANEL EP 1 25 25
16

FIRE-FIGHTING PANEL EP 1 30 30
17

MECHANICAL EQUIPMENT EP 4 150 180


18

HIGH MAST-1 EP 2 15 15
19

HIGH MAST-2 EP 2 15 15
20

STREET LIGHT EP 4 10 10
21

SERVER/UPS (OFFICE AREA) UPS-10 kVA EP 2 120 0


22

7500

TOTAL 27 8 8 100 100 30 30 20 20 20 20 375 405 7500 120 0

CONT 10.0% 2.7 0.8 0.8 10 10 3 3 2 2 2 2 37.5 40.5 750 12 0

GRAND TOTAL 30 9 9 110 110 33 33 22 22 22 22 413 446 8250 132 0

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

INVENTORY FOR LIGHTNING PROTECTION SYSTEM

Conductor Holder GI tape 32 25X5 G.I. G.I.


Alumunium Conductor Universal
S.No. DESCRIPTION With Adhessicve Holder Clamp Test Clamp mm X 6 (in STRIP IN EARTHIN
Conductor Holder Roof Clamp
Pad Ground) PIPE G
i. MAIN SHED

MAIN SHED (INSPECTION SHED,


A. HEAVY REPAIR SHED,WHEEL &
BOGIE SHOP & STORE WARD

1 Horizontal Conductor 3420 171 3249 684 40

2 Vertical Conductor 420 420 40 880 750

OVER ALL TOTAL 3840 171 3249 684 420 40 880 750 40
CONT. 10% 384 17.1 324.9 68.4 42 4 88 75 4
GRAND TOTAL 4224 188 3574 752 462 44 968 825 44

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
INVENTORY FOR BBT

LIGHTING BUS BAY, 40


AMPS DOUBLE CIRCUIT (8-
POWER BBT CONDUCTORS) BBT

250

400

40

63
AL

AL

AL

AL
A

A
S.No. DESCRIPTION
i. SHED

MAIN SHED (INSPECTION SHED, HEAVY


REPAIR SHED,WHEEL & BOGIE SHOP & STORE 1386 0 1365 0
A. WARD

OVER ALL TOTAL 1386 0 1365 0


CONT. 5% 69.3 0 68.25 0
GRAND TOTAL 1455 0 1433 0

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

CABLE SCHEDULE & VOLTAGE DROP CALCULATIONS FOR ELECTRICAL WORK - EXTERNAL OF VANDE BHARAT COACHING COMPLEX AT SHALIMAR
Cable Size
Cable Current Rating Voltage drop
(Sqmm)
Derated
Current Current Voltage
X- Single Single carryingc Single Max. Total
Carryingc Drop in End
Load in Section Cable Cable Cable Demand Cable
S. No. From To No. of apacity Length Runs apacity Current Volts/ Terminatio
kW area of Type Current Current % age Volts. (In
Core at 0.8 (Mtrs) (A) after Km/ n
Cable Rating Rating (in (A) Mtrs)
derating Amps
(sqmm) (in Air) Ground)

