SCA Installation 030701
SCA Installation 030701
Menen version
SCA
Gas-Fired, Balanced-Flue or Power-Vented Unit Heater
INSTRUCTION DOCUMENT
Please read this document carefully before commencing installation commissioning and/or
servicing.
Leave it with the user or attached to the appliance or gas service meter after installation.
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause
property damage, injury, or death. All work must be carried out by appropriately quali-
fied persons.
Subject to modifications
Ambi-Rad Limited, Fens Pool Avenue, Brierley Hill, West Midlands DY5 1QA (United Kingdom)
Tel : 01384 489700 fax : 01384 489707
Table of Contents
0307SCA0AMEN 2/26
1.2 Warranty
a) Model SCA heaters are installed in atmospheres b)The installation is not in accordance with these instructions.
containing flammable vapors or atmospheres containing
chlorinated or halogenated hydrocarbons or atmospheres c) Axial fan-type unit heater is connected to a duct system or
containing any silicone, aluminum oxide, etc., that fitted with a non-AmbiRad authorized air distribution
adheres to spark ignition flame sensing probes. device.
2.1 Specifications
Model Heat input Heat output Max. air Gas rate 3 Power Running Fuse size
volume Consumption Amps
G20 G30 G31
1 2
kW gros kW net kW m³/h m³/h kg/h kg/h kW A
45 13.20 11.91 10.80 1008 1.26 0.96 0.94 0.16 0.61 2AF
250 17.60 15.85 14.50 1550 1.68 1.28 1.26 0.17 1.00 2AF
75 22.00 19.81 18.00 1700 2.10 1.61 1.57 0.20 1.29 2AF
100 29.30 26.38 24.00 2500 2.80 2.14 2.09 0.33 1.90 2AF
125 36.60 33.00 29.80 3225 3.49 2.67 2.61 0.33 2.00 2AF
150 44.00 39.60 35.80 4500 4.20 3.21 3.14 0.42 2.05 2AF
200 56.60 51.00 46.40 5050 5.40 4.13 4.04 0.45 2.12 2AF
250 73.30 66.00 60.00 7775 6.99 5.35 5.23 0.73 3.30 2AF
300 87.90 79.15 72.00 7625 8.39 6.42 6.28 0.76 3.39 2AF
Notes to table 1:
1. GCV (Hs)
2. NCV (Hi)
3. Natural gas G20 calorific value 10,48 kW m3 @ 15 °C, 1013,25 mbar
Butane gas G30 calorific value 13,7 kW/kg
Propane gas G31 calorific vale 14,0 kW/kg
0307SCA0AMEN 3/26
Table 2A: Injector size and burner pressure
G20 natural gas - inlet pressure = 17.5 mbar for UK
20.0 mbar for IE
0307SCA0AMEN 4/26
2.2 Dimensions – Figure 1A
0307SCA0AMEN 5/26
Figure 1B
0307SCA0AMEN 6/26
3.0 GENERAL REQUIREMENTS circulation can be maintained.
Where air heaters are located in the center of the space to be
3.1 Related documents heated, the air should be discharged toward outside walls. In
large areas, they should be located to discharge air along
It is important that all gas appliances are installed in accordance outside walls with additional heaters provided to blow air into
with the rules in force and by appropriately qualified persons. the center of the area.
Failure to install appliances correctly could lead to prosecution. In places where infiltration of cold is excessive, such as
It is in your own interest and that of safety to ensure entrance doors it is desirable to locate a heater so that warm air
compliance with the law. is discharged directly toward the source of cold air from a
CAUTION:Air heaters should not be installed in corrosive distance of 4,5 - 6,0 meters.
atmospheres, i.e. near plating or de- CAUTION: Do not locate the air heater where it may be
greasing plants or in areas where there is a fire risk. exposed to water spry, rain, etc.
