Manual System MINIMAX Volume 1
Manual System MINIMAX Volume 1
Control panel
Operation manual
Index
Index ..........................................................................................................................................2
Index ..........................................................................................................................................3
Preface
1 Introduction............................................................................................................................5
2 Indicator signages..................................................................................................6
2.5 Fire extinguishing agent discharge in the area without electrical activation................................7
2.7 Extinction.......................................................................................................................8
2.9 Blocking
4.3 Restocking
5.2 Restocking
Preface
Dear Customer:
Having acquired the FMZ 4100 control panel for controlling protection against
fires, you have decided on a reliable, sensitive security system,
approved by the Association of Insurers of Goods and Equipment (VdS) that
stands out for the following characteristics of early warning in case of occurring a
fire: To put you on notice and, if desired, also to the firefighters,
activate programmed systems for alarm cases and put into operation the
fire extinguisher installation. The technology and engineering that support the systems
MINIMAX electronics are so advanced that it is highly unlikely that they
produce false alarms and incorrect reactions from this command system for the
fire extinguishing.
Finally, we must also point out that for technical security reasons you
must take all appropriate measures that contribute to minimizing the
dangers of unauthorized or improper use, as well as false alarms attributable to
magnitudes that can induce them (e.g. humidity, vapor, smoke, pollution
atmospheric, etc.).
1 Introducción
The fire extinguishing control panel includes all components for detection of
fires and the control of a firefighting installation. All detections are
visualized through light-emitting diodes on its own front panel, and
additionally on the LC display and through the collective luminous diodes of the
FMZ4100.
1. Continuous light;
2. Blinking LT1 (1/4 sec. on, 3/4 sec. off);
3. Blinking LT2 (3/4 sec. on, 1/4 sec. off);
The tables in chapter 6 include the standardized assignment of the LEDs to the
different modes of operation.
For the operation of the extinguishing control panel, its front panel includes eight
buttons. All operational processes are carried out through them,
except for the lamp test. However, there are certain operational processes, such as
e.g. the replacement of fire detectors, and in connection with it the enabling
from the main detector, or the replacement of a previous alarm, which can be carried out
also through the LCD operation panel or the fire operation panel.
2 Indicator signs
The LEDs on the front panel of the extinguishing control have been assigned a large number of
functions. This chapter aims to present the user with a clear exposition and
understandable from the indicator signs.
LEDs operate with two different blinking rates (LT1 and LT2) and with light.
continue. In this regard, it is possible to make, in general, the divisions
next:
∙Brief ignition (LT1): There is a fault (in case of red LED, a prior alarm);
Prolonged ignition (LT2): A fire, activation, or
acting
Continuous light: A deactivation is being signaled.
2.2 Deactivation
Deactivations are indicated by the status permanently
LED light for corresponding faults:
Group of detectors/LED: 1/H2 - 2/H4 - 3/H6 - 4/H8 - Detector manual/
H10; - in your case Manual detector/H20;
Command group/LED: 1/H11 - 2/H12 - 3/H13 - 4/H14;
Extinction delay: H18;
Second extinction or selection
of main and reserve operation: H20.
The command groups, the extinction delay, and the second extinction or selection
main and backup operation can be put out of service
only through the deactivation of the entire extinction zone.
The leaks of the extinguishing agent are indicated as failure (leak of the extinguishing agent)
through the blinking of the LED H16 with the cadence LT1.
2.7 Extinction
If a main fire alarm has been triggered (once verified the
configured dependencies) the extinction will begin by activating the groups of
remote control of those devices that require such activation immediately, that is to say
the par with the start of the warning time (e.g. CO control bottle, 2
alarm speaker to leave the premises, control distributor). During the time
The H15 LED will be permanently on as a warning indication.
After the alarm for leaving the premises has elapsed, the
extinguisher agent. During the extinguishing time, the LED H15 blinks with the cadence
LT1. Once the extinction time is over, the blinking cadence changes to LT2.
If the entry of the extinguishing agent into the area is monitored by a pressure switch
alarm, the corresponding confirmation notice will be produced and the LED H16 will be
blinking with the cadence LT2.
In case of acting outside the prior warning time, this situation will be
interpreted as false or erroneous performance (failure) and will remain on the LC display
reflected the message 'ERROR HANDLING OPERATION for CO2'. The LED H17
estará parpadeando con la cadencia LT1.
2.9 Blocking
If the fire extinguishing installation was blocked by the locking device, it will be
LED H17 turned on with continuous light. The LC display shows the signaling.
ZE blocked. It is merely an indicator sign, not a ...
do not produce any electrical blockage.
In case of action without prior activation of the extinguishing system, this situation
it will be interpreted as a wrongful act (failure) and it will remain on the LC display
reflected the message 'ERROR HANDLING OPERATION second extinction'. The
LED H19 will be blinking with the LT1 cadence.
2.11 Review
If the card has been taken to verification mode (review), it is indicated by the
LED H21 blinking with the LT2 cadence. In case a fire alarm is received.
during the activated review mode, no termination will occur, more
well just a warning alert. The LED H15 will change directly from continuous light to the
blinking cadence LT2.
