Tips 2001 03 PopovTakhirov
Tips 2001 03 PopovTakhirov
-
.
generation, four-channel servo-actuator command, and sixteen-channel data acquisition.
For the tests the ATS system was used to monitor and control the displacement and force-
feedback signals.
Other data were monitored and recorded using an AutoNet data acquisition system with a
capacity of 64 channels. Pacific Signal Conditioners were used to amplify the transducers
and the strain gages signals and to remove frequencies above 100 Hz from the analog
signal.
3.2.4 Loading History
The testing program was based on the ATC-24 document "Guidelines for Cyclic Seismic
Testing of Steel Structures". The specimens were tested under displacement control,
following a loading history consisting of stepwise increasing deformation cycles. At
certain stage of plastic deformation of the specimens a few cycles with small amplitude
were imposed. Each loading step was defined by the peak beam end displacement and by
the number of cycle. Table 3-1 presents the testing program for the Specimen 1 and the
Specimen 2.
3.2.5 Data Processing
The specimen behavior was characterized by the following parameters: applied load,
beam end displacement, total plastic rotation of the connection, panel zone shear
deformation, column deformation, deformation in the T-section flange, and beam
deflection. A test specimen layout, the corresponding measurements, and the chosen
positive direction of applied load, and measured displacements are shown on Fig. 3-3.
Total displacement of the beam end is caused by rigid body motion of the
connection, the deformations of the beam itself, column, panel zone, and deformation in
the T-section flange. The rigid body motion was possible due small flexibility in the
vertical reaction frame. This part of the displacement was not too large, but it could not
be neglected. Therefore the beam end relative displacement was calculated from the
total one by subtracting of the rigid body displacement. As a result of the column and
panel zone deformations, the panel zone rotates trough an angle and changes its initial
configuration. Four displacement measurements ( and ) were used to compute
the connection rotation due column deflection and panel shear deformation . The
total beam rotation can be separated into four components: rotation due deformation of
the beam itself , rotation caused by rigid connection rotation , the contribution from
the panel zone , and the rotation due gap opening in the T-sections . These values
were determined as follows:
Total beam end displacement:
Relative beam end displacement: The remainder of the
calculation was done using this value of the displacement; where H is a distance from
pin to pin along the column, and L is the distance from the beam end to the center line
of the column
Total rotation:
10
total
1
2
4
5
total
, , ,
= - -
total
L H ( ) / .
6 3
= / L
c
Connection rotation due column deflection: Where d is a distance
between continuity plates
Panel zone shear deformation: . Where a and b are the
dimensions of the rectangular panel zone area (distance between targets in horizontal
and vertical directions)
Rotation due gap opening (and deformation) between T-section flange and column
flange:
Total plastic rotation: Where M=PL
0
(L
0
is a distance from center-line
of the actuator to the face of the column) is the moment at the face of the column and
is the elastic stiffness determined from M versus curve. The unloading path of
one of the elastic cycles below the reverse point was used to estimate this stiffness, to
avoid the influence of initial imperfections, clearances, hysteresis, etc.
A set of programs for the MATLAB 5.3 environment was created to process data and to
plot results in accordance with the procedure described above.
3.3 Test Results
3.3.1 Specimen 1
Testing of the first specimen was conducted on July 30, 2000. The specimen sustained all
loading steps up to and including the 5.69" beam tip displacement cycles without
significant damage. Testing was stopped because the maximum load for the test setup
was reached. Photo of the specimen's close up side view after the test is presented on Fig.
3-5. During the last set of the load reversals a slight buckling in the beam web and
flanges was observed. The residual buckling in the beam flange and web is shown on Fig.
3-6 and Fig. 3-7. During the test energy was dissipated by cyclic yielding of the flanges
of the T-sections, the gap between the T-section and column flanges was opening and
closing periodically. The residual gap in the upper T-section is shown on Fig. 3-8.