1 1000 kVA CSS-1 800 1600A BUS DUCT INTERCONNECTED CSS-1 17


2 1000 kVA CSS-2 800 1600A BUS DUCT INTERCONNECTED CSS-2 16
3 500 kVA DG-1 Main DG Panel-1 400 4 300 AL.ARM. 461 370 0.8 20 3 1106.4 695.6 0.26 0.29 1.21 60 6
4 CSS-1&2 MDB-1 Left Side 254 4 300 AL.ARM. 461 370 0.8 95 2 737.6 441.7 0.26 1.31 5.46 190 4
5 Main DG Panel-1 MDB-1 Left Side 47 4 185 AL.ARM. 339 285 0.8 110 2 542.4 81.7 0.39 0.42 1.75 220 4
6 Solar Panel MDB-1 Left Side 47 4 185 AL.ARM. 339 285 0.8 125 1 271.2 81.7 0.39 0.96 3.98 125 2
7 CSS-1&2 MDB-2 Right Side 320 4 300 AL.ARM. 461 370 0.8 280 3 1106.4 556.5 0.26 3.25 13.50 840 6
8 Main DG Panel-1 MDB-2 Right Side 82.7 4 185 AL.ARM. 339 285 0.8 290 2 542.4 143.8 0.39 1.96 8.13 580 4
9 Solar Panel MDB-2 Right Side 82.7 4 185 AL.ARM. 339 285 0.8 140 1 271.2 143.8 0.39 1.89 7.85 140 2
10 CSS-1&2 MDB-3 (Air Compressor Room) 140 4 185 AL.ARM. 339 285 0.8 280 2 542.4 243.5 0.39 3.20 13.29 560 4
11 CSS-1&2 MDB-4 (Mechanical Equipment ) 205 4 300 AL.ARM. 461 370 0.8 250 2 737.6 356.5 0.26 2.79 11.59 500 4
12 CSS-1&2 MDB-5 (ESS ROOM ) 39 4 185 AL.ARM. 339 285 0.8 25 2 542.4 67.8 0.39 0.08 0.33 50 4
13 CSS-1&2 MDB-6 (L&P ROOM ) 80 4 185 AL.ARM. 339 285 0.8 285 1 271.2 139.1 0.39 3.73 15.46 285 2
14 Main DG Panel-1 MDB-6 (L&P ROOM ) 80 4 185 AL.ARM. 339 295 0.8 285 1 271.2 139.1 0.39 3.73 15.46 285 2
15 MDB-5 (ESS ROOM ) STREET LIGHT PANEL 22 4 70 AL.ARM. 176 170 0.8 20 1 140.8 38.3 0.99 0.18 0.76 20 2
16 MDB-5 (ESS ROOM ) TOILET Block 4 4 16 AL.ARM. 70 78 0.8 75 1 56.0 7.0 2.40 0.30 1.25 75 2
17 MDB-5 (ESS ROOM ) STP 10 4 70 AL.ARM. 176 170 0.8 85 1 140.8 17.4 0.99 0.35 1.46 85 2
18 Main DG Panel-1 STP 10 4 70 AL.ARM. 176 170 0.8 85 1 140.8 17.4 0.99 0.35 1.46 85 2
19 MDB-5 (ESS ROOM ) FIRE-FIGHTING 50 4 185 AL.ARM. 339 285 0.8 75 1 271.2 87.0 0.39 0.61 2.54 75 2
20 Main DG Panel-1 FIRE-FIGHTING 50 4 185 AL.ARM. 339 285 0.8 75 1 271.2 87.0 0.39 0.61 2.54 75 2
21 STREET LIGHT PANEL HIGH MAST-1 CKT-1 5 4 25 AL.ARM. 99 95 0.8 120 1 79.2 8.7 2.66 0.67 2.78 120 2
22 STREET LIGHT PANEL HIGH MAST-1 CKT-2 5 4 25 AL.ARM. 99 95 0.8 345 1 79.2 8.7 2.66 1.92 7.98 345 2
23 STREET LIGHT PANEL STREET LIGHT CKT-3 2.5 4 16 AL.ARM. 70 78 0.8 140 1 56.0 4.3 2.40 0.35 1.46 140 2
24 STREET LIGHT PANEL STREET LIGHT CKT-4 2.5 4 16 AL.ARM. 70 78 0.8 135 1 56.0 4.3 2.40 0.34 1.41 135 2
25 STREET LIGHT PANEL STREET LIGHT CKT-5 2.5 4 16 AL.ARM. 70 78 0.8 330 1 56.0 4.3 2.40 0.83 3.44 330 2

Total End
Addition
S. No. Cable Size Cable Length Cable Say Terminati
al @ 10%
Length on
1 4Cx300 1590 159 1749 1750 20
2 4Cx185 2395 240 2635 2635 28
3 4Cx70 190 19 209 210 6
4 4Cx25 465 47 512 515 4
5 4Cx16 680 68 748 750 8