3.2 Heater location 3.3 Combustion air supply & flue system
0307SCA0AMEN 7/26
3.3.1 Flues for power vented installations 3.3.2 Combustion air inlet pipe & flue pipe for balanced
(Type B appliances) flue installation (Type C appliances)
If the air heater is to be installed as a type B appliance, air for Balanced flue air heaters are designed to be fitted with a
combustion will be taken from within the space where the combustion air inlet duct that obtains outdoor air and a flue
heater is installed. Ensure that an adequate air supply for pipe that exhausts flue products to outdoors.
combustion and ventilation is provided within the building in
accordance with the regulations & rules in force. Air heaters if fitted with a power venter permitting either a
vertical or horizontal combustion air inlet/flue pipe system. The
heaters must be installed with a concentric vertical or
Table 5 shows flue pipe sizes and maximum vent lengths. The horizontal flue/air inlet. The heaters are only approved for
minimum flue length is 0.5 metres. use when installed with the appropriate approved
concentric vent terminal. See table 6.
Table 5 Flue pipe diameters & maximum lengths Both the flue and combustion air pipes must be sealed. Use
75,100, 150,200,
gasket sealed seamless aluminium pipe or equivalent.
SCA 45,60, 125 250,300 The flue pipe must include a re-sealable test port to allow good
average sampling of the flue gas mixture for testing, the port
Heater socket & mm 80 100 130
pipe f must be at least 450 mm away from the air heater flue
connection socket.
Maximum straight m 9
length
Follow any flue pipe manufacturers installation instructions for
Equivalent length m 0.75 making joints, including connections to the air heater, for
of 45° elbow passing through a building element and for support
Equivalent length m 1.5 requirements. If more than one air heater is being installed in
of 90? elbow the same place each heater must have a separate flue system.
0307SCA0AMEN 8/26
Table 6
Combustion air inlet & flue pipe requirements
Inlet pipe 9 9 9
Concentric vertical vent or wall terminal: types : Mugro/Burfix dia80 - Mugro/Burfix dia100 - Mugro/Burfix dia130
Concentric horizontal vent or roof terminal: types : Mugro/Burfix dia80 - Mugro/Burfix dia100 - Mugro/Burfix dia130
It is important to ensure that there is an adequate air supply at Figure 2c : Combustion air and flue pipe sockets
all times for both combustion and heating requirements. Type B
Modern constructions involve the greater use of insulation,
improved vapour barriers, and weather proofing. This practice
means that buildings are sealed much tighter than in the past.
The combustion air supply for a power vented gas fired air
heater (Type B installation) can be affected by lack of air
supply. Natural infiltration may not be adequate. Use of extract
fans aggravates this situation. It is important to ensure that there
is an adequate air supply at all times. Reliance on doors and
windows is not allowed. Always ensure that an adequate inlet
for fresh air for combustion is provided sized to suit the total
installation of any combustion apparatus.
Legend :
Fit an access guard to the combustion air inlet on the back of
the heater and take appropriate action to ensure that it remains ¬combustion products flue outlet socket
unblocked. See figure 2c.
-combustion air inlet opening
WARNING: This model air heater is installed as a type B
®Protection grill (option)
application and is designed to take air for combustion from SCA 45/60 : PN 08 17512 01
the space in which it is installed. Do not restrict the SCA 75→125 : PN 02 250090
combustion air intake. SCA 150→300 : PN 02 25094
0307SCA0AMEN 9/26
3.5 Air distribution 4.0 INSTALLATION
Follow recommended practice for building air distribution.