Table 3-1 presents the loading protocol for the both specimens. The first row in the table
presents total beam end displacement (in other words: beam end total vertical
deflection). The loading history for Specimen 1 is plotted in Fig. 3-9.
The plot of applied force versus beam tip displacement response is presented on
Fig. 3-10. The values of the displacement were obtained directly from the LVDT reading.
The relative displacement ( ) was calculated from previous displacement by subtracting
the specimen's displacement as rigid body. Because of some small flexibility in the
vertical reaction frame occurred this displacement could not be neglected. The plot of
applied force versus relative beam tip displacement is presented on Fig. 3-11.
Based on the values of the relative beam tip displacement the total beam rotation is
calculated. The imposed moment versus beam total rotation is presented on Fig. 3-12.
Figure 3-13 shows the applied moment versus the beam plastic rotation. The deformation
of the column panel zone is presented on Fig. 3-14.
11
c
d = - ( )/ .
5 4
a b ab = - + ( ) / ( )
5 4
2 2
2
T
d = - / ( ) .
8 7
pl
M K = - / .
K
pl
total
total
During the test the visible opening between the T-section flanges and the column flanges
was observed. The amplitude of the opening between flanges was measured in the
following way, the installed DCDT shows the relative displacement between targets
located at the center plane of the column and the T-section flanges (see details in Fig.3-
3). Therefore during mutual compression of two flanges this displacement is negative,
whereas the tension in T-sections web increases this distance and it becomes positive.
This relative displacement between the flanges is called as "gap opening" in the report.
Figure 3-15a and 3-15b shows these values during the test. The gap opening between T-
section flange and column flange for the upper T-section is presented on Fig. 3-15a. The
same value for the lower T-section is presented on Fig. 3-15b. The beam rotation due
these openings in the T-sections is presented on Fig.3-16.
The imposed force versus beam rotation due panel zone rotation is presented on Fig. 3-
17. The relative beam rotation calculated by subtracting rotation of the panel zone,
rotation due gap opening in T-sections and the panel zone deformation is presented on
Fig.3-18.
3.3.2 Specimen 2
Testing of the second specimen was conducted on July 20, 2000. The specimen sustained
all loading steps up to the 5.69" beam tip displacement cycles and failed at the first ramp
of the last cycle. The fracture was caused by crack in the web of the lower T-section. The
crack line started at the end of the weld and went through the hole for 1 inch bolt. Testing
was stopped after the finishing this cycle. Photo of the specimen's side view after the
testing is presented on Fig. 3-19.
During the test some energy was dissipated by cyclic yielding of the T-sections, the gap
between the T-section and the column flanges was open and closed periodically. The
residual gap in the top T-section is shown on Fig. 3-20.
At the end of the test a slight buckle in the beam web and flanges was observed. The
residual buckling in the beam flanges is shown on Fig. 3-21 and Fig. 3-22.
The crack in the stem of the bottom T-section is shown on Fig. 3-23 and 3-24. Fig. 3-23
presents the view of the location of this crack on the stem of the T-section. The location
was close to the K-line of the T-section and it was parallel to it. The crack started from
the end of the fillet weld, continues through the nearest hole for the 1 in bolt and ends at
the next bolt hole. The close view of the crack is presented on Fig. 3-24. The arrows trace
the crack line.
The loading protocol for the Specimen 2 is presented in Table 3-1. The loading history is
plotted in Fig. 3-25.
The layout of the displacement measuring instrumentation was identical for both
specimens given in Fig. 3-3. The displacement at the beam tip was measured by LVDT,
whereas the remainder of displacement measurement was done using DCDT.
12
The plot of applied force versus beam tip total displacement is presented on Fig. 3-26.
The values of the displacements were obtained directly from the LVDT reading. The
relative displacement was calculated from previous displacement by subtracting the
specimen's displacement as a rigid body. The flexibility of the reacting frame was taken
into account. The plot of applied force versus relative beam tip displacement is presented
on Fig. 3-27.