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
INVENTORY FOR EXTERNAL

SYSTEM SUITABLE FOR


LED BOLLARD LIGHT

200 DIA HDPE/HUME


OCTAGONAL POLE

OCTAGONAL POLE

16Mtr. HIGH MAST

12 LUMINAIRES
5Mtr. LONG GI

7Mtr. LONG GI
DESCRIPTION

PIPE
1 MASTER PLAN 0 33 0 2 210

TOTAL 0 33 0 2 210
CONT 5% 0 1.65 0 0.1 10.5
GRAND TOTAL 0 35 0 2 221

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

CABLE SCHEDULE & VOLTAGE DROP CALCULATIONS FOR ELECTRICAL WORK- MAIN SHED BUILDING
Cable Size
Cable Current Rating Voltage drop
(Sqmm) Single Current Voltage
Cable Derated Single Max. Total
X- Single Carryingc Drop in End
Load in Cable Curren Current Length Runs apacity Demand Volts/ Cable
S. No. From To Section Cable Termin
kw No. of Type t carryingc (Mtrs) Current (In
area of Current (A) after Km/ % age Volts. ation
Core Rating apacity (A) Mtrs)
Cable Rating derating Amps
(in at 0.8
(sqmm) (in Air)
Groun
1 250A BBT-1 63.0 4 150 CU.ARM. 294 255
d) 0.8 25 1 235.2 109.6 0.48 0.32 1.31 25 2
2 250A BBT-2 63.0 4 150 CU.ARM. 294 255 0.8 45 1 235.2 109.6 0.48 0.57 2.37 45 2
3 250A BBT-3 63.0 4 150 CU.ARM. 294 255 0.8 60 1 235.2 109.6 0.48 0.76 3.16 60 2
4 SDB-1 L&P DB 18.0 4 50 CU.ARM. 140 140 0.8 15 1 112.0 31.3 1.43 0.16 0.67 15 2
5 MDB-1 Left Side EOT CRANE 25/5 TON 40.0 4 70 CU.ARM. 176 170 0.8 55 1 140.8 69.6 0.99 0.91 3.79 55 2
6 EOT CRANE 25/5 TON 40.0 4 70 CU.ARM. 176 170 0.8 85 1 140.8 69.6 0.99 1.41 5.85 85 2
7 EOT CRANE 5 TON 6.0 4 25 CU.ARM. 99 95 0.8 125 1 79.2 10.4 2.66 0.84 3.47 125 2
8 EOT CRANE 5 TON 6.0 4 25 CU.ARM. 99 95 0.8 145 1 79.2 10.4 2.66 0.97 4.02 145 2
9 POLICE LIGHT DB 1.5 2 6 CU.ARM. 40 43 0.8 90 1 32.0 2.6 6.40 0.36 1.50 90 2
10 TYPICALLY INDUSTRIAL SOCKET-1 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
11 TYPICALLY INDUSTRIAL SOCKET-2 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
12 TYPICALLY INDUSTRIAL SOCKET-3 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
13 TYPICALLY INDUSTRIAL SOCKET-4 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
14 TYPICALLY INDUSTRIAL SOCKET-5 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
15 TYPICALLY INDUSTRIAL SOCKET-6 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
16 TYPICALLY INDUSTRIAL SOCKET-7 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
17 TYPICALLY INDUSTRIAL SOCKET-8 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
18 TYPICALLY INDUSTRIAL SOCKET-9 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
19 250A BBT-1 AL. AIR INSULATED TYPICALLY INDUSTRIAL SOCKET-10 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
20 BBT (GRID-01 TO 21 & GRID-B-B1) TYPICALLY INDUSTRIAL SOCKET-11 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
21 TYPICALLY INDUSTRIAL SOCKET-12 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
22 TYPICALLY INDUSTRIAL SOCKET-13 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
23 TYPICALLY INDUSTRIAL SOCKET-14 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
24 TYPICALLY INDUSTRIAL SOCKET-15 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
25 TYPICALLY INDUSTRIAL SOCKET-16 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
26 TYPICALLY INDUSTRIAL SOCKET-17 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
27 TYPICALLY INDUSTRIAL SOCKET-18 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
28 TYPICALLY INDUSTRIAL SOCKET-19 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