The following notes are of particular importance: 4.1 Unpacking and preparation
"Where free blowing air heaters are installed it must be taken Prior to dispatch, the air heater was operated and tested at the
into account that heated air is buoyant when it leaves the factory. If the heater has incurred any damage in shipment, file
appliance, therefore, air patterns within the space being heated a report claim within 2 working days from receipt.
will modify the air throw pattern achieved. Check the shipping label and data plate to ensure the
In building having low heat loss where single heaters are specification of gas and electrical supplies are compatible. Read
required to cover a large floor area and in buildings with high this document and become familiar with the installation
ceiling heights, air re-circulation fans e.g. AmbiRad Maximizors requirements and the appliance before commencing installation.
may be fitted to ensure even heat distribution and minimize
stratification. Care should be taken to avoid impeding air flow
with storage racking, partitions, etc." 4.2 Suspending the air heater
The electrical connection to the air heater is at the back of the When the heater is lifted for suspension, support the bottom of
appliance. the final connection must be made in the terminals the heater with plywood or other appropriately place material.
provided in the control compartment. Follow the wiring If the bottom is not supported, damage could occur.
diagram provided with the air heater.
Electrical supply cable conductor size should be 1.5 mm. Fit The heater is supplied with four point suspension. All points
the cord grip supplied with the heater. The length of conductors must be used. Two threaded nut retainers are provided on each
between the cord grip and the terminals must be such that in the side of the top of the heater. See dimensions in section 2.2 and
event that the cable becomes taut the line conductors do so figure 3.
before the earth conductor.
Figure 3 Suspension detail
The gas meter and gas service must be checked by the supply
undertaking to ensure that they are adequate to deal with the
total load of all gas fired apparatus installed.
Be sure that the threaded hanger rods are locked to the heater as
illustrated. Recommended maximum hanger rod length is 1.8m.
0307SCA0AMEN 10/26
IMPORTANT: Figure 4
Suspend the heater from the threaded nut retainers. Do not
suspend from the heater cabinet panels.
Do not place or add additional weight to the suspended air
heater. See hazard levels, page 2.
The heater must be installed in a level plane to ensure
proper operation.
0307SCA0AMEN 11/26
Air heaters suspended by flexible suspension materials or drop The minimum external controls required for the air heater are a
rods must be connected to the gas supply using an approved room thermostat. It is essential the main input line and
flexible connector. Sufficient slack must be provided in the neutral to terminals L and N remains live at all times even
connection to allow for movement of the appliance. Use a when the appliance is switch off this is to ensure correct
flexible connector of suitable size to reduce the pressure drop operation of the unit.
and the possibility of gas flow noise.
An indicator light and burner reset button are fitted inside the
CAUTION: Do not use the appliance gas supply to balance or appliance. To add a remote reset button, make connections to
support any part of the appliance. the terminals in the electric box as indicated on the wiring
diagram.
Figure 6
IMPORTANT: If the reset button requires activating for
any reason the cause should be identified before resetting.
After resetting stay with the appliance for long enough to
ensure that lock-out does not reoccur (suggest 5 minutes).
Fix all electric cables and installer’s wiring to the gas pipe
and ensure they do not touch the combustion collector box.
0307SCA0AMEN 12/26
6.0 COMMISSIONING & TESTING meter must be inspected, tested for soundness and purged in
accordance with appropriate requirements by a qualified
The commissioning and testing may only be carried out by person.
appropriately qualified persons.
This section should be read and fully understood before CAUTION: Never use a flame for checking gas soundness.
commencing commissioning and testing.
* Ensure that all cables & installer’s wiring are fixed to the 6.4 Lighting the air heater
gas pipe & that they do not touch the combustion
collector box SCA air heaters are all fitted with automatic spark ignition
* Check that all wiring is connected in accordance with the systems. When adequate airflow for combustion is proven by
appliance circuit diagram; an air proving control and a pre-purge period has elapsed, the
* Ascertain that the correct fuse value and cable size has integral ignitor and multi-functional gas control operate. The
been provided; ignition spark ignites the gas creating the burner flame which is
* Check to ensure that the appliance is earthed by detected by a flame rod sensor. If a burner flame is not
conducting an earth continuity test. Connect a test meter, detected, the ignition controller proceeds to lock-out and
one lead to the appliance earth terminal and the other to requires manually resetting. Lock-out is indicated by the red
the mains incoming earth point at the electrical isolator. A warning light on the air heater.
