LOAD CALCULATION
Solar panel
Width of the solar panel 2.28 m
Breadth of the solar panel 1.13 m
Weight of solar panel 34 kg
Conversion 0.00981
Load due to Solar panel 0.33 KN
No.of solar panels 6
Total load 0.77 kN/m²
Bay spacing 3.1 m
Purlins
No.of Purlins 4
Weight of the purlin 13.41 kg
Conversion 0.00981
Bay spacing 3.1 m
Dead load of Purlins 0.13 KN
Length of the rafter 4.79 m
DEAD LOAD (IS 875 - 1)
Loads
Solar panel 2.40 kN/m
Purlin 0.34 kN/m
Connections and sag rods 0.41 kN/m
(15% of total dead load )
Total 3.15 kN/m
Total load acting on rafter 3.15 kN/m
Total load acting on purlin 2.40 kN/m
WIND LOAD CALCULATION
(IS 875 Part 3)
Given
Location Thoothukudi
Basic wind speed 39 m/s
Calculations
Deisgn Wind speed, Vz Vp.K1.K2.K3.K4
K1 1
K2 1.05
K3 1
K4 1
Vz 40.95 m/s
Wind pressure, Pz 0.6Vz²
Pz 1.006142 KN/m²
Design Wind pressure, Pd Kd.Ka.Kc.Pz
Kd 0.9
Ka 1
Kc 0.9 Check
> 0.7Pz
Pd 0.81497462 KN/m² > 0.704299
Pd 0.81497462
Internal pressure on roof, Cpi ±0.7
Opening area > 20 %
At 0° Cpi 0.7
-0.9
-0.9
0.7
0.7
At 0° Wind load at roof, F Cp.A.Pd (+0.7)
Bay spacing 3.1
Cp F
-1.6 -4.0422741 KN/m
-1.6 -4.0422741 KN/m
At 90° Cpi 0.7
-1.3
-1.3
0.7
0.7
At 90° Wind load at roof, F Cp.A.Pd (+0.7)
Bay spacing
Cp F
-2 -5.052843 KN/m
-2 -5.052843 KN/m
Wind load on mono column of C Section (See table 29 IS 875 part 3 2015, Pg.No.41)
Degree(°) Cf F
0 + 2.05 5.1792 KN/m
- 2.05 -5.179164 KN/m
90 + 0.6 1.5159 KN/m
- 0.6 -1.515853 KN/m
At 0° Cpi -0.7
-0.9
-0.9
-0.7
-0.7
At 0° Wind load at roof, F Cp.A.Pd (-0.7)
m
Cp F
-0.2 -0.505284 KN/m
-0.2 -0.505284 KN/m
At 90° Cpi -0.7
-1.3
-1.3
-0.7
-0.7
At 90° Wind load at roof, F Cp.A.Pd (-0.7)
3.1 m
Cp F
-0.6 -1.515853 KN/m
-0.6 -1.515853 KN/m
part 3 2015, Pg.No.41)
Surface Roughness C
Exposure C
Kd 0.85