29 TYPICALLY INDUSTRIAL SOCKET-20 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
30 TYPICALLY INDUSTRIAL SOCKET-21 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
31 TYPICALLY INDUSTRIAL SOCKET-1 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
32 TYPICALLY INDUSTRIAL SOCKET-2 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
33 TYPICALLY INDUSTRIAL SOCKET-3 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
34 TYPICALLY INDUSTRIAL SOCKET-4 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
35 TYPICALLY INDUSTRIAL SOCKET-5 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
36 TYPICALLY INDUSTRIAL SOCKET-6 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
37 TYPICALLY INDUSTRIAL SOCKET-7 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
38 TYPICALLY INDUSTRIAL SOCKET-8 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
39 TYPICALLY INDUSTRIAL SOCKET-9 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
40 250A BBT-2 AL. AIR INSULATED TYPICALLY INDUSTRIAL SOCKET-10 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
41 BBT (GRID-01 TO 21 & GRID C-CI) TYPICALLY INDUSTRIAL SOCKET-11 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
42 TYPICALLY INDUSTRIAL SOCKET-12 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
43 TYPICALLY INDUSTRIAL SOCKET-13 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
44 TYPICALLY INDUSTRIAL SOCKET-14 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
45 TYPICALLY INDUSTRIAL SOCKET-15 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
46 TYPICALLY INDUSTRIAL SOCKET-16 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
47 TYPICALLY INDUSTRIAL SOCKET-17 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
48 TYPICALLY INDUSTRIAL SOCKET-18 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
49 TYPICALLY INDUSTRIAL SOCKET-19 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
50 TYPICALLY INDUSTRIAL SOCKET-20 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
51 TYPICALLY INDUSTRIAL SOCKET-21 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
52 TYPICALLY INDUSTRIAL SOCKET-1 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
53 TYPICALLY INDUSTRIAL SOCKET-2 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
54 TYPICALLY INDUSTRIAL SOCKET-3 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
55 TYPICALLY INDUSTRIAL SOCKET-4 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
56 TYPICALLY INDUSTRIAL SOCKET-5 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
57 TYPICALLY INDUSTRIAL SOCKET-6 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
58 TYPICALLY INDUSTRIAL SOCKET-7 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
59 TYPICALLY INDUSTRIAL SOCKET-8 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
60 TYPICALLY INDUSTRIAL SOCKET-9 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
61 250A BBT-3 AL. AIR INSULATED TYPICALLY INDUSTRIAL SOCKET-10 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
62 BBT (GRID-01 TO 21 & GRID-A) TYPICALLY INDUSTRIAL SOCKET-11 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
63 TYPICALLY INDUSTRIAL SOCKET-12 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
64 TYPICALLY INDUSTRIAL SOCKET-13 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
65 TYPICALLY INDUSTRIAL SOCKET-14 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
