FIRE DETECTION
AND
ALARM SYSTEM
(FDAS)
NOTIFIER
By: Honeywell
FIRE DETECTION AND ALARM SYSTEM
Automatic fire alarm system is designed to detect and
warn people through visual and audio appliances when
smoke, heat, flame, carbon monoxide or other products of
fire are present. These alarms may be activated
automatically from smoke detectors, and heat detectors or
may also be activated via manual fire alarm activation
devices such as manual call points or pull stations.
NOTIFIER INTELLIGENT
ADDRESSABLE PANELS
NFS2 – 640E
Two SLC / Loop
1 loop is equivalent to 159 addressable detectors and
159 addressable modules
Total of 636 addressable devices
636 ≈ 640
NFS2 – 640E
Smoke Detector Heat Detector
Up to
EOL
Manual
Two
One Loop
Loops
HORN Pull Station
STROBE
FRM
Interfacing;
1. Panel to Panel
2. PA/BGM
3. Door Access
NFS2 – 640E FDAS SEQUENCE
HORN HORN
STROBE STROBE FRM
Smoke Detector
1 MIN 3 MINS Interfacing;
DELAY DELAY 1. Panel to Panel
TWO FLOOR 2. PA/BGM
ONE FLOOR
ONLY GENERAL ALARM 3. Door Access
HORN HORN
FRM
Heat Detector STROBE STROBE
Interfacing;
1 MIN 3 MINS
DELAY
1. Panel to Panel
DELAY
2. PA/BGM
ONE FLOOR TWO FLOOR
GENERAL ALARM
3. Door Access
ONLY
FRM
IMMEDIATELY Interfacing;
TRIGGER 1. Panel to Panel PANEL INDICATION
TWO FLOOR
2. PA/BGM IMMEDIATELY
GENERAL ALARM 3. Door Access FIRE ALARM
Manual
Pull Station
PHOTOELECTRIC SMOKE DETECTOR
(FSP-851)
Have unique optical sensing chamber is engineered to sense
smoke produced by a wide range of combustion sources. FSP-851
series detectors are compatible with all ONYX
series Notifier intelligent Fire Alarm Control Panels (FACP).
NOTE:
Flashing GREEN light on normal operation
Steady RED light when on alarm
Addressable Smoke Detector
FSP 951W
The FSP-951 Series intelligent plug-in
smoke detectors are designed for both
performance and aesthetics, and are
direct replacements for FSP-851 series. A
new modern, sleek, contemporary design
and enhanced optical sensing chamber is
engineered to sense smoke produced by
the wide range of combustion sources in
accordance with more stringent code
standards.
HEAT DETECTOR
Use an innovative thermistor sensing circuit to produce 135°F/
57°C fixed-temperature (FST-851) and rate-of-rise thermal detection
(FST-851R) in a low-profile package. FST-851 Series detectors are
compatible with all Notifier intelligent Fire Alarm Control Panels,
except FireWarden series panels.
NOTE:
Flashing GREEN light on normal operation
Steady RED light when on alarm
Addressable Heat Detector
FST 951W
The FST-951 Series intelligent thermal
detectors are designed for both
performance and aesthetics, and are
direct replacements for the FST-851
Series. A new modern, sleek,
contemporary design and advanced
thermal technologies make the FST-951
Series ideal for both system operation
and building design. The point ID
address, set using rotary decimal
switches, provide specific locations.
Addressable Manual Pull Station
NBG-12LX
The NBG-12LX is a state-of-the-art,
dual action (i.e., requires two motions
to activate the station) pull station that
includes an addressable interface for
any Notifier Intelligent control panel
except FireWarden series panels, and
the NSP-25 panel. Because the NBG-
12LX is addressable, the control panel
display the exact location of the
activated manual station.
FIRE MONITOR MODULE
(FMM-101)
Is a mini monitor module that supervises a class B
circuit of dry-contact input devices.