Based on the values of the relative beam tip displacement the total beam rotation is
calculated. The imposed moment versus the beam total rotation is presented on Fig. 3-28.
Figure 3-29 shows the applied moment versus the beam plastic rotation. The deformation
of the column panel zone is presented on Fig. 3-30.
During the test the visible opening between the T-section and column flanges was
observed. The values of the gap opening were measured by DCDT. Figure 3-3la and 3-
31b shows these values during the test. The gap opening between the T-section flange
and column flange for the top T-section is presented on Fig. 3-3la. The same data for the
bottom T-section is presented on Fig. 2-31b. The beam rotation due these openings in the
T-sections is presented on Fig. 3-32.
The imposed force versus beam rotation due panel zone rotation is presented on Fig. 3-
33. The relative beam rotation calculated by subtracting rotation of the panel zone,
rotation due gap opening in the T-sections and the panel zone deformation is presented on
Fig.3-34.
4 Experimental Results and Conclusions
4.1 Experimental results
A brief summary of experimental results and key parameters characterizing the
performance of tested specimens is presented in Table 4-1. The beam end displacement
corresponds to the relative beam end displacement .
4.2 Conclusions: advantages and disadvantages of proposed connections
4.2.1 Advantages
The design and performance of the proposed beam-to-column connections shows the
following advantages:
- all welding work can be done in a welding shop, in convenient welding positions
final assembling with bolts is relatively easy procedure and does not require a
rigorous quality assurance inspection (in order to achieve the required clamping force
between the column and the T-section flanges the widely available torque multiplier
from WRIGHTTOOL: Model 9S393A was used; the device does not produce any
noise and has an accuracy of 5%)
13
-
after test disassembling of Specimen 2 shows that repairing and replacing beam with
new T-section is neither difficult nor expensive
the beam deformation is minimal due to active participation of the T-sections flanges
and the column flanges during cyclic input
with shims properly installed, the connection develops less residual strain
eliminating large quantities of field weld greatly helps the connecting work to keep
up with the steel erection.
4.2.2 Disadvantages
The chosen design and the failure of Specimen 2 show the following disadvantages and
suggested improvements:
steel along the K-line of the T-section must be carefully selected
1 inch bolts (as used in Specimen 2 to pre-stress the T-section web to beam flange)
requires a greater distance between the bolt and the end of the fillet weld.
Alternatively, it appears that the bolts can be omitted altogether
- steel material of 1 " bolts has to be high quality as used in the tested connections
- connection based on the proposed design require shims for field assembly
- beams with welded top and bottom T-sections require more shipping space during
transportation.
4.2.3 Future Research Directions
Based on the conducted tests and followed data analysis the following future research on
this type of connections is planned:
- conduct 3D finite element analysis (FEA) of the connection to explore the possibility
of exchanging the existing 1 inch bolts to clamps and to investigate the decision to
remove some or all of them
- conduct 3D FEA of the connection to evaluate the critical parameters at the column-
tee joint, including the T-section size, bolt diameter, the clamping load variation and
the prying action
- fabricate and test new specimens with an improved design based on the theoretical
research and results of the previous tests.
14
-
-
-
-
-
-
References:
1. Tsai, K.C. and Popov, E.P. 1990. Cyclic behavior of end-plate moment connections.
ASCE J. of Struct. Engineering, Vol.116, No.11.
2. Tsai, K.C. and Popov, E.P. 1988. Steel Beam-Column Joints in Moment Resisting
Frames. Report No. UCB/EERC 88/19, Earthquake Engineering Research Center,
University of California at Berkeley.
3. Murray, T.M. et al. 2000. Cyclic testing of bolted moment end plate connections.
Struct. And Materials Lab., Virginia Polytechnic Institute and State University.
4. Leon, Roberto et al. 2000. Tests on bolted connections. School of Civil and
Environmental Engineering, Report No. SEMM 00-02, Georgia Institute of
Technology.