66 TYPICALLY INDUSTRIAL SOCKET-15 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
67 TYPICALLY INDUSTRIAL SOCKET-16 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
68 TYPICALLY INDUSTRIAL SOCKET-17 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
69 TYPICALLY INDUSTRIAL SOCKET-18 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
70 TYPICALLY INDUSTRIAL SOCKET-19 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
71 TYPICALLY INDUSTRIAL SOCKET-20 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
72 TYPICALLY INDUSTRIAL SOCKET-21 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
73 LIGHTING BUS WAY-1 15.0 4 10 CU.ARM. 62 72 0.8 25 1 49.6 26.1 3.81 0.60 2.48 25 2
74 LIGHTING BUS WAY-2 3.0 4 10 CU.ARM. 62 72 0.8 45 1 49.6 5.2 3.81 0.22 0.89 45 2
75 LIGHTING BUS WAY-3 3.0 4 10 CU.ARM. 62 72 0.8 60 1 49.6 5.2 3.81 0.29 1.19 60 2
76 L+PDB LEAN TO SHED AREA 3.0 4 10 CU.ARM. 62 72 0.8 75 1 49.6 5.2 3.81 0.36 1.49 75 2
77 LDB-01 INSPECTION PIT-1 3.0 4 6 CU.ARM. 40 43 0.8 95 1 32.0 5.2 6.40 0.76 3.17 95 2
SDB-1 L&P DB
78 LDB-02 INSPECTION PIT-2 3.0 4 6 CU.ARM. 40 43 0.8 80 1 32.0 5.2 6.40 0.64 2.67 80 2
79 LDB-01 INSPECTION PIT-5 3.0 4 6 CU.ARM. 40 43 0.8 85 1 32.0 5.2 6.40 0.68 2.84 85 2
80 LDB-02 INDUSTRIAL
32AMP INSPECTIONSOCKET
PIT-7 FOR 3.0 4 6 CU.ARM. 40 43 0.8 15 1 32.0 5.2 6.40 0.12 0.50 15 2
81 BATTERY
32AMP CHARGERSOCKET
INDUSTRIAL FOR MOVEABLE
FOR 3.0 2 6 CU.ARM. 40 43 0.8 40 1 32.0 5.2 6.40 0.32 1.34 40 2
82 PLATFORM
BATTERY CHARGER FOR MOVEABLE 3.0 2 6 CU.ARM. 40 43 0.8 45 1 32.0 5.2 6.40 0.36 1.50 45 2
83 PLATFORM
250A BBT-4 57.0 4 150 CU.ARM. 294 255 0.8 15 1 235.2 99.1 0.48 0.17 0.71 15 2
84 250A BBT-5 60.0 4 150 CU.ARM. 294 255 0.8 125 1 235.2 104.3 0.48 1.51 6.26 125 2
85 250A BBT-6 60.0 4 150 CU.ARM. 294 255 0.8 145 1 235.2 104.3 0.48 1.75 7.26 145 2
86 250A BBT-7 60.0 4 150 CU.ARM. 294 255 0.8 165 1 235.2 104.3 0.48 1.99 8.26 165 2
87 SDB-1 L&P DB 21.7 4 50 CU.ARM. 140 140 0.8 15 1 112.0 37.7 1.43 0.20 0.81 15 2
MDB-2 Right Side
88 EOT CRANE 25/5 TON 40.0 4 70 CU.ARM. 176 170 0.8 145 1 140.8 69.6 0.99 2.41 9.99 145 2
89 EOT CRANE 25/5 TON 40.0 4 70 CU.ARM. 176 170 0.8 160 1 140.8 69.6 0.99 2.66 11.02 160 2
90 EOT CRANE 5 TON 14.0 4 25 CU.ARM. 99 95 0.8 160 1 79.2 24.3 2.66 2.50 10.36 160 2
91 EOT CRANE 5 TON 14.0 4 25 CU.ARM. 99 95 0.8 120 1 79.2 24.3 2.66 1.87 7.77 120 2
92 POLICE LIGHT DB 1.5 2 6 CU.ARM. 40 43 0.8 55 1 32.0 2.6 6.40 0.22 0.92 55 2
93 TYPICALLY INDUSTRIAL SOCKET-1 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
94 TYPICALLY INDUSTRIAL SOCKET-2 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
95 TYPICALLY INDUSTRIAL SOCKET-3 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
96 TYPICALLY INDUSTRIAL SOCKET-4 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
97 TYPICALLY INDUSTRIAL SOCKET-5 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
98 TYPICALLY INDUSTRIAL SOCKET-6 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
99 TYPICALLY INDUSTRIAL SOCKET-7 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
100 TYPICALLY INDUSTRIAL SOCKET-8 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
101 250A BBT-4 AL. AIR INSULATED TYPICALLY INDUSTRIAL SOCKET-9 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
102 BBT (GRID-32 TO 14 & GRID-C') TYPICALLY INDUSTRIAL SOCKET-10 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2

