A
Paper on
CONSTANT
IMPEDANCE,
CURRENT, POWER- ZIP
LOADS
By
G. SARAVANAN
31st August 2025
ZIP Loads
Types of Loads in Power System are as
1 Constant Impedance Load (Z)
2 Constant Current Load (I)
3 Constant Power Load (P)
1 Constant Imp,Current,Power Loads (ZIP)
Example
Grid Voltage 11 KV
Transformer Rating 2.5 MVA
HV Voltage 11 KV
LV Voltage 0.433 KV
HV Current 131.216 A
LV Current 3333.431 A
A Transformer HV side Power Factor calculation
P 988.7 KW
Q 790.3 KVAR
Tanphi=Q/P
Tanphi 0.799332457
Cosphi 0.781123
B Transformer LV side Power Factor calculation
P 982.1 KW
Q 750.8 KVAR
Tanphi=Q/P
Tanphi 0.764484268
Cosphi 0.794442
Constant Impedance Load
P : V^2
Z
Power is directly proportional to square of the voltage
Current is directly proportional to Voltage
Impedance is constant
Constant Current Load
P : VI
Power is directly proportional to voltage
Current is constant
Constant Power Load
P : VI
Power is constant
C Constant Impedance Load calculation
Lump5 Given Prated 365 KW
Qrated 341.7 KVAR
PF 0.73
Vrated 1 pu
Vactual 1.019 pu
To Find Pactual=Pr*(Vact/Vrated)^2
P 379.001765
Qactual=Qr*(Vact/Vrated)^2
Q 354.8079537
D Constant Current Load calculation
Lump6 Given Prated 425 KW
Qrated 263.4 KVAR
PF 0.85
Vrated 1 pu
Vactual 1.019 pu
To Find Pactual=Pr*(Vact/Vrated)
P 433.075
Qactual=Qr*(Vact/Vrated)
Q 268.4046
E Constant Power Load calculation
Motor2 Given Prated 170 KW
Srated 200 KVA
PF 0.8
FLA 295.6311619 A
Prated 170 KW
Qrated=sqrt3*Vrated*Irated*sinphi
Qrated 127.5
F Transformer LV current Calculation
Current Power factor
Costant Z load Lump5 708.8 A 0.73
Costant I load Lump6 695.6 A 0.85
Costant P load Motor2 290.1 A 0.8
Polar Format Rectangular format
Magnitude Angle
Lump5 708.8 43.1136 517.424+j484.427
Lump6 695.6 31.78833 591.26+j366.430
Motor2 290.1 36.86989 232.08+j174.06
Rectangular Total current 1340.764+j1024.917 A
Polar Total current 1687.632 37.39529 A
Transformer LV side current 1687.632 A
Power factor 0.794464
G Current Calculations for Different Loads
Z Constant Impedance Load
Current is directionally proportional to voltage
V=IZ
Lump-5 Irated : 695.6 A
Vrated : 1 pu
Vactual : 1.019 pu
Iactual=Irated*(Vactual/Vrated)
Iactual : 708.8164 A
I Constant Current Load
Lump-6 Current is constant
Irated : 696 A
P Constant Power Load
P=VI
Current is Inversely proportional to voltage
Motor-2 Irated : 295.6 A
Vrated : 1 pu
Vactual : 1.019 pu
Iactual=Irated*(Vrated/Vacual)
Iactual : 290.0883219 A