On the front panel of the extinguishing control, the devices can be connected and disconnected.
extinction zone groups. The extinction zone can be taken to the modality
for review, and the extinguishing control can be restored through this panel of
operation.
The LEDs of the disabled groups will be lit with continuous light (see
also 2.2).
The S6 button is used to connect and disconnect the complete extinguishing control.
for the extinction zone. In this case, all groups will be out of service
of command and surveillance, as well as the delay group for extinction and the second one
extinction. If the second extinction group was configured for operation
detectors for manual operation, these manual detectors can be
disconnected only along with the complete extinction set.
The LEDH11, H12, H13, H14, H18, and H20 are continuously lit.
If the fire suppression control panel is in the review state, I don't know
no initiation of any extinction will occur, as the command groups will not be activated either for the
activation of the fire extinguisher agent in case of triggering the extinguishing system.
The other activations and other functions are not affected by this.
situation and continue to operate without any restrictions. The H15 LED changes light
continue directly to the LT2 blinking cadence, as no action is taken
flooding of the extinction zone.
Through the LCD control panel of the FMZ 4100, the following can be carried out
functional operations:
Lamp test;
External acoustic signals disconnected;
Replacement of the fire detections.
If the prior alarm changes to the main alarm, the sequence of will be initiated.
extinction. The early warning team takes charge now, along with the horn, of the
alarm for the abandonment of the premises, so it can no longer be disconnected to
through the function 'External acoustic signals disconnected.'
4.3 Reposición
If a reset is performed on the LCD operation panel, this reset takes effect
effect on the fire detection of the extinguishing control panels. This
Fact does not affect the development of command operations. If new ones come in
fire detections, the new start of the sequence will not occur
extinction, since a premature replacement of the detectors must be assumed
still interconnected. The sequence of extinction can be repositioned
only through a reset carried out on the operation panel of the
extinguishing control card.
If the prior alarm changes to the main alarm, the sequence of will be initiated.
extinction. The pre-alarm team now takes over, along with the horn, of the
alarm for the abandonment of the premises, so that it can no longer be disconnected
through the function "External acoustic signals disconnected."
5.2 Restocking
If a replacement is carried out in the firefighters' operation panel, this
replacement has an effect on the fire detection of the control boards of
extinction. This fact does not affect the development of command operations. If they enter
new fire detections, the new start of the sequence will not occur
of extinction, since a premature replenishment of the
detectors still interconnected. The extinction sequence can be
repositioned solely through a reset performed on the panel of
operation of the extinguishing control card.
Button Function
LED Function
H1 Pre-alarm group 1 of automatic detectors
H2 Malfunction group 1 of automatic detectors
H3 Pre-alarm group 2 of automatic detectors
H4 Malfunction of group 2 of automatic detectors
H5 Pre-alarm group 3 of automatic detectors
H6 Malfunction of group 3 of automatic detectors
H7 Pre-alarm group 4 of automatic detectors
H8 Fault group 4 of automatic detectors
H9 -/-
H10 Malfunction of the group of contact or manual detectors
H11 Control group malfunction 1
H12 Control group malfunction 2
H13 Command group failure 3
H14 Fault in control group 4
H15 The extinction zone is flooded
H16 Line leak or malfunction
H17 False or incorrect operation of the delay extinguishing button
H18 Failure of the extinction delay button
H19 False or erroneous operation of the second extinction button or
middle position of the selector switch Operation/Reserve
H20 Failure of the second extinguishing button or
Breakdown of the main operation selection and reserve or
Fault of the detector group for manual activation
H21 -/-
H22 -/-
LED Function
H1 Fire group 1 of automatic detectors
H2 -/-
H3 Fire group 2 of automatic detectors
H4 -/-
H5 Fire group 3 of automatic detectors
H6 -/-
H7 Fire group 4 of automatic detectors
H8 -/-
H9 Fire group of contact or manual detectors
H10 -/-
H11 Command group 1 activated
H12 Command group 2 activated
H13 Command group 3 activated
H14 Command group 4 activated
H15 Time of extinction elapsed
H16 Confirmation notice: The extinguishing agent has been downloaded in
the zone
H17 Activated delay extinguishing button
H18 -/-
H19 Second extinction switch activated or
Fire group of detectors for manual operation
H20 -/-
H21 REVIEW
H22 -/-
LED Function
H1 -/-
H2 Deactivation group 1 of automatic detectors
H3 -/-
H4 Deactivation of group 2 of automatic detectors
H5 -/-
H6 Deactivation of group 3 of automatic detectors
H7 -/-
H8 Deactivation of group 4 of automatic detectors
H9 -/-
H10 Deactivation of the group of contact or manual detectors
H11 Deactivation of command group 1
H12 Deactivation of command group 2
H13 Deactivation of command group 3
H14 Deactivation command group 4
H15 Protected premises abandonment alarm
H16 -/-
H17 Blocking
H18 Deactivation of the extinguishing delay button
H19 -/- the selected main electric battery
H2O Deactivation of the second extinction button
H21 -/-
H22 CPU failure
Disconnectors groups 3 + 4
Button Function
S1 Connect/disconnect group 1 of automatic detectors