ELECTRICAL TENDER
250A BBT-4 AL. AIR INSULATED VANDE BHARAT COACHING COMPLEX AT SHALIMAR
BBT (GRID-32 TO 14 & GRID-C')
103 TYPICALLY INDUSTRIAL SOCKET-11 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
104 TYPICALLY INDUSTRIAL SOCKET-12 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
105 TYPICALLY INDUSTRIAL SOCKET-13 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
106 TYPICALLY INDUSTRIAL SOCKET-14 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
107 TYPICALLY INDUSTRIAL SOCKET-15 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
108 TYPICALLY INDUSTRIAL SOCKET-16 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
109 TYPICALLY INDUSTRIAL SOCKET-17 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
110 TYPICALLY INDUSTRIAL SOCKET-18 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
111 TYPICALLY INDUSTRIAL SOCKET-19 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
112 TYPICALLY INDUSTRIAL SOCKET-1 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
113 TYPICALLY INDUSTRIAL SOCKET-2 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
114 TYPICALLY INDUSTRIAL SOCKET-3 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
115 TYPICALLY INDUSTRIAL SOCKET-4 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
116 TYPICALLY INDUSTRIAL SOCKET-5 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
117 TYPICALLY INDUSTRIAL SOCKET-6 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
118 TYPICALLY INDUSTRIAL SOCKET-7 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
119 TYPICALLY INDUSTRIAL SOCKET-8 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
120 TYPICALLY INDUSTRIAL SOCKET-9 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
121 250A BBT-5 AL. AIR INSULATED TYPICALLY INDUSTRIAL SOCKET-10 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
122 BBT (GRID-41 TO 42 & GRID C1-C) TYPICALLY INDUSTRIAL SOCKET-11 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
123 TYPICALLY INDUSTRIAL SOCKET-12 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
124 TYPICALLY INDUSTRIAL SOCKET-13 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
125 TYPICALLY INDUSTRIAL SOCKET-14 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
126 TYPICALLY INDUSTRIAL SOCKET-15 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
127 TYPICALLY INDUSTRIAL SOCKET-16 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
128 TYPICALLY INDUSTRIAL SOCKET-17 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
129 TYPICALLY INDUSTRIAL SOCKET-18 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
130 TYPICALLY INDUSTRIAL SOCKET-19 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
131 TYPICALLY INDUSTRIAL SOCKET-20 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
132 TYPICALLY INDUSTRIAL SOCKET-1 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
133 TYPICALLY INDUSTRIAL SOCKET-2 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
134 TYPICALLY INDUSTRIAL SOCKET-3 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
135 TYPICALLY INDUSTRIAL SOCKET-4 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
136 TYPICALLY INDUSTRIAL SOCKET-5 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
137 TYPICALLY INDUSTRIAL SOCKET-6 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
138 TYPICALLY INDUSTRIAL SOCKET-7 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
139 TYPICALLY INDUSTRIAL SOCKET-8 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
140 TYPICALLY INDUSTRIAL SOCKET-9 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
141 250A BBT-6 AL. AIR INSULATED TYPICALLY INDUSTRIAL SOCKET-10 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
142 BBT (GRID-41 TO 22 & GRID B-B1) TYPICALLY INDUSTRIAL SOCKET-11 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
143 TYPICALLY INDUSTRIAL SOCKET-12 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
144 TYPICALLY INDUSTRIAL SOCKET-13 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
145 TYPICALLY INDUSTRIAL SOCKET-14 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
146 TYPICALLY INDUSTRIAL SOCKET-15 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
147 TYPICALLY INDUSTRIAL SOCKET-16 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
148 TYPICALLY INDUSTRIAL SOCKET-17 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
149 TYPICALLY INDUSTRIAL SOCKET-18 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
150 TYPICALLY INDUSTRIAL SOCKET-19 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
151 TYPICALLY INDUSTRIAL SOCKET-20 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
152 TYPICALLY INDUSTRIAL SOCKET-1 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