resistance reading of 1,0 ohm or less must be indicated. If NOTE: If the first reset is not successful, wait 15 seconds
a higher reading is obtained, check all cable connections before attempting reset.
to ensure adequate security and cleanliness. If problem
still exists , it may be necessary to consult the electricity
supply undertaking; 6.4.1 To turn the air heater "ON"
* Carry out a polarity test. Connect one lead of a suitable The following checks should be carried out before attempting
AC voltmeter to earth and connect the other lead to the to light the air heater.
live supply terminal (L) at the air heater. Switch ON the
power to the air heater and check for correct voltage. * Ensure that the gas supply to the air heater is turned ON;
The same result should be obtained by connecting the test * Ensure that the electrical supply to the air heater is switched
leads between live and neutral. ON;
Connect the voltmeter test leads to N and E. A reading of * If fitted ensure that a time switch is set to an ON period
± 0V should be obtained. If these tests do not conform * Set room thermostat to call for heat. e.g. to above room
with the above, there is a fault which must be rectified ambient temperature. The burner will now light.
before proceeding further with the commissioning; The burners can be seen through the viewing port.
* Check that a suitable thermostat or control panel has been * Adjust the room thermostat to the required operating
fitted; comfort temperature. The air heater will now start
* Ensure that an electrical isolator with two pole separation automatically when heat is called for by the room
with a minimum air break between poles of 3,0 mm has thermostat.
been fitted adjacent to the air heater.
NOTE:
6.2 Gas connection If the air heater will not start on initial start-up, the ignition
controller may be in lock-out position and require resetting.
Only persons formally qualified to work on gas fired This may occur especially if the appliance has been on
apparatus may carry out commissioning and testing. stand-by for a prolonged period.
The whole of the gas service installation including the
0307SCA0AMEN 13/26
6.4.2 To turn the air heater "OFF" for short periods Figure 7a : SIT gasvalve
Adjust the room thermostat to its lowest setting or 'OFF'. The
fan will continue to run to cool the heater and then switch OFF
automatically.
0307SCA0AMEN 14/26
6.8 Air heater controls and operation Advise the appropriate person how to safely use and operate the
air heater and describe the use of appropriate external controls.
Check air heater operation after all adjustments have been Ensure that the person understands how to start the heater and
carried out. Set the temperature control above ambient how to turn it OFF.
temperature. Suggest that the instructions are placed close to the air heater
for future reference. In the absence of an appropriate location
SCA air heaters are fitted with a pressure sensitive, combustion fix them to the gas service meter. Ensure they are not placed
air safety control that monitors the combustion airflow. where they may restrict the airflow from the heater or where
The control operates with the settings given in table 10 (settings they may catch fire from a hot surface.
are for sea level installations)
Advise the person who is resuming responsibility that for
When the combustion air safety control closes, verifying continued safe operation the air heater should be serviced at
airflow, the gas control valve will open and the burner will least once a year.
light.
When insufficient airflow, the burner will extinguish until the
airflow returns to the acceptable level.
7.0 SERVICING INSTRUCTIONS
Wait approximately 30 seconds after the burner has lit, the time
delay relay will activate the thermal fan control which will IMPORTANT:
energize the fan motor. Continue to operate the air heater for Only appropriately qualified persons may carry out
several minutes to ensure correct operation. servicing and fault finding on this gas fired equipment.
Before commencing service ensure that both the gas and
Turn room thermostat to its lowest setting. The main burners the electricity are turned and switched "OFF" and that the
should extinguish while the fan continues to run to cool the air air heater has cooled down.
heater. The fan delay relay will normally be de-energized and Inadvertent substitution or replacement of components
stop the fan motor in approximately 45 seconds. similar to those specified or replacement in a manner
contrary to the method herein described could constitute a
Table 10 Combustion air pressure control settings hazard and lead to prosecution.