5. FEMA-267. 1995a. Interim guidelines: evaluation, repair, modification and design of
welded steel moment frames. FEMA Report No. 267. Washington, D.C.: Federal
Emergency Management Agency.
6. FEMA-267. 1995b. Interim guidelines: advisory No. 1. supplement to FEMA 267.
FEMA Report No. 267. Washington, B.C.: Federal Emergency Management Agency.
7. AISC. 1995a. Manual of steel construction. Load & resistance factor design. Vol.1,
Structural members, Specifications & codes, Second edition. Chicago: American
Institute of Steel Construction, Inc.
8. AISC. 1995b. Manual of Steel Construction. Load & Resistance Factor Design.
Vol.2, Connections, Second edition. Chicago: American Institute of Steel
Construction, Inc.
15
Table 2-1. Dimensions of the W36xl50 beam.
Flange width,
b
fb
[inch]
12
Flange
thickness, t
fb
[inch]
0.94
Web
thickness,
t
wb
[inch]
0.625
Depth, d
b
[inch]
35.85
Section
modulus,
z
b
[inch
3
]
581
Area, A
b
[inch
2
]
44.2
Moment of
inertia, I b
[inch
4
]
9040
Length, L
b
[inch]
134
Table 2-2. Dimensions of the W14x283 column.
Flange width,
b
f
[inch]
16.125
Flange
thickness, t
fc
[inch]
2.06
Web
thickness,
t
f
[inch]
1.29
Depth, d
c
[inch]
16.74
Section
modulus,
Z
c
[inch
3
]
542
Area, A
c
[inch
2
]
83.3
Moment of
inertia, I
c
[inch
4
]
3840
Length, L
c
[inch]
136
Table 2-3. Dimensions of the T-sections cut fromW40x264.
Flange width,
f
ts
[inch]
12
Flange thickness,
[inch]
1.73
Stem thickness,
t
sts
[inch]
0.96
Total depth for Specimen 1
(Specimen 2), d
sts
[inch]
28.75 (20)
Length, L
ts
[inch]
16
Table 2-4. Material Properties.
No
1
2
3
Part of Connection
Beam
Column
T-section
Yield Stress, F
y
[ksi]
56.6
52
64
Ultimate Stress
[ksi]
74.4
66
79
Section Size
W36xl50
W14x283
WT40x264
Grade
Gr50
Gr50
Gr50
Table 3-1. Testing program for the both specimens.
Total beam end
displacement
[inch]
No of cycles
0.36
6
0.53
6
0.71
6
1.07
6
1.42
4
2.14
2
0.53
2
2.85
2
4.27
3
5.69
6*
* Only 2 cycles at this level were performed for Specimen 2.
16
t
fts
Table 4-1. Short summary of test results
Key parameters
Yield load [kips]
Beam end displacement at the yield point [inch]
Elastic stiffness of the connection [kips/inch]
Maximum beam end displacement
Beam end displacement at failure [inch]
Maximum imposed load [kips]
Maximum imposed moment at the column face [kips*inch]
Maximum connection rotation [ % ]
Maximum plastic connection rotation [ % ]
Maximum rotation due gap opening [ % ]
Maximum relative beam rotation itself [ % ]
Specimen 1
230
1.2
180
5.2
N/A
345
48645
4
2.5
1.0
0.6
Specimen 2
230
1.2
178
5.2
3.5
327
43164
4
3.3
0.7
1.5*
This value is high because it includes the beam rotation after the bottom beam flange failure
17
Figure 1-1. Design details of end-plate connections for Specimens 10 and 10R, and that
of direct welding to column, Specimen 9 (K.C. Tsai, E.P. Popov 1988, 1990).
L
o
a
d
(
k
i
p
s
)
Beam Rotation (%)
Figure 1-2. Cantilever beam load versus beam rotation for Specimen 10R (K.C. Tsai, E.P.