153 TYPICALLY INDUSTRIAL SOCKET-2 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
154 TYPICALLY INDUSTRIAL SOCKET-3 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
155 TYPICALLY INDUSTRIAL SOCKET-4 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
156 TYPICALLY INDUSTRIAL SOCKET-5 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
157 TYPICALLY INDUSTRIAL SOCKET-6 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
158 TYPICALLY INDUSTRIAL SOCKET-7 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
159 TYPICALLY INDUSTRIAL SOCKET-8 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
160 TYPICALLY INDUSTRIAL SOCKET-9 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
161 250A BBT-7AL. AIR INSULATED TYPICALLY INDUSTRIAL SOCKET-10 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
162 BBT (GRID-41 TO 22 & GRID A) TYPICALLY INDUSTRIAL SOCKET-11 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
163 TYPICALLY INDUSTRIAL SOCKET-12 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
164 TYPICALLY INDUSTRIAL SOCKET-13 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
165 TYPICALLY INDUSTRIAL SOCKET-14 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
166 TYPICALLY INDUSTRIAL SOCKET-15 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
167 TYPICALLY INDUSTRIAL SOCKET-16 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
168 TYPICALLY INDUSTRIAL SOCKET-17 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
169 TYPICALLY INDUSTRIAL SOCKET-18 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
170 TYPICALLY INDUSTRIAL SOCKET-19 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
171 TYPICALLY INDUSTRIAL SOCKET-20 15.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 26.1 2.40 0.23 0.94 15 2
172 LIGHTING BUS WAY-4 15.0 4 10 CU.ARM. 62 72 0.8 15 1 49.6 26.1 3.81 0.36 1.49 15 2
173 LIGHTING BUS WAY-5 3.0 4 10 CU.ARM. 62 72 0.8 125 1 49.6 5.2 3.81 0.60 2.48 125 2
174 LIGHTING BUS WAY-6 3.0 4 10 CU.ARM. 62 72 0.8 145 1 49.6 5.2 3.81 0.69 2.88 145 2
175 LIGHTING BUS WAY-7 3.0 4 10 CU.ARM. 62 72 0.8 165 1 49.6 5.2 3.81 0.79 3.28 165 2
176 LDB-03 INSPECTION PIT-3 3.0 4 10 CU.ARM. 62 72 0.8 85 1 49.6 5.2 3.81 0.41 1.69 85 2
177 LDB-04 JACK PIT-2 3.0 4 6 CU.ARM. 40 43 0.8 120 1 32.0 5.2 6.40 0.97 4.01 120 2
178 LDB-08 INSPECTION BAY LINE-1 3.0 4 6 CU.ARM. 40 43 0.8 110 1 32.0 5.2 6.40 0.89 3.67 110 2
179 LDB-09 INSPECTION BAY LINE-1 3.0 4 6 CU.ARM. 40 43 0.8 115 1 32.0 5.2 6.40 0.93 3.84 115 2
180 LDB-06 INSPECTION BAY LINE-2 3.0 4 6 CU.ARM. 40 43 0.8 110 1 32.0 5.2 6.40 0.89 3.67 110 2
32AMP INDUSTRIAL SOCKET FOR
SDB-1 L&P DB
181 BATTERY CHARGER FOR MOVEABLE 3.0 2 6 CU.ARM. 40 43 0.8 55 1 32.0 5.2 6.40 0.44 1.84 55 2
PLATFORM
32AMP INDUSTRIAL SOCKET FOR
182 BATTERY CHARGER FOR MOVEABLE 3.0 2 6 CU.ARM. 40 43 0.8 45 1 32.0 5.2 6.40 0.36 1.50 45 2
PLATFORM
40AMP INDUSTRIAL SOCKET FOR
183 BATEERY CHARGER FOR FORK 3.0 4 10 CU.ARM. 62 72 0.8 60 1 49.6 5.2 3.81 0.29 1.19 60 2
LIFTER 3T
40AMP INDUSTRIAL SOCKET FOR
184 BATEERY CHARGER FOR FORK 3.0 4 10 CU.ARM. 62 72 0.8 55 1 49.6 5.2 3.81 0.26 1.09 55 2
LIFTER 3T
185 AIR COMPRESSOR-1 500 CFM 70.0 4 150 CU.ARM. 294 255 0.8 15 1 235.2 121.7 0.48 0.21 0.88 15 2
MDB-3 (Air Compressor Room)
186 AIR COMPRESSOR-1 500 CFM 70.0 4 150 CU.ARM. 294 255 0.8 20 1 235.2 121.7 0.48 0.28 1.17 20 2
187 8-CAR PIT JACK SYSTEM 100.0 4 150 CU.ARM. 294 255 0.8 160 2 470.4 173.9 0.48 1.61 6.68 320 4
188 MDB-4 (Mechanical Equipment ) TANDOM PIT WHEEL LATHE 65.0 4 185 CU.ARM. 339 285 0.8 85 1 271.2 113.0 0.39 0.90 3.75 85 2
189 PORTAL WHEEL LATHE 40.0 4 95 CU.ARM. 221 200 0.8 60 1 176.8 69.6 0.72 0.72 3.00 60 2
190 LDB-1 GROUND FLOOR 5.0 4 6 CU.ARM. 40 43 0.8 15 2 64.0 8.7 6.40 0.10 0.42 30 4
191 LDB-2 GROUND FLOOR 5.0 4 6 CU.ARM. 40 43 0.8 20 1 32.0 8.7 6.40 0.27 1.11 20 2
192 PDB-1 GROUND FLOOR 10.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 17.4 2.40 0.15 0.63 15 2
193 PDB-2 GROUND FLOOR 10.0 4 16 CU.ARM. 70 78 0.8 20 1 56.0 17.4 2.40 0.20 0.83 20 2
194 ACDB-1 GROUND FLOOR 10.0 4 16 CU.ARM. 70 78 0.8 20 1 56.0 17.4 2.40 0.20 0.83 20 2
195 UPS-1- 10 kVA GROUND FLOOR 10.0 4 16 CU.ARM. 70 78 0.8 15 1 56.0 17.4 2.40 0.15 0.63 15 2
MDB-6 (L&P ROOM )
196 LDB-1 FIRST FLOOR 5.0 4 6 CU.ARM. 40 43 0.8 20 2 64.0 8.7 6.40 0.13 0.56 40 4
197 LDB-1 FIRST FLOOR 5.0 4 6 CU.ARM. 40 43 0.8 25 1 32.0 8.7 6.40 0.34 1.39 25 2
198 PDB-1 FIRST FLOOR 10.0 4 16 CU.ARM. 70 78 0.8 20 1 56.0 17.4 2.40 0.20 0.83 20 2
199 PDB-2 FIRST FLOOR 10.0 4 16 CU.ARM. 70 78 0.8 25 1 56.0 17.4 2.40 0.25 1.04 25 2
200 ACDB-1 GROUND FLOOR 10.0 4 16 CU.ARM. 70 78 0.8 25 1 56.0 17.4 2.40 0.25 1.04 25 2
201 UPS-1- 10 kVA FIRST FLOOR 10.0 4 16 CU.ARM. 70 78 0.8 20 1 56.0 17.4 2.40 0.20 0.83 20 2