0307SCA0AMEN 15/26
7.1 Service procedure
The following procedures should be carried out at least Brush inside each heat exchanger tube until all foreign
annually: material has been removed. The use of a flashlight is
necessary to carry out this operation.
1. Remove the burner assembly as in section 8.1. Clean
thoroughly, (cleaning the burners requires an emery cloth, 3. Clean the axial fan blades, fan guard, and fan motor to
wire brush and a cleaning cloth -stubborn deposits on remove all external dirt . Check the security of the fan on
burners are best cleaned using "acetone" as a solvent). the motor. NOTE: Fan motors are lubricated for life and do
not require greasing.
* Check the condition of the ignitor and clean to remove all
deposits. Check the spark gap (3,0 mm). 4. Remove any dirt and/or grease that may have accumulated
* Check the sensor - clean as necessary. on the venter fan motor and its housing. NOTE: Venter fan
* Remove any soot deposits from the burner with a wire motors are lubricated for life and do not require greasing.
brush. Clean the ports with a degreaser or acetone. A
vacuum cleaner or compressed air may assist in this 5. The gas multi-functional control valve requires no field
cleaning operation. Wipe the inside of the burner tube maintenance except cleaning of it's exterior and checking
clean (cleaning thoroughly with a degreaser as the condition of the wire connections. Instructions for
recommended will retard future buildup of dirt). testing pressure are given in section 6.6.
Inspect the burner for any damage or deterioration. If the
burner is damaged or corroded, replace it. 6. Check the flue/combustion air system for soundness.
Reseal/replace any parts that are not sound.
2. The heat exchanger should remain clean unless a problem
has developed due to poor combustion. Examine the heat 7. Check all wiring connections. Check wiring for
exchanger tubes internally and externally for any sign of any signs of damage. Replace any suspect wiring
deterioration. The outside of the tubular heat exchanger can with an equivalent specification.
be cleaned from the front of the heater with an air jet and/or
a flexible brush. Remove any dust and grease deposits. 8. Check operation of thermal fan control and control relay.
The inner surfaces of the heat exchanger can be reached for 9. When service is complete carry out full commissioning
cleaning with the burner and combustion air fan (venter) procedure as per section 6 of this document.
assemblies removed. Clean with a flue brush or a heavy
wire to which wire wool has been attached.
8.1 Main burner removal 5. Remove gas supply pipe from multi-functional gas control
Instructions for burner removal (see figure 8): valve.
1. Turn OFF the gas supply to the air heater. 6. At the burner rack assembly, remove the nuts that secure
the burner manifold to the burner rack. Lift the burner
2. Switch OFF the electricity supply to the air heater.
rack/manifold assembly upward and pull the assembly out
of the air heater.
0307SCA0AMEN 16/26
Figure 8
Removing the burner rack/manifold assembly (for Instructions for re-assembly:
clarity, the heater cabinet & other parts are not illustrated)
1. Reverse the procedure for removal making sure that all
parts are installed correctly. Check that all components are
secure.
Remember!
After any service work has been carried out, the air heater must
be fully commissioned. See section 6 of this document
Figure 9
View of the Control Compartment
Legend :
1. Flame senor
2 LC1 limit control (without
reset)
3. Electrical wiring panel
4. Reset lockout signal lamp
5. Differential pressure switch
6. Burner control relay or
ignition controller
7. Flue gas extractor for
combustion products
8. Electrical connectors
9. Time delay relay
10 Fuseholder with fuse
11 Differential pressure point
12 Combination gas valve with
pressure regulation
13 Manifold & injectors
14 Ignition electrode
15 Relay K1.1 (not for UK/IE)
Relay K1.2 (not applicable on
SCA)
16 Relay main ventilator (not
applied on SCA)
17 Electronic net filter
18 LC3 max limit controller with
manual reset
19 3VA separation transformer
(not for UK/IE)
20 Fan control relay
21 Tube burner
0307SCA0AMEN 17/26
8.2 Burner injectors 8.4 Replacement of fan motor and/or fan blade
1. carry out steps 1 to 6 of section 8.1.
