The document calculates loads, tensions, and required cross-sectional areas for rods in a stayed structure. A uniform load of 1.2 kPa acts over a 13.2m span, resulting in a tributary load of 15.8 kN/m and total load of 190 kN. Rod A-B experiences a tension of 370 kN, while rod A-C has 248 kN, requiring cross-sectional areas of 894 mm^2 and 300 mm^2, respectively. This equates to rod diameters of 1.34 inches for A-B and 0.79 inches for A-C.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
26 views
Stayed Roof
The document calculates loads, tensions, and required cross-sectional areas for rods in a stayed structure. A uniform load of 1.2 kPa acts over a 13.2m span, resulting in a tributary load of 15.8 kN/m and total load of 190 kN. Rod A-B experiences a tension of 370 kN, while rod A-C has 248 kN, requiring cross-sectional areas of 894 mm^2 and 300 mm^2, respectively. This equates to rod diameters of 1.34 inches for A-B and 0.79 inches for A-C.