Total End
Addition
S. No. Cable Size Cable Length Cable Say Terminati
al @ 10%
Length on

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

1 4Cx185 85 9 94 95 2
2 4Cx150 935 94 1029 1030 22
3 4Cx70 362 36 398 400 8
4 4Cx50 30 3 33 35 4
5 4Cx25 550 55 605 605 8
6 4Cx16 2130 213 2343 2345 284
7 4Cx10 855 86 941 945 22
8 4Cx6 845 85 930 930 28
9 2Cx6 330 33 363 365 12

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR
INVENTORY FOR FDA SYSTEM PA SYSTEM
SMOKE SMOKE HEAT HEAT
BEAM BEAM 2CX1.5SQMM 2CX1.5SQ 2CX2.5SQMM WALL
DETECT DETECT DETECT DETECT R.I. R.I. CEILING
S.No. DESCRIPTION DETECT RECIEVE CM MCP HOOTER FOR MM FOR FOR MOUNTED CABLE
OR OR OR OR BELOW ABOVE SPEAKER
OR R DETECTOR HOOTER REPEATER SPEAKER
BELOW ABOVE ABOVE BELOW

i. SHED

MAIN SHED (INSPECTION SHED, HEAVY


REPAIR SHED,WHEEL & BOGIE SHOP & 10 4 910 840
A. STORE WARD

TOTAL 2 0 0 0 0 0 0 0 0 10 4 910 840 0 0 0 0

ii. BUILDING AREA

A. OFFICE BUILDINGS

i. GROUND FLOOR
ALL FLOOR POINTS 30 0 2 2 2 350 120 21 0 252

ii. FIRST FLOOR


ALL FLOOR POINTS 32 2 2 2 380 130 21 0 315

TOTAL 62 0 0 0 0 0 0 0 4 4 4 730 250 0 42 0 567

TOTAL 64 0 0 0 0 0 0 0 4 14 8 1640 1090 0 42 0 567


CONT. 5% 6.4 0 0 0 0 0 0 0 0.4 1.4 0.8 164 109 0 4.2 0 56.7
GRAND TOTAL 70 0 0 0 0 0 0 0 4 15 9 1804 1199 0 46 0 624

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

OUTDOOR ENCLOUSER
S&T WORKS

BULLET CAMERA
4 PORT SWITCH

8 PORT SWITCH

DOME CAMERA
OUTDOOR WIFI
DATA OUTLET

PATCH CORD

PTZ CAMERA
VOICE POINT

24 PORT LIU
6 PORT LIU
42 U RACK

22 U RACK

15 U RACK

9 U RACK

6 U RACK
PANEL

PANEL
WIFI
S.No. DESCRIPTION
i. SHED

MAIN SHED (INSPECTION SHED, HEAVY


REPAIR SHED,WHEEL & BOGIE SHOP &
A. STORE WARD

1 MAIN SHED AREA 2 2 2 3 5 2 11 2

GRAND TOTAL 0 0 0 0 0 0 0 0 2 0 0 2 0 0 2 3 5 2 11 2

ii. BUILDINGS

A. OFFICE BUILDING

1 GROUND FLOOR 40 41 3 0 0 0 0 0 6 0 8 14 0 168 1 1 1 0 2 0

2 MEZZANINE FLOOR 34 42 3 0 0 0 0 0 6 0 8 14 0 168 1 1 1 0 2 0

TOTAL 74 83 6 0 0 0 0 0 12 0 16 28 0 336 2 2 2 0 4 0

B. TOILET BLOCK

1 MALE TOI
2 FEMALE TOI
3 COMMON AREA

TOTAL 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

C. SUBSTATION (ESS)

TOTAL 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

D. PUMP ROOM

TOTAL 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

TOTAL 74 83 6 0 0 0 0 0 14 0 16 30 0 336 4 5 7 2 15 2
CONT. 5% 7.4 8.3 0.6 0 0 0 0 0 1.4 0 1.6 3 0 33.6 0.4 0.5 0.7 0.2 1.5 0.2
OVERALL GRAND TOTAL 81 91 7 0 0 0 0 0 15 0 18 33 0 370 4 6 8 2 17 2

ELECTRICAL TENDER
VANDE BHARAT COACHING COMPLEX AT SHALIMAR

HVAC WORKS

S.No. DESCRIPTION Hi-Wall Split Unit

1.5 TR

2.0 TR
i. SHED

MAIN SHED (INSPECTION SHED, HEAVY


REPAIR SHED,WHEEL & BOGIE SHOP &
A. STORE WARD

1 MAIN SHED AREA

TOTAL

ii. BUILDINGS

A. OFFICE BUILDING

1 GROUND FLOOR 4 6

2 FIRST FLOOR 4 6

TOTAL 8 12

B. TOILET BLOCK
1 MALE TOI
2 FEMALE TOI
3 COMMON AREA

TOTAL

C. SUBSTATION (ESS)

TOTAL

D. PUMP ROOM

TOTAL

TOTAL 8 12
CONT. 0.0% 0 0
OVERALL GRAND TOTAL 8 12