2. Unscrew the main burner injectors. Follow these instructions for the replacement of the
3. Re-fit new injectors. fan guard, fan motor or fan blade/s.
4. Re-assemble in reverse order. 1. If the air heater is installed, turn OFF the gas supply
to the air heater.
8.3 Ignition system 2. After the fan has stopped switch OFF the electricity
To access the ignition system, follow steps 1 to 3 in section 8.1. supply to the air heater.
3 Open the access panel and disconnect the wiring to
Ignitor (PN 03 400US 42)- refer to figure 9 and locate the ignitor (on the fan motor.
the side of the burner rack). Disconnect the wire, remove the screw and 4. Remove the complete fan assembly.
the ignitor. Clean with an emery cloth. 5. Dismantle and replace whatever part(s) are needed
Note: Spark gap must be maintained to 3.0 mm See and re-assemble.
figure 10a. 6. Ensure that the fan blade/s is in the correct position
Re-fit the ignitor as per figure 10b. on the shaft referring to the table and figure 11.
CAUTION: Due to high voltage on the spark wire and electrode, do
not touch when energised. See hazard levels. Fig. 11 Proper position of fan blade on motor
shaft
Flame sensor - Refer to figure 9 and locate the flame sensor.
Disconnect the wire, remove the screw and the flame sensor. Clean with
an emery cloth.
0307SCA0AMEN 18/26
4. Disconnect the gas service union between the control valve When replacing the capillary control be careful not to damage
and the gas service tap. Remove the gas control valve. the capillary tube by kinking. Make bends with a generous
5. Re-fit a replacement valve making all of the radius (± 25 mm). When replacing the disc type control never
required connections. manually attempt to operate the disc by pushing on the disc.
6 Carry out complete commissioning procedure prior to Doing so will alter the calibration and could be hazardous.
placing the appliance back into service as outlined in
section 6.0
8.7 Combustion air control/switch
CAUTION:
The gas control operating valve is the prime safety shut-off. If it is determined that the air differential pressure switch needs
All gas supply lines must be fee of dirt, scale, etc. before replacing, use only AmbiRad authorized replacements that are
connecting to the air heater thus ensuring positive closure of designed for the air heater being serviced. These switches are
the control valve. calibrated to operate at the designed combustion air flow duty
for each appliance size in the product range.
0307SCA0AMEN 19/26
9.0 FAULT FINDING
9.1 Main fault finding chart - Lock-out indicator light is "OFF", but air heater will not operate
WARNING: Fault finding may only be carried out by appropriately qualified persons
yes
yes Is power venting
Is there continuity operating?
between terminals 8 & 7
no
no yes
Reset limit control
Check electronic
ignition control Does the power venter yes Determine what caused the
operate? limit to trip
no
Is there a restriction in the
Is there 230V between no
flue pipe or inlet grill Place into normal operation
L&N?
yes no yes
Is there 230V between no
Check the mains
1&N?
Correct fault
yes
0307SCA0AMEN 19/26
9.2 Ignition Controller Lockout indicator Light Repeatedly Comes "ON"
WARNING: Fault finding may only be carried out by appropriately qualified persons
Is polarity of mains
correct?
no
Correct polarity
yes
no Does the inlet gas yes
correct the gas supply pressure agree with the
pressure data badge Wait 15" and press
reset button
Remove corrosion
& scale from flame
yes sensing rod & clean
ceramic insulation
Is there 220 to 240V
between terminals
check multi 5&N
functional
gas valve
no
Check electronic
ignition control
Check flame signal. Is it
greater than 1,0 micro yes Place in normal
Amps? operation
0307SCA0AMEN 21/26
9.3 Limit Control Fault Finding Chart (limit control trips)
WARNING: Fault finding may only be carried out by appropriately qualified persons
Note : SCA air heaters are equipped with 2 limits (a recycling limit and a manual reset limit). During normal operation, neither
limit should trip even if the main electric supply is interrupted during operation. In the event of motor failure, the recycling limit
will trip opening the gas valve.