Popov 1988, 1990).
18
Figure 1-4. Stress versus strain for coupon test of A490 1 bolt material.
19
Figure 1-3. Load versus elongation for A490 1 bolt.
F
i
g
u
r
e
1
-
5
.
G
l
o
b
a
l
d
i
m
e
n
s
i
o
n
s
a
n
d
g
e
o
m
e
t
r
y
o
f
t
h
e
t
e
s
t
e
d
s
p
e
c
i
m
e
n
s
.
20
F
i
g
u
r
e
1
-
6
.
D
e
s
i
g
n
d
e
t
a
i
l
s
o
f
S
p
e
c
i
m
e
n
1
.
21
F
i
g
u
r
e
1
-
7
.
D
e
s
i
g
n
d
e
t
a
i
l
s
o
f
S
p
e
c
i
m
e
n
2
.
22
Figure 2-1. Desired plastic frame behavior with plastic hinges developed in beams.
Figure 2-2. Probable plastic hinge location.
23
Figure 2-3. Calculation of the moment at the centerline of the column.
Figure 2-4. The weakest cross-section of the beam near the column face.
24
Figure 2-5. Dimensions of the weakest cross section near the column face.
Figure 2-6. View of the column and T-section connection with the corresponding
mechanical model.
25
Figure 3-2. View of a test in progress.
26
Figure 3-1. Test setup for both specimens.
Figure 3-3. Reference dimensions and measurements for the test specimens.
Figure 3-4. Strain gages and rosettes location for Specimen 1.
27
Figure 3-6. Residual beam flange buckling (after the test).
28
Figure 3-5. Specimen 1 after the test (side view).
Figure 3-7. Residual beam web buckling (after the test).
Figure 3-8. Residual gap opening in the upper T-section (after the test).
29
Figure 3-9. Loading history for Specimen 1.
Figure 3-10. Imposed load versus total beam end displacement for Specimen 1.
30
T
i
p
D
i
s
p
l
a
c
e
m
e
n
t
[
i
n
c
h
]
Time [sec]
A
c
t
u
a
t
o
r
f
o
r
c
e
[
k
i
p
s
]
Beam end total displacement [inch]
A
c
t
u
a
t
o
r
f
o
r
c
e
[
k
i
p
s
]
Beam end displacement [inch]
Figure 3-11. Imposed load versus beam end displacement for Specimen 1.
M
o
m
e
n
t
[
k
i
p
s
*
i
n
c
h
]
Beam Rotation [%]
Figure 3-12. Moment versus beam total rotation for Specimen 1.
31
M
o
m
e
n
t
[
k
i
p
s
*
i
n
c
h
]
Beam Plastic Rotation [%]
Figure 3-13. Moment versus beam plastic rotation for Specimen 1.
A
c
t
u
a
t
o
r
f
o
r
c
e
[
k
i
p
s
]
Panel zone shear deformation [%]
Figure 3-14. Imposed load versus deformation in panel zone for Specimen 1.
32
A
c
t
u
a
t
o
r
f
o
r
c
e
[
k
i
p
s
]
Relative displacement between flanges[inch]
Figure 2-15a. Relative displacement between column and top T-section flanges for
Specimen 1.
A
c
t
u
a
t
o
r
f
o
r
c
e
[
k
i
p
s
]
Relative displacement between flanges[inch]
Figure 3-15b. Relative displacement between column and bottom T-section flanges for
Specimen 1.
33
A
c
t
u
a
t
o
r
f
o
r
c
e
[
k
i
p
s
]
Rotation [%]
Figure 3-16. Imposed load versus beam rotation due gap opening in T-sections
(Specimen 1).
A
c
t
u
a
t
o
r
f
o
r
c
e
[
k
i
p
s
]
Rotation [%]
Figure 3-17. Imposed load versus panel zone rotation for Specimen 1.