HORN STROBE
Plug-in design
Captive mounting screw to cut installation time
Tamper resistance capability
Operates on either 12 V or 24 V.
Field-reversible strobe for left or right mounting.
Adjustable in ¼, ½, 1, 2 watts.
FIRE RELAY MODULE (FRM-1)
FIRE RELAY MODULE (FRM-1)
Addressable relay module provides the system with a dry-contact output for activating a variety of
auxiliary devices, such as fans, dampers, control equipment, etc.
NFS2-640E LED
Power ON
Releasing Zone activated
In process of discharging
Activated Abort switch
When smoke or fire exists
False Alarm
When security exists
[Door contact release]
When supervision exists
When problem in Panel exists
Silence Output
Disable Device
NFS2-640E HOW TO RESPOND
FIRE ALARM
STEP 1 STEP 2 STEP 3
STEP 1:
Press the ACKNOWLEDGE soft key.
- The local sounder will silence and the FIRE ALARM LED will change from flashing to steady.
Note : Check the Alarm message for its location and Type.
STEP 2:
Press the SIGNAL SILENCE soft key.
- Signal Silence LED light steady. And ALL activated outputs that are programmed as been
de-activated.
Note : Before pressing the Signal Silence, verify first what is the cause of FIRE ALARM.
STEP 3:
Press the SYSTEM RESET soft key.
- When the Alarm condition is corrected.
Note : Reset or clean the cause of activation of FIRE ALARM.
HOW TO RESPOND TROUBLE
STEP 1:
Press the ACKNOWLEDGE soft key.
- The local sounder will silence and the SYSTEM TROUBLE LED will change from
flashing to steady.
Note : Check the trouble message for its location and Type.
STEP 2:
- Correct the condition causing the trouble.
If Cannot handle the trouble contact YYMI technical support for assistance.
YYMI Tel. No. 242-3401 to 07
Office Hours: Monday – Friday 8:00AM – 6:30PM
NFS2-640E LCD DISPLAY
Type Code of initiating device
Custom descriptor for this
Status Banner device location
Zone
Time and date Device address
Extended 12 character of trouble
custom label
SCREEN DISPLAY WHEN
FIRE ALARM ACTIVATE
NFS2-640E LCD DISPLAY
Type of Device Custom descriptor for this
Type of Event device location
Type of Time and date Device address
Extended 12 character Trouble of trouble
custom label
SCREEN DISPLAY WHEN
TROUBE EXISTS
NFS2-640 TROUBLE
TROUBLE TYPE DESCRIPTION ACTION
AC FAILURE The auxiliary power supply has lost AC Determine whether there is an AC
power. power loss or whether the power
supply and wiring is correct.
CHGFLT The power supply’s battery charger is not Correct the Fault.
working properly.
DIRTY 1 The detector is dirty and needs cleaning. Clean the detector
DIRTY 2 The detector requires cleaning immediately. Clean the detector immediately.
It is a false alarm risk.
DISABL The point has been disabled Service and re-enable the point.
GNDFLT There is a ground fault on the main or Correct the fault.
auxiliary power
HI BAT The auxiliary power supply’s battery charge Check the batteries for problems.
is too high. Replace batteries if necessary.
NFS-320 & NFS2-640 TROUBLE
TROUBLE TYPE DESCRIPTION ACTION
INVREP The device has returned a response to the Check the device for functionality,
panel that the panel did not expect. addressing and wiring.
LO BAT The auxiliary power supply’s battery charge Check the batteries for problems.
is low. Replace batteries if necessary.
NO ANS The device (module or detector) is not Determine whether the device is
responding to the poll. Either the device is functional, and connected and
not working or it is not connected properly. addressed properly on the SLC.
OPEN The module device has an open circuit on its Check the connections from the
supervised wiring. module to the input or output device
to which it is wired.
PSFAIL The power supply is not working properly. Check the battery for problems.
Replace battery if necessary.
SHORT The module device has a short circuit on its Check the connections from the
supervised wiring. module to the input or output device
to which it is wired.