no
Is there 220-240V at
Does the fan no terminals N and 3?
motor operate? yes
yes no
no
Does the fan control no
energize the fan motor Consult fan
in less than 75"? fault finding
yes
Does the limit trip
Check for excessive yes before the fan is
main burner pressur energized?
no
Place system in normal
operation
0307SCA0AMEN 22/26
9.4 Fan Fault Finding Chart
WARNING: Fault finding may only be carried out by appropriately qualified persons
Adjust thermostat
temperature
setting above ambient to
energize the fan and the
fan solenoid valve
Place the
Is there 220-240V Does the fan system in
no
at terminals N & 3? operate ? normal
no yes operation
0307SCA0AMEN 23/26
10.0 PARTS LISTING
Overheat control device LC1 T.O.D. 60T 11 201614 03 400US 01 170F out 130F in
Overheat cut off device LC3 T.O.D. 10H14 212557 03 400US 03 240F out reset
11.1 AmbiRad SCA air heaters are designed to operate on 11.4 Changes to carry out :
natural, propane or butane gas and will be supplied for types 45/60/75/100/125/150
fitted for the gas type ordered. In the event of site natural gas : SIT Tandem 830.040
conversion to a different gas type it is necessary to (PN 03 25250) - set pressure regulator as per
convert the gas burner and burner controls. table 2A
propane/butane : set pressure regulator on
maximum pressure and seal regulation screw
11.2 Affix new data plate and gas type over-sticker. for types 200/250/300
natural gas : use Honeywell VR4601A
(PN 03 25136) - set pressure regulator as per
11.3 Upon completion of conversion re-commission the air table 2A
heater in accordance with section 6 of this document. propane/butane : use Honeywell VR4601B
(PN 03 25136B) or VR 4601A + blocking plate
0307SCA0AMEN 24/26
12.0 USER INSTRUCTIONS
OPERATING
How the air heater works: b) check if thermal overheat control requires resetting
Gas is burned by an atmospheric burner which fires into a heat 7 If the thermal overheat control requires resetting and doing
exchanger. The gas burner is controlled by a double gas valve so restarts the air heater, wait until the appliance warms to
via an electronic burner control, which is actuated thermal equilibrium, to ensure the overheat control does not
automatically via external controls i.e. a room thermostat and/or lock out again. If it does and the temperature near the heater
a time switch. The burner is ignited by a spark igniter. When is less than 30°C, then switch off the appliance and call for
the burner fires and warms the heat exchanger, the heat is service. If the temperature is over 30°C, take appropriate
sensed by a thermally actuated fan control which switches on action to reduce the ambient temperature near the air heater.
the fan when the air temperature has reached its preset
operating level. Air circulation:
At the end of a heating cycle the burner is switched off, the air 1. The space heating process is for air to be circulated through
circulation fan will continue to run until the air heater has the appliance whereby it gains heat from a heat exchanger.
cooled to a safe condition. Thereafter the fan will remain off The air is directly discharged into the space to be heated.
until the next cycle is initiated. The air is eventually recirculated. Therefore it is very
important that an unobstructed path for the circulation of
Safety: the air will be maintained. This is particularly important if
1. Flame failure is detected by the ionisation probe the air heater has been installed to blow through the wall
which is the sensor and will immediately result in gas valve between two rooms.
shut down. 2. Sometimes the air circulation fan of the appliance is
2. Safety against overheating is assured by two overheat connected to a remote over-ride switch. This enables air to
controls. The first is an automatic recycle control which be used for circulation purposes when the air heater is not
protects against low air flow i.e. clogged air ways, fan used for heating purposes e.g. in summer.
