100kW/125kW-2.
5MW
C&I ESS Solution
Fast & Reliable Switching Efficient PV Integration
Seamless Switching: STS module can switch Wide MPPT range: 1000 V PV system with
between on-grid, off-grid, and diesel modes 180–850 V MPPT window.
in <20ms. High PV input: 200 kWp max via 8 MPPT
Independent High-Power Paths: Diesel, load, channels, 40 A per MPPT.
and grid connections support 500kw.
Rugged & Reliable Advanced Energy Storage
IP65 protection: PCS & MPPT modules are IP65-rated. Smart balancing: Independent BMS
Peak power support: Handles surges up to 170%. optimizes charge distribution and extends
LFP battery (BOS-B): Robust build enhances overall battery life.
system reliability.
Intelligent Control High Performance & Scalability
Integrated EMS: Supports zero-export and Powerful capacity: 100/125 kW per PCS,
time-of-use charge/discharge. scalable up to 2.5 MW.
Easy management: Color touchscreen with High efficiency: PCS 98.5%, MPPT >99%.
local control and remote cloud adjustments.
*Preliminary model, specifications are subject to change at later stage.
100kW/125kW-2.5MW C&I ESS Solution
STS MODULE
Smoothly switch between on-grid, off-grid, and diesel generator modes with a switching time of less than 20ms. Each diesel,
load, and grid connection is independent, with each path supporting 500kW. One STS module can connect to five 100kW PCS
modules or four 125kW PCS modules.
STS Module (500kW)
Switching capacity of 500kW.
Enablessmooth switching betweenon-grid, GEN Port
off-grid, and diesel generator modes.
Load Port
Switching time of less than 20ms.
Grid Port
PCS Connection Point
STS AC Parallel Port
MPPT MODULE & PCS MODULE
MPPT Module (8 MPP Trackers) CAN/RS485
PV Input 8 MPPT
Maximum 200kWp PV module connection with
8 MPPT channels, 40A per MPP
PCS Module (100kW/125kW)
DC Port
175A/200A charge and discharge current.
Maximum efficiency of 98.5%.
System rated power up to 2.5MW.
Supports instantaneous peak power up to 170%
of rated power.
Integrates zero-export and time-of-use control Battery Port
functions.
Eliminating the need for additional EMS. CT/Meter/BMS/
MPPT/Parallel
Data Logger
AC Output
*Preliminary model, specifications are subject to change at later stage.
Battery Pack Accessories
MODEL INV-B-PDU-2
Operating Voltage 200 ~ 1000 VDC
Nominal Charge/Discharge Current 168 A
Operating Temperature -20°C to +60°C
Ingress Protection Ip20
AC Input Rating 220 V AC ±10%, 2 A
Details 788.6 × 526 × 167.2 mm (W × H × D)32 kg
COMM3: Connect to auxiliary power input AC 200–240V, 3A, 50–60Hz.
HV light indicator COMM1: Emergency power-off triggers the interface.
ALRM light indicator
START COMM2: Communication with the first battery module, provides 12VDC
Display screen PCS1+
PCS2+ power for the first module.
Ethernet B+ B- PCS1-
Bluetooth: Mobile APP connects to data acquisition rod of the energy
PCS2-
storage system.
B+: Battery common positive connection (orange).
B-: Battery common negative connection (black).
USB
Display screen: Shows SOC (State of Charge) and fault codes.
Bluetooth
START: Start switch for 12VDC inside the high-voltage control box.
HV light indicator: High-voltage hazard indicator (yellow).
PCS
COMM2 ALRM light indicator: Battery system fault alarm indicator (red).
COM IN COM OUT COM
Breaker COMM1
PCS1+: First PCS positive connection (orange).
PCS2+: Second PCS positive connection (orange).
PCS1-: First PCS negative connection (black).
Ethernet: Features not yet developed.
PCS2-: Second PCS negative connection (black).
PCS COM: Battery communication terminal for outputting battery
USB: BMS upgrade port and storage expansion port.
information to the inverter.
IN COM: Connection with previous BOS-B-PDU-2 communication OUT COM.
OUT COM: Connection with next BOS-B-PDU-2 communication IN COM.
Breaker: Manually controls the connection between the battery rack and
external devices.
*Preliminary model, specifications are subject to change at later stage.