34
A
c
t
u
a
t
o
r
f
o
r
c
e
[
k
i
p
s
]
Relative beam rotation [%]
Figure 3-18. Imposed load versus relative beam rotation for Specimen 1.
35
Figure 3-19. Specimen 2 after the test (side view).
Figure 3-20. Specimen 2: Residual gap opening in top T-section.
36
Figure 3-21. Specimen 2: top beam flange buckling.
Figure 3-22. Specimen 2: bottom beam flange buckling.
37
Figure 3-23. Specimen 2: crack line location.
Figure 3-24. Specimen 2: close view of the crack line.
38
Figure 3-25. Loading history for Specimen 2.
Tip Displacement [inch]
Figure 3-26. Imposed load versus total beam end displacement (Specimen 2).
39
F
o
r
c
e
[
k
i
p
s
]
T
i
p
D
i
s
p
l
a
c
e
m
e
n
t
[
i
n
c
h
]
Time [sec]
F
o
r
c
e
[
k
i
p
s
]
Tip Displacement [inch]
Figure 3-27. Imposed load versus beam end displacement (Specimen 2).
Beam Rotation [%]
Figure 3-28. Moment versus beam total rotation (Specimen 2).
M
o
m
e
n
t
[
k
i
p
s
*
i
n
c
h
]
40
M
o
m
e
n
t
[
k
i
p
s
*
i
n
c
h
]
Beam Plastic Rotation [%]
Figure 3-29. Moment versus beam plastic rotation (Specimen 2).
F
o
r
c
e
[
k
i
p
s
]
Panel Zone Shear Deformation [%]
Figure 3-30. Imposed load versus column panel zone deformation (Specimen 2).
41
F
o
r
c
e
[
k
i
p
s
]
Gap Opening [inch]
Figure 3-3la. Relative displacement between column and top T-section flanges
(Specimen 2).
F
o
r
c
e
[
k
i
p
s
]
Gap Opening [inch]
Figure 3-31b. Relative displacement between column and bottom T-section flanges
(Specimen 2).
42
F
o
r
c
e
[
k
i
p
s
]
Rotation [%]
Figure 3-32. Imposed load versus beam rotation due gap opening in T-sections
(Specimen 2).
F
o
r
c
e
[
k
i
p
s
]
Rotation [%]
Figure 3-33. Imposed load versus panel zone rotation for Specimen 2.
43
F
o
r
c
e
[
k
i
p
s
]
Rotation [%]
Figure 3-34. Imposed load versus relative beam rotation for Specimen 2.
44
STRUCTURAL STEEL EDUCATIONAL COUNCIL
P.O. Box 6190
Moraga, CA 94570
Tel. (925) 631-1313
Fax. (925) 631-1112
Fred Boettler, Administrator
Steel tips may be viewed and downloaded at www.aisc.org
S P O N S O R S
Adams & Smith
Bannister Steel, Inc.
Baresel Corp
Bethlehem Steel Corporation
Bickerton Industries, Inc.
Bostrum Bergen
California Erectors
Eagle Iron Construcion
Trade Arbed
Four Star Erectors
Gayle Manufacturing
The Herrick Corporation
Hoertig Iron Works
Junior Steel Co.
McLean Steel Inc.
Martin Iron Works, Inc.
Nelson Stud Welding Co.
Oregon Steel Mills
Eandi Metal Works
PDM Strocal, Inc.
Plas-Tal Manufacturing Co.
Reno Iron Works
SME Industries
Shollenbarger-Borello, Inc.
Templeton Steel Fabrication
Verco Manufacturing, Inc.
Vulcraft Sales Corp.
Western Steel & Metals, Inc.
The local structural steel industry (above sponsors) stands ready to assist you in determining the most
economical solution for your products. Our assistance can range from budget prices and estimated
tonnage to cost comparisons, fabrication details and delivery schedules.
Funding for this publication provided by the California Field Iron Workers Administrative Trust.