failure etc. The second, which is set to a higher level than To use this feature:
the first one, is a control which locks out and switches off a) switch ON electricity
the burner in the event of gross overheating for any reason. b) switch ON manual override switch, this may be fitted as
Manual intervention is necessary to reset this control a feature on a remote composite control.
device. Resetting of the automatic burner control may also
be required. Maintenance:
3. The location of the air heater should be maintained at 1. Maintenance and service must only be carried out by
normal atmospheric pressure. Changes to the building after appropriately qualified persons e.g. "Corgi" registered
air heater installation, should have regard to the heating undertakings.
installation, i.e. structural changes causing excessive 2. It is in your interest to ensure proper service and
draughts from doors, windows etc. Other air handlers and maintenance is carried out at a regular basis. Periods
installation of air extraction equipment which may cause a between service are dependent upon the local environment
negative pressure environment, can seriously affect the where the heater is installed. All gas appliances should be
operation of this type of air heater, especially if combustion serviced at least once a year.
air supply is not ducted. 3. In case of any damage to the appliance, it must be shut
down completely and checked by an appropriately qualified
To light the heater: person.
1. Turn on the gas supply to the air heater. 4. In the event of difficulties in resolving any of these matters,
2. Switch on the electricity supply to the air heater. please do not hesitate to contact AmbiRad or their official
3. Ensure time switch (if fitted) is set to a 'ON' cycle. distributor.
4. Adjust control/room thermostat to desired temperature.
5. Air heater will light automatically when the room
thermostat calls for heat after about 30 sec. NEVER SWITCH OFF ELECTRICTY SUPPLY TO THE
6. If the appliance does not light: AIR HEATER WITHOUT FIRST CLOSING THE GAS
a) check that the burner control does not require resetting. TAP
An indicator light glows at the inside panel of the appliance
and on a remote control if fitted. Reset by pushing
reset/button inside the appliance or the remote control.
0307SCA0AMEN 25/26
13.0 HEALTH & SAFETY Precautions: Wear protective gloves when handling.
People with a history of skin complaints may be
STATEMENT susceptible to irritation.
Dust levels are only likely when the material is
13.1 General abraded.
Under the Consumer Protection Act 1987 and
Section 6 of the Health and Safety at Work Act
1974 we hereby provide the following information
on substances hazardous to health. In general normal handling and use for this purpose
Product range reference Euro.C Series air heaters. will not present discomfort. Follow good hygiene
practices, wash hands before
consuming food or using the toilet.
13.2 Cautionary note First Aid: Medical attention must be sought following
During first firing some smoking may occur,this is eye contact or prolonged reddening of the skin.
due to the burning off of protective/lubricating oils
used during appliance [Link] of this will
have been removed during the production testing 13.6 Thermostat.(Thermal overheat (limit) control LC3)
[Link] is a wise precaution to ensure that Material: Illuminating Kerosene.
adequate ventilation is provided during the initial Description: Sealed phial contains a small quantity in
firing and throughout the commissioning period,this liquid form.
is particulary important if the discharge air is to Recognition: Colourless liquid,paraffin oil/petroleum
blow into a confined space. This smoking does not hydrocarbon odour.
constitute a poison hazard. Characteristics: Non-corrosive, flammable with no
poisonous reference-CH poison Class 3
Precautions: Avoid handling. This product can
13.3 Declaration irritate and defat the skin. Prolonged contact may
AmbiRad products contain no asbestos; copper is cause dermatitis. Avoid breathing vapour. Avoid eye
not employed in gas carrying components; solder contact. Do not ingest.
which has a melting point below 450°C is not used; First Aid: Skin. Wash thoroughly with soap and
paints for corrosion protection and decoration are water.
heat cured and contain no lead. Eyes. Rinse immediately with copious amounts of
The above appliances meet the Electrical Safety clean water.
requirements of EN60 335 Pt 1 1988. Ingestion: Seek medical advice.
0307SCA0AMEN 26/26