100kW-2.5MW C&I ESS Solution
MPPT MODULE INV-MPPT-L01-EU-AM8
PV String Input Data
Max. PV Input Power (kW) 200
Max. PV Input Voltage (V) 1000
Start-up Voltage (V) 200
MPPT Voltage Range (V) 180-850
Full Load MPPT Voltage Range (V) 480-850
Rated PV Input Voltage (V) 600
Max. Operating PV Input Current (A) 600 40+40+40+40+40+40+40+40
Max. Input Short-Circuit Current (A) A 60+60+60+60+60+60+60+60 A
No. of MPPT Trackers 8
Efficiency
Max. Efficiency >99%
MPPT Efficiency >99.9%
Equipment Protection
DC input reverse protection YES
DC ARC protection Optional
Anti-PID (Potential Induced Degradation) Optional
DC Switch YES
Surge Protection Level TYPE I
General Data
Ingress Protection (IP) Rating IP65
Over Voltage Category OVC II
Cabinet Size (W×H×D) mm 543 × 198 × 700
Weight (kg) 41.75 kg
Type of Cooling Intelligent air cooling I
Safety EMC/Standard EC/EN 62109-1
STS MODULE INV-STS500L
Grid/PCS Side Data
Rated AC Input/Output Active Power (kW) 500
Rated AC Input/Output Current (A) 758/725
Rated Input/Output Voltage (V) 220/380, 230/400 (three phase)
Grid Connection Form 3L/N/PE
Rated Input/Output Grid Frequency 50Hz/60Hz
Load Side Data
Rated Output Active Power (kW) 500
Rated Output Current (A) 758/725
Rated Output Voltage (V) 220/380, 230/400 (three phase)
Grid Connection Form 3L/N/PE
Rated Output Grid Frequency 50Hz/60Hz
GEN Side Data
Rated AC Input Active Power (kW) 500
Rated AC Input Current (A) 758/725
Rated Input Voltage (V) 220/380, 230/400 (three phase)
Grid Connection Form 3L/N/PE
Rated Input Grid Frequency 50Hz/60Hz
General Data
Off grid switching time <20ms
Ingress Protection (IP) Rating Ip20
Over Voltage category OVC III
*Preliminary model, specifications are subject to change at later stage.
100kW-2.5MW C&I ESS Solution
Cabinet Size[W×H×D] (mm) 543x575x671
Weight (kg) 108
Type Of Cooling Natural Cooling
Safety EMC/Standard IEC/EN 61439-1/-2
PCS MODEL INV-100K-PCSL01HP3 INV-125K-PCSL01HP3
Battery Data
Battery Type Lithium-ion
Battery Voltage Range (V) 630-1000
Max. Charging Current (A) 175 200
Max. Discharging Current (A) 175 200
Charging Strategy for Li-ion Battery Self-adaption to BMS
Number of Battery Input 1
AC Input/Output Data
Rated AC Input/Output Active Power (kW) 100 125
Max. AC Input/Output Apparent Power (kVA) 110 125
Rated AC Input/Output Current (A) 151.6 / 145 189.4 / 181.2
Max. AC Input/Output Current (A) 166.7 / 159.5 189.4 / 181.2
Rated Input/Output Voltage/Range (V) 220/380, 230/400 0.85Un–1.1Un
Grid Connection Form 3L+N+PE
Rated Input/Output Grid Frequency/Range 50Hz / 45Hz–55Hz 60Hz / 55Hz–65Hz
Power Factor Adjustment Range -1 ~ 1
Total Current Harmonic Distortion THDi <3% (of nominal power)
DC Injection Current <0.5% In
Efficiency
Max. Efficiency 98.5%
Euro Efficiency 97.8%
MPPT Efficiency >99%
Equipment Protection
Integrated AC Output Overcurrent Protection, AC Output Overvoltage Protection,
AC Output Short Circuit Protection, Thermal Protection,Anti-islanding Protection,
Surge Protection Level TYPE II (DC), TYPE II (AC)
Interface
LCD/LED display LCD
Communication Interface WIFI, RS485, CAN, Meter
General Data
Operating Temperature Range (℃) -25°C to +60°C, >45°C Derating
Permissible Ambient Humidity 0–95%
Permissible Altitude 4000m
Noise <75dB
Ingress Protection (IP) Rating IP 65 (PCS Module)
Cabinet Size[W×H×D] (mm) 543×310×775
Weight (kg) 70.3kg
Inverter Topology Non-Isolated
Over Voltage Category OVC II (DC), OVC III (AC)
Type of Cooling Intelligent Air Cooling
Warranty 5 Years / 10 Years
the Warranty Period Depends the Final Installation Site of Inverter, More Info Please
Refer to Warranty Policy
Grid Regulation IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie
R25, G99, VDE-AR-N 4105
Safety/EMC Standard IEC/EN 62477-1
*Preliminary model, specifications are subject to change at later stage.
Typical Application Scenarios
One PCS can support up to 16 racks of batteries in parallel
Battery Stack 1
PCS 1
Battery Rack1 -------------------------------------------------------------------------------------------------Battery Rack n
Battery Stack 2
PCS 2 STS
Battery Rack 1 ----------------------------------------------------------------------------------------------- Battery Rack n
......
Battery Stack n*
PCS n*
Battery Rack 1 ----------------------------------------------------------------------------------------------- Battery Rack n
*For 100kW PCS: n ≤5; for 125kW PCS: n ≤ 4
One STS module can connect to five 100kW PCS modules or four 125kW PCS modules for parallel operation
5X100kW PCS Solution 5×100kW PCS Solution 5×100kW PCS Solution 4X125kW PCS Solution
MPPT 1 MPPT 2 MPPT 3 MPPT 4
MPPT 1
STS
PCS 1
MPPT 2 MPPT 4
STS PCS 1 PCS 2 PCS 3 PCS 4
4
PCS 2 PCS 4
4×125kW PCS Solution
MPPT 3 MPPT 5
PCS 3 PCS 5
1 2 3 5
Up to five STS modules can be paralleled to form a 2.5MW system
Battery Rack
Meter/CT GRID
STS
Loads
MPPT
PCS
GEN
PV
AC DC
*Preliminary model, specifications are subject to change at later stage.